Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹4.4 CrAccepted-AOC 20 SC BOSE COLONY GALL NO 2 DEFENCE LAB ROAD RATNADA JODHPUR 342001 | JODHPUR | JODHPUR | RAJASTHAN | 342001 | ₹4.4 Cr | L1 | Accepted-AOC Being lowest bidder and reasonable bid |
| 2 | L2₹4.7 Cr+₹25.8 L (5.85%)Rejected-Finance I 910 JAHANGIR PURI NEAR BY ANAND MAYA HOSPITAL NORTH WEST DELHI DELHI 110033 UDYAM DL 06 0040830 | NORTH DELHI | DELHI | 110033 | ₹4.7 Cr+₹25.8 L (5.85%) | L2 | Rejected-Finance Other than lowest bidder |
| 3 | L3₹4.7 Cr+₹29.5 L (6.71%)Rejected-Finance 04 L BLOCK MARKET SECTOR 11 NOIDA 201301 UP GAUTAM BUDHA NAGAR | GAUTAM BUDDHA NAGAR | UTTAR PRADESH | 201301 | ₹4.7 Cr+₹29.5 L (6.71%) | L3 | Rejected-Finance Other than lowest bidder |
| 4 | L4₹4.8 Cr+₹44.4 L (10.1%)Rejected-Finance CHANDAN NAGAR OPP IOCL PERTROL PUMP RAMPUR ROAD BAREILLY UP 243001 | BAREILLY | BAREILLY | UTTAR PRADESH | 243001 | ₹4.8 Cr+₹44.4 L (10.1%) | L4 | Rejected-Finance Other than lowest bidder |
| 5 | L5₹4.9 Cr+₹45.7 L (10.4%)Rejected-Finance 5037 5038 URBAN ESTATE PH 1 PATIALA 147002 PUNJAB | PATIALA | PATIALA | PUNJAB | 147002 | ₹4.9 Cr+₹45.7 L (10.4%) | L5 | Rejected-Finance Other than lowest bidder |
| Sl No | Description | Qty | Unit | M K ENGINEERS CO. L1 | Sant Construction Co. L5 | GEPS PROJECTS L3 | SATISH AND CO L2 | R D Bansal L6 | United Sales Corporation L8 | nhsaluji and associates L10 | BHARAT ELECTRICAL TRADERS L4 | BRITE INDUSTRIES L9 | SAGGI ELECTRIC COMPANY L7 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1.00Note: (i) Please refer schedule 'A' notes before quoting the tender. (ii) Amount of Schedule of credit shall be deducted off line by the department. | |||||||||||||
| 2.00 | Supply, Install, testing and commissioning of 11KV, 630A, 21KA/3sec, SF6 Gas Insulated, Outdoor, RHS Extensible Ring Main Unit (RMU) consist of Motorised One (01) Load Break Switch and Three (3) Vacuum Circuit Breaker (01 x Incomer & 03 x Outgoing) with SCADA Communicable Relay, rupturing capacity 250 MVA mounted on suitable 2 x RCC Foundation having width of each foundation 300mm and distance between two foundation 900mm having following parameters:-
(a) Metal Enclosed switchgear: IEC 62271-200
(b) General Purpose switches: IEC 60265-1
(c) Disconnectors and Earthing switches: IEC 62271-102
(d) Switch Fuse combination : IEC 62271-105
(e) Circuit Breakers: IEC 62271-100
(f) Common clauses: IEC 60694
(g) Pressure of SF6 gas: 1.4 bar at 20 °C
(h) Cable bushings: DIN 47636
(j) Temperature class: -25 °C - +50 °C Outdoor
(k) Degree of protection:
(l) SF6 tank: IP 67
(m) Front cover: IP 2X
(n) Cable cover: IP 3X (Contd...) | 7 | Each | 10,00,000 ₹70,00,000 Lowest | 11,60,000 ₹81,20,000 | 10,80,000 ₹75,60,000 | 10,45,000 ₹73,15,000 | 12,19,000 ₹85,33,000 | 13,00,000 ₹91,00,000 | 13,72,000 ₹96,04,000 | 12,00,000 ₹84,00,000 | 12,52,955 ₹87,70,685 | 11,85,000 ₹82,95,000 |
| 2.01(o) Outdoor Enclosure IP 54 (p) Busbars: 400 mm2 Cu (q) Earth bar (external): 120 mm2 Cu - Bolt dimension: M10 (r) Thickness of Stainless Steel Tank: 2.5 mm SS-304 (s) Thickness of Enclosure 2 mm CRCA (t) Access to cable Front cable access Colours: (u) Front cover : RAL 7035 (v) Side and Cable cover : RAL 7035 (w) Outdoor Enclosure IS5 of shade 632 (60 to 80 microns) (x) 2 x 12 V DC Battery including Battery Charger and suitable copper cable to provide 230 V auxiliary supply for battery charger from nearby LT panel is deemed to be included in the unit rate, not to be paid separately. (y) RMU must have electrical and mechanical interlocking as per latest electrical safety norms. (z) RMU's bushing (when get faulty due to damage or human error) shall have site replaceable type. | |||||||||||||
| 3.00 | Supply, Install, testing and commissioning of 11KV, 630A, 21KA/3sec, SF6 Gas Insulated, Outdoor, RHS Extensible Ring Main Unit (RMU) consist of Motorised Two (02) Load Break Switch and Two (2) Vacuum Circuit Breaker (02 x Incomer & 02 x Outgoing) with Mechanical interlocking between Load break Switch, with SCADA Communicable Relay, rupturing capacity 250 MVA mounted on suitable 2 x RCC Foundation having width of each foundation 300mm and distance between two foundation 900mm having following parameters:-
(a) Metal Enclosed switchgear: IEC 62271-200
(b) General Purpose switches: IEC 60265-1
(c) Disconnectors and Earthing switches: IEC 62271-102
(d) Switch Fuse combination : IEC 62271-105
(e) Circuit Breakers: IEC 62271-100
(f) Common clauses: IEC 60694
(g) Pressure of SF6 gas: 1.4 bar at 20 °C
(h) Cable bushings: DIN 47636
(j) Temperature class: -25 °C - +50 °C Outdoor
(k) Degree of protection:
(l) SF6 tank: IP 67
(m) Front cover: IP 2X
(n) Cable cover: IP 3X (Contd....) | 4 | Each | 8,77,000 ₹35,08,000 Lowest | 10,20,000 ₹40,80,000 | 9,33,000 ₹37,32,000 | 8,90,000 ₹35,60,000 | 10,57,000 ₹42,28,000 | 10,50,000 ₹42,00,000 | 11,90,000 ₹47,60,000 | 10,70,000 ₹42,80,000 | 10,58,755 ₹42,35,020 | 10,11,200 ₹40,44,800 |
| 3.01(o) Outdoor Enclosure IP 54 (p) Busbars: 400 mm2 Cu (q) Earth bar (external): 120 mm2 Cu - Bolt dimension: M10 (r) Thickness of Stainless Steel Tank: 2.5 mm SS-304 (s) Thickness of Enclosure 2 mm CRCA (t) Access to cable Front cable access Colours: (u) Front cover : RAL 7035 (v) Side and Cable cover : RAL 7035 (w) Outdoor Enclosure IS5 of shade 632 (60 to 80 microns) (x) 2 x 12 V DC Battery including Battery Charger and suitable copper cable to provide 230 V auxiliary supply for battery charger from nearby LT panel is deemed to be included in the unit rate, not to be paid separately. (y) RMU must have electrical and mechanical interlocking as per latest electrical safety norms. (z) RMU's bushing (when get faulty due to damage or human error) shall have site replaceable type. | |||||||||||||
| 4.00 | Supply, Install, testing and commissioning of 11KV, 630A, 21KA/3sec, SF6 Gas Insulated, Outdoor, RHS Extensible Ring Main Unit (RMU) consist of Motorised Two (02) Load Break Switch and Two (2) Vacuum Circuit Breaker (02 x Incomer & 02 x Outgoing) with Mechanical interlocking between VCB, with SCADA Communicable Relay, rupturing capacity 250 MVA mounted on suitable 2 x RCC Foundation having width of each foundation 300mm and distance between two foundation 900mm having following parameters:-
(a) Metal Enclosed switchgear: IEC 62271-200
(b) General Purpose switches: IEC 60265-1
(c) Disconnectors and Earthing switches: IEC 62271-102
(d) Switch Fuse combination : IEC 62271-105
(e) Circuit Breakers: IEC 62271-100
(f) Common clauses: IEC 60694
(g) Pressure of SF6 gas: 1.4 bar at 20 °C
(h) Cable bushings: DIN 47636
(j) Temperature class: -25 °C - +50 °C Outdoor
(k) Degree of protection:
(l) SF6 tank: IP 67
(m) Front cover: IP 2X
(n) Cable cover: IP 3X (Contd....) | 1 | Each | 8,77,000 ₹8,77,000 Lowest | 10,20,000 ₹10,20,000 | 9,00,000 ₹9,00,000 | 8,88,964 ₹8,88,964 | 10,57,000 ₹10,57,000 | 10,50,000 ₹10,50,000 | 11,75,000 ₹11,75,000 | 11,00,000 ₹11,00,000 | 10,91,500 ₹10,91,500 | 10,11,200 ₹10,11,200 |
| 4.01(o) Outdoor Enclosure IP 54 (p) Busbars: 400 mm2 Cu (q) Earth bar (external): 120 mm2 Cu - Bolt dimension: M10 (r) Thickness of Stainless Steel Tank: 2.5 mm SS-304 (s) Thickness of Enclosure 2 mm CRCA (t) Access to cable Front cable access Colours: (u) Front cover : RAL 7035 (v) Side and Cable cover : RAL 7035 (w) Outdoor Enclosure IS5 of shade 632 (60 to 80 microns) (x) 2 x 12 V DC Battery including Battery Charger and suitable copper cable to provide 230 V auxiliary supply for battery charger from nearby LT panel is deemed to be included in the unit rate, not to be paid separately. (y) RMU must have electrical and mechanical interlocking as per latest electrical safety norms. (z) RMU's bushing (when get faulty due to damage or human error) shall have site replaceable type. | |||||||||||||
| 5.00 | Supply, Install, testing and commissioning of 11KV, 630A, 21KA/3sec, SF6 Gas Insulated, Outdoor, RHS Extensible Ring Main Unit (RMU) consist of Motorised One Load Break Switch and Four (4) Vacuum Circuit Breaker (01 x Incomer & 4 x Outgoing) with SCADA Communicable Relay, rupturing capacity 250 MVA mounted on suitable 2 x RCC Foundation having width of each foundation 300mm and distance between two foundation 900mm having following parameters:-
(a) Metal Enclosed switchgear: IEC 62271-200
(b) General Purpose switches: IEC 60265-1
(c) Disconnectors and Earthing switches: IEC 62271-102
(d) Switch Fuse combination : IEC 62271-105
(e) Circuit Breakers: IEC 62271-100
(f) Common clauses: IEC 60694
(g) Pressure of SF6 gas: 1.4 bar at 20 °C
(h) Cable bushings: DIN 47636
(j) Temperature class: -25 °C - +50 °C Outdoor
(k) Degree of protection:
(l) SF6 tank: IP 67
(m) Front cover: IP 2X
(n) Cable cover: IP 3X (Contd...) | 2 | Each | 13,13,000 ₹26,26,000 Lowest | 14,75,000 ₹29,50,000 | 13,62,000 ₹27,24,000 | 13,20,000 ₹26,40,000 | 15,25,000 ₹30,50,000 | 23,00,000 ₹46,00,000 | 16,86,000 ₹33,72,000 | 15,00,000 ₹30,00,000 | 16,36,900 ₹32,73,800 | 14,78,880 ₹29,57,760 |
| 5.01(o) Outdoor Enclosure IP 54 (p) Busbars: 400 mm2 Cu (q) Earth bar (external): 120 mm2 Cu - Bolt dimension: M10 (r) Thickness of Stainless Steel Tank: 2.5 mm SS-304 (s) Thickness of Enclosure 2 mm CRCA (t) Access to cable Front cable access Colours: (u) Front cover : RAL 7035 (v) Side and Cable cover : RAL 7035 (w) Outdoor Enclosure IS5 of shade 632 (60 to 80 microns) (x) 2 x 12 V DC Battery including Battery Charger and suitable copper cable to provide 230 V auxiliary supply for battery charger from nearby LT panel is deemed to be included in the unit rate, not to be paid separately. (y) RMU must have electrical and mechanical interlocking as per latest electrical safety norms. (z) RMU's bushing (when get faulty due to damage or human error) shall have site replaceable type. | |||||||||||||
| 6.00 | Supply, Install, testing and commissioning of 11KV, 630A, 21KA/3sec, SF6 Gas Insulated, Outdoor, RHS Extensible Ring Main Unit (RMU) consist of Motorised Two Load Break Switch and Three (3) Vacuum Circuit Breaker (02 x Incomer & 03 x Outgoing) with Mechanical interlocking between Load break Switch, with SCADA Communicable Relay, rupturing capacity 250 MVA mounted on suitable 2 x RCC Foundation having width of each foundation 300mm and distance between two foundation 900mm having following parameters:-
(a) Metal Enclosed switchgear: IEC 62271-200
(b) General Purpose switches: IEC 60265-1
(c) Disconnectors and Earthing switches: IEC 62271-102
(d) Switch Fuse combination : IEC 62271-105
(e) Circuit Breakers: IEC 62271-100
(f) Common clauses: IEC 60694
(g) Pressure of SF6 gas: 1.4 bar at 20 °C
(h) Cable bushings: DIN 47636
(j) Temperature class: -25 °C - +50 °C Outdoor
(k) Degree of protection:
(l) SF6 tank: IP 67
(m) Front cover: IP 2X
(n) Cable cover: IP 3X (Contd....) | 2 | Each | 11,68,000 ₹23,36,000 Lowest | 13,50,000 ₹27,00,000 | 12,33,000 ₹24,66,000 | 11,84,000 ₹23,68,000 | 15,70,000 ₹31,40,000 | 14,75,000 ₹29,50,000 | 15,21,000 ₹30,42,000 | 14,00,000 ₹28,00,000 | 14,40,150 ₹28,80,300 | 13,30,360 ₹26,60,720 |
Tender Value
₹6.3 Cr
EMD Value
₹6.4 L
Closing Date
2 Sept 2025, 6:00 pmClosed
CHIEF ENGR, BHOPAL ZONE
HQ CHIEF ENGR BHOPAL ZONE, MES SI LINE BHOPAL 462001
PROVN OF 11 KV HT RING MAIN SYSTEM AT KAMPTEE MIL STN UNDER GE KAMPTEE
2025_MES_722336_1
CEBZ/KAM/TOKEN/11 OF 2025-26
Open Tender
Electrical and Maintenance Works
Item Rate
365 days
Kamptee
As per NIT documents
5 documents required · 5 mandatory
₹3,000
GE Kamptee
₹6.4 L
Bhopal
26 Mar 2026
24 Jul 2025
4 Sept 2025
24 Jul 2025
2 Sept 2025
26 Aug 2025
5 Aug 2025
stage.html
html • 0.08 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
tenderRMU.pdf
Tender Documents • 2.45 MB
BOQ_808631.xls
BOQ • 1.99 MB
BOQ.xls
BOQ • 1.93 MB
Tenderdocument.pdf
Tender Documents • 2.45 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .