Loading…
Loading…
Tender Value
₹1.4 Cr
EMD Value
₹2.8 L
Closing Date
16 Oct 2026, 1:00 pm
No
No
Single Packet System
Normal Tender
No
Not Applicable
Lowest to Highest
60 days
Expenditure
Capital (Works)
Above/Below/Par
TECHNICAL
14 conditions · 3 needing a document upload
Financial Eligibility Criteria: The tenderer must have minimum average annual contractual turnover of V/N or 'V' whichever is less; where V= Advertised value of the tender in crores of Rupees N= Number of years prescribed for completion of work for which bids have been invited. The average annual contractual turnover shall be calculated as an average of "total contractual payments" in the previous three financial years, as per the audited balance sheet. However, in case balance sheet of the previous year is yet to be prepared/ audited, the audited balance sheet of the fourth previous year shall be considered for calculating average annual contractual turnover. Annual Contractual Turnover Data for the Previous 3/4 Years should be submitted as per Annexure-IX.(AnnexureVIB of Tender Documents)
Technical Eligibility Criteria: (a)The tenderer must have successfully completed any of the following during last 07 (seven) years, ending last day of month previous to the one in which tender is invited: Three similar works each costing not less than the amount equal to 30% of advertised value of the tender, or Two similar works each costing not less than the amount equal to 40% of advertised value of the tender, or One similar work each costing not less than the amount equal to 60% of advertised value of the tender. (b) (i)In case of tenders for composite works (e.g. works involving more than one distinct component, such as Civil Engineering works, S&T works, Electrical works, OHE works etc. and in the case of major bridges - substructure, superstructure etc.), tenderer must have successfully completed any of the following during last 07 seven) years, ending last day of month previous to the one in which tender is invited: Three similar works each costing not less than the amount equal to 30% of advertised value of each component of tender, or Two similar works each costing not less than the amount equal to 40% of advertised value of each component of tender, or One similar work each costing not less than the amount equal to 60% of advertised value of each component of tender. Note for b(i): Separate completed works of minimum required values for each component shall also be considered for fulfillment of technical eligibility criteria. ( c) Similar nature of Work is defined as "Similar nature of Work is defined as "Supply, installation, testing & commissioning of Solar Power Plant having executed a single work of minimum 30% rating of total tendered quantity/capacity in Railway stations or Metro stations or Airports or in any Office/Service buildings/Hospitals/Residential buildings of Central Govt./State Govt./PSUs of Central or State Govt." Note: Work experience certificate from private individual shall not be considered. However, in addition to work experience certificates issued by any Govt. Organisation, work experience certificate issued by Public listed company having average annual turnover of Rs 500 crore and above in last 3 financial years excluding the current financial year, listed on National Stock Exchange or Bombay Stock Exchange, incorporated/registered at least 5 years prior to the date of opening of tender, shall also be considered provided the work experience certificate has been issued by a person authorized by the Public listed company to issue such certificates. In case tenderer submits work experience certificate issued by public listed company, the tenderer shall also submit along with work experience certificate, the relevant copy of work order, bill of quantities, bill wise details of payment received duly certified by Chartered Accountant, TDS certificates for all payments received and copy of final/last bill paid by company in support of above work experience certificate.
Similar Nature of Work: Supply, installation, testing & commissioning of Solar Power Plant having executed a single work of minimum 30% rating of total tendered quantity/capacity in Railway stations or Metro stations or Airports or in any Office/Service buildings/Hospitals/Residential buildings of Central Govt./State Govt./PSUs of Central or State Govt.
66 conditions · 9 needing a document upload
Check List: The tenderer(s) would fill up the check list, as per Annexure-XXIII to ensure that they are submitting the complete tender offer.
Please enter the percentage of local content in the material being offered. Please enter 0 for fully imported items, and 100 for fully indigenous items. The definition and calculation of local content shall be in accordance with the Make in India policy as incorporated in the tender conditions.
At TSK Division :Provision of Hybrid Solar Power Plants 100 KW(50KW*2) with Lithium Ion Battery Bank over TSK Division.
LV-T-14-TSK-963~NFR
LV-T-14-TSK-963
Open
Works - General
12 Months
Tinsukia, Assam
₹0
₹2.8 L
24 Sept 2026
24 Sept 2026
2 Oct 2026
22 items across 2 schedules
| # | Description | Unit | Qty | Rate | Amount |
|---|---|---|---|---|---|
| — | — | — | 68,95,432 | ||
| — | 1.00 | — | — | ||
| Supply, installation (erection), testing and commissioning of 50 KW capacity Battery Energy Storage System (BESS) based on Advanced Chemistry Cell (ACC) with Lithium Iron Phosphate (LFP) battery technology, designed to provide more than 4 hours backup at full load, complete in all respects, conforming to the latest applicable BIS/IS, IEC standards, MNRE guidelines, Central Electricity Authority (CEA) Regulations and other applicable statutory requirements. Contents:- 1. 50 KW Hybrid Battery Energy Storage System comprising high-efficiency Lithium Iron Phosphate (LFP) battery modules/cells of adequate capacity having suitable advance technology for BESS, with total energy storage capacity of more than 200 kWh, suitable for providing more than 4 hours backup at 50 KW full load. 2. 50 kVA/40 kW, 3-Phase Hybrid Solar Inverter/Power Conditioning Unit (PCU) with integrated MPPT charge controller, high-frequency DSP/IGBT technology and pure sine-wave output, suitable for 415 V AC, 50 Hz, 3-phase, 4-wire operation, with bidirectional battery charging/discharging facility and suitable for operation with Solar PV, Grid and connected load, including provision for automatic energy management and seamless changeover between Solar PV, Grid and Battery sources, complete with all necessary protections, controls, metering, indication and accessories as required for safe and reliable operation. 3. Battery Management System (BMS) and Energy Management System (EMS) with necessary monitoring, control and protection arrangements. 4. Battery rack/enclosure, DCDB, ACDB, MCB/MCCB, isolators, fuses, Surge Protection Devices (SPDs), connecting cables, battery cables, connectors, cable glands, lugs, ferrules, casing/conduits/pipes and all other accessories as required. 5. Earthing and lightning protection system including Lightning Arrestors, earth electrodes, GI/Copper earth conductors, earth strips, clamps and accessories as required. 6. Necessary fire detection/protection, safety, ventilation/cooling and emergency shutdown arrangements for the complete BESS system. 7. Solar PV/Grid/Load interconnection, synchronization and power evacuation system with necessary protection and control arrangements for integration with the existing electrical system. 8. Web- based monitoring and control system with RTU/data logger for real-time monitoring of battery, inverter, solar generation, grid and load parameters with daily/monthly/yearly data downloadable in MS Excel format. 9. Transportation of all equipment and materials up to the destination. 10. Installation, erection, testing and commissioning of the complete BESS system including integration with the Solar PV, Grid and connected load. 11. All necessary accessories, hardware, consumables and incidental works required for a complete, safe, reliable and functional BESS system shall be included in the scope of work. | — | — | — | 46,22,496 | |
| — | 1.00 | — | — | ||
| Supply, fitting, fixing, installation and commissioning of 50 KWp capacity of solar on grid power plant complete in all respects, conforming to the latest applicable BIS/IS, IEC standards, MNRE guidelines, Central Electricity Authority (CEA) Regulations and CPWD Specifications. Contents:- 1. 50 KWp Solar PV Power Plant comprising high-efficiency N-Type TOPCon Half-Cut Bifacial Solar PV Modules (Comprising 550 Wp or above capacity module). 2.GI module mounting structure.3.Lightening Arrestors, Earthing etc. 4. Connecting wires, MCB's, casing pipe, accessories, etc. as required.5-AJB(Array Junction Box), ACDB( AC Distribution Board) with Import- Export Meter,CO2 meter, Power Evacuation system. 6-Transportation Up to the destination. 7- Installation & commissioning included in this work.Including civil works, transportation, installation, testing and commissioning, all other accessories, hardware, consumables and incidental works as required for a complete and functional system. | — | — | — | 20,00,000 | |
| — | 100.00 | — | — | ||
| Supply, laying, connection, testing and commissioning of LT XLPE insulated, cores laid-up, PVC inner sheathed, armoured stranded aluminium conductor cable of size 120 sq.mm, 4 Core, having galvanized steel strip armouring and extruded PVC Type ST-2 outer sheathing, 650/1100 V grade, conforming to IS 7098 (Part-1):1988, including all necessary cable glands, lugs, termination accessories, jointing materials and hardware complete in all respects. The work shall include digging of cable trench and excavation of earth/concrete to a depth of 0.75 metre and breadth of 0.50 metre below ground level, preparation and leveling of trench bottom free from sharp objects, providing and laying a 0.075 metre thick layer of sand below the cable, laying of cable and covering the cable with another 0.075 metre thick layer of sand, followed by suitable backfilling and restoration of the surface. Cable route markers shall be provided at suitable intervals and at changes in direction/crossings to clearly indicate the underground cable route and prevent damage due to inadvertent digging. The work shall also include laying of cable along wall surfaces wherever required, using suitable GI/MS cable clamps, saddles, supports, brackets and necessary hardware, including drilling, fixing and securing of clamps/supports at suitable intervals, as per the direction of the Supervisor-in-Charge, complete with all accessories and incidental works.All conditions to be fulfilled as per DRG No : PCEE/ELG/DRG/2024/2 Dtd 04.10.2024 | — | — | — | 2,19,600 | |
| — | 1.00 | — | — | ||
| Supply, fitting and fixing of VTPN MCB Distribution Board complete with 100A, 4-Pole MCCB as incomer, having minimum 25 kA breaking capacity, and outgoing 63A DP MCB - 4 Nos. and 32A DP MCB - 8 Nos., having minimum 10 kA breaking capacity, complete with busbars, neutral link, earth bar, internal wiring, shrouds, labels and all necessary accessories, as per site requirement and as directed by the Site In-charge, complete in all respects. | — | — | — | 45,050 | |
| — | 2.00 | — | — | ||
| Erection of earth by 50 mm dia 3 Mtrs. long (Medium Gauge) GI pipe , 8 SWG GI wire,GI nuts, bolts including masonry materials for earthing pit, salt, charcoal etc. and construction of earth pit covered with CI plate having locking arrangement and watering pipe as per drg. Nos.PCEE/ELG/DRG/2024/1 dated 30.09.2024 | — | — | — | 8,286 |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
HTML
nit.pdf
NIT
TenderDocument963.pdf
ATTACHMENT
GCCAPRIL2022WITHALLACS.pdf GCC 2022 WITH ACS
ATTACHMENT
AnnexuresSectionVII.pdf
ATTACHMENT
GCCAPRIL2022WITHALLACS.pdf
ATTACHMENT
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .