GE (AF) FARIDABAD
GE (AF) FARIDABAD
SPECIAL REPAIR TO INTERNAL /EXTERNAL ELECTRICAL INFRASTRUCTURE AT CERTAIN OMQS AND SMQS AT AF STN CHANDINAGAR IN AOR OF GE (AF) FARIDABAD (2nd CALL)
2023_MES_585277_2
GE (FBD)/AF-73/2022-2023
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
CHANDINAGAR
Please refer Tender documents.
9 documents required · 9 mandatory
₹500
GE (AF) FARIDABAD
₹96,800
Yes
13 Jun 2023
10 Apr 2023
26 Apr 2023
10 Apr 2023
24 Apr 2023
10 Apr 2023
Amount
Taking down carefully aluminium point wiring (light, Socket or power) complete including fittings and fixtures such as switches, ceiling roses pendents, regulators, sockets etc for taking credit to be measured separetly including making good the disturbed portion/surface complete all as specified and directed by Engineer-in-Charge.
M&L for point wiring with colour coding multistranded copper conductor cable, PVC insulated and (FRLS) unsheathed size 1.5 sqmm with PVC concealed Conduit ( dia not les than 25 mm) with fixing accessories for one light /fan/bell point controlled by one switch with pressed steel concealed terminal boxes covered with 3mm thick laminated sheet incl. contineous earth wire of PVC insulated unsheathed multi stranded copper conductor cable size 1.5 Sqmm for earth wire connected to common earth dolly complete all as specified and directed by Engineer-in-Charge. Make : Havells,Polycab,Finolex and RR Kable.
All as per item No 2 above but for one 3/5 pin socket 5 Amp on same board, with 1.5sqmm wire with 1.5sqmm earth wire complete all as specified and directed by Engineer-in-Charge.
All as per item No 2 above but for one 3/5 pin socket 5 Amp on independent board with 2.5 sqmmwire with 2.5 sqmm earth wire complete all as specified and directed by Engineer-in-Charge.
All as per item No 2 above but for 3 pins socket outlet 15 Amps independent with 4.0 sq mm incl contineous earthing with multistandred copper conductor PVC insulated unsheathed size 4.0 Sq mm complete all as specified and directed by Engineer-in-Charge. Note:- (For item 02 to 05 ) Cost making good disturbed surface below existing point wiring taken out vide item No 02 and cutting chases and making good of disturbed surfaces by cement & sand mortar (1:3) and surface finish as per adjustment surface conduit and all accessories as required for concealed point wiring vide item No 02 to 05 as applicable shall be deemed to be included in the unit rate quoted against these items.
S&F Modular switch flush type, 5/6 Amps, single pole one module white colour 230 Volts , AC complete all as specified and directed by Engineer-in-Charge. Make : Crabtree, Havells ,C&S,Legrand
S&F Modular switch flush type, 15/16 Amps, single pole one module white colour 230 Volts , AC complete all as specified and directed by Engineer-in-Charge. Make : Crabtree, Havells ,C&S,Legrand
S&F Modular socket 3 pins combined, 5/6 Amp, flush type (multi purpose) two module ,230 Volts , AC complete all as specified and directed by Engineer-in-Charge. Make : Crabtree, Havells ,C&S,Legrand
S&F Modular socket 5 /6 pins combined, 15A/16 Amp, flush type(multi purpose) two module 230 Volts , AC complete all as specified and directed by Engineer-in-Charge. Make : Crabtree, Havells ,C&S,Legrand
S&F Modular white cover plate with frame suitable for three module way 230 Volts , AC complete all as specified and directed by Engineer-in-Charge.Make : Crabtree, Havells ,C&S,Legrand
S&F Modular white cover plate with frame suitable for four module way 230 Volts , AC complete all as specified and directed by Engineer-in-Charge. Make : Crabtree, Havells ,C&S,Legrand
S&F Modular white cover plate with frame suitable for six module way 230 Volts , AC complete all as specified and directed by Engr-in-Charge. Make : Crabtree, Havells ,C&S,Legrand
S&F Modular white cover plate with frame suitable for 08 module way 230 Volts , AC complete all as specified and directed by Engineer-in-Charge. Make : Crabtree, Havells ,C&S,Legrand
S&F Modular metal flush box suitable for three module way 230 Volts , AC complete all as specified and directed by Engr-in-Charge. Make : Crabtree, Havells ,C&S,Legrand
S&F Modular metal flush box suitable for four module way 230 Volts , AC complete all as specified and directed by Engr-in-Charge. Make : Crabtree, Havells ,C&S,Legrand
S&F Modular metal flush box suitable for six module way 230 Volts , AC complete all as specified and directed by Engr-in-Charge.Make : Crabtree, Havells ,C&S,Legrand
S&F Modular metal flush box suitable for 08 module way 230 Volts , AC complete all as specified and directed by Engr-in-Charge. Make : Crabtree, Havells ,C&S,Legrand
S&F switch piano flush type 5 Amps, single pole one way 230 Volts , AC complete all as specified and directed by Engr-in-Charge .Make : Anchor, Cona , Havells, Polycab
S&F socket 3/ 5 pins, 6 Amp, flush type piano (multi purpose) 230 Volts , AC complete all as specified and directed by Engr-in-Charge. Make : Anchor, Cona , Havells, Polycab
S&F Socket 15 Amps flush type,3/ 6 Pin, 230 Volts , AC complete all as specified and directed by Engr-in-Charge. Make : Anchor, Cona , Havells, Polycab
S&F switch 15 Amps flush type 230 Volts , AC complete all as specified and directed by Engr-in-Charge. Make : Anchor, Cona , Havells, Polycab
S&F Ding Dong door bell 230 Volts , AC complete all as specified and directed by Engr-in-Charge. Make : Anchor, Cona , Havells, Polycab
S&F Bell push flush type 5 Amps, single pole one way 230 Volts , AC complete all as specified and directed by Engr-in-Charge. Make : Anchor, Cona , Havells, Polycab
S&F Modular Bell push flush type 5 Amps, single pole one way 230 Volts , AC complete all as specified and directed by Engr-in-Charge. Make : Crabtree, Havells ,C&S,Legrand
S&F ceiling rose, PVC / Polycarbonate isolated body ,surface backlite, 65x50mm, three terminals, 230 Volts , AC complete all as specified and directed by Engr-in-Charge. Make : Anchor, Cona , Havells, Polycab
S&F modular stepped type electronic fan regulator flush type,2-way 230 Volts , AC complete all as specified and directed by Engineer-in-Charge. Make : Crabtree, Havells ,C&S,Legrand
S&F stepped type electronic fan regulator flush type 230 Volts , AC complete all as specified and directed by Engineer-in-Charge. Make : Anchor, Cona , Havells, Polycab
S&F Batten holder PVC/Polycarbonate base / back suitable for LED lamp. 230 Volts , AC complete all as specified and directed by Engr-in-Charge. Make : Anchor, Cona , Havells, Polycab
S&F LED Bulbs 9/10W B-22 Pin type 230 Volts , AC completeall as specified and directed by Engineer-in-Charge. Make : Crompton, Bajaj, Polycab , Wipro
S&F single pole and neutral sheet metal enclosure with a two pin and earth plug and socket complete with one single pole 20 amps MCB complete all as spec ified and directed by Engineer-In-Charge. Make : Legrand , L&T , Havells ,Schneider
S&F LED tube light fittings 20W (4 feet) wall mounted LED batten extruded PVC heat sink provided for efficient heat dissipation & integrated electronic driver optics diffused complete including electrical connection with copper cable from ceiling rose to fittings and including taking down existing fittings all as directed by Engineer-in-Charge. Make : Crompton , Havells, Polycab , Bajaj , Philips
S&F LED 6000K (2’ feet), 10W Decorative LED lighting fixture with extruded PVC . heat sink, environmental friendly, energy efficient ready to use pack, complete and including taking down existing fittings all as directed by Engineer-in-Charge. Make : Crompton , Havells, Polycab , Bajaj , Philips
S&F LED bulkhead luminaire 10W decorative type as per sample complete including electrical connection with copper cable from ceiling rose to fittings and including taking down existing fittings all as directed by Engineer-in-Charge. Make : Crompton , Havells, Polycab , Bajaj , Philips
S&F LED building secuity light 25 watt made up of pressure die cast aluminium housing with mid power LED as lightening source and PC cover having top opening inbuilt LED driver with IP66 protection and impact resistance of IK-07 complete including GI bracket with nut bolts, washers etc including electrical connection with copper cable from ceiling rose to fittings and including taking down existing fittings all as directed by Engineer-in-Charge. Make : Crompton , Havells, Polycab , Bajaj , Philips
M&L for submain wiring with 2X4.0 SQMM+1X4.0SQMM Earth Wire single core PVC insulated FRLS sheathed copper cable connecting to common earth dolly in and including heavy duty PVC concealed Conduit and dismantling and taking down existing unserviceable wiring, all accessories complete all as specified and directed by Engineer-in-Charge. Make : Havells,Polycab,Finolex and RR Kable.
M&L for submain wiring with 2X6.0 SQMM+1X6.0SQMM Earth Wire single core PVC insulated FRLS sheathed copper cable connecting to common earth dolly in and including heavy duty PVC concealed Conduit and dismantling and taking down existing unserviceable wiring, all accessories complete all as specified and directed by Engineer-in-Charge. Note:- (For item 35 to 36 ) Cost making good disturbed surface below existing point wiring taken out vide item No 35 and cutting chases and making good of disturbed surfaces by cement & sand mortar (1:3) and surface finish as per adjustment surface conduit and all accessories as required for concealed point wiring vide item No 35 to 36 as applicable shall be deemed to be included in the unit rate quoted against these items. Make : Havells,Polycab,Finolex and RR Kable.
S&F in repairs VTPN 4 way double door prewired distribution board TPN-DPX 125 MCCB including one No MCCB 125 Amps, 25 kA, 4 pole as incomer and suitable SPN/TP MCBs as outgoing double door type sheet metal enclosure 415V with 200 Amps rated standard busbar of suitable size plate and common neutral link without MCBs with blank plate suitable for 4 way complete and including taking down VTPN DB's all as specified and all as directed by Engineer-in-Charge. Make : Havells , Legrand , L&T , Seimens Note : Rates of MCCB and MCB SPN/SP/TP shall deemed to be included in the quoted rates.
S & F in repairs single pole and neutral sheet metal enclosures for Distribution board (DB's)suitable for MCBs fitted with bus bar , Neutral link ,Earth Bar and Din rail 240 V, 50 Hz supply double door SP&N DB system 12 wayscomplete all as specified and directed by Engineer-in-Charge. Make : Make : Havells , Legrand , L&T , Seimens
S & F in repairs single pole and neutral sheet metal enclosures for Distribution board (DB's)suitable for MCBs fitted with bus bar , Neutral link ,Earth Bar and Din rail 240 V, 50 Hz supply double door SP&N DB system 08 ways complete all as specified and directed by Engineer-in-Charge. Make : Make : Havells , Legrand , L&T , Seimens
S&F RCBOs for earth leakage,over load & short circuit protection 2 pole ,25 Amp rating, 300 mA capacity suitable for 240 Volts and including taking down existing MCB/ RCCB complete all as specified and directed by Engineer-in-Charge. Make : Havells , Legrand , L&T ,seimens, Schneider
S&F MCB SPN 40-63 Amps 240V incl all termnials, fitting etc. including taking down complete all as specified and directed by Engineer-in-Charge. .Make : Havells , Legrand , L&T ,seimens, Schneider
S&F MCB SP 06 to 40 Amps 240V incl all termnials, fitting etc including taking down complete all as specified and directed by Engineer-in-Charge. Make : Havells , Legrand , L&T ,seimens, Schneider
Supply & fixing of meter box sheet metal enclosure concealed type made of metal of size 36x25x14 cm of thickness 1.5 mm incl glass display having suitable for single phase/three phase temper proof electronic meter incoming & outgoing opening for cables complete all as specified and directed by Engineer in charge
M&L for Refixing carefully serviceable fans / geysers etc any type from site on completion of civil and E/& M works incl making necessary connection with suitable copper wire and testing and incl taking down complete all as specified and directed by Engineer-in-Charge.
M & L for earthing complete with galvanised steel earth plate electrode 600 x 600 x 6.3 mm thick burried directly in gorund (earth pit not less than 2.25 Mtr normal ground level),and top edge of earth plate not less than 1.5 mtr below normal ground level, connected to galvanised means of earth wire 4 mm dia with bolts, nuts & check nuts, and washers of galvanised iron protection pipe light grade of 15 mm dia and watering pipe medium grade of 20 mm dia and filled with alternate layer of charcoal and common salt, watering funnel with wire mesh, earth pit chamber and cover CI frame PCC 1:3:6 type C-2 all as shown in electrical plate No-3 of SSR part-I of 2009 connected to earthing test point all as specified and indicated including all earth work excavation, returning filling and disposal of surplus soil and testing on completion complete all as specified and directed by Engineer-in-Charge.
Excavation in trenches in soft/loose soil not exceeding 1.5 Mtr wide and not exceeding 1.5 Mtr depth for laying of cables/poles or foundation etc and getting out all as specified and directed by Engineer-In-Charge.
Returning, filling, including spreading levelling and well ramming in layers not exceeding 25cm apart complete all as specified and directed by Engineer-in-Charge.
Removing of surplus excavated soil to a distance not exceeding 50 Mtr from starting point and depositing where directed at a level not exceeding 1.5 Mtr above the starting point all as specified and directed by Engineer-In-Charge.
M&L for sand cushoning with a layer of sand 80mm thick before laying of cable and 150mm thick after laying of cable to trenches complete all as specified and directed by Engineer-in-Charge.
M&L for sub class `B` bricks for cable protection complete all as specified and directed by Engineer-in-Charge.
Taking down UNSV LT Under Ground cable of any size complete all as specified and directed by Engineer-in-Charge.
Supply and laying, connecting and testing XLPE underground cable insulated, and overall sheathed with aluminium conductor heavy duty 1100 volts grade 16 sqmm 4 core laid in trenches/ on poles/ road crossing or passing through existing/new pipe under road crossing, clamping on wall etc complete all as specified and directed by Engineer-in-Charge. Note: (i) Cost of laying electrical cable through new/existing pipe under road, buildings, railway tracks, highways and Aluminium thimbles/lugs are incl in the quoted rates. (ii) All equipments , machinery or tools if required for laying electrical cable through new/existing pipes are provided by the contractor without any extra cost. Make : Havells , Polycab , KEI ,CCI
All as per Item Ser No 52 here in before but for 3.5 core 25 Sqmm complete all as specified and directed by Engineer-in-Charge.
All as per Item Ser No 52 here in before but for 3.5 core 70 Sqmm complete all as specified and directed by Engineer-in-Charge.
All as per Item Ser No 52 here in before but for 3.5 core 95 Sqmm complete all as specified and directed by Engineer-in-Charge.
M/S Anand Enterprises
NAVYUG VYAPARI
High Tech Metal India
MAHABIR SINGH
Shikha Enterprises
M/s ELECTROSHINE ENGINEERS
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .