Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹30.0 LAccepted-AOC 32 GOLA MAHAL P O BARRACKPORE DIST NORTH 24 PARGANAS PIN 700 120 WB | 24 PARAGANAS NORTH | WEST BENGAL | 700120 | L1 | Accepted-AOC being L1 | |
| 2 | L2₹36.9 L+₹6.4 L (21.1%)Rejected-Finance | L2 | Rejected-Finance NOT BEING L1 |
Tender Value
Refer Docs
EMD Value
₹50,000
Closing Date
30 Nov 2020, 6:00 pmClosed
GE (AF) Kalaikunda
GE (AF) Kalaikunda
DAY TO DAY MAINT OF E/M SERVICES, REPAIRS/REPLACEMENT OF ELECTRICAL FITTINGS, HANGER LIGHTS, REWIRING AND ALLIED WORKS IN TECH AREA AND DDK RANGE AT AF STN KALAIKUNDA
2020_MES_368171_3
8588/E8
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
GE (AF) Kalaikunda
AS PER NIT
7 documents required · 7 mandatory
₹500
GE (AF) Kalaikunda
₹50,000
Yes
22 Mar 2021
16 Nov 2020
2 Dec 2020
16 Nov 2020
30 Nov 2020
17 Nov 2020
Amount
M & L for taking down copper/aluminium point wiring (light, fan, socket or power) complete, including fixture and fittings such as switches, ceiling roses, pendants, regulators, sockets, light fitting etc. for taking credit (credit for above items should be made as per conditions separately) and making good disturbed surfaces of walls, floors, etc.complete all as specified and directed by Engr-in-charge.
M & L point wiring for light/fan/call bell point/3 pin socket outlet 5 Amps with 1.5 Sqmm multi stranded copper conductor 1100 V grade, ISI marked , PVC insulated unsheathed cable (with approved colour code) FRLS cable drawn in & including PVC casing caping of 25 mm wide, with double locking type, including all accessories casing caping as approved by EIC, with PVC 1.5 sqmm multi stranded insulated unsheathed copper wire, ISI marked of green colour for continous earth, including sunken in cast iron/MS terminal box duly painted with aluminum paint inside and anticorrosive paint out side with 2.8 mm thick backlite hylam sheet cover,for mounting switch & sockets, complete all as specified and as directed. Note : (i) Contractor has to make the surface good after flushing the sunken box as existing without any extra cost (ii) length or wiring 10 mtrs from switch board to be considered as one point wiring.
All as per Item No. 2 here-in-before but One 3 pin socket outlet on same board, complete all as specified and as directed.
All as per Item No. 2 here-in-before but with FRLS grade, (ISI mark) PVC insulated and unsheathed two run multistranded copper conductor of size 2.5 Sqmm for one power point of 3 pin 15 Amps on independent board including FRLS grade (ISI mark), PVC insulated, unsheathed one run multi-stranded copper conductor of size 2.5 sqmm green in colour as earth continuity conductor connected to common earth dolly complete all as specified and directed.
M & L point wiring with 4 Sqmm multi stranded copper conductor 1100 V grade, ISI marked , PVC insulated unsheathed cable (with approved colour code) FRLS cable drawn in & including PVC casing caping of 25 mm wide, with double locking type, including all accessories casing caping as approved by EIC, with PVC 4.0 sqmm multi stranded insulated unsheathed copper wire, ISI marked of green colour for continous earth connected to common earth dolly,all as specified and directed.
S&F switch piano flush type single pole one way 5 Amps : Make : Anchor / L& T/ Havells (Note : Item to be measured if executed under new point wiring)
S&F socket outlet 2 in 1, flush type 5/6 Amps : Make : Anchor / L& T/ Havells (Note : Item to be measured if executed under new point wiring)
S&F Switch socket combination 2 in 1, flush type 5/6 Amps : Make : Anchor / L& T/ Havells (Note : Item to be measured if executed under new point wiring)
S&F Switch socket combined outlet 6 pin flush type 15 Amp multi purpose : Make : Anchor / L& T/ Havells (Note : Item to be measured if executed under new point wiring)
S&F ceiling rose surface bakelite 65 mm dia three terminal complete. : Make Anchor Penta / L& T (Note : Item to be measured if executed under new point wiring)
Supply and fixing of stepped type electronic fan regulator 100 watt flush type (delux) on the existing phenolic laminated sheet etc as required. Make: Anchor (Delux) / L&T/ Havells (Note : Item to be measured if executed under new point wiring)
S&F LED 18 Watt tube light fitting (T8 type) ,single end connection type including LED retrofit tube lamp 18 W , 240 Volt, PF > 0.90, colour Temp 6500 K, System Luminious efficacy > 100Lm/W, complete with powder coated CRCA decorative box type batten suitable for surface mounting on wall, complete fitting including connecting with PVC insulated multistranded copper flexible cable 0.5 sqmm three core, and PVC round/ square box white colour x 2 Nos for mounting of fitting complete all as specified & directed. Make :- Bajaj (Batten Cat No. BLRB DB 118 box type batten suitable for 18/20 watt retofit LED tube single side connection type). LED lamp : Make : Bajaj Cat No. BLRB 18W CW LED (retrofit LED tube lamp 18 Watt, Single end connection) or equivelent in Crompton / Havells as approved by GE. Note : Make of batten and LED tube lamp should be of same make. (Note : Item to be measured if executed under new point wiring)
Supply and fixing lamp holder , PVC/Poly carbonate type with back plate suitable for batten fittings to be fixed on PVC box including supply and fixing 10 watt LED lamp. Make For holder : Anchor / L& T/ Havells. LED lamp : Philips/ Bajaj/ Crompton/ Surya (Note : Item to be measured if executed under new point wiring)
Supply and fixing of stepped type electronic fan regulator 100 Watt flush type (delux) on the existing hylam laminated sheet etc as required including taking down old unserviceable one complete all as directed. Make: Anchor (Delux) / L&T/ Havells
S&F switch piano flush type single pole one way 5 Amps including taking down old unserviceable one complete all as directed: Make : Anchor / L& T/ Havells
S&F Switch socket combination 2 in 1, flush type 5/6 Amps including taking down old unserviceable one complete all as directed : Make : Anchor / L& T/ Havells
S&F switch socket combined outlet 6 pin flush type 15 Amp multipurpose including taking down old unserviceable one complete all as directed : Make : Anchor / L& T/ Havells
S&F modular switch piano 1 way 6A, 1 Module including taking out unserviceable one complete all as directed : Make : Anchor / L& T/ Havells
S&F in repair modular switch piano 1 way 16A, 1 Module including taking down old unserviceable one complete all as directed : Make : Anchor / L& T/ Havells
S&F modular socket 6A/16A 2/3 Pin combined -2 module including taking down old unserviceable one complete all as directed : Make : Anchor / L& T/ Havells
S&F modular switch socket combination 16A , 6 Pin combined -3 module including taking down old unserviceable one complete all as directed : Make : Anchor / L& T/ Havells
S&F in repair LED 18 Watt tube light fitting (T8 type) ,single end connection type including LED retrofit tube lamp 18 W , 240 Volt, PF > 0.90, colour Temp 6500 K, System Luminious efficacy > 100Lm/W, complete with powder coated CRCA decorative box type batten suitable for surface mounting on wall, complete fitting including connecting with PVC insulated multistranded copper flexible cable 0.5 sqmm three core, and PVC round/ square box white colour x 2 Nos for mounting of fitting complete all as specified & directed including taking down old unserviceable. Make :- Bajaj (Batten Cat No. BLRB DB 118 box type batten suitable for 18/20 watt retofit LED tube single side connection type). LED lamp : Make : Bajaj Cat No. BLRB 18W CW LED (retrofit LED tube lamp 18 Watt, Single end connection) or equivelent in Crompton / Havells as approved by GE. Note : Make of batten and LED tube lamp should be of same make.
S&F in repair LED tube lamp 18 Watt (reterofit type, T8 pattern, single side connection) 240 V, PF > 0.90, colour Temp 6500 K, System Luminious efficacy > 100Lm/W, to be fixed in existing or new batten/ patti including changing the wiring suitable for T8 LED retrofit lamp in existing tube light fitting complete including taking down old u/s. Make :- Bajaj Cat No. BLRB 18W CW LED or equivalent in Philips/CG.
S&F in repair LED 9/10 Watt tube light fitting intergated type, 240 v, PF > 0.90, colour Temp 6500 K, suitable for surface mounting on wall, complete fitting including connecting with PVC insulated multistranded copper flexible cable 0.5 sqmm three core, and PVC round block white colour x 2 Nos for mounting of fitting complete including taking down old u/s all as specified & directed. Make :- Bajaj/ Crompton/Havells.
S&F in repair LED lamp 18 Watt 4 Pin type, colour Temp 6500K, retrofit type in existing fitting with necessary change in wiring complete including taking down old u/s all as specified and directed by Engineer in charge. Make : Bajaj/ Crompton/Havells
S&F in repair LED light with pressure die-cast housing along with prismatic polycarbonate diffuser and LED's with secondary optics and IP-65 protection of 25 watt,PF>0.9 for building security light complete including taking down old u/s all as specified and directed by Engineer in charge. Make : Bajaj Cat Part No. BCLST25 W LED IV2 or equivelant in Crompton/Havells
S&F in repair LED bulkhead light of 10W with pressure die-cast housing along with polycarbonate diffuser and LED's IP-65 protction of watt,PF>0.95 complete including taking down old u/s all as specified and directed by Engineer in charge. Make : Bajaj/ Crompton/Havells/Wipro
S&F in repair LED high bay light with pressure die-cast housing,having fin ventilation technology for better thermal management of capacity of 200 watt for installation at hanger complete including taking down old u/s all as specified and directed by Engineer in charge. Make : Havells Cat Part No. RADIOSOHB200WLED7590DBOPC white or equivalent in Philips/ Bajaj.
S&F in repair Aviation LED light luminaires with aluminium housing with polycarbonate enclosure complete including taking down old u/s all as specified and directed by Engineer in charge. Make : Bajaj Cat Part No. BGAV 302 LED or equivalent in Philips/ Havells
Taking down existing u/s CFL light fitting any type (600 mm x 600 mm) recess mounting/surface and S&F LED light fitting 36 watt recess mounting of size 600 mm x 600 mm , white powder coated CRCA housing with LEDs, seam less front frame with flat white high transmission acrlyic cover, classic design with glare free soft illumination, cool white,including making electric connection from source with PVC sheathed copper conductor wire complete all as specified and directed by Ein C. .Make : Bajaj Cat Part No. BZRSQL 36W GZi CW or equivalent in Philips/ Havells
S&F in repair die cast aluminium housing with front toughened glass type LED flood light of 100W luminaires (Luminous efficancy 120 lumen/watt) with all accessories including necessary electrical connections by three core sheathed aluminium/ copper conductor all as directed and specified by Engr-in-Charge. Make : Bajaj Cat Part No. BJFL100W LED I or equivalent in Philips/ Havells
Taking down old unserviceable TPN / SPN MCB DB's/MCCB enclosure of any size and any description all as directed by Engr-In-Charge.
S & F in repair single pole and neutral enclosure with two pin and earth, plug and socket , suitable for single phase 240 V,complete with one single pole MCB of capacity 20 amps having `C` charactristic, breaking cap 10 KA, including industial plug top, complete all as specified and as directed.
S & F sheet metal enclosure for MCB, DB, VTPN 415 Volts 100 Amps rated busbar 4 way Double door ( Vertical DB with MCB as incomer) Conf to IS including fixing the DB box flush in wall of any type and making good the distrubed surface to match as the existing complete all as specified and directed by Engr-in-charge. Make Legrand/ Seimens/ Schinder
S&F sheet metal enclosure for VT DB TPN, MCB DB TPN 4 way (with MCCB as INCOMER), double door with 63 Amp, 25 KA,FP MCCB as incomer (Vertical type double door, 63 Amps MCCB rate inclusive) including fixing the DB box flush in wall of any type and making good the distrubed surface to match as the existing complete all as specified and directed by Engr-in-charge. Make Legrand/ Seimens/ Schinder.
S & F sheet metal enclosure for MCB, DB, SPN, 240 Volts, 100 Amps rated busbar, 12 way Double door enclosure made up of CRCA sheet steel,powder coated, IP 43, including fixing the DB box flush in wall of any type and making good the distrubed surface to match as the existing with all as specified and directed by Engr-in-charge Make Legrand/ Seimens/ Schinder.
S & F sheet metal enclosure for MCB, DB, SPN, 240 Volts, 100 Amps rated busbar, 8 way Double door enclosure made up of CRCA sheet steel, powder coated, IP 43 including fixing the DB box flush in wall of any type and making good the distrubed surface to match as the existing with all as specified and directed by Engr-in-charge Make Legrand/ Seimens/ Schinder.
S & F sheet metal enclosure for MCB, DB, SPN, 240 Volts, 100 Amps rated busbar, 4 way Double door enclosure made up of CRCA sheet steel, RAL powder coated, IP 43 including fixing the DB box flush in wall of any type and making good the distrubed surface to match as the existing with all as specified and directed by Engr-in-charge Make Legrand/ Seimens/ Schinder..
S&F for thermoplastic circuit breaker boxes where MCB to be fix with PE+N terminals 1 row 4 module of size 126X228X111 mm IP 65 halogen free and weather proof including four hexagonal anticorrosive screws for out door installation all as specified and directed by Engr-in-charge.
S&F for thermoplastic(polycarbonate)circuit breaker boxes where MCB to be fix with PE+N terminals 1 row 12 module of size 295X333X129 mm IP 65 halogen free and weather proof including four hexagonal anticorrosive screws for out door installation all as specified and directed by Engr-in-charge.
S& F SS enclosure for MCCB of rating 250 Amp In-built neutral Link for TPN system l IK08 and IP30 Protection having Louvers for better heat dissipation Suitable to accommodate upto 185 sq. mm. 3 1/2 core Aluminum armoured cable incl taking down unsv one and refixing serviceable/ new MCCB in enclosure and connectiing existing IC/OG cable with proper dimension lugs all as specified and directed. Make L &T Cat Part No. CM91003OOOO or equivalent in Havells /CG
S& F SS enclosure for MCCB 125 Amp In-built neutral Link for TPN system l IK08 and IP30 Protection having Louvers for better heat dissipation Suitable to accommodate upto 70 sq. mm. 3 1/2 core Aluminum armoured cable incl taking down unsv one and refixing serviceable/ new MCCB in enclosure and connectiing existing IC/OG cable by providing lugs of suitable dimension all as specified and directed. Make L &T Cat Part No. CM90996OOOO or equivalent in Havells /CG
S&F MCCB with Thermal - magnetic release of 200-250 Amps, 4 Pole, 415V, 36 kA, Ics=100%Icu with adjustable over load setting and adjustable short circuit setting including all accessories like spreader terminals and face barriers including making all electrical connections by providing lugs of suitable size, including making all arrangements for fixing of new MCCB at the existing location of unserviceable one and taking down old unserviceable MCCB. Make : L & T Cat Part No. CM92109OOP10G or equivalent in Schneider/ Legrand
S&F MCCB with Thermal - magnetic release of 100-125 Amps, 4 Pole, 415V, 25 kA, Ics=100%Icu with adjustable over load setting and adjustable short circuit setting including all accessories like spreader terminals and face barriers including making all electrical connections by providing lugs of suitable size, including making all arrangements for fixing of new MCCB at the existing location of unserviceable one and taking down old unserviceable MCCB. Make : L & T Cat Part No. CM90642OOLO or equivalent in Schneider/ Legrand
S&F in repair MCB FP 50 to 63 Amps, 10 KA 'C' Curve breaking capacity, including connection with suitable size copper lugs including taking down u/s complete all as specified and directed by Engr-In-Charge.
S&F in repair MCB FP 100 Amps, 10 KA 'C' Curve breaking capacity, including connection with suitable size copper lugs including taking down u/s complete all as specified and directed by Engr-In-Charge..
S&F in repair MCB SP 240 volts 6 to 32 Amps, 10 KA breaking capacity, 'C' Curve including connection with suitable size copper lugs including taking down u/s complete all as specified and directed by Engr-In-Charge .
S&F in repair MCB DP 6 to 32 amps 10 KA , 'C' Curve including connection with suitable size copper lugs including taking down u/s complete all as specified and directed by Engr-In-Charge Make- Legrand/ Seimens/ Schinder.
Taking down old unserviceable sub main wiring of any size and any description all as directed by Engr-In-Charge.
M&L for Sub main wiring with two single core PVC insulated unsheathed cable 1100 volts grade, 6.0 Sqmm size with multistranded copper conductor, FRLS cable drawn in but including non metallic rigid PVC conduit of 25 mm dia ISI marked including PVC insulated unsheathed 6.0 Sqmm cable with multistranded copper conductor green PVC insulated as contineous earth conductor cable connected to earth dolly complete. L&T / Polycab/ C&S/Anchor
M&L for Sub main wiring with two single core PVC insulated unsheathed cable 1100 volts grade, 4 Sqmm size with multistranded copper conductor FRLS cable (with colour code), drawn in but including PVC casing capping not less than 25 mm ISI marked including all accessories of casing caping as approved by EIC, including PVC insulated unsheathed 4.0 Sqmm cable with multistranded copper conductor green PVC insulated as contineous earth conductor cable connected to earth dolly complete. Make of wire : L&T / Polycab/ Havells
M&L for Sub main wiring with two single core PVC insulated unsheathed cable 1100 volts grade, 6 Sqmm size with multistranded copper conductor, FRLS cable drawn in but including PVC casing capping not less than 25 mm ISI marked including all accessories of casing caping as approved by EIC including PVC insulated unsheathed 6.0 Sqmm cable with multistranded copper conductor green PVC insulated as contineous earth conductor cable connected to earth dolly complete. Make of wire : L&T / Polycab/ Havells
M&L for Sub main wiring with two runs of single core PVC insulated unsheathed cable 1100 volts grade, multistranded copper conductor FRLS cable of 10.0 Sqmm (with colour code), drawn in but including PVC casing caping not less than 25 mm width ISI marked double locking type including one including one run of PVC insulated unsheathed, multistranded copper conductor FRLS cable of 10.0 Sqmm (Green colour) as contineous earth conductor cable connected to earth dolly in surface/ recess complete all as specified and directed by EIC. Make of wire : Polycab/ Havells/L&T
M&L for Sub main wiring with Four single core (3 phase) PVC insulated unsheathed cable 1100 volts grade, 6 Sqmm size with multistranded copper conductor, FRLS cable drawn in but including PVC casing capping not less than 32 mm ISI marked including all accessories of casing caping as approved by EIC including two run of PVC insulated unsheathed 6.0 Sqmm cable with multistranded copper conductor green PVC insulated as contineous earth conductor cable connected to earth dolly complete ( 4 x 6.0 sqmm + 2 x 6.0 Sqmm earth wire) . Make of wire : L&T / Polycab/ Havells
M&L for Sub main wiring with Four single core (3 phase) PVC insulated unsheathed cable 1100 volts grade, 10 Sqmm size with multistranded copper conductor, FRLS cable drawn in but including PVC casing capping not less than 32 mm ISI marked including all accessories of casing caping as approved by EIC including two run of PVC insulated unsheathed 10.0 Sqmm cable with multistranded copper conductor green PVC insulated as contineous earth conductor cable connected to earth dolly complete ( 4 x 10.0 sqmm + 2 x 10.0 Sqmm earth wire) . Make of wire : L&T / Polycab/ Havells
S&F in repair PVC casing caping of min 25 mm dia exclusive of boxes (junction/ terminals) but inclusive of all tees, bends, elobows, reducers, bell mouth tube ends and fixing accessories such as coupler, lock nuts, saddles , pipe hook etc to be fixed on surface for dressing of wiring in neat presentable condition including taking down old u/s all as specified and directed by Engineer in charge.
S&F in repair PVC casing caping (RACEWAY) of single compartment having size 50 mm x 38 mm, standard length 2 meters exclusive of boxes (junction/ terminals) but inclusive of all tees, bends, elbows, reducers, bell mouth tube ends and fixing accessories such as coupler, lock nuts, saddles , pipe hook etc to be fixed on surface for dressing of wiring in neat presentable condition including taking down old u/s all as specified and directed by Engineer in charge.
S&F in repair PVC casing caping (RACEWAY) of two compartments having size 100 mm x 38 mm, standard length 2 meters exclusive of boxes (junction/ terminals) but inclusive of all tees, bends, elobows, reducers, bell mouth tube ends and fixing accessories such as coupler, lock nuts, saddles , pipe hook etc to be fixed on surface for dressing of wiring in neat presentable condition including taking down old u/s all as specified and directed by Engineer in charge.
S&F in repair Surge protection device Type 1 + 2 to withstand impluse current with 10/350 us wave to simulate lightining current. SPD having max contionous operating voltage - 440 Uc (v), I imp in KA(10/350 Us wave) - 12.5 KA , I max in KA(8/32 Us wave) - 80 KA, Pole 3+1 (3 Pole + Neutral), 4 module including installation in parallel connection in DB and making all electrical connections with 4 x 6.0 Sqmm single core copper wire with copper lugs complete all as specified and directed by Engineer in charge. Make ABB cat Part No. OVR T1-T2 3N 12.5-440s P QS (2CTBB15710R4800) or equivalent in Havells/ L&T.
S&F in repair Surge protection device Type - 2, having max contionous operating voltage - 440 Uc (v), I max in KA(8/32 Us wave) - 40 KA, Pole 3+1 (3 Phase + Neutral), 4 module including installation in parallel connection complete including taking down old u/s in DB and making all electrical connections with 4 x 6.0 Sqmm single core copper wire with copper lugs complete all as specified and directed by Engineer in charge. Make ABB cat Part No. OVR T2 3N 40-440 P QS (2CTB803973R1400) or equivalent in Havells/ L&T.
S&F in repair Lightening strike counter for counting the number of lightening strikes received on ESE lightening arrestor during thundering, Digital type , IP 67, with 6 digit counting, minimum current counting 8/20 us more than 500 Amp, working humidity greater than 95, down conductor max dia up to 25 mm, operating tempreatur -40 +80 degree celcius of size 100 mm x 68 mm x 70 mm including making all necessary connections & taking down old u/s all as specified and directed. Make : SABO System Pvt Ltd or equivalent in ABB/ L&T/Havells.
S & F in repair sheet metal enclosures triple pole and earth plug with socket, as per IEC 61439-3 complete with one four pole MCB of capacity 63 A (3P+N+E-FP) , 415 V , with neutral links including taking down unserviceable one all as specified and directed by Engineer in charge. Make: Legrand Cat Part No. 5078 64 or equivalent in L&T, ABB.
S & F in repair type 1 + 2 AC surge protection device 1P+ N , Uc=320 V and Imax=50kA in exisiting DBs including taking down unserviceable one all as specified and directed by Engineer in charge. Make : Havells Cat Part No. DHSAANAC50320 or equivalent in ABB/Legrand
S & F in repair bakelite rotary switch knob for Flame proof switch as per existing one including taking down old u/s all specified and directed by engr-in charge.
S & F in repair switch flame proof rotary type with termination box in LM6, 16A, single pole 250V including taking down old u/s all as specified and directed by engr-in charge.
M & L for taking down defective 250/400 Watt MV/SV/MH high bay light fittings (any type and any size) Hangers/workshop or any type of bldgs (up to 15 mtr height),disconnecting, testing all components, dismantling of defective components such as holder, choke, ignitors,capacitors, lamps, replacing the defective components with new component, connecting electric supply cable with fitting , replacing of defective cable if required with new one of suitable size , including cleaning of cover, and then refixing/ mounting it on its existing /new location, making electrical connection, checking / testing for its fuctioning complete all as specified and directed by Engineer in Charge. Note : (i) Contractor has to arrange the T&P and ladder required at site for repairing of lights. No T &P will be issued by the Department. (ii) Spares such as choke, ignitors, , lamps, holders, starter, driver etc (supplied by contractor) shall be paid and measured separately under appropriate items.
Supply only HPSV/MH/MV open construction electromagnetic ballast consisting of high quality silicon steel lamination with argon welding,, super enamelled copper wire, vacuum impriganated with white resin, terminal block with tapping for 220/240 volt supplied ,50 Hz , of 400 watt. Make :Havells Cat No. LHGMCKENEBE1400 SV/MH or equivelent in Havells / CG
All as per item No. 67 here-in-before but of capacity 250 Watt. Make :Havells Cat No. LHGMCJENEAC 1250 SV/MH or equivelent in Bajaj / CG
Supply only MH lamp 6000K for integral / non integral high bay/flood light fittings of capacity 400 Watt. Make:: Havells Cat No. LHLQALIGUL7O400 or equivelent in Philips / Bajaj.
Supply only MH lamp for integral / non integral high bay/flood light fittings of capacity 250 Watt. Make: Havells Cat No. LHLQABIGUC8O250 or equivelent in Philips/Bajaj.
Supply only electronic ignitors suitable for 150/250/400 Watt SV/MH street light fitting 240V, 50HZ complete all as specified and directed .Make Havells Cat Part No. LHGEAJENNNA100 or equivelent in Philips/Bajaj.
Supply only porcelain holder (threaded type ) with Base E-40 suitable for 250/400 Watt SV/MH lamp fitting complete all as specified and directed .
Supply only capacitor 30 MFD suitable for 150/250/400 Watt SV/MH street light fitting 250V, 50HZ complete all as specified and directed .Make : Bajaj/philips/CG.
Taking down old unserviceable GI/Copper earth plate from soft and hard soil from any location as directed by Engineer -in- charge.
M&L Earthing complete with copper earth plate electrode 600mm x 600mm x 3 mm thick burried direct in ground (Earth pit not less than 3.25 m deep below ground level) with top edge of the plate not less than 2.5 m below ground level connected to copper strip 20 X 3 mm as earth lead by means of bolts nuts, check nuts and washers of glavanised iron and as shown in electrical plate No 3 connected to earth test point including necessary excavation in hard dense soil and refilling of earth pit after placing the electrode with agriculture soil, removal of existing excavated soil upto a distance of 100m, RCC chamber cover plate, wire mesh, funnel, test point, 40 mm dia GI protection pipe medium grade and separate pipe of 40 mm dia medium grade GI pipe for watering etc complete and testing on completion. The electrode and lead shall be of copper all as specified and directed by Engr-in-charge (Copper strip upto 7.5 RM will be included in the item rate and copper strip beyond 7.5 RM will be measured seperately. NOTE: 1. The unit rate includes for protection GI pipe and watering pipe of 40 mm bore including excavation for earth pit in any type of soil/ disintegrate rock. 2. Contractor has to bring agriculture soil from outside of defence land and fill in earth pit to achieve desired result as the soil resistiviy is very high. 3.The cost of Copper strip of size 20X3 mm from top of earth plate upto 7.5 meter above ground level is deemed to be included in the unit rate of above item.and copper strip beyond 7.5 RM will be measured seperately. 4. All the joints in copper strip and connection with Earth Plate to be welded through brazing and in addition by proving brass nut bolt and washer. 5. Cost of brazing / welding and nut bolts are deemed to be included in the unit rate.
Taking out old unserviceable GI/aluminium/copper earth wire/strip of any size and type in any height and any location as directed by Engineer In charge.
M & L for copper earth contInuity conductor of size 20 x 3 mm strip with insulator fixed to wall or drawn in conduit/pipe as required all as directed by Engineer In charge. Note: Insulator to be fixed on every one meter distance and cost of insulator is deemed to be included in unit rate of item.
S&F in repairs laminated hylam sheet cover of sizes (11 x 13) inches, ISI marked of Make" Hylam" cut with grooves for mounting of fittings like switches, sockets, fan regulators etc. including fixing with new galvanised screw and cup washer complete all as specified and as directed.
All as per Item No. 78 here-in-before but laminated hylam sheet cover of sizes (9 x 11) inches, complete all as specified and as directed.
All as per Item No. 78 here-in-before but laminated hylam sheet cover of sizes (5 x 8) inches, complete all as specified and as directed.
All as per Item No. 78 here-in-before but laminated hylam sheet cover of sizes (5 x 5) inches, complete all as specified and as directed.
S&F Hylam sheet ISI marked min 2.8 mm sheet of suitable size as per site requirement to cover the DB box including cut with grooves for operation of MCB including fixing of sheet with providing steel /brass screw and cup washers as required at site complete as directed by Engineer in Charge.
S&F in repairs PVC insulated, Single core, unsheathed, HRFR copper conductor flexible cable, 1100 Volt, Conf to IS 694, ISI marked of size 25 Sqmm including copper lugs, brass nut and bolt with washer of suitable size as per site requirement to connect the cable including taking down u/s complete all as specified and directed by Engineer in Charge. Make : Havells / Polycab/ Finolex.
S&F in repairs PVC insulated, Single core, unsheathed, HRFR copper conductor flexible cable, 1100 Volt, Conf to IS 694, ISI marked of size 35 Sqmm including copper lugs, brass nut and bolt with washer of suitable size as per site requirement to connect the cable including taking down u/s complete all as specified and directed by Engineer in Charge. Make : Havells / Polycab/ Finolex.
S&F in repairs PVC insulated, Single core, unsheathed, HRFR copper conductor flexible cable, 1100 Volt, Conf to IS 694, ISI marked of size 70 Sqmm including copper lugs, brass nut and bolt with washer of suitable size as per site requirement to connect the cable including taking down u/s complete all as specified and directed by Engineer in Charge. Make : Havells / Polycab/ Finolex.
S&F Copper lugs of size 16 Sqmm including taking down u/s
S&F Copper lugs of size 25 Sqmm including taking down u/s
S&F Copper lugs of size 35 Sqmm including taking down u/s
S&F Copper lugs of size 70 Sqmm including taking down u/s
S&F in repairs lamp holder , PVC/Poly carbonate type with back plate suitable for batten fittings to be fixed on PVC box including supply and fixing 10 watt LED lamp including taking down old u/s. Make For holder : Anchor / L& T/ Havells. LED lamp : Philips/ Bajaj/ Crompton/ Surya.
S&F in repair ceiling rose surface bakelite 65 mm dia three terminal complete including taking down old u/s. : Make Anchor Penta / L& T.
S& F in repair metal socket 20A, 3 pin with earth (SC) including making all electrical connections and taking down old existing one all as specified and directed by Engr-in-charge. Make : L&T Cat Part No. MPS320S or euivalent in Legrand/ ABB.
S& F in repair metal socket 20A, 2 pin with earth (SC) including making all electrical connections and taking down old existing one all as specified and directed by Engr-in-charge. Make : L&T Cat Part No. MPS220S or euivalent in Legrand/ ABB.
S& F in repair metal plug 20A, 3 pin with earth (SC) including making all electrical connections and taking down old existing one all as specified and directed by Engr-in-charge. Make : L&T Cat Part No. MPS320P or euivalent in Legrand/ ABB. General Notes :(i) For item to be replaced under repair (day to day complaint) contactors trade man should report to E/M complaint cell daily and take complaint from concren JE E/M and after attending complaint he should give feedback and return the complaint slip to concern JE E/M in the evening at 17.30 Hrs on same day. (ii) Tradesman deployed for work should wear proper uniform with full shirt and full Pant. Colour code will be decided by EIC. (iii) Being a maintenance contract site will be handover to contractor as per complaint received from user and as per site requirement. (iv) For any minor repair required in wiring or their is any fault in circuit where the item under repair is to be replaced, contractor has to identify and recitified the fault without any extra cost.
CASTLE BUILDERS
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .