Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹40.8 LAccepted-AOC | L1 | Accepted-AOC Accepted | |
| 2 | L2₹42.1 L+₹23,370 (0.56%)Rejected-Finance CHOWDHARY APARTMENT BLOCK II FLAT NO 7 3RD FLOOR PUNJABIPARA SEVOKE ROAD SILIGURI DIST DARJEELING 734001 | JALPAIGURI | WEST BENGAL | 734001 | L2 | Rejected-Finance Not Lowest | |
| 3 | L3₹50.4 L+₹8.5 L (20.3%)Rejected-Finance | L3 | Rejected-Finance Not Lowest | |
| 4 | L4₹50.6 L+₹8.7 L (20.8%)Rejected-Finance | L4 | Rejected-Finance Not Lowest | |
| 5 | L5₹51.0 L+₹9.1 L (21.8%)Rejected-Finance | L5 | Rejected-Finance Not Lowest |
Tender Value
₹45 L
EMD Value
₹90,000
Closing Date
14 Jan 2023, 6:00 pmClosed
GE SEVOKE ROAD
GE Sevoke Road Post Salugara Dist Jalpaiguri PIN 734008
REPAIR TO INTERNAL ELECTRIFICATION CONNECTED WORKS IN MD ACCN AND OTM ACCN AT SEVOKE STN UNDER GE SEVOKE ROAD
2022_MES_569395_1
GE/SEV/59 of 2022-23
Open Tender
Civil Works
Item Rate
270 days
GE SEVOKE ROAD
AS PER TENDER DOCUMENTS
8 documents required · 8 mandatory
₹500
Yes
GE SEVOKE ROAD
₹90,000
Yes
9 Feb 2023
16 Dec 2022
16 Jan 2023
16 Dec 2022
14 Jan 2023
31 Dec 2022
17 Dec 2022 - 26 Dec 2022
Amount
Taking down carefully old unserviciable copper /aluminium point wiring (light, fan, socket or power) complete including fittings and fixtures, removing materials to store for keeping in safe custody or for taking credit all as directed making good disturbed surfaces of walls with putty, cement and matching the colour of the surface as per existing.
M&L for concealed point wiring with two single core PVC insulated, FRLSH unsheathed, multistranded copper conductor of size 1.5 sqmm and one single core PVC insulated FRLSH unsheathed stranded copper conductor of size 1.50 sqmm green in colour as earth lead in and including PVC rigid conduit (medium grade) with all fittings & accessories including provn of MS sunk terminal box of appropriate size suitable for flush to wall for mounting switch, sockets, fan regulators etc with 3mm thick hylum sheet top cover with screws & cup washers for one light / fan point / call bell complete. . Note: Cost of making good the disturbed surfaces (if any) & matching with the existing surface is deemed to be included in the quoted rate.
All as per Item Sl No - 02 here in before but for one light point controlled by two 2 way switches complete all as specified and directed.
All as per Item Sl No - 02 here in before but for 5 pin, 5/6 A socket point on the independent board complete all as specified and directed.
All as per Item Sl No - 02 here in before but for 5 pin, 5/6 A socket point on the same board complete all as specified and directed.
All as per Item Sl No - 02 here in before but with two single core PVC insulated, unsheathed, multistranded copper conductor of size 2.5 sqmm and one single core PVC insulated unsheathed stranded copper conductor of size 2.5 sqmm green in colour as earth lead for 15/16 A switch-socket point on independent board complete all as specified and directed.
All as per Item Sl No - 02 here in before but for modular fittings excluding MS sunk terminal box & hylum sheet. (Note: Modular fittings will be measured & paid under relevent items separately)
All as per Item Sl No - 02 here in before but for one light point controlled by two way switches for modular fitting excluding MS sunk terminal box & hylum sheet complete all as specified and as directed.(Note: Modular fitting will be measured & paid under relevent items separately)
All as per Item Sl No - 02 here in before but for 5 pin, 5/6 A socket point on the independent board complete but for modular fittings excluding MS sunk terminal box & hylum sheet. (Note: Modular fitting will be measured & paid under relevent items seprately).
All as per Item Sl No - 02 here in before but for 5 pin, 5/6 A socket point on the same board complete but for modular fittings excluding MS sunk terminal box & hylum sheet. (Note: Modular fitting will be measured & paid under relevent items seprately).
All as per Item Sl No - 02 here in before but with two single core PVC insulated, unsheathed, multistranded copper conductor FRLSH of size 2.5 sqmm and one single core PVC insulated unsheathed stranded copper conductor FRLSH of size 2.5 sqmm green in colour as earth lead for 15/16 A switch -socket point on independent board complete but for modular fitting excluding MS Sunk terminal box & hylum sheet.(Note: Modular fitting will be measured & paid under relevent items seprately).
M&L for wiring in existing conduit with two single core PVC insulated, unsheathed, multistranded copper conductor FRLSH of size 1.5 sqmm and one single core PVC insulated unsheathed stranded copper conductor FRLSH of size 1.50 sqmm green in colour as earth lead including provn of MS sunk terminal box of appropriate size suitable for flush to wall for mounting switch, sockets, fan regulators etc with 3mm thick hylum sheet top cover with screws & cup washers for one light / fan point / call bell complete all as specified and directed by Eng-in-charge... NOTE : Cost of making good the disturbed surfaces (if any) matching with the existing surface is deemed to be included in the unit quoted rates.
M&L for point wiring with two single core PVC insulated, unsheathed, multistranded copper conductor of size 1.5 sqmm and one single core PVC insulated unsheathed stranded copper conductor of size 1.50 sqmm green in colour as earth lead in and including PVC rigid casing caping (medium grade) with all fittings & accessories including provn of MS sunk terminal box of minimum size 75 x75 mm fixed flush to wall for mounting switch, socket, fan regulator etc with 3mm thick hylum sheet top cover with screws & cup washers for one light / fan point / complete.. NOTE : Cost of making good the disturbed surfaces (if any) matching with the existing surface is deemed to be included in the unit quoted rates.
All as per Item Sl No - 13 here in before but for 5 pin, 5/6 A socket point on the independent board complete.
All as per Item Sl No - 13 here in before but for 5 pin, 5/6 A socket point on the same board complete.
All as per Item Sl No - 13 here in before but with two single core PVC insulated, unsheathed, multistranded copper conductor of size 2.5 sqmm and one single core PVC insulated unsheathed stranded copper conductor of size 2.5sqmm green in colour as earth lead for 15/16 A switch-socket point on independent board complete.
S & F switch piano flush type single, pole one way, 5 Amp completed all as specified and as directed.
S&F ceiling rose, surface bakelite 3/2 terminals completed all as specified and as directed.
S & F switch socket combination 5 in 1, 5/6A completed all as specified and as directed.
S & F Bell push flush type 5 amp, 240 volts completed all as specified and as directed.
S & F Bell Ding Dong AC , 230 volts single pole completed all as specified and as directed.
S & F wireless Bell Ding Dong AC , 230 volts single pole completed all as specified and as directed.
S & F switch socket combination 5 in 1, 15/16A completed all as specified and as directed.
S & F socket outlet 5 in 1,5A completed all as specified and as directed.
S&F electronic step regulator (speed regulation in 5 steps) suitable for ceiling fan 1200 sweep/1400 mm, 120 Watt complete all as specified and directed.
Taking down existing unservisiable FTL light fitting and S&F in repair decorative box type fitting with LED tube 9 watt 2 feet with Aluminium extruded batten luminaire for 230 volt AC complete all as directed by Engineer in Charge
Taking down existing u/s FTL light fitting and S&F in repair decorative box type fitting with LED light fitting, 3000K 9 watt 2 feet with Al extruded batten luminaire for 230 volt AC all as directed by EIC.
Taking down existing u/s FTL light fitting and S&F in repair decorative box type fitting with LED light fitting 20 watt 4 feet with Al extruded batten luminaire for 230 volt AC all as directed by EIC.
Taking down existing u/s FTL light fitting and S&F in repair decorative box type fitting with LED light fitting 3000K, 20 watt 4 feet with Al extruded batten luminaire for 230 volt AC all as directed by EIC.
S & F energy saving surface mounted round decorative LED luminaries 12 W with PDC Aluminium housing, soft moon light effect produced when in operation complete all as specified and directed.
Fixing only serviceable light fittings, any type recovered from item no.1 including making necessery end connections with suitable wire all as directed.
S&F MCB, DB, TPN, 4 ways double door, IP-42, IK-09 with metal door, 160 Amp rated bus bars, earth bar, neutral links complete including blanking plates as required & fixed flush to wall and making good the disturbed surfaces including taking down unserviceable one with MCBs complete all as specified and directed.
All as per item No.32 here in before but SPN 12 way complete all as specified and directed.
All as per item No. 32 here in before but SPN 8 way complete all as specified and directed.
S&F MCB, SP, 10KA, 230V, "C" curve, 06-32 A, ISI Marked complete all as specified and directed.
S&F MCB, DP, 10KA, 415V, "C" curve, 06-32 A, ISI Marked complete all as specified and directed.
S&F MCB, TPN, 10KA, 440V, "C" curve, 40/63 Amp, ISI Marked complete all as specified and directed.
M&L for submain wiring in and including casing caping (medium grade) with two single core PVC insulated, FRLSH unsheathed, stranded copper conductor of size 6.0 Sqmm and one single core PVC insulated, FRLSH unsheathed solid copper conductor 6.0 Sqmm green in colour as earth lead including taking down old unserviceable aluminium sub-main wiring complete all as specified and directed by Eng-in-Charge.
M&L for submain concealed wiring with two single core PVC insulated, FRLSH unsheathed, stranded copper conductor of size 4.0 Sqmm and one single core PVC insulated, FRLSH unsheathed solid copper conductor 4.0 Sqmm green in colour as earth continuity conductor drawn into and including PVC conduit (medium grade) with all fitting & accessories including taking down old unserviceable sub-main wiring complete all as specified.
M&L for submain wiring in existing conduit with two single core PVC insulated, unsheathed, FRLSH stranded copper conductor of size 6.0 Sqmm and one single core PVC insulated, unsheathed solid copper conductor 6.0 Sqmm green in colour as earth lead in existing cancealed PVC conduit with all fitting & accessories including taking down old unserviceable aluminium sub-main wiring from existing concealed conduit complete all as specified and directed by Eng-in-Charge
M&L for submain wiring with and including casing caping with two single core PVC insulated, FRLSH unsheathed, stranded copper conductor of size 4.0 Sqmm one single core PVC insulated, FRLSH unsheathed solid copper conductor 4.0 Sqmm and green in colour as earth lead with all fitting & accessories including taking down old unserviceable aluminium sub-main wiring complete all as specified and directed by Eng-in-Charge.
S&F in repair exhuast fan AC , single phase, 230/240 V, of size 230 mm seep hevy duty steel/aluminium metal body including making holes on wall & making good the disturbed surfaces with all connceting arrangements complete all as specified and as directed.
S&F in repair ventilation fan with louvers, single phase, 230/240V, of size 200mm sweep polycarbonate body, rustproof body & blades, low noise and weight, making good the distrubed surface with all connecting arrangements complete all as specified and directed.
S&F in repair ventilation fan with louvers, single phase, 230/240V, of size 250mm sweep polycarbonate body, rustproof body & blades, low noise and weight, making good the distrubed surface with all connecting arrangements complete all as specified and directed.
Taking down existing u/s light fitting and S&F in repair wall fancy light,3000K fitting with holder point 230 Volts necessery fixing arrangements complete all as specified and directed.
Taking down existing u/s light fitting and S&F in repair wall fancy light,6500K fitting with holder point 230 Volts necessery fixing arrangements complete all as specified and directed.
S&F new generation energy saving & environmental friendly long life versatile pressure die-cast aluminium building security light with high power LED as light source lamp type 25W with SPD , IP:66 protection with fixing rod and connecting arrangements including taking out existing complete all as specified and as directed
S&F modular switch one way 6 Amps 230 volts, 1 module all specified and as directed by the Engineer in Charge
S&F modular bell push switch one way 6 Amps 230 volts, 1 module all specified and as directed by the Engineer in Charge
S&F modular bell push switch two way 6 Amps 230 volts, 1 module all specified and as directed by the Engineer in Charge
S&F modular switch one way with indicator 16 Amps 230 volts, 1 module all specified and as directed by the Engineer in Charge
S&F modular socket 2 in 1, 2/3 pin, 6 Amp all as specified and as directed by the Engineer in Charge.
S&F moduular socket 3 pin 6 Amp-16 Amp combined shuttered all as specified and directed by Engineer in Charge.
S&F modular white cover plate with frame 1 module inclusive of inner & outer plate complete all as specified and as directed by the Engineer in Charge.
S&F modular white cover plate with frame 2 module inclusive of inner & outer plate complete all as specified and as directed by the Engineer in Charge.
S&F modular white cover plate with frame 3 module inclusive of inner & outer plate complete all as specified and as directed by the Engineer in Charge.
S&F modular white cover plate with frame 4 module inclusive of inner & outer plate complete all as specified and as directed by the Engineer in Charge.
S&F modular white cover plate with frame 6 module inclusive of inner & outer plate complete all as specified and as directed by the Engineer in Charge.
S&F modular white cover plate with frame 8 module inclusive of inner & outer plate complete all as specified and as directed by the Engineer in Charge.
S&F modular white cover plate with frame 12 module inclusive of inner & outer plate complete all as specified and as directed by the Engineer in Charge.
S&F modular metal flush box 1/2 module all as directed
S&F modular metal flush box 3 module all as directed
S&F modular metal flush box 4 module all as directed
S&F modular metal flush box 6/8 module all as directed
S&F modular metal flush box 12 module all as directed
S&F modular electronic step regulator (speed regulation in 5 steps) 1 module suitable for ceiling fan 1200 sweep/1400 mm, 100 watt complete.
S&F PVC casing caping (medium grade) of size 25x16 mm with all connecting accessories all as per directed.
S&F PVC box with SSC 5/6 A complete all as specified and directed
S&F PVC box with SSC 15/16 A complete all as specified and directed
Taking down existing unserviceable light fitting and S&F in repair ceiling mounted square pattern LED luminaire light 3000K, 36W, 230 Volts including driver and necessary fixing arrangements complete all as specified and directed.
Taking down existing unserviceable light fitting and S&F in repair ceiling mounted square pattern LED luminaire, 36W, 230 Volts including driver and necessary fixing arrangements complete all as specified and directed
Taking down existing unserviceable light fitting and S&F in repair ceiling mounted pride plus slim LED panel round light 3000K, 18W, 220mm x 23mm, 230 Volts including driver and necessary fixing arrangements complete all as specified and directed
Taking down existing unserviceable light fitting and S&F in repair ceiling mounted square pattern LED luminaure light 3000K, 20W, 230V including driver and necessary fixing arrangements complete all as specified and directed
Taking down existing unserviceable light fitting and S&F in repair ceiling mounted square pattern LED luminaure light, 20W, 230V including driver and necessary fixing arrangements complete all as specified and directed
Taking down existing unserviceable light fitting and S&F in repair LED Warm bulb 3000K, 9W 230V, all as specified and directed.
S&F energy saving decoratie LED post top lantern with diffuser and painted aluminium deflector 30W with base including making necessary fixing and connection arrangements complete all as specified and directed.
M & L for earthing complete with galvanized steel pipe electrode 40mm bore, medium grade, 2.5 meters length, buried directly and preferably vertically in ground with top edge not less than 1.25 meters below ground level connected with earthing lead galvanized iron strip of size 25x5 mm connected to galvanized earth pipe by means of bolts, nuts, checknuts and washer of galvanized iron including PCC (1:2:4) type B1 precast RCC cover slab with suitable handle made of 6 mm round bar, including necessary excavation and earth work in any type of soil, 20mm dia medium grade galvanized steel tube for watering with one and fix with cast iron funnel and wire-mesh, with protection pipe of 32mm dia light grade galvanized steel tubing upto 7.5 meters length for drawing earthlead including common salt, charcol, bentonite in alternate layers etc, complete all as shown in EP number 2 of SSR Part-I including testing on completion and including taking down old u/s earthing & testing complete all as specified and as directed..
ASSOCIATED TRADING CORPORATION
LIBERAL ENGINEER CONSTRUCTION
M/S Bikash Saha
SHRI JIBANDHAN PAUL
M S ALOK SAHA
D.D. BROTHERS
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .