Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹48.4 CrAdmitted-Finance | ₹48.4 Cr | L1 | Admitted-Finance |
| 2 | L2₹49.1 CrAdmitted-Finance | ₹49.1 Cr | L2 | Admitted-Finance |
| Sl No | Description | Qty | Unit | KAPAHI CONSTRUCTION COMPANY L2 | Sanjiv Kumar Sharma L1 |
|---|---|---|---|---|---|
| 1.00 | Earthwork in excavation by mechanical means (Hydraulic excavator) over areas (Exceeding 30cm in depth, 1.5 M in width as well as 10 Sqm on plan) including disposal of excavated earth, lead upto 50 M and lift upto 1.50 M, disposed earth to be leveled and neatly dressed in all kind of soil. | 12,401.07 | Cum | 153 ₹19.0 L | 200 ₹24.8 L |
| 2.00Extra for every additional lift of 1.5 M or part therefore in all kinds of soil. | |||||
| 2.10 | All kind of Soil | 3,347.96 | Cum | 45 ₹1.5 L | 100 ₹3.3 L |
| 3.00 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering all work up to plinth level in 1:4:8 : (1 cement : 4 coarse sand crushed. 8 graded stone aggregate) 40mm nominal size | 744.25 | Cum | 5,000 ₹37.2 L | 4,000 ₹29.8 L |
| 4.00 | Providing and laying in position machine batched and machine mixed design mix M-25 grade cement concrete for reinforced cement concrete work, using cement content as per approved design mix, including pumping of concrete to site of laying but excluding the cost of centering, shuttering, finishing and reinforcement, including admixtures in recommended proportions as per IS: 9103 to accelerate, retard setting of concrete, improve workability without impairing strength and durability as per direction of Engineer-incharge. Note: - Cement in this item is @ 330 kg/ cum. Excess or less cement used as per design mix is content considered payable or recoverable separately. All works upto plinth level | 3,284.66 | Cum | 7,000 ₹2.3 Cr | 7,800 ₹2.6 Cr |
| 5.00 | Providing and laying in position machine Providing and laying in position machine batched and machine mixed design mix M-25 grade cement concrete for reinforced cement concrete work, using cement content as per approved design mix, including pumping of concrete to site of laying but excluding the cost of centering, shuttering, finishing and reinforcement, including admixtures in recommended proportions as per IS: 9103 to accelerate, retard setting of concrete, improve workability without impairing strength and durability as per direction of Engineer-incharge. Note: - Cement in this item is @ 330 kg/ cum. Excess or less cement used as per design mix is content considered payable or recoverable separately.All works above plinth level upto floor V level | 4,129.75 | Cum | 7,500 ₹3.1 Cr | 8,200 ₹3.4 Cr |
| 6.00 | Providing and laying in position machine Providing and laying in position machine batched and machine mixed design mix M-30 grade cement concrete for reinforced cement concrete work, using cement content as per approved design mix, including pumping of concrete to site of laying but excluding the cost of centering, shuttering, finishing and reinforcement, including admixtures in recommended proportions as per IS: 9103 to accelerate, retard setting of concrete, improve workability without impairing strength and durability as per direction of Engineer-incharge. Excess or less cement used as per design mix is content considered payable or recoverable separately.All works upto plinth level | 150.43 | Cum | 7,700 ₹11.6 L | 8,000 ₹12.0 L |
| 7.00 | Providing and laying in position machine Providing and laying in position machine batched and machine mixed design mix M-30 grade cement concrete for reinforced cement concrete work, using cement content as per approved design mix, including pumping of concrete to site of laying but excluding the cost of centering, shuttering, finishing and reinforcement, including admixtures in recommended proportions as per IS: 9103 to accelerate, retard setting of concrete, improve workability without impairing strength and durability as per direction of Engineer-incharge. Excess or less cement used as per design mix is content considered payable or recoverable separately.All works above plinth level upto floor V level | 355.75 | Cum | 7,800 ₹27.7 L | 8,300 ₹29.5 L |
| 8.00 | Extra for providing richer mixes at all floor levels. Note:- Excess/ less cement over the
specified cement content used is payable/ recoverable separately. Providing M-30 grade concrete instead of M-25 grade BMC/RMC. | 1,500 | Cum | 500 ₹7.5 L | 100 ₹1.5 L |
| 9.00 | Providing and laying in position cement concrete of 1:3:6 grade (1 cement : 3 coarse sand : 6 graded crushed stone aggregate 40mm nominal size) excluding the cost of centering and shuttering. All work upto plinth work. | 360 | Cum | 500 ₹1.8 L | 4,300 ₹15.5 L |
Tender Value
₹57.7 Cr
EMD Value
₹1.2 Cr
Closing Date
15 Mar 2022, 6:00 pmClosed
XEN PWD Udhampur
Udhampur
Pl. refer to BOQ
2022_PWDJK_162746_1
Fresh e-NIT No. 194 of 2021-22 dated 02.03.2022
Open Tender
Civil Works
540 days
Udhampur
Pl. refer to NIT/SBD
3 documents required · 3 mandatory
₹6,000
Chief Accounts Officer, PW(RandB) Dpartment, Jammu
₹1.2 Cr
O/O Chief Engineer, PW (RandB) Dpartment, Jammu
25 Mar 2022
2 Mar 2022
16 Mar 2022
3 Mar 2022
15 Mar 2022
3 Mar 2022
10 Mar 2022
Amount
Earthwork in excavation by mechanical means (Hydraulic excavator) over areas (Exceeding 30cm in depth, 1.5 M in width as well as 10 Sqm on plan) including disposal of excavated earth, lead upto 50 M and lift upto 1.50 M, disposed earth to be leveled and neatly dressed in all kind of soil.
Extra for every additional lift of 1.5 M or part therefore in all kinds of soil.
All kind of Soil
Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering all work up to plinth level in 1:4:8 : (1 cement : 4 coarse sand crushed. 8 graded stone aggregate) 40mm nominal size
Providing and laying in position machine batched and machine mixed design mix M-25 grade cement concrete for reinforced cement concrete work, using cement content as per approved design mix, including pumping of concrete to site of laying but excluding the cost of centering, shuttering, finishing and reinforcement, including admixtures in recommended proportions as per IS: 9103 to accelerate, retard setting of concrete, improve workability without impairing strength and durability as per direction of Engineer-incharge. Note: - Cement in this item is @ 330 kg/ cum. Excess or less cement used as per design mix is content considered payable or recoverable separately. All works upto plinth level
Providing and laying in position machine Providing and laying in position machine batched and machine mixed design mix M-25 grade cement concrete for reinforced cement concrete work, using cement content as per approved design mix, including pumping of concrete to site of laying but excluding the cost of centering, shuttering, finishing and reinforcement, including admixtures in recommended proportions as per IS: 9103 to accelerate, retard setting of concrete, improve workability without impairing strength and durability as per direction of Engineer-incharge. Note: - Cement in this item is @ 330 kg/ cum. Excess or less cement used as per design mix is content considered payable or recoverable separately.All works above plinth level upto floor V level
Providing and laying in position machine Providing and laying in position machine batched and machine mixed design mix M-30 grade cement concrete for reinforced cement concrete work, using cement content as per approved design mix, including pumping of concrete to site of laying but excluding the cost of centering, shuttering, finishing and reinforcement, including admixtures in recommended proportions as per IS: 9103 to accelerate, retard setting of concrete, improve workability without impairing strength and durability as per direction of Engineer-incharge. Excess or less cement used as per design mix is content considered payable or recoverable separately.All works upto plinth level
Providing and laying in position machine Providing and laying in position machine batched and machine mixed design mix M-30 grade cement concrete for reinforced cement concrete work, using cement content as per approved design mix, including pumping of concrete to site of laying but excluding the cost of centering, shuttering, finishing and reinforcement, including admixtures in recommended proportions as per IS: 9103 to accelerate, retard setting of concrete, improve workability without impairing strength and durability as per direction of Engineer-incharge. Excess or less cement used as per design mix is content considered payable or recoverable separately.All works above plinth level upto floor V level
Extra for providing richer mixes at all floor levels. Note:- Excess/ less cement over the specified cement content used is payable/ recoverable separately. Providing M-30 grade concrete instead of M-25 grade BMC/RMC.
Providing and laying in position cement concrete of 1:3:6 grade (1 cement : 3 coarse sand : 6 graded crushed stone aggregate 40mm nominal size) excluding the cost of centering and shuttering. All work upto plinth work.
Brick work with common burnt clay F.P.S (non modular) bricks of class designation 75 upto plinth level in cement mortar 1:4 (1 cement : 4 fine sand).
Providing and laying DPC 50mm thick in 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20mm nominal size crusher aggregate).
Brick work with common burnt clay F.P.S (non modular) bricks of class designation 75 in super structure in cement mortar 1:6 (1 cement : 6 fine sand).
Extra for brick work with common burnt clay bricks/cement concrete bricks in superstructure above plinth level upto floor five level.
Half brick masonry with bricks of class designation 75 in foundation, plinth and superstructure upto floor V-level in cement mortar 1:4 (1 cement : 4 coarse sand).
Extra for half brick work in super structure above plinth level upto floor V-level.
Extra for providing and placing in position 2 Nos. 6mm dia. M.S. bars at every third course of half brick masonry (with F.P.S bricks).
Applying a coat of residual petroleum bitumen of grade VG-10 of approved quality using 1.7 kg per square metre on damp proof course after cleaning the surface with brushes and finally with a piece of clothkerosene oil.lightly soaked in
Reinforcement for RCC work including straightening, cutting, bending, placing in position and binding all complete TMT bars.
Centering and shuttering including strutting, propping etc. and removal of form work for :-
Foundations, footings, bases of columns.
Suspended floors, roofs, landings, balconies and access platforms.
Columns, pillars, piers, abutments, posts and struts.
Lintels, beams, plinth beams, girders, bressumers and cantilevers.
Edges of slabs and breaks in floors and walls upto 20cm wide.
Retaining walls, return walls, wall (any thickness) including attached pilasters, buttresses, plinth and string courses fillets etc.
Weather shade, chajjas, corbels etc. including edges.
Stairs (excluding landings) except spiral stair cases.
Shelves (cost in situ).
Extra for additional height in centering, shuttering where ever required with adequate bracing, propping etc. including cost of de-shuttering and decentring at all levels, over a height of 3.5m, for every additional height of 1 mtr. of part thereof (Plan area to be measured). Suspended floors, roofs landing, beams and balconies (Plan area to be measured).
Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc in layers not exceeding 20cm in depth consolidating each deposited layer by ramming and watering, lead upto 50Mt & lift upto 1.50M.
Supplying and filling in plinth with fine sand under floors including, watering, ramming consolidating and dressing complete.
Providing and laying cement concrete 1:5:10 (1 cement : 5 coarse sand : 10 graded brick aggregate 40mm nominal size)nR/Wall/Return Wall, columns etc. excluding the cost of centering and shuttering, all works upto floor V level.
6mm thick cement plaster to ceiling of mix 1:3 (1 cement : 3 fine sand).
15mm cement plaster on the rough side of single or half brick wall of mix in 1:6 (1 cement : 6 fine sand).
15mm cement plaster on the rough side of single or half brick wall of mix 1:4 (1 cement : 4 fine sand).
12mm cement plaster of mix 1:6 (1 cement : 6 fine sand).
15mm cement plaster 1:3 (1 cement : 3 coarse sand) finished with a floating cost of neat cement on the rough side of single or half brick wall.
18mm thick moulded cement mortar band in two coats under layer 12mm thick with cement mortar 1:5 (1 cement : 5 fine sand) top layer 6mm thick with cement mortar 1:4 (1 cement : 4 fine sand) for 4cm width.
Extra for plastering exterior walls of the height more than 10 Mtrs from ground level for every additional height of 3 Mtrs or part thereof.
Add or deduct for plaster drip coarse / groove in plastered moulding to RCC projections.
Making of grove 12mm x 10mm between brick and RCC.
Kota stone slab flooring over 20mm (avg.) thick base laid over and jointedwith grey cement slurry mixed with pigment to match the shade of the slab including rubbing and polishing complete with base of cement mortar 1:4 (1 cement : 4 coarse sand) 25mm thick.
Kota stone slab 25mm thick in riser of steps, skirting, dado and pillars laid on 12mm (average) thick cement mortar 1:3 (1 cement : 3 coarse sand) and jointed with grey cement slurry mixed with pigment to match the shade of the slabs, including rubbing and polishing complete.
Providing and laying glossy finished full-body vitrified premium quality floor tiles of 60x60cm sizes (thickness to be specified by the manufacturer) with water absorption less approved make of Somany, shade Ethnic-Berlinetta White, Crown White, Dacia White, Dacia Green, Dacia Pink, Dacia Ivory, Dacia Grey, Dacia Brown, Dacia Pearl, Dezzling White, Evalia, S&P Grey, S&P Brown, Ultra White, Haze Grey and Border of Royale- Crown Mint, Crown Pink, Crown Snow, Micra Brown and Radiant- Lawrence Gold, Lawrence Bianco, Lawrence Grigio, Lawernce Moka, Lawrence Jaisalmer, Nuvro Brown, Nuvaro Mocha, Nuvaro Grey, Nauvaro Nero, Nuvaro Crema, Nuvaro Bianco, Nuvaro Beige laid on 20mm thick cement mortar 1:4 (1 cement : 4 coarse sand) including grouting the joints with matching Epoxy etc. complete.
Providing and laying glossy finished full-body vitrified premium quality floor tiles with spacer in sizes 60x120cm (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS : 15622 of approved make of Somany, Kajrai, Orient and NITCO Ethnic-Magnus State Grey, Magnus White, Colpi White, Radiant-Fusion Pearl White, Fusion Ivory Brown, Spectra Imperial Red, Spectra Nero, Spectra Golden Greylaid on 20mm thick cement mortar 1:4 (1 cement : 4 coarse sand) including grouting the joints with matching Epoxy etc. complete.
Providing and fixing Ist quality ceramic glazed tiles conforming to IS : 13753 of minimum thickness 9mm of approved make like NITCO, ORIENT, SOMANY, KAJARIA make in colour and shades Glosstra Plus-Lithor Light, Lithor Dark, Canica Light, Canica Dark, Gentil Light, Gentil Dark, Propiza Beige, Cream Glossy, Arian Bianco, Bello Mint Dark, Camia Light, Verde Dark, Fabro Brown Dark, Marina Blue, Strix Grey Vivo Crema, Vivo Mushroom of size 30x60cm as approved by Engineer in charge in skirting, risers of steps and dodos over 12mm thick bed of cement mortar 1:3 (1cement : 3coarse sand) and jointing with grey cement slurry @ 3.3Kg per sqm including pointing in white cement mixed with pigment of matching shade complete.
Providing and fixing Ist quality ceramic glazed tiles conforming to IS : 13753 of minimum thickness 9mm of approved make like NITCO, ORIENT, SOMANY, KAJARIA or equivalent make in colour and shades Somany, Kajaria, NITCO and Orient make in colours and shade Super Deluxe, Slip Shield, Aegis Beige, Brown, Aegis Grey, Aegis Nero, Armor Blue, Armor Brown, Armor Verde, Champion Beige, Champion Crema, Champion Grey, Champion Nero, Fence Brown, Fence Crema, Fence Grey, Fence Nero, Foster, Ridge Bianco, Ridge Moka, Vigor of size 60x60cm as approved by Engineer in charge in skirting, risers of steps and dodos over 12mm thick bed of cement mortar 1:3 (1cement : 3coarse sand) and jointing with grey cement slurry @ 3.3Kg per sqm including pointing in white cement mixed with pigment of matching shade complete.
Providing and fixing ceramic glazed floor tiles (non-skidding) 300x300mm (thickness to be specified by the manufactures) of Ist quality conforming to IS : 13755 of NITCO, ORIENT, SOMANY, KAJARIA or equivalent make in colour such as white, Ivory, Grey, Fume Red, Brown laid on 20mm thick bed of cement mortar 1:4 (1 cement : 4 coarse sand) including pointing the joints with white cement and matching pigment etc. complete.
Providing and laying 18mm thick Granite of any colour and shape (area of slab over 0.5 Sqm) gang saw cut mirror polished (pre moulded and pre polished), machine cut for kitchen platform, vanity counters window sills facias and similar locations of required size of approved shade, colour and texture laid over 20mm thick base cement mortar 1:4 (1 cement : 4 coarse sand) with joints treated treated with white cement, mixed with matching pigment, epoxy touch ups, including rubbing, curing moulding and polishing to edge to give high gloss finish etc. complete at all levels.
Providing and laying 16mm thick Granite of any colour and shape (area of slab over 0.5 Sqm) gang saw cut mirror polished (pre moulded and pre polished), machine cut for kitchen platform, vanity counters window sills facias and similar locations of required size of approved shade, colour andtexture laid over 20mm thick base cement mortar 1:4 (1 cement : 4 coarse sand) with joints treated treated with white cement, mixed with matching pigment, epoxy touch ups, including rubbing, curing moulding and polishing to edge to give high gloss finish etc. complete at all levels.
Providing and laying 18mm thick Granite of any colour and shape (area of slab upto 0.5 Sqm) gang saw cut flamed (pre moulded and pre polished), machine cut for stairs steps and similar locations of required size of approved shade, colour and texture laid over 20mm thick base cement mortar 1:4 (1 cement : 4 coarse sand) with joints treated treated with white cement, mixed with matching pigment, epoxy touch ups, including rubbing, curing moulding and polishing to edge to give high gloss finish etc. complete at all levels.
Providing and laying Polished Granite stone flooring in required design and patterns, in linear as well as curvilinear portions of the building all complete as per the architectural drawings with 18 mm thick stone slab over 20 mm (average) thick base of cement mortar 1:4 (1 cement : 4 coarse sand) laid and jointed with cement slurry and pointing with white cement slurry admixed with pigment of matching shade including rubbing, curing and polishing etc. all complete as specified and as directed by the Engineer-in-Charge. Polished Granite stone slab jet Black, Cherry Red, Elite Brown, Cat Eye or equivalent.
Extra for providing edge moulding to 18mm thick Granite stone counters, Vanities etc. over item No. 8.2 including machine polishing to edge to give high gloss finish etc. complete as per design approved by Engineer-in-charge.
Extra for providing opening of required size and shape for wash basins/kitchen sink in kitchen platform, vanity counters and similar location in marble / stone work including necessary holes for pillar taps etc. including rubbing and polishing of cut edges etc. complete.
Providing and fixing 10mm thick acid and / or alkali resistant tiles of approved make of Somay, Kajaria, Orient and NITCO and colour Gold plus, Salted peeper light colour using acid and / or alkali resisting mortar bedding and joints filled with acid and / or alkali resisting cement as per IS : 4457 complete as per direction of Engineer-in-charge. In flooring on a bed of 10mm thick mortar 1:4 (1 acid proof cement : 4 coarse sand). Acid and alkali resistant tile (size 60x60cm).
Providing and fixing 10mm thick anti skid heavy duty vitrified tile approved make of Somay, Kajaria, Orient and NITCO,stone 10 series gray grey dark and light colour using direction of Engineer-in-charge. In flooring on a bed of10mm thick mortar 1:4 tile (size 60x60cm).
Chequerred precast cement concrete tiles 22mm thick in footpath and courtyard jointed with neat cement slurry mixed with pigment to match the shade of the tiles, including rubbing and cleaning etc. complete on 20mm thick bed of cement mortar 1:4 ( 1 cement : 4 coarse sand). Medium shade using 50% white cement and 50% ordinary cement.
Providing and laying factory made 80 mm thick C.C. paver block of M-30 grade with approved color design and pattern chamfered edge Cement Concrete paver blocks in footpath, parks, lawns, drive ways or light traffic parking etc, of required strength, thickness & size/ shape, made by table vibratory method using PU mould, laid in required colour & pattern over 50mm thick compacted bed of sand, compacting and proper embedding/laying of inter locking paver blocks into the sand bedding layer through vibratory compaction by using plate vibrator, filling the joints with sand and cutting of paver blocks as per required size and pattern, finishing and sweeping extra sand complete all as per direction of Engineer-in-Charge.
Cement concrete flooring 1:2:4 finished with a floating coat of neat cement including cement slurry, but excluding the coat of nosing of steps etc. complete 50mm thick with 20mm nominal size of stone aggregate.
Cement plaster skirting (upto 30cm height) with cement mortar 1:3 (1 cement : 3 coarse sand) finished with a floating coat of neat cement 18mm thick.
Providing and laying integral cement based water proofing treatment including preparation of surfaces as required for treatment of roofs, balconies, terraces etc. (Make Armocreate of SWC Chryso France) consisting of (a) applying a slurry coat of neat cement using 2.75 kg/sqm of cement admixed with water proofing compound conforming to IS 2645 and approved by Engineer-in-charge over the RCC slab including adjoining walls upto 300mm height including cleaning the surface before treatment. (b) Laying brick bats with mortar using broken bricks / brick bats 25mm to 115mm size with 50% of cement mortar 1:5 (1 cement : 5 coarse sand) admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge over 20mm thick layer of cement mortar of mix 1:5 admixed with water proofing compound conforming to IS 2645 and approved by Engineer-in-charge to required slope and treating similarly the adjoining was upto 300mm height including rounding of junction of walls and slaps. (c) After two days of proper curing applying a second coat of cement slurry using 2.75 kg / sqm of cement admixed with water proofing compound conforming to IS 2645 and approved by Engineer-in-charge. (iv) Finishing the surface with 20mm thick joint less cement mortar of mix 1: 4 admixed with water proofing compound conforming to IS 2645 and approved by Engineer-in-charge including laying glass fiber cloth of approved quality in top layer of plaster and finally finishing the surface with trowel with neat cement slurry and making patternof 300x300mm / sq 3mm deep. (e) The whole terrace so finished shall be flooded with water far a minimum period of two weeks for curing and for final test. All above operations to be done in order and as directed and specified by Engineer-in-charge. With average thickness of 120mm and minimum thickness at khurras as 65mm.
Providing and laying water proofing treatment (Make Armocreate of SWC Chryso France) to vertical and horizontal surface of depressed portions of W.C., kitchen and the consisting of (i) Ist course of applying cement slurry @ 4.4 kg /sqm mixed with water proofing compound conforming to IS : 2645 in recommended proportions including rounding of junctions of vertical and horizontal surface. (ii) IInd course of 20mm cement plaster 1:3 (1 cement : 3 coarse sand) mixed with water proofing compound in recommended proportions including rounding of junctions of vertical and horizontal surface. (iii) III course of applying blown or / residual bitumen applied hot at 1.7 kg per sqm of area. (iv) Ivth course of 400 micron thick PVC sheet (Overlaps at joints of PVC sheet should be 100mm wide and pasted to each other with bitumen @ 1.7 kg/sqm.
Making plinth protection 50mm thick cement concrete 1:3:6 (1 cement : 3 course sand : 6 graded stone aggregate 20mm nominal size) over 75mm bed of dry brick ballast 40mm nominal size well rammed and consolidated and grouted with fine sand including finishing the top smooth crushed
Brick edging 7 cm wide 11.4cm deep to plinth protection with bricks of class designation 75mm including grouting with cement mortar 1:4 (1 Cement : 4 fine sand)
Providing and fixing aluminium work for doors, windows, ventilators andpartitions with extruded built up standard tubular sections/appropriate Z. sections and other sections of approved make conforming to IS : 733 and IS : 1285, fixed with rawl plugs and screws or with fixing clips, or with expansion hold fastners including necessary filling up of gaps at junctions at top, bottom and sides with required PVC / neoprene felt etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminium snap beading for glazing / panelling, C.P. brass / stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge (glazing and panelling to be paid for separately).
For fixed portion using Powder coated aluminium (minimum thickness of powder coated 50 microns).
For shutters of doors, windows and ventilators including providing and fixing hinges / pivots and making provision for fixing of fittings wherever required including the cost of EPDM rubber/neoprene gasket required (Fittings shall be paid for separately). Powder coated aluminium (minimum thickness of powder coated 50 microns)
Providing and fixing glazing in aluminium door, window, ventilator shutters and partition etc. with PVC / neoprene gasket etc. complete as per the architectural drawings and the directions of Engineer-in-charge. (Cost of aluminium snap beading shall be paid in basic item). With glass panes of 5.50 mm thickness (weight not less than 12.50 kg/sqm).
Providing and fixing 12mm thick prelaminated three layer medium density (exterior grade) particle board Grade-I, Type-II conforming to IS : 12823 bonded with phenol formaldehyde synthetic resin, of approved brand andmanufacture in panelling fixed in aluminium doors, windows shutters and partition frames with C.P brass / stainless screws etc. compete as per architectural drawings and directions of Engineer-in-charge. Pre-laminated particle board with decorative lamination on both sides.
Providing and fixing double action hydraulic floor spring of approved brand and manufacture IS:6315 marked for doors including cost of cutting floors as required, embedding in floors and cover plates with brass pivot and single piece M.S. sheet outer box with slide plate etc. complete as per the direction of Engineer-in-charge with brass cover plate.
Providing and fixing fly proof stainless steel grade 304 wire gauze with 0.5mm dia wire and 1.4mm wide aperture in aluminium door, window, ventilator shutters and partition etc. with PVC / neoprene gasket etc. complete as per the architectural drawings and the directions of Engineer-in-charge. (Cost of aluminium snap beading shall be paid in basic item).
Providing and fixing aluminium tower bolts ISI marked (anodized anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour or shade with necessary screws etc. complete.
Providing and fixing aluminium sliding door bolts ISI marked (anodized anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour or shade with necessary screws etc. complete. 300x16mm.
Providing and fixing aluminium handles ISI marked (anodized anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour or shade with necessary screws etc. complete.
Providing and fixing aluminium casement stays ISI marked anodized (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour or shade with necessary screws etc. complete.
Providing and fixing aluminium hanging floor door stopper ISI marked anodized (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour or shade with necessary screws etc. complete. Twin rubber stopper.
Providing and fixing aluminium pull bolt lock anodized ISI marked (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour and shade with necessary bolt nuts and washers etc. complete.
Providing and fixing aluminium tubular handle bar 32mm outer dia, 3.0 mm thick and 2100mm long with SS screw etc. complete as per direction of Engineer-in-charge. Powder coated minimum thickness 50 micron aluminium tubular handle bar.
Providing and fixing 100 mm brass locks (best make of approved quality) for aluminium doors including necessary cutting and making good etc. complete.
Providing and fixing 12mm thick frameless toughened glass door shutter of approved brand and manufacture including providing and fixing top and bottom pivot and spring type fixing arrangement and making necessary holes etc. for fixing required door fittings, all complete as per direction of Engineer-in-charge (door handle, lock and stopper etc. to be paid separately).
Providing and fixing anodized aluminium grill (anodized transparent or dyed to required shade according to IS : 1868 minimum anodic coating of Grade AC 15 of approved design / pattern, with approved standard section and fixing to the existing windows frame with C.P. brass/stainless steel screws @ 200mm centre to centre, including cutting the grill to proper opening size for fixing and operation of handles and fixing approved anodized aluminium standard section around the opening, all complete as per requirement and direction of Engineer-in-charge. (only weight of grill to be measured for payment).
Filling the gap in between aluminium frame and adjacent RCC /Brick/Stone work by providing weather silicon sealant over backer rod of approved quality as per architectural drawings and direction of Engineer-in-charge complete upto 5mm depth and 5mm width.
Providing and fixing structural glazing on required portion of the building with aluminium section (12 gauze using 5.5mm toughen glass with all necessary fittings) as per direction of Engineer-in-charge (AIS CHROMA – VLT – 23, u.v-4, SHGC-26, U Value-3.7.
P/F stainless steel (Grade 304) railing made of Hollow tubes channels, plates etc, including welded, grinding, buffing, polishing and making curvature (wherever required) and fitting the same withnecessary stainless steel nuts and bolts complete, i/c fixing the railing with necessary accessories and stainless steel dash fasteners, stainless steel bolts etc. of required size on the top of the floor or the side of waist slab with suitable arrangement as per approval of Engineer-in-charge, (for payment purpose only weight of stainless steel members shall be considered including fixing accessories such as nuts, bolts, fasteners etc.
Steel work welded in built-up sections/framed work including cutting hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required in gratings, frames, guard bar, ladders, railings, brackets, gates and similar work.
Providing and fixing false ceiling (ceiling tiles mineral fibre and ceiling 8821 of diamond make) at all height including providing and fixing of frame work made of special sections, power pressed from M.S. sheets and galvanized with zinc coating of 120 gms/sqm (both side inclusive) as per IS : 277 and consisting of angle cleats of size 25mm widex 1.6mm thick with flanges of 27mm and 37mm at 1200 mm centre to centre, one flange fixed to the ceiling with dash fastner 12.5mm dia x 40mm long with 6mm dia bolts, other flange of cleat fixed to the angle hangers of 25x10x0.5mm of required length with nuts and bolts of required size and other end of angle hanger fixed with G.I channels 45x15x0.9mm running at the spacing of 1200 centre to centre, to which the ceiling section 0.5mm thick buttom wedge of 80mm with tapered flanges of 26 mm each having clips of 10.5mm at 450mm centre to centre, shall be fixed in a direction perpendicular to G.I. intermediate channel with connecting clips made out of 2.64mm dia x 230mm long G.I wire at every junction, including fixing perimeter channels 0.5mm thick 27mm high having flanges of 20mm and 30mm long, the perimeter of ceiling fixed to wall / partition with the help of rawl plugs at 450mm centre to centre, with 25mm long drive all screws @ 230mm interval, including fixing of gypsum board to ceiling section and perimeter channels with the help of dry wall screws of size 3.5x25mm at 230mm C/C, including jointing and finishing to a flush finish of tapered and square edges of the gypsum board with recommended jointing compound, jointing tapes, finishing with jointing compound in 3 layers covering upto 150mm on both sides of joint and two coats of primer suitable for board, all as per manufactures specification and also including the cost of making openings for light fittings, grills diffusers, cutouts made with frame of perimeter channels suitably fixed all complete as per drawing and specification and direction of Engineer-in-charge.
P/F of Acoustical ceiling with 30% total area with black painted 8mm thick Hilus Calium Silicate in a way of step including G.I framing as per instructions (manual of manufacturer) and 70% area with 10mm GRGAcoustical panels (diamond made) 595x595Sqm edge with NRD > or 0.75 RH :99% fire resistance clause A 85-475 (suspension system) laid on powder coated “T” grid (24mm) made “Diamond” with batching of 50mm mineral wool complete job as per drawing.
Design manufacture, supply, installation, testing and commissioning Lift (Gearless with Machine room) of following specifications:- Drive Machine :- Geared Traction Load Capacity :- 1360 Kg Passenger Capacity :- 20 persons (Bed Lift) Control System :- Simplex automatic operation Maximum no. of stops :- 6 Max. rise :- 30 meters Car speed :- 1.00m/s Car Inside :- 1300 X 2400mm Power Supply :- 3 phase, 400/415V(+/-10) volts, 50(+/-5) Hz frequency Entrance :- Front only Door :- Automatic (Centre opening door) Pit Depth :- 1600mm Make:- OTIS, Johnson or equivalent.
P/F of 8mm thick Pleni Hilux Calcium Silicate ceiling moisture proof and heat proof with G.I framing.
Providing Acoustical wall cladding :-
a) Upto 4’ all round paneling with heavy duty stain resistance sq. edge planks with properties of dirt, dust and dirt repellence and scratchresidence, filled and fixed to wall with batching of 50mm thick mineral wool of plank size 1215x195x8.3mm (with wood grain surface).
b) Above 4’ upto ceiling level, covering on corner of walls and ends of windows with 8mm thick Hilux Calcium Silicate block painting and combination of 10mm GRG 595x595 Acoustical panel (diamond made) with 50mm thick mineral wood back filler filled and fixed with G.I framing as per instructions and drawings.
Providing and applying white cement based putty of average thickness 2mm, of approved brand and manufacture, over the plastered wall surface to prepare the surface even and smooth complete.
Distempering with oil bound washable distemper of approved brand and manufacture to give an even shade new work (two or more coats) over and including priming coat with cement primer.
Applying one coat of water thin able cement primer of approved brand and manufacture on wall surface.
Wall painting with plastic emulsion paint of approved brand and manufacture to give an even shade. Two or more coat on new work.
Finishing wall with premium acrylic smooth exterior paint with silicon additives of required shade on new work (two or more coats applied @ 1.43 ltr./10sqm over and including base coat of water proofing cement paint applied @ 2.20kg/10sqm).
Finishing walls with textured exterior paint of required shade on New work (two or more coats Rustic Regular of any colour as per Engg. incharge) over and including base coat of exterior primer applied @ 3.00kg/10sqm.
Providing and fixing nickel plated S.S. pipe curtain rods with nickel plated brackets. 25mm dia (heavy type).
Providing and fixing of hospital curtain track cubicle standard 9920 bent into “U” Shape and attached to the ceiling with 9953 bracket and fitted with 9932 iv tree carriers with white anodized as standard curtain ring complete job.
Providing and fixing aluminium composite panel 3mm exterior grade wooden shade and colour with complete installation testing and commission as per manufacturers with two layer of aluminium skins of 0.25mm thick sandwiching a thermo plastic core in continuous lamination process with PVDF coating exterior grade ensuring long colour and no fungal attacks. Base frame work with aluminium section shall be fixed over the brick work and RCC work it is includes cost of labour material accessories adhensive scaffolding wastages transport taxes fixing in to a neat finish in aesthetic point of view with out any undulation in the facias all complete as per drawing and instruction of Engineer-in- -charge.specific aluminium channel as per approved make
Providing and fixing AC-4 wooden flooring of tongued and grooved joint as per approved make EGO.
Providing and fixing vertical / roller blinds as per approved make DECK.
P/F of compact material impregnated with thermosetting resigns and bonded together by the high pressure process. The surface on both sides, having decorative colours or design are impregnated with melamine based resins. The core layers are impregnated with phenolic based resins. The high pressure process is defined as the simultaneous application of heat (temperature > 120 C) and high specific pressure (> 5 Mpa), to provide flowing and subsequent curing of the thermosetting resins to obtain a homogenous non-porous material with increased density (> 1350 kg/m3), and with the required surface finish. The board is manufactured as per IS 2046.
Glass reinforced concrete (GRC) screen made of white cement with a blend of glass fibre and other pigments in a dimension and size of 2”x2” thick border and customized size in terms of length and breadth all along the vertical and horizontal direction to be fixed on 3” x 3” MS hollow section square pipes of 3.5mm thick wall thickness to be fixed all along the surface with the help of dash fasterners by creating a grid of size 2’x4’ or 3’x6’. The complete MS Grid frame work is to be applied with red oxide metal primer and synthetic enamel paint and all screens (Jaali) to be fixed in uniform manner by using SS nail. Make :- Birla / Classic complete job.
Providing and fixing of exterior wall cladding made of Grc of size 8” x 2 ¼” (Brick type) made by using high quality pigments, with ruff texture finish with acrylic urethane transparent coating to prevent it from aungus nad elgae. Shade / colour to be approved by the Engineer-in-charge. Tiles to be fixed by using grey cement and curing to be done twice a day for proper bonding. The tiles to be fixed on dry plaster surface with spacer of 5mm and then filled it with matching grout and then deep cut pointing horizontally and vertically. Make :- Classic – GRC, Granimitz (Complete job).
Carriage of material by Mechanical Transport including loading / unloading and stacking at site complete.
Sand for an average lead of 40 Kms.
Stone aggregate below 40mm size for an average lead of 10 Kms.
Stone aggregate 40mm and above 40mm size for an average lead of 10 Kms.
Bricks for an average lead of 70 Kms
Disposal of excavated earth by MT including loading and unloading for an average lead 7 Kms outside municipal limit.
SITC of Prefabricated EPG puff wall panel and ceiling Panel (50mm thickness& 30 mm) for 08 nos of Operating Area as per tender technical specification enclosed. Make:- Hi-tech Med Gas Solutions /Life Line Medisol /Medical Healthcare Solution.
Painting of wall and ceiling with Anti microbial Paint as per specification Make:- Hi-tech Med Gas Solutions /Life Line Medisol /Medical Healthcare Solution.
SITC of Unidirectional Laminar Flow Air System with 6 H14 Minipleat HEPA Filters as per tender technical specification enclosed . Make:- Hi-tech Med Gas Solutions /Life Line Medisol /Medical Healthcare Solution.
SITC of Seamless flooring with perfectly curved resistance to mechanical stress and dynamic load and having Electro static discharge (ESD) / (anticonductive) protection characteristics 2 mm thick, washable- complete As per enclosed tender technical specification Make:- Hi-tech Med Gas Solutions /Life Line Medisol /Medical Healthcare Solution.
SITC of Recess LED luminaire dimension: (L x W) (590- 600)x(590-600) mm fitting made of powder coated finish with Fully Covered IP 65 with gasketting Make:- Hi-tech Med Gas Solutions /Life Line Medisol /Medical Healthcare Solution.
S/I/T/C of manual Screen Surgeon control panel, mounted flush in the theatre wall as per enclosed tender technical specifications. Make:- Hi-tech Med Gas Solutions /Life Line Medisol /Medical Healthcare Solution.
Double Arm Movable Pendant for Anaesthetist as per Tender Specifications Fully complies and meetas with HTM 02-01 and European Standards. Duly CE Marked Make:- Hi-tech Med Gas Solutions /Life Line Medisol /Medical Healthcare Solution.
Single Arm Movable Pendant for Surgeon as per Tender Specifications Fully complies and meetas with HTM 02-01 . Ce mark Make:- Hi-tech Med Gas Solutions /Life Line Medisol /Medical Healthcare Solution.
SITC of Twin Plate LED X-ray viewing Screen designed toprovide a high level of control luminance without flicker. Size 1000x700x95 mm Deep complete set as per enclosed tender technical specifications. Make:- Hi-tech Med Gas Solutions /Life Line Medisol /Medical Healthcare Solution.
SITC of Operating List Board as per tender Specification Make:- Hi-tech Med Gas Solutions /Life Line Medisol /Medical Healthcare Solution.
SITC of Storage Shelves as per tender Specification Make:- Hi-tech Med Gas Solutions /Life Line Medisol /Medical Healthcare Solution.
SITC of Scrub Sink- 2 bay- made in Stainless steel 304 Finish, having Sensor & Foot Operated with Thermostatic Mixing valve Make:- Hi-tech Med Gas Solutions /Life Line Medisol /Medical Healthcare Solution. control to Size maintain the water temperature, complete set, as per enclosed tender technical pecifications. The washing faucet will be made of Chrome plated brass hand. Make:- Hi-tech Med Gas Solutions /Life Line Medisol /Medical Healthcare Solution.
SITC of Hermetically Sealed Automatic operated with 2 door leaf , Complete with Automation Unit, frame, viewing window, complete set, as per enclosed tender technical specifications. Make:- Hi-tech Med Gas Solutions /Life Line Medisol /Medical Healthcare Solution.
SITC of Pressure Relief Dampers as per tender Specification Make:- Hi-tech Med Gas Solutions /Life Line Medisol /Medical Healthcare Solution.
SITC of Hatch box should be provided in each Operation Theatre to remove waste materials from the operation theatre to the dirty linen area just adjacent to operation theatre- as per technical specification Make:- Hi-tech Med Gas Solutions /Life Line Medisol /Medical Healthcare Solution.
SITC of Medical Gas copper pipeline inside the OT and the Provision to connect to Pendant Systems as per tender specifications (for all Modular Ots) Make:- Hi-tech Med Gas Solutions /Life Line Medisol /Medical Healthcare Solution.
Supply installation testing and commissioning of electrical wiring inside OT with all switch and sockets Make:- Hi-tech Med Gas Solutions /Life Line Medisol /Medical Healthcare Solution.
Planair Ceiling (Plenum box – Air Diffuser) – (cladding type OT) duly CE Marked as per technical specification Make:- Hi-tech Med Gas Solutions /Life Line Medisol /Medical Healthcare Solution.
Cascade Pressure stabiliser having muliti 304 grade stainless steel blade to control the room air pressure . Make:- Hi-tech Med Gas Solutions /Life Line Medisol /Medical Healthcare Solution.
DOUBLE COMBINATION OT CEILING LIGHT WITH LED TECHNOLOGY –indian as per tender technical specification enclosed Make:- Hi-tech Med Gas Solutions /Life Line Medisol /Medical Healthcare Solution.
SITC of 15 KVA UPS with Three Phase Input and Single phase Output and 30 Mins. Backup of APC / Numeric / IPS make Make:- Hi-tech Med Gas Solutions /Life Line Medisol /Medical Healthcare Solution.
Zonal Valve Box 5 Gas CE mark Make:- Hi-tech Med Gas Solutions /Life Line Medisol /Medical Healthcare Solution.
Oxygen - Indigenous
Cylinder Manifold with Individual NRV 10 + 10
Emergency Manifold Individual NRV 3 +3
Semi Automatic Control Nitrous imported Nitrous Mainfold 2+2 Make:- Greggerson/ Tedisel/ Trump.
Cylinder Manifold with Individual NRV 2 + 2
Manifold Line Regulator
Manifold Pigtail - Copper Tailpipe
Fully automatic oxygen control Panel (1500lpm) Imported CE Marked with Modified body Make:- Greggerson/ Tedisel/ Trump No. (0482).
Distribution of Copper Pipe Line (with Llyod Certification ) Indigenous Make:- Maxflow/Janya
12 mm O.D. X 0.7 mm thick
15 mm O.D. X 0.9 mm thick
22 mm O.D. X 0.9 mm thick
28 mm O.D. X 1.2 mm thick
42 mm O.D. x 1.2 mm thick
B.P.C. Flow Meter Metallic body with Humidifier Bottle Indigenous
Area Alarm Indigenous
Area valve service unit Indigenous CE Marked
Line Shut Off Isolation Valve - Indigenous Make:- RR/Universal/Conex
Gas outlet Front Loaded DIN/BS STD.with Probe - Imported with Modified body Make:- Greggerson/ Tedisel/ Trump No. (0482).
Oxygen
Nitrous
Vacuum
Conversion Kit for O.T. - Indigenous ( 3m Pipe ) Oxygen -7 Nitrous- 7 Make:- Hi-tech Med Gas Solutions /Life Line Medisol /Medical Healthcare Solution.
High Pressure Tubing Indigenous
Oxygen
Vacuum
Duplex Reciprocating Type Air Cooled Oil Free Air Compressors10HP motor (1 working, 1 Stand by) Make:- Anistiwata/IR
Vertical Air storage tank with all accessories Capacity:500 L
Electrical Control Panel
Air Dryer-60 CFM Dessicant type
Air filters (3 Stage) 1 micron 0.1micon,0.01 micron
Air Regulator with guage ( Pressure Reducing System ) 4kg 2 regulators 1 in standby condition 1 working condition similarly for 7 kg 2 regulators 1 in standby condition 1 working condition
Duplex Vacuum pump with motor 15 HP (1 working, 1 Stand by) Make:- Anistiwata/IR
Vacuum reservoir Tank with safety accessories Capacity: 1500L
Electrical Control Panel
Filter with Secretion Tap Bottle
Ward Vacuum Jar with regulator Indigenous Capacity:600 mL
Vacuum Jar Trolley for O.T. Indigenous
PLUMBING
SUB HEAD - I : SANITARY FIXTURES
Providing and fixing water closet squatting pan (Indian Type W.C Pan) with 100mm sand cost iron P or S trap, 10 ltrs low lewel PVC flushing cistern including flush pipe (Hindware make Cat No. 20070/ Kerovit make Cat No. 606) Manually controlled device (Handle lever) conforming to IS : 7231, with all fitting and fixture complete including cutting and making good the wall and floows wherever required. Orissa Pan white viterous china pan of size 580x440mm with integral type footrests.
Providing & fixing of white vitreous China pedestial type water closet (European Type) with cistern (A/PHAS-100 Cat No. 201100+Cat No. 21054 / Kerovit model No. 112 and flush tank model no. 1001) with CP bolts, nuts, CI chair hanging arrangements, bakelite seat & cover with CP hinges & rubber buffers, CP brass screw, washer with all accessories with WC connector with Rubber Lip / Buffer and side gap filled with silicon sealant wherever required. Including brass / SS screws and washer complete including cutting, making good the walls, floors, slab wherever required as per direction of Engineer-in-charge.
Providing & fixing of white vitreous china under counter oval wash basin/circular basin (Hindware 10080 / Kerovit model No. 206 & 207) with CP brass waste assembly, CP cast brass bottle trap with extension piece (Parko1535 or approved equivalent), 450mm long CP copper connections pipes ( Parko 1535 or approved equivalent), wall flanges and rubber adapters for waste connection complete including CI/MS brackets duly painted, nuts, washers, cutting and making good the walls floors wherever required as per direction of Engineer-Incharge.
Providing & fixing of white vitreous china wash basin with pedestal (Hindware Cat No. 1008 + Ped Cat No. 11003 / Kerovit model No. 234 Ped Model no. 305) with CP brass waste assembly, CP cast brass bottle trap with extension piece ( Parko1535 or approved equivalent), 450mm long CP copper connections pipes ( Parko 1535 or approved equivalent), wall flanges and rubber adapters for waste connection complete including CI/MS brackets duly painted, nuts, washers, cutting and making good the walls floors wherever required as per direction of Engineer-Incharge.
Providing and fixing of C.P. brass Central Hole Basin Mixer without Popup Waste System including with 450mm Long Copper Pipes & Brass Nuts with all fittings and accessories as per direction of Engineer-Incharge. (Kerovit make Cat No. 1511010-ND-CP or approved equivalent).
Providing & fixing white vitreous china flat back urinal with automatic flushing systems (Hindware 60021 / Kerovit model No. KS 510) comprising of all plumbing, electronic and electrical items. CP brass flush pipe with CP brass elbow, CP brass spreader, CP wall flange, infrared photo cells, eyes electrically operated solenoid valve, step down transformer / equipment and any other item required to provide satisfactory functioning including necessary wall cutting / chasing and making good, as required for urinal flushing complete as mentioned above as per direction of Engineer-Incharge.
Providing & fixing C.P. hand spray with lever control (health faucet) (Kerovit make KA580001 or approved equivalent) and flexible hose 1 m long connection with C.P. holder for hand spray complete in all respects as per direction of Engineer-Incharge.
Providing and fixing C.P. brass angle valve for basin mixer and geyser points of approved quality conforming to IS:8931 a) 15 mm nominal bore (Make Kerovit make Cat No. KB 1511003 or approved equivalent).
Providing & fixing C.P. brass robe hook ( Kerovit Cat No. 660003) or approved equivalent) fixed to wall/door with plastic rawl plugs and C.P brass screws including cutting and making good the walls wherever required as per direction of Engineer-Incharge.
Providing & fixing recessed liquid soap dispenser (Kerovit Cat No. 930009 or approved equivalent) as per direction of Engineer-Incharge.
P/F of Soap Dish Holder with all fittings as per direction of Engineer-in-charge (Kerovit Cat No KA 680004 or approved equivalent).
P/F of glass shelf 600mm long with all C.P fittings of approved quality complete item ( Kerovit Cat No KA 930005 or approved equivalent).
P/F of regular body concealed stop cock suitable for 15mm pipe line with protection cap ( Kerovit make Cat No. KB 111030 CP and exposed part Cat No. KB 1511032 or approved equivalent) with exposed part angular stop cock with flange FUS 29.53.
P/F PVC connection (Complete item).
Providing and fixing complete set of sanitary fixtures for handicapped toilets, Hindware Cat. no. 70002) comprising of EWC - P , Cistern, Seat Cover, Twin Flush Fittings, Wash Basin 450x300, Half pedestal, 1 faucet with spatula lever, 1 hinged rail and 2 grab bars, including cutting and making good the walls and floors wherever required complete as per directions of Engineer in charge.
Providing and fixing 6mm copper backed float glass mirror MODI / SAINT-GOBAIN including 6mm thick BWR type ply board, 40mm stainless steel channel plugged to wall, hard wood treated with two coats of wood preservative, etc. all complete as specified and shown in drawing complete to the satisfaction of Engineer in charge.
Providing and fixing Stainless Steel A ISI 304 (18/8) kitchen sink as per IS 13983 with C.I. brackets and stainless steel plug 40 mm including painting of fittings and brackets, cutting and making good the walls wherever required. Kitchen sink without drain board 610 x 460 mm bowl depth 200 mm (Pantry)
Providing and fixing, testing and commissioning of C.P. brass single hole sink mixer with CP wall flange, swinging spout complete as required and making good as per direction of Engineer-in-Charge ( Kerovit Cat No KB 2111025 or approved equivalent)
Providing and fixing CP brass towel rail of approved make complete with CP brackets fixed to wooden cleats with CP brass screws.(Kerovit make Cat No. KA 930001 or approved equivalent).
Providing and fixing 15 mm dia. C.P. brass bib cock of approved quality conforming to IS standards and weighing not less than 690 gms. (Short Body) (Make Kerovit Cat No. KB 2011004 or approved equivalent)
Providing and fixing C.P. brass long nose bib cock of approved quality conforming to IS standards and weighing not less than 810 gms. (15 mm dia.) (Make Kerovit make Cat No. KB 1511004 CP or approved equivalent)
Providing and fixing of wall mixer with provision for over head shower with 115mm long bend pipe on upper side connecting legs and wall flenges of approved quality with all fittings(Make Kerovit Cat No. KB 2011019 or approved equivalent).
Providing and fixing heavy class SS grating plane floor trap and setting in floor with cement mortar to matach the floor finish as per direction of Engineer-in-charge (size 100mm dia) ISI marked.
Providing & fixing storage type water cooler with plain & cold water facility of the following capacity, I.S.I marked, stainless steel front panel, C.P brass push cock, inlet float valve with all plumbing and electrical accessories, inlet, outlet, overflow and PVC drain out connection to F.D complete as required (Blue Star or equivalent).
Cooling capacity 20 Ltrs./hr (Model No. Bluestar PC240). Storage capacity 40 Ltrs.
Cooling capacity 40 Ltrs./hr (Model No. Bluestar PC480). Storage capacity 80 Ltrs.
Providing & fixing commercial 10 LPH water purifier of required capacity. Including all components as per manufacture specifications, including connection from water supply line, and final connection to water cooler electric wiring & plug top etc. with all accessories.
Providing & fixing vitreous china flat back C complete with pedestal size 550x430mm with C.I. brackets painted white, 32mm dia. C.P. waste, C.P chain and rubber plug, C.P. cast brass bottle trap with C.P.pipe to wall and C.P wall flange, rubber adapter for waste connection complete including cutting and making good the walls wherever required. (Hindware Cat no: 10032, Vijay Cat No: 565 Kerovit Cat No KO 285 & KO 314W or approved equivalent). Star White colour.
Providing and fixing White Vitreous bed pan sink with "P" traps bed pan accessories, vitreous china cistern of 10 liters capacity , flush pipe etc. including cost of cutting and making good the walls and floors wherever required complete. (VIJAY Cat No: 1025 or approved equivalent).
Providing and fixing CP Double Elbow action Surgical Basin mixer (Floor mounted) complete (Vijay Cat No: 1125).
Providing and fixing white vitreous china laboratory sink with C.I. brackets, C.P. brass chain with rubber plug, 40 mm C.P brass waste and 40mm C.P. brass trap with necessary C.P. brass unions complete, including painting of fittings and brackets, cutting and making good the wall wherever required. Size 600x450x200 mm.
Providing and Fixing stainless steel Laboratory sink 380 diax18 cms including CP Brass Waste with Bottle trap and connecting pipe to wall complete (Make-Anupam Modal No.510 or approved equivalent).
Providing and Fixing CP Brass Lab sink mixer with swinging spout (Wall mounted model) with 450 mm long braided hoses.(Make Vijay Cat. 891 or approved equivalent).
SUB HEAD - II : WATER SUPPLY.
Providing and fixing of Polyethylene/Aluminium/Polyethylene (PE-AL-PE) Composite Pipes as per IAPMO IGC- INDIA 308, UMC-1TM certification marked on the pipe at the interval not greater than 1 meter with nominal pipe size with manufacturer’s name or trade mark including all relevant DZR brass fittings as Female Elbows/Tees, MTC /FTC and Engineering plastic fittings with internal sealing system like Eq. elbows, Eq. tees, reducers, Straight couplers Connectors, clamps at one meter spacing, with PAP valves etc. Make Kitec , Maithilee and Vista. Concealed installation including cutting chases and making good in the wall etc, Complete in all respect.
1216 (16mm OD) pipe.
1620 (20mm OD) pipe.
Providing and fixing Polyethelene-Aluminium–Polyethelene (PE-ALPE) Composite Pressure Pipes conforming to IAPMO-IGC-INDIA 308. U.V. stabilized with carbon black having thermal stability for hot & cold water supply, capable to withstand temperature upto 80 0C, including all special fittings of composite material (engineering plastic blend and and brass inserts wherever required) e.g. elbows, tees, reducers, couplers & connector etc. with trenching, refilling and testing of joints complete as per direction of the Engineer-in-charge. External work.
1216 (16mm OD) pipe.
1620 (20mm OD) pipe.
2025 (25mm OP) pipe.
2532 (32mm OP) pipe.
3240 (40mm OP) pipe.
4050 (50mm OP) pipe.
Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer in Charge. Internal work.
15 mm nominal outer dia Pipes.
20 mm nominal outer dia Pipes.
25 mm nominal outer dia Pipes.
32 mm nominal outer dia Pipes.
Providing and fixing G.I. pipes complete with G.I. fittings excluding trenching and refilling etc. (external work) (Medium Class)
65 mm dia. nominal bore
80 mm dia. nominal bore
100 mm dia. nominal bore
150 mm dia. nominal bore
Providing and fixing ball valve (brass) of approved quality, High or low pressure, with plastic floats complete copatable to connection with composite pipe make :Rehau / Kitech/gebbrat )
15 mm nominal bore
20 mm nominal bore
25 mm nominal bore
32 mm dia. Nominal bore
40 mm dia. Nominal bore
50 mm dia. Nominal bore
Providing and fixing G.l. pipes complete with G.l. fittings and clamps, including cutting and making good the walls etc.INTERNAL WORK-Exposed on wall
15 mm dia. nominal bore (Medium)
20 mm dia. nominal bore (Medium)
25 mm dia. nominal bore (Medium)
32 mm dia. nominal bore (Medium)
40 mm dia. nominal bore(Medium)
50 mm dia. nominal bore(Medium)
Providing and fixing nitrile rubber insulation on hot water supply / return pipes. Make:- thermaflex/careflex
15 mm dia (9 mm thickness)
20 mm dia (9 mm thickness)
25 mm dia (9 mm thickness)
Providing and fixing insulation for Hot Water/ Steam with rockwool mattress of min. density 100 kg/cm2 and 50mm thick, to hot water and steam pipes, including cleaning of pipes, securely fixing of the sections of insulation to the pipes with all joints butted together tightly and stitching 24 SWG x 20mm mesh G.I. wire netting -over the pipe section and cladding with 24 gauge aluminum sheets with 50mm overlap and fixing with self tapping recessed screws complete. Make:- thermaflex/careflex
32 mm dia (13 mm thickness)
40 mm dia (13 mm thickness)
50 mm dia (13 mm thickness)
65 mm dia (13 mm thickness)
80 mm dia (13 mm thickness)
BUTTERFLY VALVE (MANUAL) with C I body SS Disc, Nitrile Rubber Seal & O- Ring PN 16 pressure rating for chilled water/hot eater circulation as specified Make:- NEU-G/sant/NVR
65mm dia.
80mm dia.
100mm dia.
Making connection of G.I. distribution branch with G.I. main of following sizes by providing and fixing Tee, including cutting and threading the pipe etc. complete
25 to 40 mm nominal bore
50 to 80 mm nominal bore
Providing & fixing Auto Air vent for cold water supply risers, suitable for pressure not less than 15 Kg/Sq.cm. Make:- NEU-G/sant/NVR
15 mm dia
20 mm dia
Providing and fixing in position of approved quality high pressure rated Brass Float Valve with copper ball float and brass rods of required length suitable for test pressure of not less than 15 Kg/sqcm of the following sizes. Make:- NEU-G/sant/NVR
40 mm dia
50 mm dia
Providing and laying Double Flanged (Screwed/ Welded) Centrifugally (Spun) Ductile Iron Pipes of Class K-9 conforming to IS : 8329 Make:- NEU-G/sant/NVR
100 mm dia Ductile Iron Double Flanged
Providing and placing on terrace (at all floor levels) polyethylene water storage tank ISI : 12701 marked, with cover and suitable locking arrangement and making necessary holes for inlet, outlet and overflow pipes but without fittings and the base support for tank Make:- suprime/sintax
Excavation of trenches of required width for pipes etc., including excavation for sockets, and dressing of sides, ramming of bottoms, depth upto 1.5m, including getting out the excavated soil, and then returning soil as required, in layers not exceeding 20cm depth including consolidating each deposited layer by ramming, watering etc. and disposing of surplus excavated soil as directed outside the site to the approved dumping ground. Minimum width of the trench should be external dia plus 400mm. Trenches to be excavated with required slope and shall be aligned as per drawing .
Pipes, cables etc, not exceeding 80 mm dia.
Pipes, cables etc. exceeding 80 mm dia. but not exceeding 300 mm dia
SUB HEAD - III : DRAINAGE SYSTEM.
Providing and fixing sound insulated Polyproplene piping (PP) system as per ON EN 1451-Part 1 & EN 12056 Part 1-5 , DIN 1986-100 - class B & D, with 3 layer pipe made of PP/PP-MV/PP in Blue Ral 5014 colour (free from halogen, cadmium and heavy metals), push-fit type, food safe, having high impact and stiffness, offering sound levels of not more than 16 dBA as per DIN 4109 at a flow rate of 4 l/s and having pipe ring stiffness of 6kN/m2 or more as per EN ISO 9969, density and elongation of pipe not more than 1.25gms/cm3 and 0.05mm/m0K respectively, tensile strength to be > 24 N/mm2, cost including all necessary fittings in blue colour, fitted with factory fitted lip ring Pipes and fittings to carry a 20 year guarante including supporting system GI clamps / hangers/G.I structure supports as per approved make with angle & fastner as required. including cost of core/hole cutting and making good the walls and floors wherever required. (Approved Make-Astral /Rehau/shanah )
160mm dia
110mm dia
75 mm dia
Providing and fixing to the inlet mouth of rain water pipe cast iron grating 15 cm diametre and weighing not less than 440 grams.
Providing, laying, testing & commissioning of UPVC pressure pipes of 6 Kg/Sq.cm pressure rating class V (IS : 4985-2000) including fittings, tees, bends, clamps, coupling and adaptors supports, and jointing with solvent joint, testing and necessary earth work in excavation, backfilling, disposal of surplus earth with a lead upto 50m complete, compaction and consolidation including bed concrete (if required), sand bedding all around UPVC pipe & fittings and thrust blocks at bends as per standard design (for Drainage Sump Pump Discharge Header). (Approved Make-Astral /Suprime /Truflow )
75 mm dia
110 mm dia
160 mm dia
200 mm dia
Providing and fixing sound insulated Polyproplene piping (PP) system as per ON EN 1451-Part 1 & EN 12056 Part 1-5 , DIN 1986-100 - class B & D, with 3 layer pipe made of PP/PP-MV/PP in Blue Ral 5014 colour (free from halogen, cadmium and heavy metals), push-fit type, food safe, having high impact and stiffness, offering sound levels of not more than 16 dBA as per DIN 4109 at a flow rate of 4 l/s and having pipe ring stiffness of 6kN/m2 or more as per EN ISO 9969, density and elongation of pipe not more than 1.25gms/cm3 and 0.05mm/m0K respectively, tensile strength to be > 24 N/mm2, cost including all necessary fittings in blue colour, fitted with factory fitted lip ring Pipes and fittings to carry a 20 year guarantee. for wash basin, urinals, indirect waste, Bath Tub etc (Approved Make-Astral /Rehau/shanah )
Providing & fixing Polyproplen clean out Plug (FCO & COP) with suitable insert keys for opening, male threaded joint with socket soil pipe/waste pipe of Polyproplen pipe as required. (Both for Pipes running under floor & along ceiling level) (Approved Make-Astral /Rehau/shanah )
Providing & fixing Polyproplen door cleaning piece male threaded joint with socket soil pipe/waste pipe of Polyproplen pipe as required. (Both for Pipes running under floor ) (Approved Make-Astral /Rehau/shanah )
Providing and laying cement concrete 1:5:10 (1 cement: 5 coarse sand: 10 graded stone aggregate 40 mm nominal size) including bed concrete as per standard design.
100 mm diameter
External
Excavation of trenches of required width for pipes etc., including excavation for sockets, and dressing of sides, ramming of bottoms, depth upto 1.5m, including getting out the excavated soil, and then returning soil as required, in layers not exceeding 20cm depth including consolidating each deposited layer by ramming, watering etc. and disposing of surplus excavated soil as directed outside the site to the approved dumping ground. Minimum width of the trench should be external dia plus 400mm. Trenches to be excavated with required slope and shall be aligned as per drawing .
Pipes, cables etc, not exceeding 80 mm dia.
Pipes, cables etc. exceeding 80 mm dia. but not exceeding 300 mm dia
Providing, fixing, jointing, testing and commissioning of UPVC “NU-DRAIN” for Drainage and sewerage/strom water application Pipe conforming to IS:15328 with all fittings such as bends, tees, elbow. The wall thickness of pipe and technical characteristic conforms to IS:15328 in SN8 stiffness class. The fitting dimension conforming to BS: EN1401-1998. The jointing to be completed with rubber ring/solvent weld joint as suitable at site for above basement level.(Aprroved Make- Supreme/astral/jain)
200 mm diameter
250 mm diameter
315 mm diameter
Providing, fixing, jointing, testing and commissioning of UPVC “ECODRAIN” structured wall Drainage Pipe conforming to IS:16098 (Part-I) with all fittings such as bends, tees, elbow. The wall thickness of pipe and technical characteristic conforms to IS:16098 (Part-I) in SN8. The fitting dimension conforming to BS: EN1401-1998. The jointing to be completed with rubber ring/solvent weld joint as suitable at site for use at non basement area. Make- Supreme/astral/jain
Providing and laying cement concrete 1:5:10 (1 cement: 5 coarse sand:10 graded stone aggregate 40 mm nominal size) including bed concrete as per standard design.
All around S.W. pipe
100 mm diameter S.W. pipe
150 mm diameter S.W. pipe
200 mm diameter S.W. pipe
250 mm diameter S.W. pipe
300 mm diameter S.W. pipe
Upto haunches of S.W. pipe
100 mm diameter S.W. pipe
150 mm diameter S.W. pipe
200 mm diameter S.W. pipe
250 mm diameter S.W. pipe
300 mm diameter S.W. pipe
Providing and fixing square- mouth PVC/S.W. gully trap class SP-1 complete with C.I. grating brick masonry chamber with water tight C.I. cover with frame of 300x300 mm size (inside) the weight of cover to be not less than 4.50 kg and frame to be not less than 2.70 kg as per standard design.
100x100 mm size P type
With common burnt clay F.P.S. (non modular) bricks of class designation 7.5
With Sewer bricks conforming to IS : 4885
150 x 100 mm size P type
With common burnt clay F.P.S. (non modular) bricks of class designation 7.5
With Sewer bricks conforming to IS : 4885
180 x 150 mm size P type
With common burnt clay F.P.S. (non modular) bricks of class designation 7.5
With Sewer bricks conforming to IS : 4885
Constructing brick masonry manhole in cement mortar 1:4 ( 1 cement: 4 coarse sand ) with R.C.C. top slab with 1:1.5:3 mix (1 cement : 1.5 coarse sand (zone- III) : 3 graded stone aggregate 20 mm nominal size), foundation concrete 1:4:8 mix (1 cement : 4 coarse sand (zone- III): 8 graded stone aggregate 40 mm nominal size),inside plastering 12 mm thick with cement mortar 1:3 (1 cement : 3coarse sand) finished with floating coat of neat cement and making channels in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4graded stone aggregate 20 mm nominal size) finished with a floating coat of neat cement complete as per standard design :
Inside size 90x80 cm and 45 cm deep including C.I. cover with frame (light duty) 455x610 mm internal dimensions, total weight of cover and frame to be not less than 38 kg (weight of cover 23 kg and weight of frame 15 kg) :
With common burnt clay F.P.S. (non modular) bricks of class designation 7.5
With Sewer bricks conforming to IS : 4885
Inside size 90x80 cm and 60 cm deep including C.I. cover with frame (light duty) 455x610 mm internal dimensions, total weight of cover and frame to be not less than 38 kg (weight of cover 23 kg and weight of frame 15 kg) :
With common burnt clay F.P.S. (non modular) bricks of class designation 7.5
With Sewer bricks conforming to IS : 4885
Extra for depth for manholes
Size 90x80 cm
With common burnt clay F.P.S. (non modular) bricks of class designation 7.5
With Sewer bricks conforming to IS : 4885
Providing orange colour safety foot rest of minimum 6mm thick plastic encapsulated as per IS : 10910 on 12mm dia steel bar conforming to IS : 1786 having minimum cross section as 23 mmx25 mm and over all minimum length 263mm and width as 165mm with minimum 112 mm space between protruded legs having 2 mm tread on top surface by ribbing or chequering besides necessary and adequate anchoring projections on tail length on 138 mm as per standard drawing and suitable to with stand the bend test and chemical resistance test as per specifications and having manufacture’s permanent identification mark to be visible even after fixing. including fixing in manholes with 30x20x15 cm cement concrete block 1:3:6 ( 1 cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size) complete as per design.
Supplying and fixing C.I. cover without frame for manholes:
455x610mm rectangular C.I. cover (light duty) the weight of the cover to be not less than 23 kg.
500 mm diameter C.I. cover (medium duty) the weight of the cover to be not less than 58 kg.
560 mm diameter C.I. cover ( heavy duty) the weight of the cover to be not less than 108 kg
Supplying and fixing C.I. cover 300x300 mm without frame for gully trap (standard pattern) the weight of cover to be not less than 4.5kg.
Making connection of drain or sewer line with existing manhole including breaking into and making good the walls, floors with cement concrete 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) cement plastered on both sides with cement mortar 1:3 ( 1 cement : 3 coarse sand) finished with a floating coat of neat cement and making necessary channels for the drain etc. complete
For pipes 100 to 250 mm diameter
Providing sand cast iron drop connection externally for 60 cm drop from branch sewer line to main sewer manhole including inspection and cleaning eye with chain and lid, sand cast iron drop pipe and bend encased alround with cement concrete 1:5:10 ( 1 cement : 5 fine sand : 10 graded stone aggregate 40 mm nominal size) with all centering and shuttering required, cutting holes in walls and making good with brick work in cement mortar 1:4 ( 1 cement : 4coarse sand) plastered with cement mortar 1:3 (1 cement :3 coarse sand)on inside of the manhole wall lead caulked joints between sand cast iron pipes and fittings, stiff cement mortar 1:1 ( 1 cement : 1 fine sand) joints between sand cast iron tee and S.W. pipe, making required channels complete as per standard design and specifications :
100 mm dia. sand cast iron drop connection
150 mm dia. sand cast iron drop connection
Extra for depths beyond 60 cm of sand cast iron drop connection complete :
For 100 mm dia. sand cast iron drop connection
For 150 mm dia. sand cast iron drop connection
WATER SUPPLY, DRAINAGE, PUMPS & EQUIPMENT
Providing and fixing centralized water level controller cum indicator system, as per the following details:
Centralised PLC control panel along with touch-screen display board (min. 8" Diag. size) along with all accessories for complete controls & indication. Panel shall be made out of CRCA sheet min. 2mm thick having necessary interlocks, I/O's, required number of repeater amplifiers, all audio-visual alarms as required specifications as listed below. An emergency stop push button shall be provided in the panel. The panel shall have Modbus compatibility for seamless BMS/BAS Integration and shall be of approved make. The complete system control matrix, wiring diagram, SLD's and technical details shall be submitted by the vendor and gotten approved before commencement of execution of works.(Approved Make:-Domond electrical/Advance automission).
Water level indicators cum controllers working on hydrostatic pressure measurement principle made of Stainless Steel for installation on storage tanks, and capable of providnig 4 to 20 mA analog signal compatible with PLC signal inputs and complete as per working requirements for details of equipment below. All control outputs to MCC panel shall be included as per requierments.Approved Make : Diomond electrical & Advanace Automission)
Fire Static Underground tanks
Real-Time water level indication monitoring
V. Low Level audio-visual alarm at less than 25% total capacity.
Raw Water Underground tanks
Real-Time water level indication monitoring
V. Low Level audio-visual alarm at less than 30% total capacity.
V. High Level audio-visual alarm at more than 100% total capacity.
Auto cut-in of tubewell pumps at 35%
Auto cut-out of tubewell pumps at 95%
Auto cut-out of raw water pumps at 35%
Domestic Water Underground tanks
Real-Time water level indication monitoring
V. Low Level audio-visual alarm at less than 30% total capacity.
V. High Level audio-visual alarm at more than 100% total capacity.
Auto cut-in of raw water pumps at 35%
Auto cut-out of domestic water pumps at 35%
Flushing Water Underground tanks At STP
Real-Time water level indication monitoring
V. Low Level audio-visual alarm at less than 30% total capacity.
V. High Level audio-visual alarm at more than 100% total capacity.
Auto cut-in of raw water pumps (from STP) at 35%
Auto cut-out of flushing water pumps at 35%
Domestic Water Overhead tanks
Real-Time water level indication monitoring
V. Low Level audio-visual alarm at less than 30% total capacity.
V. High Level audio-visual alarm at more than 100% total capacity.
Flushing Water Overhead tanks
Real-Time water level indication monitoring
V. Low Level audio-visual alarm at less than 30% total capacity.
V. High Level audio-visual alarm at more than 100% total capacity.
Providing complete testing kit with all chemicals complete suitable for conducting test on water quality. The test kit shall be suitable to measure TDS, pH, Hardness, Iron content and other parameters
Supply, installation, testing and commissioning of horizontal centrifugal pumping set with cast iron body, bronze impeller, shaft of SS 316l and C.I. base & head with mechanical seal, connected to a TEFC induction motor suitable for 415 +/- 10% volts, 3 phase 50 cycles A.C supply with 150 mm dia pressure gauge with gunmetal isolation cock, vibration eliminating pads under foundation, dry running Protection, 80x40 mm I section base plate bolted to cement concrete foundations complete including isolation valves, vibration eliminators on both suction & delivery side of pumps and NRV on delivery side of pumps .Vendor to submit performance curves and technical catalogue of the proposed model for review and information. (Approved Make:-Groundfoss/Lubi ).
Filter Feed Pumps
Set of two pumps (1 Working + 1 Standby)
Capacity - 12LPS ( Suggested and quoted for 5000LPH)
Head - 30.0 Mtr.
H.P. - 7.0 HP Approx.
Supply, installation, testing & commissioning of vertical self supporting filtration unit fabricated from MS sheet as per IS: 2825 (minimum thickness of shell 10 mm and dished ends 12 mm) pressure gauges, sample cock, GI class 'C' face piping, CI butterfly valves and all accessories, with initial charge of filter media including anthracite, painting inside with epoxy paint and outside with two coat of red oxide primer and two or more coat of synthetic enamel paint, testing and commissioning complete.
Mulitgrade Pressure Sand Filter
Capacity - 42000 lph
Filtration rate - 17500 lph/sqm
Filter dia approx. - 1400 mm
Working pressure: 3.0 Kg/sq cm.
Test pressure : 4. 5 Kg/sq cm
Activated Carbon Filter
Capacity - 42000 lph
Filtration rate - 17500 lph/sqm
Filter dia approx. - 1400 mm
Working pressure: 3.0 Kg/sq cm.
Test pressure : 4. 5 Kg/sq cm
Supply, installation, testing & commissioning of metering pump type chemical doser with 100 lits. PVC/HDPE solution tank, injection fitting assembly, suction and delivery hose upto the point of injection, capacity 0-6 lph, complete in all respects.
Flow Rate : 42 Cum/Hr
Supply, installation, testing & commissioning of all pipings (as described below) and isolation control valves including all necessary fittings and clamps, supports, hangers as required i/c cutting and making good the walls wherever required complete in all respects for making the system complete.
GI : Submerged air piping( We suggest uPVC. GI is never used for submerged piping)
MS Epoxy : Air piping & pumped effluent riser (non-submerged)
G.I Class : Interconnecting pipe line after delivery header of pump/filter
Controllers with low voltage relays, stainless steel probes and pvc shroud, control cabling as required length. (No of probes as required for function of each controller).
Hydro-pneumatic pumping system for Domestic water supply to OHT
Providing, fixing and testing of packaged type skid mounted hydropneumatic system with variable frequency drive type comprising of :
(i) Vertical, inline multistage centrifugal pumping set with stainless steel SS-316l stage casing and SS-316L impellers with stainless steel SS-316L shaft as per IEC standards and GJL250 cast iron suction & discharge casing, connected to TEFC ventilated induction motor of 2 pole, 2900rpm, suitable for 400/440 Volts, 3 phase, 50 Hz A.C. supply.
(ii) Pressure vessel of non corrosive FRP composite construction lined with NSF and/or FDA listed material, like high density polyethylene with fully replaceable polyurethane. Air cell burst pressure of minimum of 5 times the vessel operating pressure and cycle tested for 2,50,000 cycles.
(iii) Control Panel with programmable logic controller (PLC) for cyclic operation of pumps + Multi Variable Frequency Drive. The Pump working sequence should change after every operation.Contractor overload relays and MCBs should confirm to IEC 898 – 1995/ specifications. Blinking indications for pumps start, trip, low level trip, health supply should be provided in the panel along with the ammeter & voltmeter. Control panel should also consist of cooling fan.
(iv) Pressure switches bellow type fitted with micro switch and having maximum pressure and differential scale should confirming BS-6134 standards and IP55 protection class.
(v) All required Ball Valves, Non-return valves, flexible connectors etc. and all required accessories, Heavy Duty S.S 316 Manifold to make the system completely operational as a skid mounted system. Ball valves to be used should be Hot Pressed brass OT-58 with stainless steel ball and P.T.F.E seal and O-Ring. NRVs to be used should be with Springs and O-Ring arrangement.
(Vendor to submit performance curves and technical catalog of the proposed model for review & information)
Complete manifold system shall be factory aasembled & totally mounted on a common base frame with following duties:
Note: Contractor to note that the suction header is required to have inlet connection from the Puddle Flange @ water tanks and to the pump suction. Provision of delivery header is required to have outlet connection from the pumps. Suitable outlet flanges from the delivery mainfold / header shall be provided as required.(Approved Make:-Groundfos/Lubi ).
For Domestic water supply
No. of Pumps :1 (1 Working +1 Standby)
Capacity : 600 LPM each pump
Head : 75 Meters
apx. HP (Motors) :7,5 HP
Location : Plumbing Plant Room
For soft water supply
No. of Pumps :1 (1 Working +1 Standby)
Capacity : 100 LPM each pump
Head : 70 Meters
apx. HP (Motors) : 5 HP
Location : Plumbing Plant Room
For flushing water
No. of Pumps :1 (1 Working +1 Standby)
Capacity : 300 LPM each pump
Head : 75 Meters
apx. HP (Motors) : 3 HP
Location : STP Plant Room
Garden hydrents & floor washing Relift pump
Providing and fixing vertical, inline multistage centrifugal pumping set (Complete manufactured Skid-Mounted arrangement with manifold and accessories) with stainless steel SS-304 stage casing and SS-304 impellers with stainless steel shaft as per IEC standards and GJL250 cast iron suction & discharge casing, connected to TEFC ventilated induction motor of 2 pole, 2900 RPM, suitable for 400/440 Volts, 3 phase, 50 Hz A.C. supply with pressure gauge and with gunmetal isolation cocks, vibration elimination pads etc. complete with base and frame, nuts and bolts and necessary RCC foundations as per requirement as per instructions and pump shall have following duty:(Approved Make:-Groundfoss/Lubi ).
No. of Pumps :2 (1 Working +1 Standby)
Capacity : 350 LPM each pump
Head : 55 Meters
apx. HP (Motors) : 4 HP
Location : STP Plant Room
Vendor to submit proposed pump model with duty curve.
For WTP & STP Plant room drainage
Flow rate : 450 LPM
Head : 15 Mts
Solid Handling : 100 MM
Location : Sump of Basement
Purpose : Plant Room & general area Drainage
MOC : SS body SS Impeller & Shaft
Grase separator
Providing and installation For underground installation, installation depth 550 - 950 mm, with integrated sludge trap, polymer upper section, vertically adjustable, rotatable and tiltable up to 5°, cast iron cover in load class B based on EN 124, odor tight. Ø 110 in- and outlet according to DIN 1953419560 (PP or AS piping). Version: Right (can be changed to left side version by exchanging inlet and outlet). Certification number: Z-54.1-474 Size: NS 4 Sludge trap capacity: 400 liter Total separator capacity: 400 liter Grease storage capacity: 160 liter Inlet / Outlet: DN 100 (DA 110 mm) Sludge trap capacity: 400 l Total separator capacity: 370 l Fat storage: 160 l Certification: Z-54.1-440 Weight: 130 kg Dimension: 1470 x 1300 mm Inspection chambers may be installed in a maximum of 500 mm groundwater Recomended Manufacturer: KESSEL
Sump Pumps for Sewarage Sumps
Providing and fixing compact monoblock dry motor submersible pumps for suitable rating, with non-clog free flow open impeller, minimum solid handling capacity of 100mm suitable for operation on 220/415 volts + 5% -15%, 50 C/s A.C single/3 phase supply, speed 960/1440R&M including oil chamber, guide wire for lifting & lowering of pump, M.S. galvanized lifting chain, duck foot bend with following specifications: (2 No. of Pumps : - 1 working + 1 stand by)
The above pump sets must be supplied complete with following accessories.
Complete piping 100mm dia common delivery upto 1.5m as per enclosed tentative layout. (The pipe should be preferably CI LA/heavy duty M.S) -- 1 Set
100mm dia K sluice valve.-- 2 Nos
100 mm dia Flap type Non-return valve.-- 2 Nos
Necessary cables from pump set to control panel (position of panel marked in enclosed layout in plant room).-- 1 Set
Electrical switch panel having all necessary accessories & safety devices of standard specifications. (Panels with sump pumps near each sump as per site conditions). --1 No.
Automatic built-up water level controller with necessary length of cable upto control panel.
Discharge - 15 Cu.m/hr.
Total head - 15 m
Make - KSB
(Complete set as above with 2 nos. pumps. No extra payment shall be made for valves)
Manhole Cover for U.G Tanks and Sumps
Supplying and fixing C.I. cover without frame for manholes :
Providing and fixing extra heavy duty, double seal, water tight C.I manhole cover and frame specially casted for placing over the underground water tanks with lifting and locking arrangements as per approved sample, complete in all respect including fixing in PCC as per site requirement.
Providing and fixing stainless steel ladder, wall mounted of 4m height(app) for underground tanks complete with flanged ends and inserts (removable type) made of 38mm/42mm dia 16 G S/S 304 quality pipe made as per international quality standards of approved shape and size with non skidding steps at 300mm vertical spacing, complete as directed by the engineer in charge.
FIRE PUMPS AND ACCESSORIES
DSR_AOR_FOR_WET_RISER_AND_SPRINKLER_SYSTEM_2019
Supplying, installation, testing and commissioning of Electric driven Main Fire Pump suitable for automatic operation and consisting of following, complete in all respects, as required :
Horizontal type, multistage, centrifugal, split casing pump of cast iron body & bronze impeller with stainless steel shaft, mechanical seal conforming to IS 1520.
Suitable HP Squirrel cage induction motor, TEFC, synchronous speed 1500 RPM, suitable for operation on 415 volts, 3 phase 50 Hz, AC supply with IP 55 protection for enclosure, horizontal foot mounted type with Class-'F' insulation, conforming to IS-325.
M.S. fabricated Common base plate, coupling, coupling guard, foundation bolts etc. as required.
Suitable cement concrete foundation duly plastered with anti vibration pads.
Complete manifold system shall be factory aasembled & totally mounted on a common base frame with following duties:
Approved Make of Pump - Grundfos/ LUBI/ Mathenplatt
Note: Contractor to note that the suction header is required to have inlet connection from the Puddle Flange @ water tanks and to the pump suction. Provision of delivery header is required to have outlet connection from the pumps. Suitable outlet flanges from the delivery mainfold / header shall be provided as required.
2850 lpm at 70 m Head
Supplying, installation, testing and commissioning of diesel engine driven main fire pump suitable for automatic operation and consisting of following, complete in all respects,as required : (Diesel Driven Pump)
Horizontal type, multistage, centrifugal pump of cast of iron body and bronze impeller with stainless steel shaft, mechanical seal conforming to IS 1520.
Suitable HP, 1500 RPM water cooled with radiator, diesel engine conforming to relevant IS standard complete with auto starting mechanism, 12 /24 volts electric starting equipment, diesel tank, exhaust pipe extended upto 10 m outside pump house duly insulated with 50 mm thick glass wool with 1.0 mm thick aluminium sheet cladding, residential silencer, instruments and protection as per standard specification, stop solenoid for auto stop in the event of fault with audio indications, painted with post office red colour etc. as required.
M.S fabricated, common base plate, coupling, coupling guard, foundation bolts etc. as required.
Suitable cement concrete foundation duly plastered and with anti vibration pads.
2850 lpm at 70 m Head
Complete manifold system shall be factory aasembled & totally mounted on a common base frame with following duties:
Approved Make of Pump - Grundfos/ LUBI/ Mathenplatt
Note: Contractor to note that the suction header is required to have inlet connection from the Puddle Flange @ water tanks and to the pump suction. Provision of delivery header is required to have outlet connection from the pumps. Suitable outlet flanges from the delivery mainfold / header shall be provided as required.
Supplying, installation, testing and commissioning of electric driven pressurisation pump suitable for automatic operation and consisting of following, complete in all respects, as required : (Jockey Pump)
Horizontal type, multistage, centrifugal pump of cast iron body and bronze impeller with stainless steel shaft, mechanical seal conforming to IS : 1520.
Suitable HP squirell cage induction motor TEFC type suitable for operation on 415 volts, 3 phase 50 Hz AC supply with IP 55 class of protection for enclosure, horizontal foot mounted type with Class-'F' insulation, conforming to IS : 325.
M.S.fabricated Common base plate, coupling, coupling guard, foundation bolts etc. as required.
Suitable cement concrete foundation duly plastered and with anti vibration pads.
180 lpm at 70 m Head
Complete manifold system shall be factory aasembled & totally mounted on a common base frame with following duties:
Approved Make of Pump - Grundfos/ LUBI/ Mathenplatt
Note: Contractor to note that the suction header is required to have inlet connection from the Puddle Flange @ water tanks and to the pump suction. Provision of delivery header is required to have outlet connection from the pumps. Suitable outlet flanges from the delivery mainfold / header shall be provided as required.
CONTROL PANELS
Fabrication, supply, Insallation testing & commissioning of Electrical control panel of cubical construction, floor mounted type, fabricated out of 2mm thick CRCA sheet, compartmentalised with hinged lockable doors, dust and vermin proof, powder coated of approved shade after 7 tank treatment process, cable alley, inter-connection with suitable size copper conductor cable/solid copper strip, having switchgears and accessories, mountings and internal wiring, earth terminals, numbering etc. complete in all respect, suitable for main fire pump, pressurisation pump & diesel pump set complete as per CPWD specification with following in coming and Outgoings, suitable for operation on 415V, 3 phase, 50Hz Ac Supply with enclosure protection class IP 42 as required :
Incomings
LED type RYB phase indicating lamps, ON, OFF, trip indicating lamps Set of Copper Bus Bar 800Amps
Outgoings
Main Fire Pump
Jockey Pump
Diesel Engine Control
Control for diesel engine comprising -Automatic/Manual selctor switch & 3 attempts starting device, timers and relays as required, push buttons, start/stop in manual mode
Indicating lamp for high/ Low Lub. Oil pressure, High Water Temp and Engine on indication
System Controller
Designing, Supply, Installation, Testing and commissioning of system controller to control operation of main electric fire pump, diesel pump, Pressurization pump, Terrace pump in sequence as per specification consisting of relays, timers. Sensors, annunciation window for fault indication, complete as per specification
Designing, Supply, Installation, Testing and commissioning of system controller to control operation of main electric fire pump, diesel pump, Pressurization pump, Terrace pump in sequence as per specification consisting of relays, timers. Sensors, annunciation window for fault indication, complete as per specification
Providing laying, testing & commissioning of 'C' class heavy duty MS Pipe conforming to IS1239/3589 i/c fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. in ground including welding, excavation & providing cement concrete blocks as supports, anticorrosive treatment with coaltar/asphalt tape as per IS 10221, refilling the trench etc. of following sizes complete as required.
200 mm. dia (wall thickness = 6.3 mm)
150 mm. Dia
Providing laying, testing & commissioning of 'C' class heavy duty MS Pipe conforming to IS3589 i/c fittings like elbows, tees, flanges etc. below 50mm should be of Ductile iron conforming to ASTM A-536, Grade 65-45-12, BSPT threads with FM approval and UL listed. Fittings should be anti rust coated in threadings and anti rust black finish. Make:- NEW/VICTUALIC/TYCO. for fitting above 50mm like elbow, tees, couplings, concentric reducers, flanges etc should be grooved fittings shall be manufactured in two segments of cast ductile iron, conforming to ASTM A-536, Grade 65-45-12. Gasket shall be pressure-responsive EPDM rubber, grade to suit the intended service, conforming to ASTM D-200. Mechanical coupling bolts shall be zinc plated/chrome finish, heat treated carbon steel track conforming to ASTM A-449 and A-183, No welding is to be done anywhere in the fire fighting system. Rubber gasket should be of EPDM grade. The grooving machine shall be supplied by the same company as grooved fittings as to maintain conformity of grooving.Make:- NEW(JTPR)/VICTUALIC/TYCO.
25 mm dia
32 mm dia
40 mm dia
50 mm dia
65 mm dia
80 mm dia
100 mm dia
150 mm dia
200 mm dia (IS:3589 (wall thickness = 6.3 mm)
250 mm dia IS:/3589 (wall thickness = 6.3 mm)
Providing laying, testing & commissioning of 'C' class heavy duty MS Pipe conforming to IS1239 & IS3589 i/c fittings like elbows, tees, flanges etc. below 50mm should be of Ductile iron conforming to ASTM A-536, Grade 65-45-12, BSPT threads with FM approval and UL listed. Fittings should be anti rust coated in threadings and anti rust black finish. Make:- NEW(JTPR)/SANT /NVR. for fitting above 50mm like elbow, tees, couplings, concentric reducers, flanges etc should be grooved fittings shall be manufactured in two segments of cast ductile iron, conforming to ASTM A-536, Grade 65-45-12. Gasket shall be pressure-responsive EPDM rubber, grade to suit the intended service, conforming to ASTM D-200. Mechanical coupling bolts shall be zinc plated/chrome finish, heat treated carbon steel track conforming to ASTM A-449 and A-183, No welding is to be done anywhere in the fire fighting system. Rubber gasket should be of EPDM grade. The grooving machine shall be supplied by the same company as grooved fittings as to maintain conformity of grooving.Make:- NEW(JTPR)/SANT /NVR.
OPTIONAL
65 mm dia
80 mm dia
100 mm dia
150 mm dia
200 mm dia (IS:3589 (wall thickness = 6.3 mm)
250 mm dia IS:/3589 (wall thickness = 6.3 mm)
Supplying and fixing single headed internal hydrant valve with instantaneous Gunmetal/Stainless Steel coupling of 63 mm dia with cast iron wheel ISI marked conforming to IS 5290 (Type -A) with blank Gunmetal/Stainless Steel cap and chain as required :Make:- Safeguard
Single headed Gunmetal
Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required : MAKE;- NEU-G/SANT /NVR
80 mm dia
100 mm dia
150 mm dia
Supplying, fixing, testing & commissioning of double flanged sluice valve of rating PN 1.6 with non rising spindle, bronze/gun metal seat, ISI marked complete with nuts, bolts, washers, gaskets and conforming to IS 780 of following sizes as required : MAKE;- NEU-G/SANT /NVR
80mm dia
100mm dia
150mm dia
200mm dia
Supplying and fixing orifice plate made out of 6 mm thick stainless steel (Grade 304) with orifice of required size to be fitted between flange & landing valve of external and internal hydrants to reduce pressure at the outlet to the level of 3.5 kg/cm2 complete as required.Make:- Safeguard
Providing, installation, testing and commissioning of non-return valve of following sizes confirming to IS: 5312 complete with rubber gasket, GI bolts, nuts,washers etc.as required MAKE;- NEU-G/SANT /NVR
100mm dia
150mm dia
200mm dia
Providing, installation, testing and commissioning of stainless steel Y-strainer fabricated out of 1.6 mm thick stainless steel, Grade 304, sheet with 3 mm dia holes with stainless steel flange. MAKE;- NEU-G/SANT /NVR
100mm dia
150mm dia
Supplying and fixing 63 mm dia, 15 m long RRL hose pipe with 63 mm dia male and female couplings duly bound with GI wire, rivets etc. conforming to IS 636 (type-A) as required :
Gun Metal
Supplying and fixing first-aid Hose Reel with MS construction spray painted in post office red, conforming to IS 884 complete with the following as required.Make:- Safeguard
20 mm nominal internal dia water hose thermoplastic (Textile reinforced) type -2 as per IS: 12585
20 mm nominal internal dia gun metal globe valve & nozzle.
Drum and brackets for fixing the equipmets on wall.
Connections from riser with 25 mm dia stop gun metal valve & M.S. Pipe and socket.
Supplying & fixing 63 mm dia gun metal short branch pipe with 20 mm nominal internal diameter size nozzle conforming to IS 903 suitable for instantaneous connection to interconnect hose pipe coupling as required :Make:- Safeguard
Gun metal
Supplying and fixing of fire brigade connection of cast iron body with gun metal male instantaneous inlet couplings complete with cap and chain as reqd. for suitable dia MS pipe connection conforming to IS 904 as required :Make:- Safeguard
2 way-100 mm dia M.S. Pipe
4 way - 150 mm dia M.S. Pipe
3 way - 150 mm dia M.S. Pipe
Supplying and fixing air vessel made of 250 mm dia, 8 mm thick MS sheet, 1200 mm in height with air release valve on top and flanged connection to riser, drain arrangement with 25 mm dia gun metal wheel valve with required accessories, pressure gauge and paintingwith synthetic enamel paint of approved shade as required.Make:- Safeguard
Providing, fixing, and testing of 15mm dia. Chrome finished sprinkler head with Quick response 5mm quartz bulb and to operate at 68°C (of K-Factor 5.6 or as NFPA) complete as per given specifications.(UL Listed & FM Approved) Make : Rapid drop/ Viking/TYCO
Pendent Sprinkler 68°C (Quick Response)
Upright Sprinkler 68°C (Quick Response)
Side wall Sprinkler 680C (Quick Response) with rosette plate
Pendant Sprinklers (Concealed Model complete with mounting cup & white painted cover plate.
Providing & fixing of pressure switch in M.S. pipe line including connection etc. as required.
Providing & fixing flow switch in following sizes M.S. pipe including connection etc as required.
100mm dia
150mm dia
Providing, fixing, testing & commissioning of installation control valve of cast iron body, brass/bronze working parts comprising of water motor alarm, bronze seat clapper, clapper arm and hydraulically driven mechanical gong bell to sound continuous alarm when the wet riser/sprinkler system activates, pressure gauges, emergency releases, strainer, pressure switch, cock valve complete with drain valve and bypass, test control box, ball valves, MS pipe of required size, flanges, orifice plate, gasket etc of follwing sizes as required :Make:- Rapid drop/vking/tyco .
150mm dia
Supplying, installation, testing & commissioning of sprinkler flexible pipe (UL Listed) of stainless steel complete with 15 NPT on reducer thread with maximum working pressure of 175 PSI test pressure of 875 PSI (Burst) with branch line (Inlet) 25mm NPT male thread to sprinkler head (Outlet) 15mm NPT female thread with reducer, nipple, 2 side brackets, center bracket, stockbar of following sizes complete as required.Make:- Rapid drop/safeguard.
Providing and fixing in position the industrial type pressure gauges with gun metal / brass valves complete as required (E&M)
Providing and fixing MS cabinet (size 750x600x250 mm) fabricated from 16 gauge MS sheet with full front glass door & locking arrangement for pad lock with suitable shelves for keeping 25 Nos. spare sprinklers & one no. spanner properly fixed in shelves. Cabinet shall be painted with enamel paint of approved shade. (Cost shall include 20 Nos. spare sprinklers (5 Nos side wall 20Nos pendent, one No. spanner and 5 rolls of teflon tape ). :Make:- Safeguard
Providing & fixing FIRE shaft door with frame section (100X50)mm made up of 1.6mm (16SWG) MS sheet with Powder coated including necessary locking arrangement & 5mm glass with Chest handle as required,including painting (RED Powder Coated ) with "FIRE SHAFT " legend. Size (1200 x 2100) mm: Make:- Safeguard
Providing and fixing weather proof lockable cabinet of size notless than 2100mmx900mmx715mm made out of G.I. sheet of 18 gauge thickness having central opening and 4mm thik glazed glass doors(two no.) suitably marked on the out side with the letters FIRE HOSE including necessary locking arrangement and shall be painted with powder coating and two coat of synthetic enamel paint of approved shade. The cabinet shall be suitable to accommodate 2no.or4 no. 15mtr long hose pipe &2no branch pipe nozzle.It shall be mounted on raised brick platform complete as required:Make:- Safeguard
NOVEC-1230 GAS BASED FIRE TRACE SYSTEM COMPRISING OF PROVIDING ALL MATERIAL, EQUIPMENT, INSTALLATION, LABOUR, TESTING, COMMISSIONING & HANDING OVER OF THE ENTIRE SYSTEM, WITH THE FOLLOWING COMPONENTS:
MAIN SYSTEM
Providing & fixing 180 Liters Capacity (or as per Calculation)Seamless Steel Cylinder Complete with Pnematical Valve Assembly arrangement, supervisory switch connection for minitoring cylinder pressure, in compliance with Chief Controller of Explosive, Nagpur with electric & pressure operated control heads as per requirement (Master/Slave Actuation Packages) a safety burst disc, and any other accessories to make the cylinder completely operational. . (UL Listed & FM Approved)
Providing NOVEC 1230 Gas, factory-filled in the Gas Cylinder, as per the specifications and manufracturer recommendations.. (UL Listed & FM Approved)
Providing & Fixing Discharge Nozzles designed to provide the proper flow rate and distribution of gas to total flood a hazard area : (180/360 deg. As per requirement) . (UL Listed & FM Approved)
Providing & Fixing Flexible discharge Hose to route the Gas from storage cylinders to the discharge piping by a 2" flexible rubber hose with wire braided reinforcements. The hose shall be connected to the discharge outlet of the cylinder valve and terminated at the system piping or discharge manifold.
Providing & Fixing Manifold Check Valve installed as required to allow removal of any Gas cylinder from the manifold while still retaining a closed system.. (UL Listed & FM Approved)
Providing & Fixing M. S. Container strap
Providing & Fixing Flexible Actuation Hose (directed to a pressure operated control head on each cylinder valve using 1/4 inch actuation hose)
Providing & Fixing Manifold fabricated from seamless pipe schedule:80
Providing & Fixing Micro-processor based Alarm Panel (addressable panel of single loop) for 550 devices capacity, discharge module with minimum 80 character LCD type display & LED indication for all zones, complete with internal sounder, alarm/fault indications & standby 24 v lead acid batteries with charger. This panel needs to be compatible with the central BMS/BAS System through interface convertors.. (UL Listed & FM Approved)
Providing & Fixing Gas Release Panel with 2-Zone Fire detection and 1-Zone gas discharge module with binary switch timer for release delay and potential free contact to relay "Gas Release" signal panel. This panel needs to be compatible with the Fire Alarm Panel.. (UL Listed & FM Approved)
Providing & Fixing Electronic Hooter with flashing type multi-Strobe for combined audio + visual alarms, to be wired and located as per instructions of the engineer-in-charge.. (UL Listed & FM Approved)
Providing & Fixing Manual Call Station (Break Glass type). (UL Listed & FM Approved)
Providing & Fixing Abort Switch of approved Pull-Type, as per approved location . (UL Listed & FM Approved)
Providing & Fixing analogue addressable Laser-Type Photoelectric Smoke detectors complete with mounting base LED, address switch, as per requirements.. (UL Listed & FM Approved)
Providing & Fixing Photoelectric cum heat multi-criteria type smoke detectors complete with LED, address switch, as per requirements. . (UL Listed & FM Approved)
Providing & Fixing Release Switch as per approved location.. (UL Listed & FM Approved)
Providing & Fixing Electrical Cable 2 cores X 1.5 mm Sq. Cu. Armored (Along with suitable conducting wherever required)
Providing & Fixing MS pipes (Seamless piping as per ASTMA 106, Grade 'B') Schedule 40 including all necessary fittings as per NFPA 2001 guidelines.
Providing & Fixing Comcon/Serial RS485 to RS232C interface converters with all necessary accessories for BMS interface.
Providing & Fixing M.S. stuctural work fabricated from standard steel sections incluing cutting, drilling, welding, fixing and welding to insert plates in RCC structural members as directed by engineer-in-charge including cutting and making good the walls, ceilings and floors and including all fasteners, nuts, bolts etc. (for pipe supports clamps etc.) All structural fasteners shall be UL Listed/FM Approved of approved make.
Providing & Fixing Interface module for communication between Gas Release Panel and specified devices as per the instructions of the engineer-in-charge.
Photoluminiscent Gas Release caution sign board complete with fixing arrangements
Providing & fixing Electric Gas Release caution sign boards(24 V DC) for approved locations.
Providing and fixing sprinkler pipe seismic bracings including for lateral and longitudinals sway bracings, complete with mounting arrangements, necessary adjustable threaded rods (M10/12 as per required), pins anchor fasteners, knurled nuts, locking devices etc. including all tools and plants required for fixing in structural members as directed by Engineer-in-charge including cutting and making good the ceilings as per requirements.Sway brace spacing for pipes greater than 50mm in diameter shall be 25-30 feet on center. Sway brace spacing for pipes less than or equal to 50mm dia in diameter shall be 10 feet on center.Seismic bracings shall be Factory Mutual (FM) approved as per approved technical datasheets, calculations and catalogues to be submitted by the contractor, and shall be for the following sizes:
For 150 mm dia pipes
For 100 mm dia pipes
For 80 mm dia pipes
For 65 mm dia pipes
For 50 mm dia pipes
For 40 mm dia pipes
For 32 mm dia pipes
For 25 mm dia pipes
Providing and fixing photoluminiscent non-toxic material signages and labels (self-adhesive type) for basement service areas, plant rooms, fire fighting equipment, directional & route signages and exits etc. as per DIN 67510 Part 4 & BS 5499-1, complete in all respects as per requirements and instructions of the engineer-in-charge. (Recommended make: Autoglo)
Providing and fixing photoluminiscent non-toxic material signages and labels (self-adhesive type) as per DIN 67510 Part 4 & BS 5499-1.
Water Curtain Nozzle (Horizontal mounted)
Providing, Fixing, Testing and Commissioning of, NB of 15 mm dia, GM/SS Water Curtain Nozzle, maximum working pressure of 12.3 kg / cm2 (175 PSI) (HD Make) complete as per instructions of the Engineer-In-Charge
Supplying of NB of 15 mm dia, GM/SS Water Curtain Nozzle, maximum working pressure of 12.3 kg / cm2 (175 PSI) (HD Make) complete
Deluge Valve
Providing, Fixing, Testing and Commissioning of Deluge Valve with ACV trim set to water motor alarm/gong, retard chamber, UL Listed / FM Approved, complete with drain cock arrangement and with all accessories, wleded or screwed as required including cutting holes and chased in brick or RCC walls and making good complete as per approved model.
Supplying of Deluge Valve with ACV trim set to water motor alarm/gong, retard chamber, UL Listed / FM Approved
150mm dia
Providing and fixing ceiling mounted type modular automatic extinguishing system with FE 36 Clean Agent , with all accessories including sprinkler bulb of 68 degrees, flanges, actuating gas cartidge, to be installed at the ceiling level IN Server & UPS Room with proper supporting arrangements, complete as per required specifications, with body tested to a pressure of 30 kgf/cm2 .
5 Kgs Capacity
10 Kgs Capacity
Note: All valves shall be of PN16 rating
PORTABLE FIRE EXTINGUISHERS
Providing & fixing of ISI marked (IS:15683) portable fire extinguisher, carbondioxide type flat base including valve, discharge hose of not less than 10 mm dia. 1 M long & complete in all respects including initial fill with CO2 gas confirming to IS:307-1966 filled to a filling ratio of not more than 0.667 of not more than 0.667 and wall suspension bracket
Capacity 4.5 kg
6 Kg. ABC Powder type fire extinguishers are manufactured and marked to Indian standard IS: 15683. Suitable first aid appliance for fighting fires in Class A, B & C fire that is wood, textile, flammable liquids & gases.
Providing and fixing ceiling mounted type modular automatic extinguishing system with FE 36 Clean Agent , with all accessories including sprinkler bulb of 68 degrees, flanges, actuating gas cartidge, to be installed at the ceiling level OTes area Room with proper supporting arrangements, complete as per required specifications, with body tested to a pressure of 30 kgf/cm2 .(Make: FYREX)
5 Kgs Capacity
10 Kgs Capacity
Providing and fixing mechanical foam type fire extingushers consisting of welded M.S. trolley mounted cylindrical body, squeeze lever discharge valve fitted with pressure discharge hose, discharge nozzle, trolley etc., ISI marked as per IS:IS:13386 finished externally with red enamel paint.(Make: FYREX)
Capacity 45 lit (D.G.Room)
Providing and fixing carbon-di-oxide fire extingushers trolley mounted with all accessories internal discharge tube,high pressure discharge hose,discharge nozzle, ISI marked as per IS:2878 finished externally with red enamel paint. (Make: FYREX)
Capacity 22.5 kg.
Variable Refrigerant Flow System
Variable Refrigerant Flow System Supply Installation Testing and Commissioning of Imported Variable Refrigerant Flow air cooled Outdoor Units suitable for cooling and heating, having all hermetically sealed inverter type Scroll / Twin rotary Compressor(s) ,minimum 2 compressors above 16HP ODU, microprocessor based controller, top discharge type condensing units with R410 A refrigerant , vibration isolators with suitable foundation etc. complete as required. The Outdoor unit should have anti corrosive, black coated fins along with auto dust removal as a standard feature. The unit shall deliver the rated capacity at AHRI conditions and work even at 50 Deg C ambient temperature without tripping. The unit shall be suitable to work on 400 V+/-10% 3 phase , 50 Hz AC power supply. The COP at AHRI in Cooling mode should not be less than 3.8. The quoted cost sould include custom clearence , transit cost , ocean freight & forwarding charges . The ODU should have powerful BLDC fan motor that allows to extend the external static pressure of Outdoor unit shuld be 110 Pa. Make: Carrier/Toshiba/Mitsubishi Electric
Supplying, installing, testing and commissioning of Wall mounted type indoor units each complete with coil, filter, etc. Air conditioners with evaporating unit comprising of cooling coil, blower with motor , and 220 volt, 1 phase, 50 Hz, AC supply all and as per specifications. Make: Carrier/Toshiba/Mitsubishi Electric
4 Way Cassette indoor unit Supply Installation Testing and Commissioning of following minimum capacity 4-way flow VRV/VRF Cassette Type Indoor ceiling mounted unit equipped with synthetic washable media pre-filter, fan section with low noise fan/dynamically balanced blower, multispeed motor, coil section with DX copper coil, electronic expansion valve ,outer cabinet, drain pump, necessary supports, vibration isolation, etc suitable for operation on 230 V +- 10% 50 Hz AC supply Make: Carrier/Toshiba/Mitsubishi Electric
Supply Installation Testing and Commissioning of Cassette Decorative Grill Panel. Make: Carrier/Toshiba/Mitsubishi Electric
Supply Installtion Testing & Commsiosning of Double Skin AIR HANDLING UNIT Comprising of Framework Assembled Out of Extruded AluminIum Thermal Break Profiles and Perralumin Naylon Glass, Fibre Reinforced Corner Joints Having Double Skin Sandwich Panels Injected with PUF 43 mm,PUF insulation panel of density 40 ± 2 Kg/m³,Panel inner sheet GI 0.6 mm and outer sheet 0.6 mm Pre Painted GI .Drain pan SS 304 (18 swg).Base Section (GI).Limit switch, Marine light, Backward Curved With Plug Fan, Mixing Box with VFD
Pre FilterEU-4]: Flange type,Al. const.,Washable HDPE,90% down to 10µ With Mixing. Fine filter[EU-5]: AHU mounted,Flange type,AL construction, to remove particles down to 5Microns with an efficiency of 95 %. Hepa filter[EU-13]: AHU mounted,Flange type,AL construction, to remove particles down to 0.3 Microns with an efficiency of 99.997 %. (Super Hepa)
Casing:G.I.sheet/MOC Tube:0.4mm thick,12.5mm dia,Copper,Hydraulically tested at 250psi./MOC Fins:0.16 mm thick,Aluminum,12 fins/inch proparly bonded with tube/Face Velocity:@500FPM/Row 6 Row Deep
Type:TEFC,IP:55,Foot Mounted, Poles: 2 or 4/RPM:1440/2800, Volts:3Ø,415,Mounting:Heavy duty chennels,motor should move on both axis[X & Y]
3600 CFM with 125 mm Static Pressure inclusing OEM AHU Kit for VRF Connectivity. Make: Zeco / Edgetech/Cooltech
Y Joints Supply, fixing and commissioning of refrigerant joint / Branch distibutors between Outdoors with nitrile rubber insulation, supporting etc. complete as required. Make: Carrier/Toshiba/Mitsubishi Electric
Supply, fixing and commissioning of refrigerant joint / Branch distibutors between Indoors with nitrile rubber insulation, supporting etc.complete as required. Make: Carrier/Toshiba/Mitsubishi Electric
Supply Testing and Commissioning of Cordless Remote controller suitable for Controlling all indoor units as complete as required. Make: Carrier/Toshiba/Mitsubishi Electric
Supply installation Testing and Commissioning of Touch Type centralised controller suitable for Controlling to connect all indoor units as complete as required. Make: Carrier/Toshiba/Mitsubishi Electric
Refrigerant Piping Supply installation Testing and Commissioning including vaccumiazation and Nitrogen testing of following nominal sizes of soft/hard drawn copper refrigerant piping for F/VRV system, complete with fittings, with suitable adjustable ring type hanger supports, ng/brazing including accessories insulated with XLPE Class O tubular insulation/with Class O closed cell elastometric nitrile rubber tubular sleeves sections of specified thickness as given below for Suction and Liquid lines, all accessories. Make: Totaline/Met Tube/Rajco
6.5 mm dia (OD) (soft drawn) with appropriate tube thickness with 13mm thick insulation
9.5 mm dia (OD) (soft drawn) with appropriate tube thickness with 13mm thick insulation
12.7 mm dia (OD) (soft drawn) with appropriate tube thickness with 13mm thick insulation
15.86 mm dia (OD) (soft drawn) with appropriate tube thickness with 13mm thick insulation
19 mm dia (OD) (Soft/Hard drawn) with appropriate tube thickness with 13mm/19mm thick insulation
22.2 mm dia (OD) (Hard drawn) with appropriate tube thickness with 19mm thick insulation
28.58 mm dia (OD) (Hard drawn) with appropriate tube thickness with 19mm thick insulation
31.8 mm dia (OD) (Hard drawn) with appropriate tube thickness with 19mm thick insulation
34.9 mm dia (OD) (Hard drawn) with appropriate tube thickness with 19mm thick insulation
38.1 mm dia (OD) (Hard drawn) with appropriate tube thickness with 19mm thick insulation
41.27 mm dia (OD) (Hard drawn) with appropriate tube thickness with 19mm thick insulation
44.5 mm dia (OD) (Hard drawn) with appropriate tube thickness with 19mm thick insulation
50 mm dia (OD) (Hard drawn) with appropriate tube thickness with 19mm thick insulation
Drain Piping Supply Installation Testing & Commissioning of rigid UPVC piping with fittings, supports as per specifications and duly insulated with 6 mm thick closed cell nitrile rubber insulation etc. complete as required. Make: Supreme/Prince/Finolex
25 mm dia ( with 6 mm nitrile rubber Insulation)
32 mm dia ( with 6 mm nitrile rubber Insulation)
Supply Installation Testing and Commissioning of Site fabricated GSS sheet metal rectangular ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required. Make: Tata/Jindal/Sail
Thickness 24G Sheet
Thickness 22G Sheet
Supply and fixing of following thickness duly laminated aluminium foil finish closed cell Nitrile rubber ( Class O) insulation on duct after applying suitable adhesive for Nitrile rubber . The joints shall be sealed with 50 mm wide and 3mm thick self adhesive nitrile rubber insulation complete as per specifications and as required. (a)13 mm thick insulation with Aluminium foil. Make: Supreme/A Flex/K FLex.
Supply, installation and testing of acoustic lining of ducts with glass wool of 24 Kg/sqcm , the glasswool shall be covered with RP tissue paper and fixed with roofing nut and bolt complete as per specification and complete as per requirement.. Thermal conductivity of the insulation material shall not exceed 0.047 W/moK at an average temperature of 20oC. 25 mm thick acoustic lining Make: UP Twiga/ Ownes Corning
Supply installation and fixing of fire retardant non porous double layer flexible connection between each Ducted Indoor as complete as required.
Grilles Supplying & fixing of powder coated extruded aluminum Supply Air Grills with aluminum volume control dampers as per specifications. Make: Tristar/Airflow/Ravistar
Diffuser Supplying & fixing of powder coated extruded aluminum Supply Air Diffuser with aluminum volume control dampers as per specifications. Make: Tristar/Airflow/Ravistar
Cable Tray Fabrication, supplying and installing of GI tray with cover of following sizes of horizontal and vertical bends, reducers, tees, cross members & other accessories etc. as required and duly supported from the ceiling with dash fastness including painting of suspenders required for accomodating/ laying of refrigerant pipes as complete as required. Make:- Sheetal Industries/Echo Duct
a) 150 x 50 x 1.6 mm(With Cover)
b) 300 x 50 x 1.6 mm(With cover)
Supply & Installation of control cum transmission wiring of 3/2 core x 1.5 sqmm Shielded copper in suitable pvc conduits between indoor and outdoor unit as complete as required. Make: Polycab/Finolex/KEI
Refrigerant gas R-410 for top up as complete as required. Make: Refron/Mefron/Dupont
MS Fabricated (Heavy Duty ) ODU Frame
Supply Installtion Testing & Commisioning of Heat Reclaiim Ventalltion system with Dx Coil as per below specifications 950CMH/135 Pascals ESP/8.25 KW & 10.92 KW should be the fresh air conditioning load in cooling & heating Capacities. Make: Carrier/Toshiba/Mitsubishi Electric
Electrical Estimate
Sub-Head-I : DG set & Auxiliary works
D.G. Set
Design, manufacture, supply, erection, testing & commissioning of following rating of DG Sets in Accoustic Enclosure, having self excited & self regulated 415 V, 3 Phase, 4-Wire, 50 Hz, 0.8 p.f. Alternator coupled with multi-cylinder, turbo-charged/ turbo-charged after cooled as called for, Diesel Engine capable to generate the power not less than the required BHP to achieve the alternator capacity as given below, with Air-cooled radiator, hospital type silencers and Electronic governer suitable for Synchronised Operation including providing of AMF relay, 1250A Circuit Breaker as called for, & Engine control panel, 24V batteries of suitable rating, battery-charger with battery leads and complete with all standard accessories & protection as required and as per specifications, including first filling of lube oil providing common base plate, anti vibration pads, drip trays, foundation bolts, nuts, bolts, cable termination/adopter box sutiable to terminate upto 3.5Cx300 sq.mm. XLPE cables, as required for a complete installation including initial filling of fuel and lubricants required during
required during trial run of DG sets on full load for 12 hours followed by 10% overload for one hour in any 12 hours duration, as per specifications & drawings complete with RCC/PCC foundation for DG set as per the structural detail for Dynamic Load submitted by the Vendor and approve by the Consultant.
Note : The exhaust system should have exhaust bellow just near to DG sets and before the exhaust silencer to accommidate the expansion in the exhaust system.
750 KVA (With Acoustic Enclosure)
Design, manufacture, supply, erection, testing & commissioning of following rating of DG Sets in Accoustic Enclosure, having self excited & self regulated 415 V, 3 Phase, 4-Wire, 50 Hz, 0.8 p.f. Alternator coupled with multi-cylinder, turbo-charged/ turbo-charged after cooled as called for, Diesel Engine capable to generate the power not less than the required BHP to achieve the alternator capacity as given below, with Air-cooled radiator, hospital type silencers and Electronic governer suitable for Synchronised Operation including providing of AMF relay, 500A Circuit Breaker as called for, & Engine control panel, 24V batteries of suitable rating, battery-charger with battery leads and complete with all standard accessories & protection as required and as per specifications, including first filling of lube oil providing common base plate, anti vibration pads, drip trays, foundation bolts, nuts, bolts, cable termination/adopter box sutiable to terminate upto 3.5Cx300 sq.mm. XLPE cables, as required for a complete installation including initial filling of fuel and lubricants required during
trial run of DG sets on full load for 12 hours followed by 10% overload for one hour in any 12 hours duration, as per specifications & drawings complete with RCC/PCC foundation for DG set as per the structural detail for Dynamic Load submitted by the Vendor and approve by the Consultant.
Note : The exhaust system should have exhaust bellow just near to DG sets and before the exhaust silencer to accommidate the expansion in the exhaust system.
250 KVA (With Acoustic Enclosure)
Exhaust Piping
Supply, installation, testing & commissioning of Class ‘C’ M.S. pipe including bends, flanges, supports etc. as required complete with 75 mm dia fibre glass wool insulation with 26 swg aluminium sheet cladding.
300 mm dia pipe
250 mm dia pipe
200 mm dia pipe
Fuel Day Oil Tank ,Vall valves & stainers
Supply, fabrication, installation testing & commissioning of M.S. day oil tanks of following capacity fabricated out of min. 6mm thick sheet installed on steel frame with all associated accessories, filters, breathers and fittings including level indicator, complete as required, including level controller for automatic operation of pumps. The tank shall be suitably treated with anti corrosive treatment on inside & outside surface complete with PCC foundation 75mm thick (1:3:6)
990 Litre
Fuel Oil Piping
Supply, installation, testing and commissioning of following 'C-class' M.S. piping conforming to IS:1239 for fuel piping complete with all necessary fittings and valves between day oil storage tanks & DG sets/ priming motor including jointing of pipes, painting of pipes with two coats of red oxide & two coats of black enamel paint.
32 mm dia Pipe
25 mm dia Pipe
32 mm dia Ball valves
25 mm dia Ball valves
Y-strainer suitable for 32mm dia. pipe.
Y-strainer suitable for 25mm dia. pipe.
Providing Accoustic insulation in DG Rooms walls & roof by providing 50 mm thickfiber glass blanket of 42 Kg/Cu.M density on angle iron frame and making a grid of 500mmx500mm. The fiber glass blanket will be covered with 20 gauge, GI chicken wire mesh and hold to wall/roof by means of Hilti, Dash fasteners or approved equivalent. This will be further covered with 26 gauge perforated GI sheet fitted to angle iron with self tapping screws or other suitable fasteners in grid of 600x600mm. A thick coat of bitumin primer will be applied to wall before putting up this accoustic lining.
Note:- The contractor shall consider the following details in their item rates, wherever required:
Supporting rigid steel framework.
Cubicle types 2mm thick CRCA
Complete with inter connections and distribution busbars.
Proper bonding to earth.
Embossed PVC plates on boards, showing circuit diagrams.
Padlocking of panel doors.
Padlocking of MCCB’s handle in off position.
Providing cable supports within cable Alley.
ACBs for all incomers shall have led indication for fault type, Microprocessor failure and LCD display for curves & parameters.
TPN ACB mean 3 pole & neutral
TPN MCCB mean 3 pole & neutral
ACB’s shall have minimum 35 MVA breaking capacity, unless specified otherwise.
All Incomers MCCB of Meter board panels shall be provided with Earth-fault module with CTs of suitable rating complete
MCB’s shall have 10 KA breaking capacity.
All motor feeders' MCCB / MCB shall be suitable for motor duty application.
All DOL & Star-Delta Starters shall be provided with SPPR (single phase preventor relay) and 2 nos. of Aux.Contacts for Remote operation/monitor.
All MCCB's shall be provided with Extended Rotatry operating handle.
The Panel fabricator shall provide Al./ Copper Bus-bars link from Breakers wherever more than two nos. of cables are terminated in the breakers.
All breakers in panels shall have a fault level as indicated in single line diagram.
Readymade 16SWG Sheet steel Enclosure with cutout For MCBs
All DBs shall be Double Door type
Embossed PVC plates on boards & DB chart inside of the DB door.
All MCBs in Panel shall be suitable for motor duty application.
PLC based AMF & Synchronisation control Panel-1 for D.G.sets for L&P
INCOMER FOR GENERATORS 1nos.-250 KVA )
Each Incomer for D.G. set shall be provided with the following:
1 no. 500A TP EDO ACB with 500A Neutral Isolation Contactor having programmable trip setting for releases with the following microprocessor based integral protection:
Voltage restraint IDMTL Overcurrent relay,
Unbalance Load protection
Reverse power Protection.
U/V & O/V protection
Master trip relay
Restricted Earth fault relay along with 500/1A PS class CT to be mounted on neutral of D.G. set
In addition to above relays shall be provided for the following protection:
Anti Pumping device
Trip circuit supervision relay
The ACB shall be complete with 3nos. 500A/5A, 15VA, 5P10 CTs for protection .
Metering & Indication
1 set of R,Y,B phase indicating lamps with 3 nos. 2A SP MCBs.
1 No. Load Analyser cum digital Multifunction Meter with 3 nos. 500/5A, CL-1 CTs, as required.
1 Set of Breaker ON-OFF-TRIP, Spring charged & Trip circuit healthy indication Lamps
1 set of Indication Lamps for NeutraI Isolation Contactor ON & OFF and Battery charger ON
INCOMER FOR GENERATORS 2 no.- (750 KVA )
Each Incomer for D.G.set shall be provided with the following:
1 no. 1250A TP EDO ACB with 500A Neutral Isolation Contactor having programmable trip setting for releases with the following microprocessor based integral protection:
Voltage restraint IDMTL Overcurrent relay,
Unbalance Load protection
Reverse power Protection.
U/V & O/V protection
Master trip relay
Restricted Earth fault relay along with 1250/1A PS class CT to be mounted on neutral of D.G. set
In addition to above relays shall be provided for the following protection:
Anti Pumping device
Trip circuit supervision relay
The ACB shall be complete with 3nos. 1250A/5A, 15VA, 5P10 CTs for protection .
Metering & Indication
1 set of R,Y,B phase indicating lamps with 3 nos. 2A SP MCBs.
1 No. Load Analyser cum digital Multifunction Meter with 3 nos. 1250/5A, CL-1 CTs, as required.
1 Set of Breaker ON-OFF-TRIP, Spring charged & Trip circuit healthy indication Lamps
1 set of Indication Lamps for NeutraI Isolation Contactor ON & OFF and Battery charger ON
BUS COUPLERs
1no.1250A FP EDO ACB (65KA) with all accessories required.
1 Sets of Breaker ON-OFF-TRIP, Spring charged indication Lamps as required.
INTERLOCKING
Incomers from D.G. sets & Bus couplers shall be electrically & mechanically interlocked.
The Interlocking scheme shall be such that Bus Bar shall be fed individually by only One D.G. sets under normal operation (No syncronisation) or all the bus bars shall be fed by any D.G.set in case of Synchronisation mode.
BUS BARs
2 Sets of 2000A, TPN Aluminum bus bars with colour coded PVC sleeves
OUTGOINGS
2nos.1250A FP EDO ACB
2 nos. 315A TPN MCCB
2 nos. 160A TPN MCCB
Microprocessor based PLC Synchronisation Panel
Design, manufacture, assembly, supply, Installation , Testing & Commissioning of PLC based Logic Control having follwing features:
Auto Synchronisation system.
Auto Load sharing among D.G. sets.
The automatic operations to be incorporated in the panel are as follows:-
The system will directly accept Digital meter & voltmeter signals for Electrical parameter monitoring and control. Only 1 no. Phase Angle Transducer shall be provided for all the DG Set Synchronization.
DG Panel’s logic shall be able to automatically start generators when mains supply fails by closing the DG switchgear for generator supply. It shall also transfer the power from emergency to mains supply, when the main healthy voltage persists for more than two minitues.
The Transfer of load shall take place only when the generator output reaches 90% of its rated voltage and frequency.
Automatic load transfer should take place within thirty seconds of mains fail.
‘B’ checkup alarm of each D.G. set after 300 hours of running for proper maintenance.
All parameters of individual D.G. set shall be monitored & necessary commands shall adjust the parameters of that D.G. Set feeding the bus bar of Main Panel.
Auto synchronizing system shall verify the phase angle of D.G. sets and also compensate for ACB closing time by initiating closing of the breaker ahead of the actual predictable synchronism thereby ensuring a phase difference of zero degree.
System shall also monitor the slip frequency and the beat voltage of the machine or system.
Neutral Isolation switch of Generator running in the system shall not trip until the Neutral Isolation switch of other Generator is closed in the event of shutting off of first Generator and starting the other.
Active power shall be made equal on all the sets automatically with the help of ACTIVE LOAD BALANCING system through Governor Control.
Reactive power shall be balanced automatically with the help of quadrature droop kit already fitted on the machine.
However if qudrature droop system is not functioning accurately ‘REACTIVE LOAD BALANCING’ system shall control the motorised potentiometer to achieve KVAR regulation within preset band.
In the event of set failing to synchronize, alarm from Annunciator would invite attention of operator for manual intervention.
It shall be possible to alter crucial setting / time delays through MAN MACHINE INTERFACE. (through BMS Software)
Relays shall have compatibility for future interface with BMS Software graphic displays / report generation.
System shall have TOTAL MANUAL synchronization facility.
The Microprocessor (PLC) shall start DG sets in sequence as per the readings of KW/KVA meter provided on transformer & D.G. set incomers at the instant of power failure and the sequence of operation will be as specified.
The PLC shall start the the two bigger set to fed the two bus of the Hospital feeders first and it will share the load of the other two bus if the total demand load on the two segement on each side of central Bus-coupler is below 90% of the capacity of the running D.G.set,by closing the smaller rating of bus-coupler.
The PLC system shall able to monitor the Load on the each Bus-section individually.
If the Total/ Individual demand Load on Bus-section increases from the 90% capacity of the running D.G. sets then the PLC will start the other D.G. sets one by one as per the Demand load requirement, and after sysnchronising with the system bus it will transfer the proportional load on the set by closing the Incomer of that set, and accordingly switch OFF the smaller D.G. sets as per the Demand Load on that Bus.
Similiary during the reduction of Demand load the Relay will switch OFF or Switch ON the relevant D.G.sets as per preset demand load.
On restoration of grid supply, Incomer Switches from D.G. sets and Bus coupler shall be switched ‘OFF’ in preset sequence and then switch ON the Incomer ACB of Transformer. DG Set shall continue to run for three minutes at reduced speed after DG Switch has been switched ‘OFF’ after that the D.G. set will be Switched Off.
The PLC panel shall be provided with all the necessary protection switches, relays, potential free contacts , Anuunciation windows, etc as required to achieve the above logic and complete with the following:
D.G. control Panel with Mannual synchronization for Each D.G. set with the following:
1 No. Digital Multifunction Meter
1 No. D.C. Voltmeter for Battery
1 No. D.C. Ammeter for Battery
Switch for Speed Raise & Low
Switch for Voltage Raise & Low
Push Button for D.G. Start
Push Button for D.G. Stop
Emergency Stop Push Button
16 windows Annunciator with hooter.
Field Failure Relay
Out of Step protection Relay
AMF Relay
3 nos. Potentiometers
AUTO SYNCHRONIZING
1 No. PLC Comprising of:
Main Processing unit
Power Monitor 3000.
Digital input Modules
Digital output Modules
EPROM for Main Processor
Panel view 550
1 No. Double Voltmeter
1 No. Double Frequency Meter
1 No. Synchroscope
1 No. Synchronizing Switch
1 Set Dark Lamps
Manual Overriding facility from Auto Synchronizing.
Auto / Manual / Test Switch
2 Nos. 16 windows Annunciator with hooter for status indicator for breakers.
Mimic with Led Indicator for Power supply Status
The PLC shall be complete with all necesaary switches, fuses etc. as given below, to fulfill the desired application as required.
Aux. Relays
Indicating Lights & Push Buttons
Control fuses/ MCBs
Load Analyser (Power monitor)shall have following features: -
Voltage, current, frequency, P.F., KVA, KVAR, KW, KVAH, KVARH, KWH measurement for single and three phase source.
50 ms update rates for metering results
Port for PC compatibility
Output Control via control relays or PLC
Input monitoring via status inputs
Time stamped data logging of system measurements and events
Total Harmonic Distortion
Configurable trend log, upto 45,000 records
Firmware upgrades without removing module
Annunciation Window for each Generator as follows:
Electrical Fault
Excitation Failure
Reverse Power
Emergency Shutdown
Over Speed
Low Lube Oil Pressure
High Water Temperature
Engine Overheating
Cooling Water Flow Failure
Bearing Temperature High
Winding Temperature High
Low Fuel Level
Spare- 4nos.
Annunciation Window for Auto Synchronising
DG - 1 Fails to Start
DG - 1 Fails to Synchronize
DG - 1 Neutral Discrepancy
DG - 1 ACB Fails to close
DG - 2 Fails to Start
DG - 2 Fails to Synchronize
DG - 2 Neutral Discrepancy
DG - 2 ACB Fails to close
DG - 3 Fails to start
DG - 3 Fails to synchronize
DG - 3 Neutral discrepancy
DG - 3 ACB Fails to close
DG - 4 Fails to start
DG - 4 Fails to synchronize
DG - 4 Neutral discrepancy
DG - 4 ACB Fails to close
Bus coupler - Fails to close
Spare-3nos.
For Power Supply Status Indicator (Mimic)
DG - 1 Supply available
DG - 1 Neutral '‘ON/ OFF'
DG - 2 Supply available
DG - 2 Neutral '‘ON/ OFF'’
DG - 3 Supply available
DG - 3 Neutral ‘'ON/ OFF'’
DG - 4 Supply available
DG - 4 Neutral ‘'ON/ OFF'’
Bus coupler - ‘'ON/ OFF'’
Mains Supply available
All the above mentioned components like I/O ports, relay modules, synchronisation relay, annunciation window shall be housed in the Synchronisatio Panel.
The PLC control panel shall be complete in alll respect to accompolished the desired operation and the vendor shall supply all the necessary switches fuses, relays, CTs, Digital/ Analogue Input/Output racks for interface, 1 KVA UPS backup with SMF battery
Contractor shall provide the detail of NO & NC contacts required in the D.G.sets' control panel for AMF & Auto-synchronisation proccess which will be provided alongwith the motorised potentio-meter with the D.G.set within the accoustic enclosure.
Supply Installation, testing & Commissioning for the above Panel-1. as described above
SANDWICH TYPE BUS TRUNKING
Design, supply, installation, testing and commisioning of following ratings of powder coated sheet steel enclosed (IP 42) 415V, 50 Hz., Three phase & neutral Aluminium conductor Bus Duct suitable for 25 MVA fault rating, including bends/elbows, transposition piece, expansion joint, Terminal End connector & all flexible connections as per specifications with all accessories, supports, hardwares and termination of bus duct to switchgear.
1250A TPN Aluminium Bus Duct (35 MVA fault rating) in weather proof Enclosure
Copper flexible End Termination for 1250A TPN
LT NORMAL CABLE
Supplying of following sizes of XLPE/ PVC insulated Aluminum/ Copper conductor and Armoured, overall PVC sheathed 1.1 KV grade cables conforming to relevant IS code and technical specifications.
XLPE insulated Al. Ar.Cable
3.5C x 300 sq.mm.
SUBSATION EQUIPMENTS
TWO POLE STRUCTURE WITH GO-DO SWITCH
Supplying, fixing, testing and commissioning of two pole structure for receiving 11 KV 3 phase incoming line for dept. comprising of :-
2 nos 11 mtrs long, Steel pole as per sate electicity board(SEB) specifications.
Cement Concrete foundation (1:2:4), 2250 mm below ground and 450 mm above including excavation and refilling etc as shown on drawings.
Steel cection, channels, angles, flats, clamps, GI nuts, bolts and required hardware etc. of different sizes for cross arms, bracings, supports for pole, insulators, lightning arrestors, GO switch, GI pipe for 11 KV cables, supports for terminations, including anti climbing barbed wires, danger plate as per specification of SEB.
11 KV class disc / pin / support insulator complete with clamps and fixing hardware etc.
3 nos , one per phase ,11 KV station class thyrite type lightning arrestors complete with mounting arrangement on the incoming overhead line along with earthing connections complete as per specification and as required.
1 set of G.O. Air break switch with DO fuse 400 Amp. With gang operated devices, with pad locking arrangement. Operating rod, supports, complete with operating handle and locking arrangement complete as per UHBVN.specification and as required.
50 Mtrs. - size 6/1/4.09 mm ACSR Conductor and connectors for tapping the connection and for connections with in two pole structure with heat shrinkable insulating sleeves for protection of connections etc as shwon on drawing.
50 mtrs -Earth connection with 50 x 6 mm GI Strip.
SUPPLY & INSTALLATION OF TWO POLE STRUCTURE WITH GO-DO SWITCH
11 KV ENERGY METER
Supply, fixing , testing and commissioing of Energy meter for the 11 KV connections including testing of the meter by SEB lab and control cabling from CTPT to the meter complete with all respect as per the norms and the requirement of SEB.
11KV HT PANELS (NEAR METER)
Design, manufacture, assembly,Testing & inspection at works, supply, and delivery (at Site), of 11kV, 350 MVA, in-door type Switchgear Panel with horizontal Isolation and Horizontal draw out vacuum circuit breaker, having anti pumping and trip free feature and complete In metal clad floor mounted vermin proof panel board, fabricated out of minimum 2mm thick CRCA sheet as per specifications. The panel shall be complete with all accessories / fitting / wiring, cable termination boxes suitable for 3C x 185 Sqmm XLPE armored, aluminium conductor cable for incoming and outgoing feeder, foundation bolts etc. The Panel shall be complete with required for Metering and protection relays,CTs/PTs and other related accessories, as required as per SLD and as per specifications. The Panel Shall consisting of following:-
1 Nos 11 kV, 350 MVA, 630A, Electrically operated, draw-out VCB complete with stored energy mechanism for manual operation, three position isolator/ earthing switch with manual operating mechanism & auxillary switch with 6NO + 6NC contacts, busbars, interlocking and earth bar etc.as per specifications. Incommer shall be provided with necessary auxiliary relays, control switches, emergency hand trip devices and mechanical ON / OFF indicator etc.
Breaker shall be provided with the following for metering Indication and protection:
One (1) set of CTs of ratio 200/10/5-5A with metering and protection cores. Metering core shall be of class 0.5 and of 5VA, the core for protection shall be of 15VA and class 5P10.
One (1) set of PTs of ratio 11KV/rt3 / 110V/rt3 , class 0.5 and of burden 100 VA.
One (1) No. Multifunction meter (MFM-1) with RS-485 Port suitable for measurement of voltage, currents, power factor, frequency, Energy (KWH, KVARH KVAH), Power (KW, KVA and KVAR), harmonics and maximum demand indication.
One (1) Set of phase indication lamps with 2Amp SP MCB for protection (Red, Yellow and Blue).
One (1) set of Red/ Green indicating lamp for close and open position.
One (1) No. amber indicating lamp for auto trip.
One (1) No. clear indicating lamp for trip circuit healthy.
One (1) No. blue indicating lamp for spring charged.
One (1) Set of Power Pack
One (1) No Hooter
One (1) Set of Multifunctional, Protection Relay with communication compatibility and with min. protection 51, 51N, 27 & 59
Master Trip Relay.
Trip circuit supervision relay
Note : Necessary Co-ordination shall be done by the Panel Manufacturer / Vendor with the vendor of "Gas flooding system" for fire protection, for making suitable provisions in the panels, at the Design stage, Manufacturing stage, stage of testing at works & stage of commissioning at site.
SUPPLY & INSTALLATION OF MAIN DISTIBUTION BOARD AS DESCRIBED ABOVE
OIL TYPE TRANSFORMER
Supplying, installation, testing and commissioning of out door type 800 KVA 11/0.433 KV Delta/Star, vector group Dyn11, outdoor mounting, oil naturally cooled (ONAN), transformer with on load tap changer (OLTC) having AVR relay and RTCC for automatic sensing of incoming voltage, automatic operation of OLTC and facility for remote manual operation of OLTC suitable for incoming voltage with 16 steps OLTC for HV variation from 5% to-15% in steps of 1.25% to give a constant secondary voltage. The transformer shall be Confirming To BIS Energy Efficiency Level 2 And provided with fittings, accessories, protection, first filing of oil etc. including buchholz relay, oil/winding temperature alarm/trip protection complete as per specifications including 10% extra oil in non returnable drum for topping up as required. The transformer shall be provided with cable box suitable for cable terminate on HT side and LT side. MAKE:- KOTSONS/ KIRLOSKAR/ AREVA-SCHNEIDER/ GTBSYNERGY
11KV HT PANEL (NEAR TRANSFORMER)
Design, manufacture, assembly,Testing & inspection at works, supply, and delivery (at Site), of 11kV, 350 MVA, in-door type Switchgear Panel with horizontal Isolation and Horizontal draw out vacuum circuit breaker, having anti pumping and trip free feature and complete with copper bus bar, enclosed in metal clad floor mounted vermin proof panel board, fabricated out of minimum 2mm thick CRCA sheet as per specifications. The panel shall be complete with all accessories / fitting / wiring, cable termination boxes suitable for 3C x 300 Sqmm XLPE armored, aluminium conductor cable for incoming and outgoing feeder, foundation bolts etc. The Panel shall be complete with required No. of bays for Metering and protection relays,CTs/PTs and other related accessories, as required as per SLD and as per specifications. The Panel Shall consisting of following:-
Incomer
1 Nos 11 kV, 350 MVA, 630A, Electrically operated, draw-out VCB complete with stored energy mechanism for manual operation, three position isolator/ earthing switch with manual operating mechanism & auxillary switch with 6NO + 6NC contacts, busbars, interlocking and earth bar etc.as per specifications. Incommer shall be provided with necessary auxiliary relays, control switches, emergency hand trip devices and mechanical ON / OFF indicator etc.
Each incomming Breaker shall be provided with the following for metering Indication and protection:
One (1) set of CTs of ratio 100/50/5+5A with metering and protection cores. Metering core shall be of class 0.5 and of 5VA, the core for protection shall be of 15VA and class 5P10.
One (1) set of PTs of ratio 11KV/rt3 / 110V/rt3 , class 0.5 and of burden 100 VA.
One (1) No. Multifunction meter (MFM-2) with RS-485 Port suitable for measurement of power factor, Energy (KWH, KVARH KVAH) & Power (KW, KVA and KVAR), (Conzerv EM6434 or Equivalent make).
One (1) Set of phase indication lamps with 2Amp SP MCB for protection (Red, Yellow and Blue).
One (1) set of Red/ Green indicating lamp for close and open position.
One (1) No. amber indicating lamp for auto trip.
One (1) No. clear indicating lamp for trip circuit healthy.
One (1) No. blue indicating lamp for spring charged.
One (1) Set of Multifunctional, Protection Relay with communication compatibility and with min. protection 51, 51N
Master Trip Relay.
Trip circuit supervision relay
One (1) Set of Power Pack
One (1) No Hooter
Busbar:
1 Sets of 700 Amp, duly insulated with Color coded heat shrinkable PVC sleeved, TP copper busbar of 350MVA fault rating.
1 Nos of 24 V, Power Pack of suitable back up rating for Indication, Annunciation and trip coil operation as required and as per specifications.
Outgoings (2 Nos.):
2 Nos 11 kV, 350 MVA, 630A, Electricaly operated, draw-out VCB complete with stored energy mechanism for manual operation, three position isolator/ earthing switch with manual operating mechanism & auxillary switch with 6NO + 6NC contacts, busbars, interlocking and earth bar etc.as per specifications. Outgoing shall be provided with necessary auxiliary relays, control switches, emergency hand trip devices and mechanical ON / OFF indicator etc.
Each Breaker shall be provided with the following for metering Indication and protection:
One(1) set of CTs of Dual ratio 60/30/5+5A with metering and protection cores. Metering core shall be of class 1.0 and of 5VA, the core for protection shall be of 15VA and class 5P10.
One (1) set of Red/ Green indicating lamp for close and open position.
One (1) No. amber indicating lamp for auto trip.
One (1) No. clear indicating lamp for trip circuit healthy.
One (1) No. blue indicating lamp for spring charged.
One no. 4 window Audio/visual annunciator system complete with hooter, Ack, test & Reset PBs for annunciation of WTI Alarm / Trip etc.
One (1) Set of Multifunctional protection relay with Communication Compatibility with minimum protection 50,50N,51, 51N .
Master Trip Relay.
Trip circuit supervision relay
Note : Necessary Co-ordination shall be done by the Panel Manufacturer / Vendor with the vendor of "Gas flooding system" for fire protection, for making suitable provisions in the panels, at the Design stage, Manufacturing stage, stage of testing at works & stage of commissioning at site.
11KV HT PANEL as described above
MV SWITCHGEAR PANELS & DISTRIBUTION BOARDS :
Design, manufacture, supply, installation, testing and commissioning of following Utility panels suitable for 415 V, 3 phase, 4 wire, 50 Hz power distribution system. The panel shall be Indoor, free standing, floor mounting, sheet metal clad, cubicle, dead front, dust and vermin proof type compartmentalised design fabricated out of 2mm thick CRCA sheet steel for Load bearing members and 1.6 mm thick for non-load bearing members, complete with colour coded, heat shrinkable PVC insulated, aluminium bus bars and separate earth bus bar of adequate cross section through out the length of the panel. The incoming and outgoing feeders shall be accommodated in a fully segregated, modular multitier arrangement with adequate size and distinct cable alley, bus bar alley/chamber (form-3b Construction). The panel shall be complete with name plate, earthing, numbering, danger plate etc. as required and as per specifications and drawings. The panel shall withstand the fault level of as indicated elsewhere or shown in Single Line Diagram.
Important Notes: Common for all Switchboard:
The BOQ shall be read inconjunction with general notes, specification and Single Line Diagram (attached for Ref.). Incase of any discrepancy between specification, BOQ and SLD, the same shall be brought to the notice of Client/Consultant before quoting the rates, otherwise stringent condition shall be deemed to have been considered.
Fault current wherever mentioned shall be Ics value. (Ics = 100% Icu).
All MCCB shall be provided with door interlocked rotary handle with ON/TRIP/OFF position indicator, continious variable thermal magnetic O/C and S/C releases. All rating MCCB's shall be thermalmagnetic type.
Incoming MCCBs shall be provided with O/C, S/C, and Earth fault protection releases.
Outgoing MCCBs shall be provided with O/C, short circuit protection.
All feeder doors shall have pad locking arrangement.
All TP feeders shall have solid isolable neutral link.
All MCCB used in starter feeder shall be suitable for motor duty application.
All power contactors including NIC shall be of AC3 duty.
All ACB's shall be with micro processor based releases and Breaker Control Switch (BCS) having lost motion device.
Spare contaCTs of ACB/Relays/Contactor etc. shall be wired upto terminal block.
All switchgear used in starter feeder shall be type-2 co-ordinated. Manufacturer is required to submit manufacturers type-2 co-ordination chart for the make used.
All meters are digital type.
Panel shall be powder coated of approved shade with minimum 60 micron thickness.
ACB's/MCCB's in one particular panel shall be of one similar make.
Size of Voltmeter / Ammeter for incomer also, 96mm x 96mm flush mounted with shrouded terminal shall be used in the panel.
Bus bar chamber shall be kept at top of the all panels.
All bus bar shall be insulated with coloured PVC Sleeve i.e.RYB,BK as per colour code.
Internal wiring of panel shall be with size 2.5sqmm Flexible Copper Conductor for CT circuit and control wiring with 1.5 sqmm.
All Lift Panels transport section should not be more then 1000 mm.
In soft starter Vender should supply power contactor with aux. Contactor & All necessary accessories required etc. (As per BOQ & specification )
All indicating light shall be LED type .
Each vertical section of floor mounted panel shall have independent base frame (75mm x 40mm) size made out of 3 mm sheet steel (LT Panel & DG Panel).
All the makes shall be as per Client approved make list only.
Wherever only voltmeter & ammeter are required, the same may be provided in combined meter suitable for both parameter.
Main LT Panel
Incoming : (TRANSFORMER)
Metering & indication and Annunciation for Transformer Supply incoming breakers :
Each transformer supply breaker shall be provided with the following:
One (1) No. Digital Multifunction meter with RS-485 port suitable for measurement of voltage, currents, Power Factor, Frequency, Power & Energy (Conzerv EM 6400 or equivalent) with one set (3 Nos.) of CTs of ratio 1250/5A Class 1.0, 15VA.
One set (3 nos.) phase indication lamps with control MCB.
One (1) set of 1250/5 A, C.L 1.0 CTs for input to APFC relay.
Protection Relays & Interlocking for transformer breaker:
Each Transformer breaker to be provided with :
One (1) no. REF (CAG14) or equivalent relay with stabilising resistance for transformer REF protection with 4 nos. 1200/1A,CL-PS CTs of suitable VA and knee point voltage.
Trip Circuit supervision relay (VAX-31 of Areva or Equivalent).
Master trip relay (VAJH-13 of Areva or Equivalent).
Incoming : (D.G SET)
Metering & indication and Annunciation for Transformer Supply incoming breakers :
Each transformer supply breaker shall be provided with the following:
One (1) No. Digital Multifunction meter with RS-485 port suitable for measurement of voltage, currents, Power Factor, Frequency, Power & Energy (Conzerv EM 6400 or equivalent) with one set (3 Nos.) of CTs of ratio 1250/5A Class 1.0, 15VA.
One set (3 nos.) phase indication lamps with control MCB.
Protection Relays & Interlocking for transformer breaker:
Trip Circuit supervision relay (VAX-31 of Areva or Equivalent).
Master trip relay (VAJH-13 of Areva or Equivalent).
Notes :
Sufficient No. of contacts terminals shall be provided in the panel as required for necessary remote operation and indications etc.
Operation interlocks as per specification & drawings indicating sufficient nos. of potential free contacts for interlocking/indication annunciation/ control etc shall be provided by the bidder as required.
Bus Coupler :
1 no.1250 Amps, 415 V, 50KA four pole EDO ACB Bus coupler breaker complete with shunt trip release, anti pumping protection, ON/OFF/ indication etc.
Electrical & mechanical interlocking shall be provided between two incomers and one bus coupler.
Busbar :
2 Sets of 1600A, 65kA,TPN Al. Busbar insulated with heat shrinkable sleeves and shall be colour coded.
Separate earth bar of 50 x 6 mm Aluminium shall be provided.
Outgoings :
Each outgoing feeder shall be provided with ON/OFF/ Trip indication lamps with back-up SPMCB.
2 No. 800A, 65KA TPN MCCB.
7 No 630/500A 50KA TPN MCCB
4 No 315A 50 KA TPN MCCB
2 No 200/250A 50 KA TPN MCCB
6 No 160A 50 KA TPN MCCB
4 No 63A 50 KA TPN MCCB
Note : Necessary Co-ordination shall be done by the Panel Manufacturer / Vendor with the vendor of "Gas flooding system" for fire protection, for making suitable provisions in the panels, at the Design stage, Manufacturing stage, stage of testing at works & stage of commissioning at site.
Main LT Panel described as above.
Capacitor Panels (250 kVAR)
Incoming :
Metering, Indication and Protection :
One (1) set of RYB phase indication lamps with control SP MCB.
Busbar :
600A TPN Al. Busbar insulated with heat shrinkable sleeves and shall be color coded.
Separate earth bar of 50 x 6 mm of Aluminium shall be provided.
Outgoings :
250 KVAR Capacitor Panel in steps of 3 nos. of 1 x 50 kVAR banks 1 nos. of 1 x 25 kVAR banks, 2 Nos. of 1 x 25 kVAR banks,2 No.of 1X 10 kVAR bank and 2 No.of 1X 5 kVAR bank
Notes:
Each capacitor bank should have its individual MCCB/MCB & Contactor suitable for capacitor duty including fuses for each capacitor unit as per specifications and approved SLD.
Enclosure of capacitor panel shall be liberally designed to take care of internal heat emission by capacitor unit without forced cooling and to limit the temperature rise with in permissible limit. However, louvers are allowed to facilitate extra cooling.
Enclosure shall be so designed as to keep the space for Detuned reactors for future if required.
Capacitors shall be of Heavy duty grade MPP type.
HT CABLE
Supplying of following sizes of XLPE/ PVC insulated Aluminum/ Copper conductor and Armoured, overall PVC sheathed 11 KV grade cables conforming to relevant IS code and technical specifications.
3C x 240sq.mm.
HT CABLE LAYING (DSR ITEM)
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required.
Above 120 sq. mm and upto 400 sq. mm
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required.
Above 120 sq. mm and upto 400 sq. mm
HV CABLE JOINTING & END TERMINATION (DSR ITEM)
Supplying and making indoor cable end jointing with cast resin compound, including lugs and other jointing materials, for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required :
Supplying and making outdoor cable end jointing with cast resin compound, including lugs and other jointing materials, for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required :
MISC. CIVIL ITEMS (DSR ITEM)
Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc.direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required.
63 mm dia (OD-63 mm & ID-51 mm nominal)
160 mm dia (OD-160 mm & ID-135 mm nominal)
CABLE TRAYS (DSR ITEM)
Supplying and installing following size of perforated painted with powder coating M.S. cable trays bends with perforation not more than 17.5%„ joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required.
600 mm width X 75 mm depth X 2.0 mm thickness
750 mm width X 75 mm depth X 2.0 mm thickness
900 mm width X 75 mm depth X 2.0 mm thickness
Sub-Head : WIRING
Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable Gl box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required.
Group C
Wiring for group controlled (looped) light point/fan point/exhaust fan point/ call bell point ( without independent switch etc.) with 1.5 sq. mm ERLS PVC insulated copper conductor single core cable in surface/ recessed PVC conduit, and earthing the point with 1.5 sq. mm ERLS PVC insulated copper conductor single core cable etc. as required.
Group C
Wiring for light/ power plug with 2X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit alongwith 1 No. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required.
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required.
2 X 1.5 sq. mm +1X 1.5 sq. mm earth wire (For Light)
2 X 2.5 sq. mm +1X 2.5 sq. mm earth wire (For Light)
2X6 sq. mm +1X 4 sq. mm earth wire
4 X 10 sq. mm +2X 6 sq. mm earth wire
Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.
5/6 A switch
15/16 A switch
3 pin 5/6 A socket outlet
6 pin 15/16 A socket outlet
Telephone socket outlet
TV antenna socket outlet
Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required.
Supplying and fixing following size/ modules, Gl box alongwith modular base & cover plate for modular switches in recess etc. as required.
1 or 2 Module (75mmX75mm)
3 Module (100mmX75mm)
4 Module (125mmX75mm)
6 Module (200mmX75mm)
Installation ,Testing, Commissioning of wall bracket /ceiling fittings of all sizes and shapes containing upto two GLS/CFL/LED lamps per fitting, complete with all accessories including connections etc. as required.
Installation, testing and commissioning of pre-wired, fluorescent fitting / compact fluorescent fitting of all types, complete with all accessories and tube/lamp etc. directly on ceiling/ wall, including connections with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable and earthing etc. as required.
Installation, testing and commissioning of ceiling fan, including wiring the down rods of standard length (upto 30 cm) with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable, including providing and fixing phenolic laminated sheet cover on the fan box etc. as required.
Numbering of ceiling fan/ exhaust fan/ fluorescent fittings as required.
Installation of exhaust fan in the existing opening, including making good the damage, connection, testing, commissioning etc. as required.
Upto 450 mm sweep
Extra for fixing the louvers/ shutters complete with frame for a exhaust fan of all sizes.
Supplying & fixing suitable size Gl box wih modular plate and cover in front on surface or in recess including providing and fixing 25 A modular socket outlet and 25 A modular SP MCB, "C" curve including connections, painting etc. as required.
Sub-Head : MCCB, MCB & OB'S
Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without
4 way (4 +12), Double door
6 way (4 +18), Double door
8 way (4 +24), Double door
Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/lsolator)
6 way, Double door
8 way , Double door
12 way , Double door
Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer ) as required . (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.)
8 way (4 + 24), Double door
12 way (4 + 36), Double door
Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.
Single pole
Double pole
Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required.
Supplying and fixing following rating, double pole, (single phase and neutral), 240 V, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required.
Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required.
100 A,30KA,FPMCCB
Providing and fixing M.V. danger notice plate of 200 mm X 150 mm, made of mild steel, at least 2 mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required.
Supplying and drawing co-axial TV cable RG-6 grade, 0.7 mm solid copper conductor PE insulated, shielded with fine tinned copper braid and protected with PVC sheath in the existing surface/recessed steel/PVC conduit as required.
Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required.
Sub-Head : EARTHING
Earthing with G.l. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/coke and salt as required. (For LT Panel)
Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
Supplying and laying 25 mm X 5 mm copper strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm)
Supplying and laying 25 mm X 5 mm G.l strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.l. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.l. nut bolt & spring washer spaced at 50mm)
Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required.
Providing and fixing 25 mm X 5 mm G.l. strip on surface or in recess for connections etc. as required.
Providing and fixing 6 SWG dia G.l. wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/cable as required.
Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.l. suspenders including G.l. bolts & nuts, etc. as required.
150 mm width X 50 mm depth X 1.6 mm thickness
450 mm width X 50 mm depth X 2.0 mm thickness
600 mm width X 50 mm depth X 2.0 mm thickness
Sub-Head : LIGHTNING CONDUCTOR
Providing and fixing of lightning conductor finial, made of 25 mm dia 300 mm long, G.l. tube, having single prong at top, with 85 mm dia 6 mm thick G.l. base plate including holes etc. complete as required.
Fixing of lightning conductor finial (single prong) with base plate including holes etc. complete as required.
Jointing copper / G.l. tape (with another copper/ G I tape, base of the finial or any other metallic object) by riveting / nut bolting/sweating and soldering etc as required.
Providing and fixing G.l. tape 20 mm X 3 mm thick on parapet or surface of wall for lightning conductor complete as required.(For horizontal run) ____
Providing and fixing G.l. tape 20 mm X 3 mm thick on parapet or surface of wall for lightning conductor complete as required.(For vertical run) //
Providing and fixing testing joint, made of 20 mm X 3 mm thick G.l. strip, 125 mm long, with 4 nos. of G.l. bolts, nuts, chuck nuts and spring washers etc. complete as required.
Earthing with G.l. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/coke and salt as required.
Providing and laying G.l. tape 32 mm X 6 mm from earth electrode directly in ground as required.
Sub-Head : MV CABLE LAYING
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required.
Above 185 sq. mm and upto 400 sq. mm
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required.
Upto 35 sq. mm (clamped with 1mm thick saddle)
Above 95 sq. mm and upto 185 sq. mm (clamped with 25/40x3mm MS flat clamp)
Supplying and fixing cable route marker with 10 cm X 10 cm X 5 mm thick G.l. plate with inscription there on, bolted /welded to 35 mm X 35 mm X 6 mm angle iron, 60 cm long and fixing the same in ground as required.
Sub-Head : MV CABLE JOINTING & END TERMINATION
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.
3½ X 300 sq. mm
3½ X 240 sq. mm
3½ X 150 sq. mm
4 X 25 sq. mm
4 X 16 sq. mm
4 X 10 sq. mm
Sub-Head : MISC. CIVIL ITEMS
Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc.direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required.
63 mm dia (OD-63 mm & ID-51 mm nominal)
160 mm dia (OD-160 mm & ID-135 mm nominal)
Sub-Head : FIRE DETECTION AND ALARM SYSTEM
INTELLIGENT FIRE ALARM SYSTEM
Ten Loop Panel.
Supplying, installation, testing & commissioning of repeater panel wih 320 character/ Touch screen LCD display with inbuilt reset, acknowledge and silence switches complete as required.
Supplying, installation, testing & commissioning of intelligent analog addressable photoelectric detector complete with mounting base complete as required.
Supplying, installation, testing & commissioning of fault isolator complete with base as required.
Supplying, installation, testing & commissioning of addressable fire control module complete as required.
Supplying, installation, testing & commissioning of addressable manual call point complete as required.
Supplying, installation, testing & commissioning of addressable horn cum strobe complete as required.
Supplying, installation, testing & commissioning of fire fighter telephone handset complete as required.
Supplying, installation, testing & commissioning of fire fighter phone jack complete as required.
Supplying, installation, testing & commissioning of addressable phone control module complete as required.
PUBLIC ADDRESS SYSTEM
Supplying, installation, testing & commissioning of 6 zone, voice alarm controller with USB, MP3 player (including 6 zone button paging station) with seamless integration facility with main fire alarm panel for voice evacuation complete as required.
Supplying, installation, testing & commissioning of 1.5/3/6W ceiling speaker complete as required.
Supplying, installation, testing & commissioning of digital audio amplifier 75 Watt, 25V rms operating at 240 Volt AC Supply complete as required.
CABLING & WIRING
Supplying & laying of 2x1.5 sqmm fire survival armoured cable, 600/1000V rated with annealed copper conductor having glass mica fire barrier tape covered by an extruded layer of Cross Linkable Ethylene Propylene Rubber (EPR) insulation and LSZH inner bedding, steel wire armouring & LSZH outer sheath complete as required.
Supplying and drawing of cable Fire Retardant PVC insulated copper conductor cable in the existing surface / recessed steel conduit of following pairs, cores and size including connections and interconnections etc. as required.
speaker cable Single pair, 2-core, 1.5 sqmm
speaker cable Four pair, 2-core, 1.5 sqmm
Supplying and fixing 25 mm dia MS flexible pipe with PVC coating along with all ancillaries and accessories like coupler etc. as required.
Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required.
2 x 1.5 sq. mm
Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required.
MV SWITCHGEAR PANELS & DISTRIBUTION BOARDS :
Design, manufacture, supply, installation, testing and commissioning of following Utility panels suitable for 415 V, 3 phase, 4 wire, 50 Hz power distribution system. The panel shall be Indoor, free standing, floor mounting, sheet metal clad, cubicle, dead front, dust and vermin proof type compartmentalised design fabricated out of 2mm thick CRCA sheet steel for Load bearing members and 1.6 mm thick for non-load bearing members, complete with colour coded, heat shrinkable PVC insulated, aluminium bus bars and separate earth bus bar of adequate cross section through out the length of the panel. The incoming and outgoing feeders shall be accommodated in a fully segregated, modular multitier arrangement with adequate size and distinct cable alley, bus bar alley/chamber (form-3b Construction). The panel shall be complete with name plate, earthing, numbering, danger plate etc. as required and as per specifications and drawings. The panel shall withstand the fault level of as indicated elsewhere or shown in Single Line Diagram.
Important Notes: Common for all Switchboard:
The BOQ shall be read inconjunction with general notes, specification and Single Line Diagram (attached for Ref.). Incase of any discrepancy between specification, BOQ and SLD, the same shall be brought to the notice of Client/Consultant before quoting the rates, otherwise stringent condition shall be deemed to have been considered.
Fault current wherever mentioned shall be Ics value. (Ics = 100% Icu).
All MCCB shall be provided with door interlocked rotary handle with ON/TRIP/OFF position indicator, continious variable thermal magnetic O/C and S/C releases. All rating MCCB's shall be thermalmagnetic type.
Incoming MCCBs shall be provided with O/C, S/C, and Earth fault protection releases.
Outgoing MCCBs shall be provided with O/C, short circuit protection.
All feeder doors shall have pad locking arrangement.
All TP feeders shall have solid isolable neutral link.
All MCCB used in starter feeder shall be suitable for motor duty application.
All power contactors including NIC shall be of AC3 duty.
All ACB's shall be with micro processor based releases and Breaker Control Switch (BCS) having lost motion device.
Spare contaCTs of ACB/Relays/Contactor etc. shall be wired upto terminal block.
All switchgear used in starter feeder shall be type-2 co-ordinated. Manufacturer is required to submit manufacturers type-2 co-ordination chart for the make used.
All meters are digital type.
Panel shall be powder coated of approved shade with minimum 60 micron thickness.
ACB's/MCCB's in one particular panel shall be of one similar make.
Size of Voltmeter / Ammeter for incomer also, 96mm x 96mm flush mounted with shrouded terminal shall be used in the panel.
Bus bar chamber shall be kept at top of the all panels.
All bus bar shall be insulated with coloured PVC Sleeve i.e.RYB,BK as per colour code.
Internal wiring of panel shall be with size 2.5sqmm Flexible Copper Conductor for CT circuit and control wiring with 1.5 sqmm.
All Lift Panels transport section should not be more then 1000 mm.
In soft starter Vender should supply power contactor with aux. Contactor & All necessary accessories required etc. (As per BOQ & specification )
All indicating light shall be LED type .
Each vertical section of floor mounted panel shall have independent base frame (75mm x 40mm) size made out of 3 mm sheet steel (LT Panel & DG Panel).
All the makes shall be as per Client approved make list only.
Wherever only voltmeter & ammeter are required, the same may be provided in combined meter suitable for both parameter.
MAIN MDB-G.F
INCOMER
Metering & indication and Annunciation for incoming breakers :
Breaker shall be provided with the following:
One (1) No. Digital Multifunction meter with RS-485 port suitable for measurement of voltage, currents, Power Factor, Frequency, Power & Energy (Conzerv EM 6400 or equivalent) with one set (3 Nos.) of CTs of ratio 800/5A Class 1.0, 15VA.
One set (3 nos.) phase indication lamps with control MCB.
BUSBAR
2Set of 1000A, TPN Aluminum bus bars with colour coded sleeves.
Bus Coupler :
1 no.630 Amps, 415 V, 50KA TPN MCCB with thermal magnetic releases, Bus coupler breaker complete with ON/OFF/ indication etc.
Electrical & mechanical interlocking shall be provided between two incomers and one bus coupler.
OUTGOING UNITS
6 Nos. 315Amp TPN MCCB 35KA with thermal magnetic releases.
5 Nos. 100Amp TPN MCCB 35KA with thermal magnetic releases.
7 Nos. 63Amp TPN MCCB 35KA with thermal magnetic releases.
SUPPLY & INSTALLATION OF MAIN DISTIBUTION BOARD AS DESCRIBED ABOVE
MDB-1ST. TO 4TH. FLOOR (TYPICAL MDB)
INCOMER
1 Nos. 315Amp 25KA 4P MCCB complete having microprocessor based over current, short circuit & earth fault protection incomer shall be complete with following.
METERING FOR EACH INCOMER
3 Nos. Cast resin current transformers of Class 1.0 for metering.
Three phase indicating lamps (LED type) with MCB.
ON OFF TRIP indicating lamps (LED type).
BUSBAR
1 Set of 400A, TPN Aluminum bus bars with colour coded sleeves.
OUTGOING UNITS
14 Nos. 63/100Amp TPN MCCB 25KA with thermal magnetic releases.
SUPPLY & INSTALLATION OF MAIN DISTIBUTION BOARD AS DESCRIBED ABOVE
MDB-5TH. FLOOR
INCOMER
1 Nos. 400Amp 25KA 4P MCCB complete having microprocessor based over current, short circuit & earth fault protection incomer shall be complete with following.
METERING FOR EACH INCOMER
3 Nos. Cast resin current transformers of Class 1.0 for metering.
Three phase indicating lamps (LED type) with MCB.
ON OFF TRIP indicating lamps (LED type).
BUSBAR
1 Set of 600A, TPN Aluminum bus bars with colour coded sleeves.
OUTGOING UNITS
2 Nos. 160Amp TPN MCCB 25KA with thermal magnetic releases.
10 Nos. 63/100Amp TPN MCCB 25KA with thermal magnetic releases.
SUPPLY & INSTALLATION OF MAIN DISTIBUTION BOARD AS DESCRIBED ABOVE
UPS MDB TYPICAL FLOOR
INCOMER
1 Nos. 63Amp 16KA 4P MCCB complete having microprocessor based over current, short circuit & earth fault protection incomer shall be complete with following.
METERING FOR EACH INCOMER
3 Nos. Cast resin current transformers of Class 1.0 for metering.
Three phase indicating lamps (LED type) with MCB.
ON OFF TRIP indicating lamps (LED type).
BUSBAR
1 Set of 100A, FP Cu, bus bars with colour coded sleeves.
OUTGOING UNITS
4 Nos. 32/40Amp FP MCB 10KA.
2 Nos. 25/32Amp DP MCB 10KA.
SUPPLY & INSTALLATION OF MAIN DISTIBUTION BOARD AS DESCRIBED ABOVE
UPS MDB-5TH. FLOOR
INCOMER
2 Nos. 160Amp 25KA 4P MCCB complete having microprocessor based over current, short circuit & earth fault protection incomer shall be complete with following.
METERING FOR EACH INCOMER
3 Nos. Cast resin current transformers of Class 1.0 for metering.
Three phase indicating lamps (LED type) with MCB.
ON OFF TRIP indicating lamps (LED type).
BUSBAR
1 Set of 300A, FP, Cu, bus bars with colour coded sleeves.
Bus Coupler :
1 Nos. 160Amp 25KA 4P MCCB complete having microprocessor based over current, short circuit & earth fault protection incomer shall be complete with following.
OUTGOING UNITS
14Nos. 63Amp TPN MCCB 25KA with thermal magnetic releases.
SUPPLY & INSTALLATION OF MAIN DISTIBUTION BOARD AS DESCRIBED ABOVE
LIFT PANEL
(Loc. Lift Machine Room)
Incoming:
One (1) No.80A 4P on Load COS.
One (1) No. 80A TPN MCCB (25KA)
Metering, Indication and Protection :
Three (3) Nos. phase indication lamps and three (3) Nos. status indication lamps with control MCB.
Busbar:
160A, 16kA TPN AL Bus Bar. Bus bar shall be insulated with heat shrinkable sleeves & shall be colour coaded.
Outgoings:
3 Nos 63A 4P MCB
1 Nos. 63A TPN MCCB (16KA)
SUPPLY & INSTALLATION OF LIFT PANEL AS DESCRIBED ABOVE
MCB FOR DB's
Supplying and fixing following rating, four pole, 415 V, MCB in the existing MCB DB complete with connections, testing and commissioning etc. as required.
STATIC SINE WAVE INVERTER FOR COMMON AREA :
Design, manufacturing,Testing at works, supply erection, testing (at site) and commissioning of 1Ph AC input & 1Ph AC output Inverter system suitable for 230VAC, 50Hz supply, variation +/-1% , PF 0.8 as per specification.
Design, manufacturing, supply ,erection, testing (at site) and commissioning of One sets of SMF VRLA battery with each inverter, having back up time as mentioned below at full load,with interconnecting cables, cabinets and standard accessories as per specification and as required for the Inverter system.(12V Cells) with wire & assessories etc.
90 Minutes back up for 6 kVA
90 Minutes back up for 3 kVA
UNINTERRUPTED POWER SUPPLY SYSTEM
Supply, Installation, Testing and Commissioning of true parallel redundant 1 x 60kVA, online, UPS system suitable for providing power supply to emergency lighting and Computerised Control panel load of approved make, suitable for incoming 440 volts, single phase +10 % -20%, 50 Hz, supply and three phase 440 volts, output voltage, variation ± 1%, including inbuilit , rectifier/dual converter, static switch, inverter, filters, Bypass & static transfer switch for automatic switch over without giving any break of power, maintenance bypass switch, Microprocessor/software controlled annunciation, protection (including against input phase reversal), and menu run diagnostic module, associated cabling and connections/terminations, erection including associated foundation/masonorey or RCC work for mounting on base channels etc. complete as per specifications and as required.
Supply, Installation, Testing and Commissioning SMF VRLA Battery Banks for UPS stipulated in item 1 above, having 30 minutes back up time at full load with interconnecting cables, racks and standard accessories UPS above. Battery shall comply with relevant regulations & Battery racks shall be made of acid resistant material and shall be supplied inclusive of above item.
Supplying, installation, testing and commissioning of accessories like Battery Rack, Interconnecting links, DC circuit breaker and cable between UPS & battery bank for above UPS.
ELV DATA POINTS
Supply, fixing, testing & commisssioning of Modular RJ-45 with data outlet socket with grid & cover plate in suitable size of 16 SWG GI box.
Supplying, drawing, connecting & testing of 4 pair CAT-6 (E) wire for Data Outlet in existing conduit
SUPPLY OF FIXTURES
Supply of the following light fixtures complete with housing, reflectors, complete with all accessories i.e. driver, lamp, holders etc. complete as required.
Ceiling Mounted recessed Round/Square type luminaire with LED (Light Emitting Diode) system power: 9-12 W, Luminous flux of luminaire 1980 lm, Colour temperature of 4000 K, Neutral white,SDCM 3, R9 Value should be ≥0, CRI > 80, 230 V constant current driver, 70% of luminous flux after 50,000 operating hours; Energy efficient LEDs, Direct light emission, Luminaire housing in die-cast aluminium, Opal protruded diffuser for homogenous light distribution, ZHLS (ZERO HALOGEN LOW SMOKE) internal wiring, Electronic control gear, Protection class II , IP 20
Suface mounted Round/Square type luminaire with LED (Light Emitting Diode) system power: 12-15 W, Luminous flux of luminaire 1980 lm, Colour temperature of 4000 K, Neutral white,SDCM 3, R9 Value should be ≥0, CRI > 80, 230 V constant current driver, 70% of luminous flux after 50,000 operating hours; Energy efficient LEDs, Direct light emission, Luminaire housing in die-cast aluminium, Opal protruded diffuser for homogenous light distribution, ZHLS (ZERO HALOGEN LOW SMOKE) internal wiring, Electronic control gear, Protection class II , IP 20.
Mirror Wall mounted luminaire Tube light with LED(Light Emitting Diode) system power: 9-11W, luminous flux of luminaire 900lm, colour temperature of 4000K, neutral white, CRI>80, 230V constant current driver, 70% of luminous flux after 50,000 operating hours, energy efficient LEDs, direct light emission, aluminium housing, satin micro liner prismatic diffuser, electronic control gear, Protection class I, IP20, Length=600mm, Bredth=21mm, Height=35mm.
Surface mounted luminaire with HE-High Efficiency LED (Light Emitting Diode) system power: 36-40W, luminous flux of luminaire 3300lm, colour temperature of 4000K, CRI>80, 230V constant current driver, 70% of luminous flux after 50,000 operating hours, energy efficient LEDs, direct light emission,anodized luminaire profile housing in die-cast aluminium, Prismatic diffuser for a homogenous light distribution, ZHLS(ZERO HALOGEN LOW SMOKE) internal wiring, integral electronic control gear, sliding fixing wire suspension. Protection class I, IP40, MacAdam 3,R9 Value should be ≥0, T.H.D≤ 10%, driver efficiency ≥ 88%, surge protection of 2.5kV Length=1175mm, Bredth=52mm, Height=64mm.
Surface mounted luminaire with HE-High Efficiency LED (Light Emitting Diode) system power: 24-30W, luminous flux of luminaire 3300lm, colour temperature of 4000K, CRI>80, 230V constant current driver, 70% of luminous flux after 50,000 operating hours, energy efficient LEDs, direct light emission in Aluminium, housing, having Prismatic diffuser luminaire profile for a homogenous light distribution, ZHLS(ZERO HALOGEN LOW SMOKE) internal wiring, integral electronic control gear, sliding fixing wire suspension. Protection class I, IP40, MacAdam 3,R9 Value should be ≥0, T.H.D≤ 10%, driver efficiency ≥ 88%, surge protection of 2.5kV Length=1175mm, Bredth=52mm, Height=64mm.
LED recessed luminaire with LED(Light Emitting Diode) system power: 36-42W, colour temperature of 5700K, 230V constant current driver, 70% of luminous flux after 50,000 operating hours, energy efficient LEDs, CRI>80, luminous flux of 3600 lm,SDCM 3, R9 Value should be ≥0 Electronic Control Gear, direct light emission, housing in die-cast aluminium, Prismatic diffuser for glare-free uniform light Protection class I, IP40, MacAdam 3, T.H.D≤ 10%, UGR<19, driver efficiency ≥ 88%, surge protection of 2.5kV Length=595mm, Bredth=595mm, Height=70mm.
Surface mounted bulkhead with LED (Light Emitting Diode) system power: 6-9 W, luminous flux of luminaire 800lm, colour temperature of 5700K, cool white, CRI>80, 230V, direct light emission, aluminium housing, powder coated white, opal diffuser for uniform illumination, electronic control gear, Protection class II, IP65, IK08.
1200 Dia Fan
225MM Dia Ex. Fan
LT NORMAL CABLE
Supplying of following sizes of XLPE/ PVC insulated Aluminum/ Copper conductor and Armoured, overall PVC sheathed 1.1 KV grade cables conforming to relevant IS code and technical specifications.
XLPE insulated Al. Ar.Cable
3.5C x 300 sq.mm.
3.5C x 240 sq.mm.
3.5C x 150 sq.mm.
4C x 25 sq.mm.
4C x 16 sq.mm.
4C x 10 sq.mm.
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required.
4 X 25 sq. mm +2X 6.0 sq. mm earth wire (For DB Submain)
CABLE RACEWAY
Fabricating and installation following sizes of Cable raceways made out of HOT DIP sheet steel including horizontal and vertical bends and others accessories as required and duly suspended from the ceiling with MS suspenders and including painting etc. as required.
200mm x 50mm
150mm x 50mm
100mm x 50mm
50mm x 50mm
VIDEO SURVEILLANCE SYSTEM (IP CCTV)
Supplying, installation, testing and commissioning of 2 megapixels resolution Network Dome Camera for true HD quality images,2.8 – 12 mm varifocal lens,True Day/Night (TDN) functionality for true color image ,Motion Detection 4 Zones, Multi- Level Sensitivity Privacy Zones 4 Zones,Snapshoot Support JPEG format Password Protection Support Character Display Support(Channel /Date) ONVIF Yes,IR Illumination20-30M IR illuminators for clear images in low light conditions Wide Dynamic Range 3D noise reduction for sharper images and lower bandwidth use in low light ONVIF compliant complete in all respect.
Supply, installation, testing and commissioning of 2 megapixels resolution Network Bullet camera camera,Imager 1/2.8” 3 mega low illumination CMOS,Video Compression. .H.264/MJPEG,Day/Night .Mechanical ICR,Minimum Illumination-0Lux/F1.4(IR ON) IR Illumination-40-50M,,Electronic Shutter-Auto/Manual(1/25~1/10000) Lens 2.8 – 12 mm varifocal lens,Resolution Main stream:D1/Q1080P(960*540)/HD720P/ HD1080P 1-25/30fps,Digital Noise Reduction-3D,Wide Dynamic Range-Digital WDR Motion Detection -4 Zones, Multi- Level Sensitivity,Privacy Zones-4 Zones,Snapshoot-Support JPEG format,Password Protection-Support,Character Display-Support(Channel /Date).Regulatory Emissions-FCC Part 15 CE: EN55022,Immunity -CE: EN50130-4,IP Rating- IP66 rated enclosure to protect against dust and water damage ONVIF compliant .
Supplying of 2U Rack mount single chassis Network Video Recorder with dual Gb NIC, 1 DVI-I + HDMI + 1 Display Port, max 2 simultaneous monitors, RS-232/485 serial port, DVD, Server Operating System-Windows 10,Ubuntu Linux 16.04, Processor-Gen 4 Intel Core i3, Local Client Display Rate (FPS)Windows – 700 FPS (HD)Linux – 900 FPS (HD),High Performance, High Reliability IP Recorder. — Continuously records 300Mbps (Windows) & 450 Mbps (Linux)of video while hosting a local client, multiple remote clients and the web server on a single server,RAM-4 GB, 8 GB, 12 GB (Optional)solid-state operating system drive,USB-6 x USB 2.0, 2 x USB 3.0 high air flow cooling and hardware monitoring features ensure maximum uptime. keyboard and mouse, Professional Grade client and server software pre-installed and software updates. Access live and recorded video on multiple client PCs with free Windows, Mac or Linux client application. web server application is pre-installed on the server to access video through a web browser or free Mobile iPhone / iPad and Android apps. Maximum Storage Capacity 30TB & Maximum Hard Drive 3 Slot(Up to 10TB) Support Up to 64 IP Camera.
Supply, installation, testing and commissioning of Network Video Recorder , Live view/Resolution 5MP/3MP/1080p/720p,Motion Detection Control Privacy Mask Control. USB interface-1 × USB 2.0 and 1 × USB 3.0,Security-HTTPS, SSL, Watermark, User Authentication, Miscellaneous-N+1 hot spare. Alarm in/out -4 / 1,Network interface-1 RJ-45 10 /100 /1000 Mbps self-adaptive Ethernet interface, Security-HTTPS, SSL,Video/Audio output-VAG,HDMI and Audio. Watermark, User Authentication,Incoming bandwidth-100Mbps,Outgoing bandwidth-80Mbps,HDMI output,VGA Output,Protocol-IPv4, IPv6, TCP/IP protocol, PPPoE, DHCP, DNS, DDNS, NTP, SADP, SMTP, SNMP, NFS, and iSCSI are supported.TCP, UDP and RTP for unicast, UPnPTM, ONVIF, PSIA,Support 16 IP Camera, 2 SATA interfaces for 4 HDDs Upto 6TB for each disk.
Supply, installation, testing and commissioning of Enterprise Class 6TB HDD.
Supply, installation, testing & commissioning of 16 Port PoE+ Switch with 2 SFP slots 12 x 10/100/1000 Base-T PoE+ ports and additional 2 100/1000X SFP PORTS Should support PoE+ as per IEEE 802.3 at with PoE budget of 100W.Should support STP, RSTP, MSTP, IGMP v1/v2/v3 snooping, STP root guard, Voice VLAN, MLD snooping (MLDv1 and v2), IEEE 802.3ac VLAN tagging IEEE 802.17/equivalent for sub 50ms ring protection in following scenario : single, dual fibre cuts in ring and when fibre cut at common shared link in between two or more rings.
Supply, Installation, Testing and Commissioning of Workstation PC: Intel(R) Core(TM) i7-3770 Processor (8M Cache, up to 3.90 GHz); Memory: 4GB, NON-ECC, 1600MHZ; RAM: 4GB (1x4GB) Non-ECC DDR3 1600MHz SDRAM Memory; Keyboard: 12 function keys; Chassis: Tower/Workstation; DVD: 8X Slimline DVD+/-RW, Data Only; 20" TFT Monitor; Dual Graphics Card; Network interface card: Integrated Intel(R) 82579LM Gigabit1 Ethernet LAN 10/100/1000; Hard disk: 250GB, 7200 RPM 3.5" SATA 6Gb/s Hard Drive; Operating system: Windows 7 Professional 64 Bit.
Supplying, Installation,Testing & Commissioning of 55 " LED Full HD TV Resolution 1920 x 1080 ,Contrast Ratio (Typical) 5000:1,Built-in Speaker (10W + 10W), Magic Clone (to USB), Auto Source Switching & Recovery, Lamp Error Detection, Super Clear Coating, Temperature Sensor, Plug and Play (DDC2B), Pivot Display, Clock Battery, PIP/PBP, Video Wall (10x10), Image Rotation, Button Lock, HDCP Support, Smart Scheduling, Smart F/W update, Built-In MagicInfo Premium-Swith Mounting Brackets as per Technical Specification complete in all respect.
Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required.
Supplying, laying, marking, making connections and testing of CAT-6 cable . (For CCTV Camera )
EPABX SYSTEM
Supply Installation, Testing and Commissioning of Server Based EPABX Fully Computerized IP System, SIP Compliant. 2U Rack Mountable,Expandable upto 700Ports.and configured as for below Ports P & T(CO Trunk) Line 10 Nos. PRI(30 Channel) 2 Nos. IPExtension Circuit 20 Nos. Digital Extension Circuit 32 Nos Analog Extension Circuit 150 Nos SIP Trunking 18 Nos.
Supply Installation and Commissioning of PC Based centralized Operator Console with all dignostic Software of IP EPABX System (Supplying with PC).
Supply Installation, Testing and Commissioning of Integrated Viocemail System 4 Level IVR software with 6 different languages and 4 time schedule(As per OEM).
Supply Installation and Commissioning of License for web integration for aspire net license integrated with hub exchange
Supply Installation Testing and Commissioning of Digital Phone (24Key+ 60-line DSS Console) Backlit keypad Hands-free, full duplex ,Headset support Easy to use soft keys/LCD prompts,Directory dialling,Navigation wheel,Call history,Backlit LCD screen,Bluetooth support (BCAZ),Security lock key XML open interface .
Supply Installation Testing and Commissioning of 24Key Digital Phone Backlit keypad Hands-free, full duplex, Headset support Easy to use soft keys/LCD prompts,Directory dialling,Navigation wheel,Call history,Backlit LCD screen,Bluetooth support (BCAZ),Security lock key XML open interface .Make-NEC/Avaya/Alacatel
Supply Installation Testing and Commissioning of Digital Phone (12Key)Backlit keypad Hands-free, full duplex Headset support Easy to use soft keys/LCD prompts Directory dialling Navigation wheel Call history ,Backlit LCD screen,Bluetooth support (BCAZ),Security lock key XML open interface.
Supply Installation Testing and Commissioning of Digital Phone (6Key)Backlit keypad Hands-free, full duplex Headset support Easy to use soft keys/LCD prompts Directory dialling Navigation wheel Call history , Backlit LCD screen,Bluetooth support (BCAZ),Security lock key XML open interface.
Supply Installation Testing and Commissioning of IP Phone (12Key)Backlit keypad Hands-free, full duplex Headset support Easy to use soft keys/LCD prompts Directory dialling Navigation wheel Call history , Backlit LCD screen,Bluetooth support (BCAZ),Security lock key XML open interface.
Supply Installation, Testing and Commissioning of Analog Speaker Phone with backlight.
Supplying, of 100 Pair anealed tinned copper conductor PVC insulated and sheathed armoured copper telephone cables with suitable clamps, saddles and including making terminal joints complete as required.
Supplying, of 50 Pair anealed tinned copper conductor PVC insulated and sheathed armoured copper telephone cables with suitable clamps, saddles and including making terminal joints complete as required.
Supplying, Installation, Testing & Commissioning of of 50 Port telephone Jack Panel
DATA NETWORKING SYSTEM
Supply, Installation, testing and commissioning of following 24 Port Switch Ethernet work station , layer 2, managed 1 Ghz, Network Switch with POE+ facility and 2 Nos. of Fiber Ports
Supply, Installation, testing and commissioning of 24 Port Patch Panel Category 6, IDC patch panel prepackaged with wiring block with legs with legs insert labels, label holders, jumper troughs, metal back panel, duct assembly, screws, washers and an instruction sheet for termination of incoming pairs and all necessory accessories to complete the work
Supply and laying of 6 core MM 50/125 micron OM3 , LSZH, Fibers multitube type Optical Fiber Cable of Armoured type.
Supply, installation, testing and commissioning of 4 pair Category 6 UTP cable consisting of 23 AWG solid copper conductors and as per the specification. The cable should have flexible jacket and ripcord for easy stripability.
Supply , Installation , Testing and Comissioning of CAT6 information outlet (I/O) for Data at user end. (
Supply , Installation , Testing and Comissioning of CAT6 patch cord 3 feet for rack side switch to jack panel connectivity.
Supply , Installation , Testing and Comissioning of CAT6 patch cord 7 feet for information outlet (I/O) to end user device connectivity.
Supply , Installation , Testing and Comissioning of 1, 2 and 4 port face plate white for I/O fixing at user side.
Supply , Installation , Testing and Comissioning of Fiber LIU 12 Port Loaded with pig tails
Supply , Installation , Testing and Comissioning of Fiber Module MM LC Gigabit
Supply , Installation , Testing and Comissioning of Network Rack 18 U 600x800 Floor Mount, 2 cable managers , satationary shelf , 2 Nos. of hardware pkts. This rack is common for Telephone, Data, Access Control system.
Supply , Installtion , Testing and Comissioning of 4U wall mount rack with fans , 2 cable managers , satationary shelf , 2 Nos. of hardware pkts. This rack to be used for CCTV, DATA networking also and to be placed in shaft.
Providing and fixing in position the 25 mm dia conduit FRLS PVC conduits concealed or exposed as called for including all acessories i.e. bends, junction boxes, outlet boxes with cover plates of approved make and design.
EXTERNAL LIGHTING
Supplying, erection, testing and commissioning of HOT dip galvanized octagonal steel pole of 7 meter height made out of 3mm thick sheet having 2 NOS. bracket length of 500mm long including built in connector control box with flush cover and supplying and fixing of 6 Amp SP MCB C-Series and 32 Amp heavy duty connector etc. for making connections with suitable size of copper wire and thimbles / lugs in the connector box, base plate of 200mm x 200mm x 12mm thick, bolt size 4 nos 24mm long, bolt length 750mm, projected bolt length 125mm and anchor plate thickness of 3mm. The pole shall be installed in cement concrete foundation (1:3:6) i.e. 1 cement, 3 coarse sand and 6 graded stone with the help of anchor bolts of 3/4" dia by laying iron bar mesh fabricated with 6mm dia iron bar, earthing of pole, connection etc. complete as required.
Supplying, erection, testing and commissioning of HOT dip galvanized octagonal steel pole of 7 meter height made out of 3mm thick sheet having bracket length of 500mm long including built in connector control box with flush cover and supplying and fixing of 6 Amp SP MCB C-Series and 32 Amp heavy duty connector etc. for making connections with suitable size of copper wire and thimbles / lugs in the connector box, base plate of 200mm x 200mm x 12mm thick, bolt size 4 nos 24mm long, bolt length 750mm, projected bolt length 125mm and anchor plate thickness of 3mm. The pole shall be installed in cement concrete foundation (1:3:6) i.e. 1 cement, 3 coarse sand and 6 graded stone with the help of anchor bolts of 3/4" dia by laying iron bar mesh fabricated with 6mm dia iron bar, earthing of pole, connection etc. complete as required.
Supplying and fixing of Street light fixture 70 Watts LED complete with glass cover etc. and its wiring with 3 x 2.5 sq.mm PVC insulated copper wire from junction box complete ).
Providing and fixing 6SWG dia GI Wire on surface or in recess for loop earthing along with existing surface/recessed conduit/sub main wiring/cable as required.
Supplying, laying and connecting 2 nos 2.5. sq.mm copper conductor PVC insulated 1100 volts grade wires from terminal block to light fixture along with end terminations and including the cost of 1 no. 2.5 sq.mm PVC insulated copper wire for earthing of the light fixture complete as required.
EXTERNAL LIGHTING FEEDER PILLAR OUT DOOR TYPE
INCOMER
1 Nos. 63Amp 16KA 4P MCCB complete having microprocessor based over current, short circuit & earth fault protection incomer shall be complete with following.
1 Nos. 60Amp AC3 4P Contactor with timer be complete as required.
METERING FOR EACH INCOMER
3 Nos. Cast resin current transformers of Class 1.0 for metering.
Three phase indicating lamps (LED type) with MCB.
ON OFF TRIP indicating lamps (LED type).
BUSBAR
1 Set of 100A, TPN Aluminum bus bars with colour coded sleeves.
OUTGOING UNITS
10 Nos. 6/32Amp TPN MCB 10KA
SUPPLY & INSTALLATION OF EXTERNAL LIGHTING FEEDER PILLAR AS DESCRIBED ABOVE
Supplying of following sizes of XLPE/ PVC insulated Aluminum/ Copper conductor and Armoured, overall PVC sheathed 1.1 KV grade cables conforming to relevant IS code and technical specifications.
4C x 25 sq.mm.
2C x 10 sq.mm.
Isolation panel - Type-1 (for OTs)
INCOMER
1No. 63A DP MCB(10KA)
1No. 63A DP ELCB(300mA)
METERING & INDICATION
1 set of ON /OFF indicating lamps
1 No. (0-500V) Voltmeter (size-72 sq.mm.) with Built-in VSS with 2A SP MCB
1 No. (0-63A) Ammeter
Green indication lamp for safe zone
Red indication lamp for hazard zone
1 No. Buzzer for Alarm
LINE ISOLATION MONITOR
Solid state Line isolation monitor suitable for detecting 2-4 mA (adjustable) leaKAge current
TRANSFORMER
1 no. 12.5 KVA, Single Phase, air cooled, copper conductor, double wound core type Isolation transformer
OUTGOINGS
12 Nos 6A /16A SP MCB(10KA)
Supply Receiving, fixing, testing & commissioning of Isolation Panel(Type-1) as described above
KAPAHI CONSTRUCTION COMPANY
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 1.33 MB
SBD.pdf
Tender Documents • 1.83 MB
BOQ_374382.xls
BOQ • 2.00 MB
4Drawings_compressed.pdf
Tender Documents • 13.30 MB
Lectmakelist.pdf
Other Document • 1.19 MB
2General.pdf
Additional Documents • 0.33 MB
Download all tender documents and submit your bid