GE LALGARH JATTAN
GE LALGARH JATTAN - 335037, RAJASTHAN
REPLACEMENT OF SECURITY LIGHTS AT DEPOT PERIMETER AT 24 FAD AND PROVN OF ELECTRIC CHIMNEYS IN CERTAIN OFFR MD ACCN AT LGJ MIL STN UNDER GE LALGARH JATTAN
2026_MES_792231_1
8937-43/GE/2026-27
Open Tender
Civil Works
Item Rate
180 days
GE LALGARH JATTAN
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
GE LALGARH JATTAN
₹38,800
Yes
3 Oct 2026
3 Oct 2026
24 Oct 2026
3 Oct 2026
22 Oct 2026
17 Oct 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Excavation in trenches by, not exceeding 1.5 metre wide and not exceeding 1.5 metre in depth for pipe line, cable trenches or for manholes etc not exceeding 10 sqm area on plan and not exceeding 1.5 metre in depth and getting out in soft/loose soil complete all as specified and directed | 240 | Cum | - | - |
| 2 | Returning filling in including spreading, levelling, watering and well ramming in layers not exc 25 cm thick complete all as specified and directed | 216 | Cum | - | - |
| 3 | Removing of surplus excavated soil to a distance not exc 50 mtr and depositing where directed at a level not exc 1.5 mtr above the starting point complete all as specified and directed | 24 | Cum | - | - |
| 4 | Supply and laying HDPE DWC Pipe of Size 40/32mm dia including fitting accessories for protection of cable ISI marked confirming IS 16205 complete all as specified and directed | 900 | RM | - | - |
| 5 | Supply and laying XLPE LT cable of size 16 Sqmm, 4 Core , 1100 Volt grade heavy duty with XLPE insulated standard aluminium conductor served with an inner sheathening of PVC tape armoured with Galvanized steel strip and over all PVC Sheathed stranded conductor conforming to IS- 7098 (Part-I) with latest amendments laid in trenches/fixed to wall/pole/laid in floor including necessary connections and suitable size of thimbling complete all as specified and directed by Engineer-in-charge. | 1,000 | RM | - | - |
| 6 | Supply and fixing LED flood light 100 watt 230 V AC outdoor type with thermal management in multiple optics and equipped with IP66 protection, with impact and corrosion resistant complete with driver and lamp. | 132 | Each | - | - |
| 7 | Supply and fixing in replacement LT cable junction box, dust and water proof (IP65), out door type, made out of Polycarbonate with glass fiber re-inforced, size of box 250 x 200 x 100 mm with swinging cover and locking clamp, pole mounting, consisting 4 Nos Al busbar mounted on SMC insulator links and provision of suitable busbar incoming/outgoing cables with gland, including in built 6Amp MCB, SP, 10KA one No complete all as specified and directed.
Note : Rate deemed to be inclusive of MS clamps and nut bolts for fixing the box along pole and connection the same to incoming and outgoing cable . | 132 | Each | - | - |
| 8 | Supply and fixing copper twin core cable of size 1.5 sqmm for light connection along with PCV conduit of 15mm dia complete all as specified and directed by Engr-in-charge. Note : Rate deemed to be inclusive of MS clamps and nut bolts for fixing the PVC conduit along pole and connection the same to LT Cable box and light . | 924 | RM | - | - |
| 9 | Material and labour for making the hole under road and hard standing for laying and including inserting Galvanised steel light grade pipe upto 100 mm dia including all fittings as required at site by mechanical drill system or Auger system and making the surface good as per existing surface completed all as specified and directed by Engineer-in-Charge.Note : The rate of Galvanised steel light grade pipe upto 100 mm dia is paid seprately under appropriate item of schedule of works | 12 | RM | - | - |
| 10 | Material and labour for taking down flood light from existing pole servicing /minor repair to make lights serviceable and refixing the same on pole at location as per direction of Engr-in-charge. Note :- Cost of PVC Conduit , copper cable and junction box will be paid seperately . | 60 | Each | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.29 MB
tender_merged.pdf
Tender Documents • 0.84 MB
BOQ_888284.xls
BOQ • 1.73 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .