Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L 1₹5.7 LAccepted-Finance | L 1 | Accepted-Finance AS PER NIT | |
| 2 | L 2₹6.3 L+₹65,735 (11.6%)Accepted-Finance | L 2 | Accepted-Finance AS PER NIT |
Tender Value
₹6.1 L
EMD Value
₹12,290
Closing Date
27 Jul 2022, 3:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
THE DIRECTOR
CSIR-CECRI, KARAIKUDI
Power supply Augmentation to the proposed Equipments in BTF(Building) at CSIR-CECRI, Karaikudi (Phase-I)
2022_CSIR_122800_1
CSIR CECRI NIT No 07/2022
Open Tender
Electrical Works
Item Rate
90 days
CSIR-CECRI, KARAIKUDI
PLEASE REFER NIT
8 documents required · 8 mandatory
₹0
₹12,290
Yes
10 Nov 2022
19 Jul 2022
29 Jul 2022
19 Jul 2022
27 Jul 2022
19 Jul 2022
90 days
Amount
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required.
2 X 10 sq. mm + 1 X 6 sq. mm earth wire
2 X 16 sq. mm + 1 X 6 sq. mm earth wire
Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm)
Providing and laying earth connection from earth electrode with 6 SWG dia G.I. Wire in 15 mm dia G.I. pipe from earth electrode including connection with G.I. thimble excavation and re-filling as required.
Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required.
Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required.
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing masonry open duct as required.
Above 35 sq. mm and upto 95 sq. mm
Above 95 sq. mm and upto 185 sq. mm
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required.
Above 35 sq. mm and upto 95 sq. mm (clamped with 25x3mm MS flat clamp)
Above 95 sq. mm and upto 185 sq. mm (clamped with 25/40x3mm MS flat clamp)
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.
3Y X 35 sq. mm (32mm)
3Y X 50 sq. mm (35mm)
3Y X 150 sq. mm (50mm)
3Y X 400 sq. mm (82mm)
Excavation for cable trenches in soft soil, depth upto 1.2 m including dressing of sides lift upto 1.5 m, including getting out the excavated soil, refilling with sand and or good soil after laying of cable/ pipe etc in layers of 20 cm, ramming, watering and disposal of surplus excavated soil as directed, within a lead of 50 metres.
Providing and laying in position cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) in foundation of pump, DG set etc including form work etc as required.
Cast Iron Body Earthing : Providing cast iron pipe earth pit with 2000mm long 100mm dia 7mm thick cast iron pipe including excavation, refilling with salt, charcoal, natural soil and providing masonry cover etc.,complete in all aspects as required.
(b) Erection, testing and commissioning of the above panel including removing the existing change over switch unit, existing cables, along with making provision for the cable trenches,cable looses, excavation,other allied civil works etc and angle iron channels of required size & qunatity for housing the panel as per standards, complete in all aspects as required as per site condition.
8 Way MCCB VTPN DB: Supplying and fixing 12 way surface/ recess MCCB mounting, 415 volts, vertical type TPN MCB distribution board (with wire way/cable end box) of sheet steel,dust protected, duly powder painted, inclusive of 200 amps tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCB's, along with 100 A,16/18 KA TPN MCCB, phase barrier and spreaders for incomer, interconnection between DB incomer and the bus bars/Existing mains shall be made with copper cables of appropriate rating as required. The VTPN DB shall be mounted on a adequate size angle/flat and grouted/ fixed (drilling,cutting welding painting etc) firmly in the existing wall/ existing base channel as required as per site condition complete in all aspects. The above DB shall include the following 'C' series, 10 kA MCB's in the out going circuits TP MCB-63A-2 Nos TP MCB-32A-3 Nos SP MCB-6-32A-6 Nos . SP MCB 40-63A-3 Nos. Blanking plates -As required. Make : ABB/Legrand /Schneider /Siemens/Hager or equivalent subject to the approval of the department.
12 Way MCCB VTPN DB: Supplying and fixing 12 way surface/ recess MCCB mounting, 415 volts, vertical type TPN MCB distribution board (with wire way/cable end box) of sheet steel,dust protected, duly powder painted, inclusive of 200 amps tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCB's, along with 160 A,16/18 KA TPN MCCB, phase barrier and spreaders for incomer, interconnection between DB incomer and the bus bars/Existing mains shall be made with copper cables of appropriate rating as required. The VTPN DB shall be mounted on a adequate size angle/flat and grouted/ fixed (drilling,cutting welding painting etc) firmly in the existing wall/ existing base channel as required as per site condition complete in all aspects. The above DB shall include the following 'C' series, 10 kA MCB's in the out going circuits TP MCB-63A-4 Nos TP MCB-32A-4 Nos SP MCB-6-32A-12 Nos Blanking plates -As required. Make : ABB/Legrand /Schneider /Siemens/Hager or equivalent subject to the approval of the department.
Removing & Shifting the existing 160 kVA Generator: Reomving and shifting the existing 160 kVA generator along with the frame and the cahnge over panel by engaging all means and materials as required as per site condition including crane charges if any from the BTF to the stroes section or any other area within the institute premises as directed by the engineer in charge.
Sastha Electrical
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .