Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹9.4 LAccepted-AOC | L1 | Accepted-AOC LOWEST BIDDER FOR THE WORK | |
| 2 | L2₹10.6 L+₹76,275 (7.77%)Rejected-AOC | L2 | Rejected-AOC OTHER THAN THE LOWEST BIDDER | |
| 3 | L3₹10.9 L+₹1.1 L (11.5%)Rejected-AOC | L3 | Rejected-AOC OTHER THAN THE LOWEST BIDDER |
Tender Value
₹9.8 L
EMD Value
₹19,600
Closing Date
2 Dec 2019, 6:00 pmClosed
CWE BHOPAL
HQ CWE BHOPAL, SI LINES, BHOPAL, PIN-462001
REPAIR / MAINT AND IMPROVEMENT OF HT LINE SYSTEM AND CONNECTED WORKS AT SI LINES BHOPAL
2019_MES_293337_1
83422
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
BHOPAL
AS PER NIT CONDITIONS
4 documents required · 4 mandatory
₹500
GE BHOPAL
₹19,600
Yes
23 Jan 2020
11 Nov 2019
9 Dec 2019
11 Nov 2019
2 Dec 2019
21 Nov 2019
Amount
Dismantling / Taking out Unserviceable HT/LT cables for replacement of any size from any position i.e ground / walls / poles / culverts etc complete with protection pipe all as specified and directed by Engineer-in-Charge. Note : Earth work shall be measured and paid seperatly
Excavation in trenches/ foundation in soft/ disintegrated soil not exc. 1.5 metre wide and n'exc. 1.50m deep for HT under ground cable/pole foundation and getting out including forming bottom surface to required level or slope, complete all as specified and directed by Engineer-in- Charge.
Returning filling including spreading leveling watering and well ramming in layers not exc 25Cm in soft/ loose soil, complete all as specified and directed.
Removing excavated material in soft/ loose soil n'exc 50M and depositing where directed at a level n'exc1.5M above the starting point, complete all as specified and directed.
M&L for sand cushioning to U/G cable in layers of 23cm thick( 8 Cm before laying the cable and 15Cm thick after laying the cable) in trenches complete all as specified and directed. Note :- Only Puned thickness / layers shall be measured.
M & L old size brick well burnt, laid flat, for cable protection complete all as specified and directed.
Supply and Laying cable XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 11000 Volts grade with stranded aluminium conductor on wall with the help of shadel of size 120 Sqmm 3 core as required at site.
Supply and Laying cable XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor on wall with the help of shadel of size 150 Sqmm 3.5 core as required at site.
M&L for outdoor end terminal joints heat shrinkable Suitable for HT 11000V, XLPE insulated armoured Heavy duty under ground cable including joint kits and labour complete for making joints suitable for aluminium conductor cable of cross sectional area 95-120 Sqmm, 3 Core, all as specified and directed. Make-Birla-3M / Denson / Raychem
M&L in replacement of air break switch vertical/horizontal rocking type gang operated (GOD) triple pole mechanically operated, mounted on insulators (09 insulators) & steel frame with operating mechanism & operating rod of GI pipe 25mm & medium grade with necessary clamps to be operated from ground level 11 KV grade working pressures and current upto 200 amps and all as spcd and directed. Make :- Jaipuria Brothers / Pactil / MEI / Rastriya
Supply and replacement of SILICA GEL Breather for transformer suitable for 1500 KVA duly filled with Silica Gel clear view design , complete with oil cup at bottam complete all as specified and directed.
Supply and replacement of SILICA GEL Breather for transformer suitable for distribution transformers 100 to 500KVA duly filled with Silica Gel clear view design , Gel Qty- 1.5 Kg , complete with oil cup at bottam complete all as specified and directed.
Supply and filling silica Gel in existing breather complete all as specified and directed .
M&L for replacement of cross arms , bracings, supports, clamps and back plate fabricated from structural sections including nuts, bolts, and washer bending hot or cold , drilling holes for bolts of any size and painting with two coats of aluminum paint over one coat of red oxide primer including preparation of surfaces, complete all as specified and directed by the Engr-in-Charge.
M&L for replacement of anti-climbing device spikes type fabricated out of MS bars ( round , squre and flat ) including nuts , bolts , washers and welding in two halves made to shape to suit the cross section of the pole .
Supply and replacement, straining for replacement of Galvanized iron earth wire 4/3.15mm dia with guarding cradle on HT / LT over head line, complete all as specified and directed by Engineer-in-Charge.
S & F for replacement of pin type insulator porcelain vitreous white/ brown or green including one galvanised mild steel spindle two GI washer and one GI nut 150mm height, 150mm dia for 11000 Volt grade complete all as specified and directed.
S & F for replacement of disc insulator porcelain vitreous 145rnm high and 225 mm dia ball & socket type with tension clamp suitable for conductor single disc assy working pressure 11000 volts complete all as specified and directed.
M & L for replacement of lightning arrestor metal oxide type confirming to IS-3070 Part 1 complete line discharge (class - 2 nominal discharge current 5 KA & high discharge 65 KA assembly suitable for 11 KV incl all clamps, nuts, bolts & washers & connecting to earth with 32 x 6 mm GI strip complete all as specified and directed. Make - Jaipuria Brothers / Pactil / OBLEM
M&L for Providing cement concrete 1:2:4 type B-1 (using 20mm graded stone aggregate) as in coping to poles & the like etc including weathering, slightly rounded or chamfered angles and throating as directed including necessary form work complete for repair to existing pole foundation.
M&L PCC (1:3:6) type C-2 using (40mm) graded stone aggregates as in foundation filling and mass concrete (for foundation bed concrete in stays /poles or any other directed site)
M&L for replacement of 80mm dia GI tubing light grade with all necessary fittings laid in trenches, fixed to walls, poles, under road / floor etc for cable protection, complete all as specified and directed.
M&L for replacement of 100mm dia GI tubing light grade with all necessary fittings laid in trenches, fixed to walls, poles, under road/ floor etc for cable protection, complete all as specified and directed.
M & L for replacement of Danger Notice plate of 1.6mm thick mild steel sheet vitreous enameled white with letters, figures & conventional skull & bones in signal red colour and fixed with MS clamps, bolts & nuts of approved size of 25 cm x 20cm for 33/11 KV , complete all as specified and directed.
M&L for one coat of aluminium paint including preparation of steel surface for 4 pole structure ( above planting depth ) 11 metere long steel tubular pole and mild steel work i.e. cross arms, bracing , clamps,,with painting Yellow and black strip etc complete all as specified and directed.
Description all as per item No 26.00 above but for two pole structure.
M&L for painting of steel tubular pole , 9 Mtr. Long , LT , 410-SP-31, vertical complete with cross arms with one coat of aluminium paint before preparation of surfaces of poles, cross arms,with painting Yellow and black strip or as ordered by engineer-in-charge on poles up to 1.5 mtr high above coping level and numbering with writing letters or figures ( Block ) ,height n'exc 10 cm high & letters or figures n'exc 10 Nos for electric LT/HT straight pole , strut pole, 2pole/4 pole structure complete all as directed.
Description all as per item No 28.00 above but for 11 Mtr Long HT ,410 - SP - 55 , complete all as specified and directed.
Supply, installation, commissioning & testing of Horn gap fuse , Tripple pole ,outdoor type fuse link suitable for vertical or horizontal installation, consisting of MS channel base , 11 KV post type insulator, complete with fuse , phosphorus bronze contacts complete all as specified. (Note :- MS structure shall be measured and paid for separately). Make - Jaipuria Brothers / Pactil / Rastriya Electrical
Trimming of tree branches adjacent to OH conductors 2 Mtr clearances from live conductor complete all as directed.
Rubbing/scratching old paint of transformer of capacity 100 KVA to 500 KVA, through cleaning with kerosene oil and providing one coats of synthetic enameled spray paint including writing SM / MES / Machine Numbers as directed.
Taking down the existing defective Post Insulator after disconnecting from HT line including supply and fix Post Insulator suitable for 33 KV complete with 6mm thick 1 feet long copper strip fixed at the top of the Post Insulator complete and connected with HT line complete all as specified and directed
S & F in replacement of MCCB 4 pole,415 Volts,adjustable type ,160 Amps, 50Hz 36KA, Make : Havells / Legrand / ABB / HPL / C & S / GE power
S & F in replacement of MCCB 4 pole,415 Volts,adjustable type ,200 Amps, 50Hz 36KA, Make : Havells / Legrand / ABB / HPL / C & S / GE power
S & F in replacement of MCCB 4 pole,415 Volts,adjustable type ,250 Amps, 50Hz 36KA, Make : Havells / Legrand / ABB / HPL / C & S/ GE power
S & F in replacement of MCCB 4 pole,415 Volts,adjustable type ,400 Amps, 50Hz 36KA, Make : Havells / Legrand / ABB / HPL / C & S/ GE power
S & F in replacement 95 sqmm PVC insulated PVC sheathed aluminium conductor single core cable in jumpers and binding with suitable size of aluminium conductors on the both ends of existing LT OH line and all as directed.
S&F Mild steel Gde Fe-410-W(Gde-E-250) quality ‘A’ joist, channel, angle or tee sections, fixed independently with out connceting plates, etc. ( cut to ordinary lengths i.e. within 20 mm of the length indicated) including two coats of synthetic enamel paint over a coat of red oxide/Zinc chrome primer complete all as specified and directed.
M&L for expanded metal cut to length bent to shape required with and including annealed mild steel not less than 0.9mm dia or fixed with galvanized steel staples or welded with supporting steel members. Weight XPM not exceeding 4 Kg/Sqm complete including painting with two coats of synthetic enameled paint over one coat of red oxide / zinc chrome primer surface of steel and iron and all as specified. Note – item shall be replaced against broken / perished horn post type fencing and retrieval there of shall be credited accordingly .
S&F MCB single pole 6 to 32 Amp 240 Volt 'B' curve 10 KA complete all as specified and directed by the Engr-in-Charge.
Supplying & erecting for replacement of steel tubular swaged type conferrming to IS, specification complete with base plate, welded top cap over all vertical length11.00 mtr type 410-SP-55 two coat of primer red oxide internally ( exposed to view) and painted internally two coats of bituminous paint through out and externally painting of one coat with alluminium paint including necessary excavation and earth work PCC (1:4:8) type D-2 in foundation and coping with (1:3:6) type C-1 including form work above ground level disposal of surplus soil to a distance not exceeding 50 mtr complete painting with aluminium painting including provision of black and yellow of 05 Nos of 30 CM each strip or as ordered by engineer-in-charge on poles up to 1.5 mtr high above coping level and numbering of poles with feeder location all as specified.
M&L for painting of Feeder Pilar box with one coat of red oxide primer after preparation on of surfaces and two coat of Synthetic enamel paint existing colour of both side complete all as specified and and directed.
Calibration and testing of combined inverse time over current earth fault and instantaneous relay for cheking and cleaning and insure physical healthlines with visul check for healthy tripping of over current and earth fault setting tripping timer ratio setting instantaneous time setting etc. as per insalled capacity of transformers with artificial current injunction on primary & secondary with current injunction machine complete all as directed.
Testing of over current & earth fault IDMT relays as per time/ current characteristics by secondary injection test at 50%, 75%, 100 % plug setting and operating time at twice the set value & TMS 1 and calibrating including well cleaning and decarbonizing of relay contacts.
Taking out Transformer from site with the help of chain pully / motorised crain and transporting to work shop and return back after repair & re-installed at site including testing,commissioning all as directed at site.
Supply and replacement unserviceable full threaded copper stud with four nos Nuts and washer as per sample suitable for LT side of 100 to 200 KVA transformer complete all as specified and directed.
Description all as item No 47.00 above but suitable for LT side of 250/400 KVA transformer complete all as specified and directed.
Supply and replacement unserviceable full threaded copper HT stud with busing cap and nuts as per sample suitable for 100 to 200 KVA transformeer complete all as specified and directed.
Description all as per Ser item No 49.00 above but suitable for 250/400 KVA transformer complete all as specified and directed.
Supply and replacement unserviceable LT bushng with rubber gasket as per sample suitable for 100 to 200 KVA transformer complete all as specified and directed.
Description all as per item No 51.00 above but suitable for 250/400 KVA transformer, complete all as specified and directed.
M&L for reconditioning of unserviceable battery 12 V, 180 AH by replacing complete cells, PVC seperators, electrolyte, terminals and final sealing, recharging and testing complete all as specified and directed.
M&L outdoor straight through joints cold shrinkable suitable for HT 11/6.6V., XLPE insulated armoured Heavy duty under ground cable including joint kits and labour complete for making joints suitable for aluminium conductor cable of cross sectional area 95-120 Sqmm, 3 Core, all as specified and directed. Make-Birla-3M / Denson / Raychem
M&L for outdoor end terminal joints cold shrinkable Suitable for HT 11000V, XLPE insulated armoured Heavy duty under ground cable including joint kits and labour complete for making joints suitable for aluminium conductor cable of cross sectional area 95-120 Sqmm, 3 Core, all as specified and directed. Make-Birla-3M / Denson / Raychem
Supply , replacement & straining the ACSR conductor, including binding wire, tape and jumper complete all as specified of size as ordered.
Purification / filteration and dehydration of transformer oil for 33/11 KV, 11/0.430 KV transformer with stream line filteration plant at a temp 60-70 degree celsius and achieving dilectric strength of oil 50 KV for one minute in 4 mm gap complete all as specified and directed.
Supply & fix in replacement transformer oil from equipment and supply and filling fresh transformer oil in transformer and OCBs, low viscosity as per IS : 335-1993 duly dehydrated and tested to BDV 50 KV at 2.5 mm gap complete all as specified and directed. Make :- Power oil / Castrol / Servo
M&L for earthing complete with galvanised steel earth plate electrode size 600x600x6.3mm thick burried directly in ground vertically in a pit of depth not less than 2.25 mtr below ground levels with top edge of the earth plate not less than 1.5 mtr below normal ground level surrounded from all sides by mixture of charcoal and common salt and electrode connected to and including galvanised iron wire 4 mm earth lead by means of bolts, nuts, check nuts and washers of galvanised steel and GI pipe light grade 20mm dia bore for watering funnel with wire mesh. CI cover with frame, PCC chamber pit with PCC 1:3:6 type C-2 excavation and earth work all as shown in electrical plate No 5 connected to earthing test point all as specified or indicated including testing on completion. NOTES : The unit rate includes for protection pipe and GI strip dia from top of earth plate upto 5.00 meter above groung level.
ELITE WORKS
M/S RAKESH TRADERS
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .