Tender Value
Refer Docs
EMD Value
₹2.2 L
Closing Date
2 Jul 2021, 6:00 pmClosed
CWE NO 2 DELHI CANTT-10
HQ CWE DELHI CANTT-10
PROVN OF PCC PLINTHS WITH WEATHER SHED VOLTAGE STABILISER LT PANEL TRANSFORMER RMU STANDBY DG SET AND OTHER CONNECTED CIVIL AND ELECTRICAL SERVICES FOR PROPOSED 2X250 LPM AND 3X500 LPM OXYGEN GENERATION PLANTS UNDER PROVN OF PARA 35 AND38 OF DWP 2020
2021_MES_453016_2
CWE/BH-15/2021-22
Limited
Electrical and Maintenance Works
Item Rate
42 days
GE E/M BASE HOSPITAL DELHI CANTT
As per Tender Documents
8 documents required · 8 mandatory
₹1,000
Yes
₹2.2 L
Yes
14 Jul 2021
26 Jun 2021
3 Jul 2021
26 Jun 2021
2 Jul 2021
27 Jun 2021
Amount
Surface excavation not exceeding 30 cm deep and averaging 15 cm deep and getting out in soft/loose soil complete all as specified and as directed.
Excavation in post holes in soft /loose soil (or similar holes) each not exceeding 0.5 cum, getting out,, returning filling in and ramming earth or broken rubble mixed with earth around, in layers not exceeding 25 cm, watering and removing surplus soil to a distance not exceeding 50m and making good surface complete all as specified and directed.
M & L for PCC type C-1 1:3:6 Using 20mm graded crushed stone aggregate as in foundation filling and mass concrete/ sub base complete all as specified and as directed.
Excavation in trenches, not exceeding 1.5m wide and not exceeding 1.5m deep, for foundation etc not exceeding 10 Sqm on plan and getting out soft/ loose soil complete all as specified and as directed.
M&L for Brickwork with sub class 'B' bricks, straight or curved on plan exceeding 6m mean radius, built in cement mortar 1:6 complete all as specified and as directed.
Returning filling including spreading leveling watering and well ramming in layer not exceeding 25cm in soft and loose soil complete all as specifed and as directed.
Removal of excavated material not exceeding 50 mtr and depositing where directed at a level not exceeding 1.5m above the starting point complete all as specified and as directed.
M&L for Brick work with sub class 'B' bricks, straight or curved on plan not exceeding 6 m mean radius, built in cement mortar 1:4 complete all as specified and as directed.
S&F factory made SFRC manhole/drain covers ( with or without hole) of area not exceeding 0.75 Sqm 100 mm thick in round or rectangular shape, M-25 medium duty complete all as specified and as directed.
M&L for rendering 15mm thick cement plaster in cement mortar 1:4 on external surfaces of brick or concrete surface finished even and smooth without using extra cement complete all as specified and directed.
M&L for rendering 15mm thick cement plaster in cement mortar 1:6 on internal surfaces of brick or concrete surface finished even and smooth without using extra cement complete all as specified and directed.
M&L for preparation of new plastered surfaces of walls and applying two coats of cement base paint over a coat of primer to walls to obtain uniform surfaces including making good the surface complete all as specifed & directed.
M&L for preparation of new plastered surface of wall and applying two coats of oil bound distermper over one coat of alkali resistant primer of any tint on walls complete all as specified and directed.
S&F angles,channel, and flats for post and struts in fencing including cutting tops to shape as directed, drilling holes, notching for wire etc, flat iron fillets (for securing wire mesh etc.) including all necessary drilling,bolting or riveting, etc., and similar work conforming to Fe-290 GdeE-165 complete all as specified and as directed.
Supply only chain link MS galvanised fencing of any size or any type complete all as specified and as directed.
Fixing only chain link fencing including lines wires, any mesh, size and type to any type of standards rails, straining bolts, etc including provision of binding wire complete all as specified.
Supply and Fix mild steel screw bolts,(machine made)and dia of neck 11 to 15mm with hexagonal or square headed one end and screwed the other, or screwed the both ends and each screwed end to be fitted with washers and one hexagonal or square length of nut bolt ex 5 cm n exc 10 cm long complete all as specified and as directed.
Supply and laying mild steel round bars 10 mm dia and over, cut to length, bent to shape required, including passing through chain link fence at intervals as directed. Complete all as specified of grader Fe 290 (Gde-E-165) complete all as specified and as directed.
M&L for Plain cement concrete 1:2:4 type B-1 (20 mm graded aggregate) as in coping , plinth courses,bed blocks,precast lintel upto 1.5 clear span etc complete all as specified and as directed.
S&F Pre-cast Plain cement concrete block as in kerb stone of size as required at site, made of PCC 1:2:4, Type B1, using 20 mm graded stone aggregate, set in cement mortar 1:6 including necessary preparation of base surface for fixing of kerb stone and all excavation & earthwork complete all as specified and as directed.
M&L for two coat of synthetic enamel paint over a coat of primer on cement concrete surfaces of any description over 10cm girth or width not herwise described including prepration of new surface complete all as directed.
M&L for RMC (ready mix concrete) M-25 using 20mm aggregate as in foundation filling and mass concrete complete all as specified and as directed.
M&L for PCC 1:4:8 type D-2 (using 40mm graded crushed stone aggregate) in foundation, filling and mass concrete complete all as specified and as directed.
S&F 40+-2 kg/m3 density, 50mm thick Panel consisting of 0.5mm TCT Lioydeck profiled coloured sheet on top and 0.5mm TCT plain PPGI sheet at the bottom with 50mm thick PUF sandwiched in between complete all as specifed and as directed.
S&F pre-painted galvatume aluminium zinc coating GI based corrugated steel sheet 0.50 mm thick of any colour having tensile strength of 550 Mpa as in roof covering/cladding to wall, fixed with self tapping screws as specified.
S&F pre-painted galvatume aluminium zinc coating GI based plain steel sheet 0.50 mm thick of an colour having tensile strength of 550 Mpa as in roof covering/cladding to wall, fixed with self tapping screws as specified.
S&F steel tubular trusses, purlins, rafter vertical post and similar works including special shaped washer etc. complete using ERW or induction butt weled tubes including cleats, plates, hold fast and including conforming to IS 1161-1998 Gde, ST-240 complete all as specified and directed.
S&F plain/chequered MS plate incl cutting / welding & drilling confirming to Fe-290 (Gde -165) complete all as specified and directed.
M&L for framed work as in doors or gates of angle or other section complete drilled for fixing of steel sheeting or other covering, doors etc. to be prepared for hanging or sliding with and including bolts, if required, hook and pintle hinges; hand made sliding bolts; clamps; hold fasts either hooks and hinges or steel hanging door fittong etc conforming to Fe-410-W Gde-250 Quality -A all as specified and directed.
M&L for preparation steel surfaces of any description, over 10 cm in width or girth, not otherwise described, two coats of synthetic painting on new steel surfaces over one coat of red oxide primer complete all as specified and as directed.
S&F Expanded metal, cut to length,bent to shape required and tying with and including annealed mild steel wire not less than 0.9mm dia or fixing with galvanised steel staples supplied and fixed complete to wood or steel members not exceeding 4 kg/sqm complete all as specified and as directed.
Supply and laying sand (25 mm thickness ) for cushioning to interlocking paver block complete all as specified and directed.
M&L for vibrator compacted rubber moulded (lacquer polish) interlocking paver block shape, size and colour (Red, Yellow, Green and Grey) as approved confirming to IS 15658-2006 of 80 mm thickness M-40 Grade made with grey cement and and colour pigment complete and including average 25 mm thick providing cement concrete type B-1, 1:2:4 (20 mm graded aggregate) as in sides of paver blocks complete all as specified and directed.
M&L plain cement concrete 1:3:6, type C1, using 20mm graded stone aggregate as in surface channel and drains complete all as specified and as directed.
Extra for forming fair finished drain or channel not exceeding 45 cm inner girth in cement concrete, using extra cement, including forms, moulds, mitred/stopped ends etc complete all as specified and as directed.
S&F Vitreous China squatting pan , "Orrissa" pattern size 580 X 440 mm white with intgrel footrest (excluding flushing cistern & flush pipe complete including provision of lime concrete complete all as specified and directed.
S&F PVC (SWR) floor trap 110mm,setting and jointing with solvent cement complete all as specified and directed.
S&F grating doom 125mm ida with waste hole of PTMT min wt 40 gms complete all as specified and as directed.
Supply and fix PVC (SWR) vent cowl 110 mm dia with rubber ring joints fixed to walls complete all as specified and directed.
S&F 110mm bore PVC (SWR) pipes single socketed in any length with rubber ring joints fixed to walls using PVC clamp suitable for 110mm bore PVC (SWR) pipe complete.
Supply and fix 75 mm bore PVC (SWR) pipes single socketed, in any length with rubber ring joint and fixed to walls using PVC clamps complete all as specified and directed.
S&F vitreous china wash hand basin white flat back of size 550mm x400 mm with 32mm CP waste coupling, 2 x600mm long hot or cold connector including cutting for and pinning in ends of brackets or erecting stand and fixed with fastener etc complete all as specified and as directed.
S&F 10 ltrs capacity PVC valveless syphonic action type flushing cistern low level white with inlet ball valve, float, chain and pull and brackets including 1x600mm long connector and 32mm dia PVC flush pipe etc complete.
S&F 15 mm bore long body Bib taps fancy type cast copper alloy chromium plated with crutch or butterfly handle, screwed down,screwed for iron pipe or brass ferrule fixed complete all as specified and directed.
S&F 15 mm bore cast copper alloy chromium plated fancy typestop/angle valve screwed down, high pressure, with crutch or butter fly handle, screwed both ends for iron pipe or unions fixed complete all as specified and directed.
S&F 15 mm bore cast copper alloy chromium plated fancy type stop cock long shank and cup (concealed type) screwed down, high pressure, with crutch or butter fly handle, screwed both ends for iron pipe or unions fixed complete all as specified and directed.
S&F chromium plated shower rose 125 mm dia with swivel joints including fixing to steel pipe or union complete all as specified and as directed.
S&F 15 mm bore centre hole basin mixer, screwed for iron pipe or for brass ferrule and fixed complete all as specified and directed.
S&F in repair GI anodised snap grid ceiling, made of Tee and angle of size 24.5 x 24.5 x1.50 mm thick, size of grid 605 x 605 mm with GI wire suspender 3 mm dia, fixed with wooden/steel truss/rafter, flat or slope, complete all as specified and as directed.
S&F hangers 6mm dia GI (upto 1200mm length adjusting level fixed to roof slabs by means of ceiling cleats made out of GI flat 40x3mm size 60mm long complete all as specifided and as directed.
M&L for 4 mm thick E-board(designer) classic of size 605 x 605mm, fixed to GI snap grid ceiling flat or slope complete all as specified and directed.
S&F solid PVC door frame of size, 50x47mm, made out of 5mm thick plain colour PVC sheet, reinforced with MS square tube fixed with screw/plugs to brick walls complete all as specified and as directed.
S&F Factory made solid panel PVC door shutter, 30mm thick (style), consisting of frame made out of MS tubes for top & bottom rails, MS frame shall be covered with heat moulded plain colour PVC 'C' channel, having a PVC sheet strip of 20mm width stuck inside with solvent cement for stiles and plain colour PVC sheets for top rail, lock rail & bottom rail on either side & as gap insert for top rail & bottom rail; panelling of plain colour PVC sheet shall be fitted in the MS frame welded/sealed to the stiles & rails with suitable PVC sheet beading, and joined together with solvent cement, supplying & fixing in the frame at site as per specification & drawing including 3 Nos 100mm stainless steel Hinge, 2 Nos 150 mm Aluminium Tower bolt and 2 Nos 150 mm Aluminium handle complete all as specified and as directed.
S&F 35mm thick, flush shutters, solid core construction, with block board core and ply wood face panels, commercial type on both sides including mild steel butt hinges100mm size -3 Nos per leaf, Aluminium tower bolt 200mm size -2 Nos per leaf and Aluminium handle, 150mm size -2 Nos per leaf complete all as specified and directed.
M&L for 2nd class Hardwood 35 mm thick Glazed and skeleton shutters, open rebated and prepared to receive glass, gauze, etc. (without sash bars), edges of framing plain, chamfered or rounded. fitted with cut and mitred beads for securing glass, etc.; sizes of me-mbers of shutters SSR Part I, Section 8, clause 8.24 (a); supplied and fitted to chowkats including mild steel butt hinges100mm size -3 Nos per leaf, Aluminium tower bolt 200mm size -2 Nos per leaf and Aluminium handle, 150mm size -2 Nos per leaf complete all as specified and directed.
M&L for powder coated aluminium window and ventilator shutters, sliding type with or without sash bars, alumiuminium sections weighing not less than 0.55 kg/mtr including necessary joiing cleats, glazing clips rubber packing, powder coated aluminium snap beading, screws, powder coated aluminium fittings such as peg stays/lock, rollers, hinges type B-21 100mm long (2nos) suitable handle (1no per shutter) complete all as specified and as directed.
S&F powder coated Aluminium grill, 8 to 10mm thick, fixed with separate channel to window/ventilator etc complete all as specified and as directed. Make-DECO grill Cat No. DG-104
S&F stainless steel wire cloth 0.36mm nominal dia of wire and average width of aperture 1.40mm and fixed with stainless steel wire stapples or powder coated aluminium beading complete all as specified and directed.
S&F 300mm long Stainless steel sliding door bolt, stove with SS bright belt not less than 12mm dia with and incl a minimum of 6 bolts and nuts four on belt plate and two on stapple plate complete all as specified and directed.
M&L for two coats of synthetic enamel paint over a coat of pink primer on new wooden surfaces width or girth exc 10cm including preperation of surfaces complete all as specified and directed.
Providing and fixing 20 mm nominal outer dia (for internal and concealed work) chlorinated polyvinyl Chroride (CPVC) pipes SDR 11 having thermal stability for hot and cold water supply including all CPVC plain and brass threaded fittings, including fixing the pipewith clamps at 1.00m spacing. This includes jointing of pipes and fittings with one step CPVC solvent cement and testing of joint complete as per direction of Engr-in-Charge Note: Rate included for cutting chasing and making good.
S&F GI tube 20 mm bore medium grade with all fittings and fixed complete to walls or laid in floorscomplete all as specified and as directed.
S&F Salt glazed stone ware pipes laid and jointed complete with collars ware drain pipes laid in trenches and jointed internal dia of pipe150 mm complete all as specified and directed.
M&L for cement concrete bed to drain pipes in PCC 1:3:6 type C-2 (using 40 mm graded crushed stone agg) incl packing under, and haunching against the sides of of pipe 150 mm dia complete all as specified and directed.
M&L for 40mm thick 1:2:4 type B-0 using 12.5 mm graded crushed stone aggregate as in damp proof course to horizontal or vertical surfaces including necessary form work complete all as sepcifed and as directed.
S&F sheet glass shelf assembly consisting of 5.5mm thick sheet glass shelf 12 cm wide with chromium plated bracket guard and railing 60 cm long complete all as specifed and as directed.
M&L for 15mm thick wear proof topping as specified (incorporating an approved metallic floor hardner), laid on concrete floors and pavings and finished even and smooth except mettlic hardner complete all as specified and as directed.
Supply only metalic hardner complete all as specified and as directed
S&F 22 mm wide Aluminium dividing strip 1.5mm thick and insert in position to confirm to design complete all as specified.
Material and labour for earthing complete with gavanised steel earth plate electrode 60 cm x 60 cm x 6.3 mm thick burried directly in ground ( earth pit not less than 2.25 Mtrs below gorund level) with top edge of the plate not less than 1.5mtr beolw normal ground level, connected to galvanised earth strip 32 x 6mm size upto a distance of 7.5 mtr long by means of bolts , check nuts and washers of galvnised iron or steel all as shown in electrical plate no 5 connected to earthing test point all as specified and indicated and testing complete including execvation earth work drilling holes for electrode PCC pit & cover , funnel , water pipe , lugs etc.
Supply , laying, testing and comissioning cable XLPE insulated screened, PVC bedded galvanised steel strip or wire amoured, electric power cable heavy duty with standard aluminimum conductor 1100 Volt grade of size 3.5 Core, 240 Sqmm.
Supply , laying, testing and comissioning cable XLPE insulated screened, PVC bedded galvanised steel strip or wire amoured, electric power cable heavy duty with standard aluminimum conductor 1100 Volt grade of size 3.5 Core, 120 Sqmm.
Supply , laying, testing and comissioning cable XLPE insulated screened, PVC bedded galvanised steel strip or wire amoured, electric power cable heavy duty with standard aluminimum conductor 1100 Volt grade of size 3.5 Core, 95 Sqmm.
Supply , laying, testing and comissioning cable XLPE insulated screened, PVC bedded galvanised steel strip or wire amoured, electric power cable heavy duty with standard aluminimum conductor 1100 Volt grade of size 3.5 Core, 70 Sqmm.
Supply , laying, testing and comissioning cable XLPE insulated screened, PVC bedded galvanised steel strip or wire amoured, electric power cable heavy duty with standard aluminimum conductor 1100 Volt grade of size 3.5 Core, 50 Sqmm.
Supply, laying, testing and comissioning cable XLPE insulated screened, PVC bedded galvanised steel strip or wire amoured, electric power cable heavy duty with standard aluminimum conductor 1100 Volt grade of size 3.5 Core, 35 Sqmm.
Supply, laying, testing and comissioning cable XLPE insulated screened, PVC bedded galvanised steel strip or wire amoured, electric power cable heavy duty with standard aluminimum conductor 1100 Volt grade of size 4 Core, 25 Sqmm.
Supply and installation, testing, commissioning outdoor type feeder piller Box made out of 3.15 mm thick CRCA sheet , 415 Volt, 3 phase , 50 HZ supply factory made & MS angle section 40 x40x 5mm frame with front and back openable double door with provision of locking arrangement dust & varmin proof , gasket,Aluminium 400 Amp TP busbar & 400 Amp for Neutral shall be insulated with colour coated heat shrinkable sleeves and shall be mounted on proper insulator, gland, welding hinges of dust proof duly spray painted inside and outside of panel with one coat of red oxide primer and two coat of synthetic enamel paint grey complete all as specifed and directed & Connisting of the following equipments:- (i) MCCB , 4 Pole , 25 KA , 250 Amp -01 No ( Incomming) (ii) MCCB , 4 pole , 16 KA, 200 Amps -01Nos (iii) MCCB , 4 pole , 16 KA, 100 Amps -02Nos (IV) single Multifuction meter RE485 Port -6436 -01 Nos, MAKE- Schneider/Siemens/Socomec) (v) Indication Lamp 22.5 mm dia LED type 240Volts AC to show three phase availability- 01 set MAKE : L & T/Secure/Conserv (vi) Solid aluminium bus bar 400 Amp for 3 phase , 400 Amp for neutral (vii) PCC and block Mesonry work for grouting of panel complete all as specified and directed by Engg-in-charge.
Supply and installation, testing, commissioning outdoor type feeder piller Box made out of 3.15 mm thick CRCA sheet , 415 Volt, 3 phase , 50 HZ supply factory made & MS angle section 70 x70x 5mm frame with front and back openable double door with provision of locking arrangement dust & varmin proof , gasket,Aluminium 1200 Amp TP busbar & 1200 Amp for Neutral shall be insulated with colour coated heat shrinkable sleeves and shall be mounted on proper insulator, gland, welding hinges of dust proof duly spray painted inside and outside of panel with one coat of red oxide primer and two coat of synthetic enamel paint grey complete all as specifed and directed & Connisting of the following equipments:- (i) ACB 1000 Amp , 4 Pole , 50 KA -01 No ( Incomming) (ii) ACB 630 Amp, 4 Pole , 50 KA - 01 No (iii) MCCB , 4 pole , 35 KA, 400 Amps -02Nos (iv) MCCB , 4 pole , 25 KA, 200 Amps -02Nos (v) MCCB , 4 Pole , 16 KA, 160 Amps - 02 Nos (vi) single Multifuction meter RE485 Port -6436 -01 Nos, MAKE- Schneider/Siemens/Socomec) (vii) Indication Lamp 22.5 mm dia LED type 240Volts AC to show three phase availability- 01 set MAKE : L & T/Secure/Conserv (viii) Solid aluminium bus bar 1200 Amp for 3 phase , 1200 Amp for neutral (ix) PCC and block Mesonry work for grouting of panel complete all as specified and directed by Engg-in-charge.
Supply and installation, testing, commissioning outdoor type feeder piller Box made out of 3.15 mm thick CRCA sheet , 415 Volt, 3 phase , 50 HZ supply factory made & MS angle section 70 x70x 5mm frame with front and back openable double door with provision of locking arrangement dust & varmin proof , gasket,Aluminium 1000 Amp TP busbar & 1000 Amp for Neutral shall be insulated with colour coated heat shrinkable sleeves and shall be mounted on proper insulator, gland, welding hinges of dust proof duly spray painted inside and outside of panel with one coat of red oxide primer and two coat of synthetic enamel paint grey complete all as specifed and directed & Connisting of the following equipments:- (i) MCCB 630 Amp, 4 Pole , 50 KA - 01 No (Incomming) (ii) MCCB , 4 pole , 35 KA, 400 Amps -01Nos (iii) MCCB , 4 pole , 25 KA, 250 Amps -03Nos (iv) MCCB , 4 Pole , 16 KA, 160 Amps - 04 Nos (v) MCCB , 4 Pole , 16 KA, 100 Amps - 02 Nos (vi) single Multifuction meter RE485 Port -6436 -01 Nos, MAKE- Schneider/Siemens/Socomec) (vii) Indication Lamp 22.5 mm dia LED type 240Volts AC to show three phase availability- 01 set MAKE : L & T/Secure/Conserv (viii) Solid aluminium bus bar 1000 Amp for 3 phase , 1000 Amp for neutral (ix) PCC and block Mesonry work for grouting of panel complete all as specified and directed by Engg-in-charge.
Supply and installation, testing, commissioning outdoor type feeder piller Box made out of 3.15 mm thick CRCA sheet , 415 Volt, 3 phase , 50 HZ supply factory made & MS angle section 40 x40x 5mm frame with front and back openable double door with provision of locking arrangement dust & varmin proof , gasket,Copper400 Amp TP busbar & 400 Amp for Neutral shall be insulated with colour coated heat shrinkable sleeves and shall be mounted on proper insulator, gland, welding hinges of dust proof duly spray painted inside and outside of panel with one coat of red oxide primer and two coat of synthetic enamel paint grey complete all as specifed and directed & Connisting of the following equipments:- (i) MCCB , 4 Pole , 25 KA , 200 Amp -01 No ( Incomming) (ii) MCCB , 4 pole , 16 KA, 100 Amps -02Nos (iii) Space for MCCB -01 Nos (vi) Indication Lamp 22.5 mm dia LED type 240Volts AC to show three phase availability- 01 set MAKE : L & T/Secure/Conserv (vii) Solid aluminium bus bar 600 Amp for 3 phase , 400 Amp for neutral (viii) PCC and block Mesonry work for grouting of panel complete all as specified and directed by Engg-in-charge.
Supplying, installation, testing and commissioning 100 KVA Servo controlled voltage stabilizer in sheet steel ventilated natural oil cooled construction (complete with first filling of transformer oil) having construction is in such a manner that all the 3 units of single phase line voltage stabilizers connected in star. The set shall cater for unbalanced load and unbalance supply provided the input voltage between any phase and neutral and output current in any phase shall be with in limits as specified below including necessary foundation with block masonry work complete all as specified and as directed: - I/P Voltage : 320V-480B, 3 Phase, unbalance I/P Frequency : 47-53 Hz O/P Voltage : 415V ± 1%, 3 Phase,50 Hz O/P should be star connected as per is 9815 O/P Adjustment : ± 5% of Rated O/P O/P Voltage accuracy : Better than + 1% Rating : 100 KVA at UPF Load : Unbalance Speed of correction : 8 V / Sec (Ph-Ph) Efficiency : Better than 96% Waveform distortion : Nil Effect of load : Nil Environment : Indoor tropical use Ambient : 0-50 Deg. C. Material for windings : Copper The Servo controlled voltage stabilizer shall also have following additional features: Full solid state control circuit, No effect ON load Power factor, Auto/manual operation facility, Tripping indication : High/Low I/P voltage tripping with overload /short circuit tripping facility, By pass arrangement with changes over switch, Audio visual alarm circuit, Indicator for I/P/O/P Volt O/P Amp frequency meter Digital/Analog.
Supplying, installation, testing and commissioning 200 KVA Servo controlled voltage stabilizer in sheet steel ventilated natural oil cooled construction (complete with first filling of transformer oil) having construction is in such a manner that all the 3 units of single phase line voltage stabilizers connected in star. The set shall cater for unbalanced load and unbalance supply provided the input voltage between any phase and neutral and output current in any phase shall be with in limits as specified below including necessary foundation with block masonry work complete all as specified and as directed: - I/P Voltage : 320V-480B, 3 Phase, unbalance I/P Frequency : 47-53 Hz O/P Voltage : 415V ± 1%, 3 Phase,50 Hz O/P should be star connected as per is 9815 O/P Adjustment : ± 5% of Rated O/P O/P Voltage accuracy : Better than + 1% Rating : 200 KVA at UPF Load : Unbalance Speed of correction : 8 V / Sec (Ph-Ph) Efficiency : Better than 96% Waveform distortion : Nil Effect of load : Nil Environment : Indoor tropical use Ambient : 0-50 Deg. C. Material for windings : Copper The Servo controlled voltage stabilizer shall also have following additional features: Full solid state control circuit, No effect ON load Power factor, Auto/manual operation facility, Tripping indication : High/Low I/P voltage tripping with overload /short circuit tripping facility, By pass arrangement with changes over switch, Audio visual alarm circuit, Indicator for I/P/O/P Volt O/P Amp frequency meter Digital/Analog.
M&L for Boring holes 2 m deep in soil for under-reamed piles and getting out and disposal of spoil to a distance of n exc. 50 m including HDPE pipe of 200 mm dia suitable for 0.4 mpa working pressure complete all as directed by Engineer-in-charge
Supply Installation Testing & Commissioning of copper pipes of following sizes which shall be drawn half hard temp., solid drawn, seamless, phosphorous deoxidized, non-arsenic and degreased copper pipe conforming to EN 13348: 2001 and chemical composition as per BS-6017 of 1981 table 2 The supplies of copper pipe would be accompanied with manufacturers test certificate for the physical properties of copper pipes and their Chemical composition. The supply of pipes be further substantiated with inspection certificate from the third party like SGS/Lloyds Register.
28mm x 0.9mm
Isolation ball valve with both sides end fittings for following pipe sizes-
Supply, assembly and erection of GI sheet with C & SS rectangular/square duct made out of 'L' shaped hollow profile, duly factory boxed, including all accessories such as Corner, Cleat, Carriage bolt, Gasket and appropriate sealant on longitudinal joints etc complete including necessary MS Channels, gurder supports as approved by Engg -in-charge including making of hole in any type of wall and making good with plastering work, mesonary work and necessary MS channel supports complete all as specified and directed for the following sizes:-
22 Gauge.
Supply and fix cable jointing kit for 11 KV grade cable for in door termination, heat shrink type, joint complete with jointing material and accessories suitable for3 core XLPE, armoured, Al conductor cable of size 95 sqmm Note :- The joniting material like long sleeve for RMU connection and other connected items will incluive in above rate )
Supply and fix cable jointing kit for 11 KV grade cable for outdoor termination , heat shrink type, joint complete with jointing material and accessories suitable for 3 core XLPE, armoured, Al conductor cable of size 95 sqmm Note :- The joniting material like long sleeve for RMU connection and other connected items will incluive in above rate )
Supply and fix cable jointing kit for 11 KV grade cable for straight through Heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE, armoured, Al conductor cable of size 50 Sqmm to 95 sqmm, Indoor/Outdoor type
Material & labour for GI steel tubing light grade for protection of cable/ earth continuty conductor fixed to poles/ walls/ roof or laid in floors, road, crossing or ducts fixed with clamps , bolts nuts and wahser etc complete all as specified and directed of pipes of size 80mm dia.
Supply, laying, testing and comissioning cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty)with stranded aluminium conductor, 11000 volts grade 95 Sqmm 3 core.
Supply, installation, testing and commissioning 500 KVA, 11/0.433KV, AN, Oil Type Transformer with corrugated off circuit tap links of rating +5 to - 5% @2.5 %.by means of hand operated off load tap changing gear 500 kVA capacity transformer copper wound step down outdoor type, 11000/433 Volt (at no load), double wound, oil immersed naturally cooled with external cooling tubes, core type delta connected on primary side (HV) and star connected on secondary side(LV) in accordance with vector symbol Dy-II (vector group) with neutral brought on secondary side (LV side) and having tapping changing at + /-7.5% in step of +/- 2.5 %, to be changed and the maximum temperature rise shall not exceed 45 degree centigrade in oil and 55 degree centigrade in HV/LV winding when measured by resistance method after continuous full load run in ambient temp of 40 degree centigrade and the transformer shall be comprised with the following standard fittings including necessary foundation with block masonry work complete all as specified and as directed with following specifications specified in Srl No 1.01 here-in-after:- Note:- Transformer shall be double copper wound (Level -03) as per IS : 1180 (Part -1) 2014 with HT, LT cable Box.
(i) Pressure Release Valve (ii) Thermometer pocket on tank cover (iii) Oil temperature indicator with 2 contacts alarm & trip (iv) Rating plate with terminal marking (v) Two earthing terminals on tank and cover to facilitate fixing of GI earth strip (vi) Oil level gauge (vii) Oil drain filter valve (viii) Lifting lugs (ix) Oil filter hole with cap/plug including connection complete (x) Four plain solid cast steel detachable rollers (xi) First fill of transformer oil confirming to relevant IS and testing up to 60 KV di-electric strength (xii) PCC Foundation with block masonry & Plaster work as per manufacturer's instruction and as directed.
Supply, installation, testing and commissioning 11 KV, 630 Amps, outdoor type Compact switch gear Ring Main unit, Extensible type, having 02 Nos. Load Break Switches and 01 No Vacuum circuit breaker, all Manual Operated modules with IP class as IP 54, for outer door separately , inside the RMU there shall be an additional cable door with IP3X and Mimic of IP2X and necessary PCC foundation work as per manufacturer's instructions, along with bottom cable entry and front cable termination complete all as specified and as directed with following accessories & specification specified in Srl No 26.01 to 26.06 here-in-after:-
(A) 630A manual Load Break Switch module for making of fault current along with Earth Switch of full making capacity - 2 Nos. Short time withstand current - 21KA/ 3 sec Making Capacity - 52.5kAp Auxiliary contacts - 1NO + 1NC Power frequency withstand voltage - 28kV Impulse withstand voltage - 75kVp Nominal operating gas pressure - 1.4 Bar abs. Front cover mechanism - IP2X Cable covers - 3X Snap action mechanism for manual operation Cable box for front termination of the cable suitable up to 3 core 300 Sqmm, 11 KV XLPE cable Right angle non-touch proof Termination boots - 1 Set (R,Y,B) Set of 03 Nos. Ring Core Metering CTs 40-80/1A as per feeder load, 2.5VA, Class 1.0
(B) 630A manual VCB module for making & breaking of fault current along with Earth Switch of full making capacity -1 No Manual operated 630 A Vacuum circuit breaker having spring stored mechanism. Three position disconnector/earthing switch downstream vacuum circuit-breaker. Three position single spring mechanism for disconnector/earthing switch “Live Cable” LED Indicators thru Capacitor Voltage Dividers mounted on the bushings. Short time breaking current - 21KA/ 3 sec Making Capacity - 52.5 kAp Auxiliary contacts - 1NO + 1NC Power frequency withstand voltage - 28KV Impulse withstand voltage - 75kVp Nominal operating gas pressure - 1.4 Bar abs. Front cover mechanism - IP2X Cable covers - 3X Green(ON)/Red(OFF) push buttons to operate VCB. 3O/C + 1E/F self powered numerical protection relay with Low and High set for Over current and Earth Fault. Mechanical ON/OFF/EARTH/Spring charge Indication Cable boxes should be Arc Proof interlocked with respective Earthing Switches. Right angle non-touch proof Termination boots - 1 Set (R,Y,B)
Stored energy mech. for manual operation - 01 Nos Set of 03nos. Ring Core Protection CTs of ratio 40-80A/1A as per feeder load, 2.5VA, 10P10 - 01 Set Capacitive voltage indication fixed type VPIS 6-12 kV - 01 Nos
• R-Y-B Phase Indication Set of Coupling bus bars along with suitable coupling kit.- 01 Nos Manometer- 01 Nos Operating handle - 01 Nos
Notes for item No 114.00:- (a) RMU Tank shall be IAC AFL 20kA/1s tested to ensure utmost operator safety .Test report (from an STL member Lab) shall be submitted along with drawings of the RMUs . In case the test report is not found suitable , the RMU shall stand liable to be rejected. (b) The Vacuum Bottle shall be of same make as that of RMU to ensure better life cycle optimization for the RMU. (c) Additional items like Operating handle etc. shall be delivered with the RMU (d) RMU tank shall be of 304 grade, Non-magnetic, Non-ferrite Stainless Steel. Inferior Grade of Steel shall not be acceptable. (e) RMU shall have site replaceable bushings for ease of trouble shooting at site and quick repair and restoration at site. (f) Earth switch shall be on line side and shall have making capacity. (g) The Quoted rates for RMU shall be inclusive of making Platform as per OEM instructions, made with bricks and necessary PCC at Bottom and Top and plastering complete all as directed.
Supply, installation, testing and commissioning 11 KV, 630 Amps, outdoor type Compact switch gear Ring Main unit, Extensible type, having 02 Nos. Load Break Switches and 01 No Vacuum circuit breaker, all Manual Operated modules with IP class as IP 54, for outer door separately , inside the RMU there shall be an additional cable door with IP3X and Mimic of IP2X and necessary PCC foundation work as per manufacturer's instructions, along with bottom cable entry and front cable termination complete all as specified and as directed with following accessories & specification specified in Srl No 27.01 to 27.06 here-in-after:- NOTE :- Contractor should responsible for couple RMU as consider in item ser no 114 . Necessary coupling attachments and accessories will be supply, fix, testing and commissioning by the contractor and rates for the same should inclusive in quoted rate.
(A) 630A manual Load Break Switch module for making of fault current along with Earth Switch of full making capacity - 2 Nos. Short time withstand current - 21KA/ 3 sec Making Capacity - 52.5kAp Auxiliary contacts - 1NO + 1NC Power frequency withstand voltage - 28kV Impulse withstand voltage - 75kVp Nominal operating gas pressure - 1.4 Bar abs. Front cover mechanism - IP2X Cable covers - 3X Snap action mechanism for manual operation Cable box for front termination of the cable suitable up to 3 core 300 Sqmm, 11 KV XLPE cable Right angle non-touch proof Termination boots - 1 Set (R,Y,B) Set of 03 Nos. Ring Core Metering CTs 40-80/1A as per feeder load, 2.5VA, Class 1.0
(B) 630A manual VCB module for making & breaking of fault current along with Earth Switch of full making capacity -1 No Manual operated 630 A Vacuum circuit breaker having spring stored mechanism. Three position disconnector/earthing switch downstream vacuum circuit-breaker. Three position single spring mechanism for disconnector/earthing switch “Live Cable” LED Indicators thru Capacitor Voltage Dividers mounted on the bushings. Short time breaking current - 21KA/ 3 sec Making Capacity - 52.5 kAp Auxiliary contacts - 1NO + 1NC Power frequency withstand voltage - 28KV Impulse withstand voltage - 75kVp Nominal operating gas pressure - 1.4 Bar abs. Front cover mechanism - IP2X Cable covers - 3X Green(ON)/Red(OFF) push buttons to operate VCB. 3O/C + 1E/F self powered numerical protection relay with Low and High set for Over current and Earth Fault. Mechanical ON/OFF/EARTH/Spring charge Indication Cable boxes should be Arc Proof interlocked with respective Earthing Switches. Right angle non-touch proof Termination boots - 1 Set (R,Y,B)
Stored energy mech. for manual operation - 01 Nos Set of 03nos. Ring Core Protection CTs of ratio 40-80A/1A as per feeder load, 2.5VA, 10P10 - 01 Set Capacitive voltage indication fixed type VPIS 6-12 kV - 01 Nos
• R-Y-B Phase Indication Set of Coupling bus bars along with suitable coupling kit.- 01 Nos Manometer- 01 Nos Operating handle - 01 Nos Notes for item No 115.00:- (a) RMU Tank shall be IAC AFL 20kA/1s tested to ensure utmost operator safety .Test report (from an STL member Lab) shall be submitted along with drawings of the RMUs . In case the test report is not found suitable , the RMU shall stand liable to be rejected. (b) The Vacuum Bottle shall be of same make as that of RMU to ensure better life cycle optimization for the RMU. (c) Additional items like Operating handle etc. shall be delivered with the RMU (d) RMU tank shall be of 304 grade, Non-magnetic, Non-ferrite Stainless Steel. Inferior Grade of Steel shall not be acceptable. (e) RMU shall have site replaceable bushings for ease of trouble shooting at site and quick repair and restoration at site. (f) Earth switch shall be on line side and shall have making capacity. (g) The Quoted rates for RMU shall be inclusive of making Platform as per OEM instructions, made with bricks and necessary PCC at Bottom and Top and plastering complete all as directed.
Notes for item No 115.00 (Contd...): - (h) The Quoted rates for RMU shall be inclusive of making Platform as per OEM instructions, made with bricks and necessary PCC at Bottom and Top and plastering complete all as directed by Engr-in-Charge.
Supply, installation, testing and commissioning Diesel Engine driven generating set of 400 KVA capacity, 3 phase, 4 wire, 415 V, 1500 RPM, AC power supply with power factor 0.8, coupled directly to alternator, mounted on a common base plate complete with integral acoustic enclosures (shall have salient features) modular bolted construction & pure polyester based coating to ensure long life in all weather conditions & for outdoor application / installation, integrated design thereby facilitating / easy handling. The design of integral acoustic enclosure shall be approved by National Physical laboratory as per central pollution control board (CPCB) latest regulation / norms with fuel tank, battery & standard accessories, tools & spares as provided by manufacturer complete with necessary PCC foundations including excavation and earth work with block measonary work and plastering complete with following specifications specified in Srl No 28.01 to 28.07 here-in-after complete all as specified and as directed:-
(A) ENGINE- Water cooled diesel engine at 1500 RPM, of capacity to match the 400 KVA alternator under NTP conditions with provision of 10 % over load for 1 hour in every 12 hours running confirming to BS 5514/ IS 10001/ 10002. The Engine shall consist of the following:-
(a) Fly wheel with starter ring (b) Flexible coupling with guard (c) Cooling fan (d) Radiator with guard and water pump engine mounted (e) Dynamo of suitable capacity (f) Air cleaner heavy duty dry (g) Fuel injection pump (h) Radiator fan (Blower type) with guard (j) Electronic governor (k) Fuel filter (Mounted) (l) Lubricating oil filters (mounted) (m) 24 v self regulating alternator belt driven by engine (n) Exhaust silencer heavy duty residential type (o) Corrosion resistor /scale inhibitor (p) Starter 24 V DC (q) Lubricating oil cooler (r) Lubricating oil pump (Gear type ) (s) Turbo charger (t) Exhaust piping shall be insulated with asbestos rope duly cladded with aluminium sheet.
(u) Instrument panel complete with :- (v) Auto manual Starting switch with key (w) Lubricating oil temperature gauge (x) Lubricating oil pressure gauge (y) Water temperature gauge (z) Battery charging ammeter (aa) Battery charging indicating lamp (ab) Hour meter with RPM indicator (ac) Safety control against high temperature of water. (ad) Safety control against low lubricating oil pressure . (ae) Over speed stop with double driven adopter.
(B) BRUSH LESS ALTERNATOR (i) Alternator coupled to engine indigenous make through a flexible coupling mounted on sturdy steel fabricated base frame suitable for mounting on a permanent foundation brushless alternator shall be confirming to BS -2613 or relevant of IS-4722/ IS 13364. (ii) Type :- Self excited self regulated with automatic voltage regulator. (iii) Rating :- 400 KVA at 0.8 PF lagging 4 pole horizontal at NTP condition. (iv) Speed :- 1500 RPM (v) System :- 415 V +/- 2.5 % AC 3 phase 4 wire 50 Hz. (vi) Connection :- 4 wire star connected. (vii) Enclosure :- Screen protected drip proof. (viii) Ventilation :- Self ventilated. (ix) Insulation :- Insulation class H
(C) CONTROL PANEL The control panel with aluminium bas bar, bottom entry and exit of cable, current transformer, set of control fuses, Multifunctional Meter, it should display time and date, Volts, Frequency, Current, KW, KWH, PF, RPM, Cumulative Run Hours, Oil Pressure, Coolant Temp, Charging current (DC Amp Meter). Emergency off, factory made floor mounted, totally enclosed, epoxy powder coated suitable for 400 KVA DG Set including all necessary operating controlled devices as stated above and MCCBs as out going with protection fuse for panel instruments duly wired with flexible copper conductor cable and cable connection with lugs/thimbles complete as per latest IS/BS complete all as specified and directed.
(D) ONE SET OF ACCESSORIES COMPRISING OF:- (a) Fuel tank - Capacity of tank shall be to hold diesel sufficient for 08 hours running at full load, with following features: (i) Level indicator. (ii) drain plug . (iii) MS class 'C' piping for inlet from pump to tank to engine. (iv) Fuel strainer. (v) Air vent. (B) Sealed maintenance free Battery :- Heavy duty battery two nos 24 plates 12 v 180 AH (02 Nos) connected to the system fully charged including lead and battery terminal's complete . (d) Base plate :- Fabricated out of MS channel's ISMC of suitable size suitable for fixing of DG set all specified by the manufacturer.
E) AMF PANEL:- Supply, fixing, testing and commissioning Auto main failure (AMF) panel, outdoor type made out of 3.15 MM thick CRCA sheet, double door type fix on trolly mounted plate form for 400 KVA DG Set totally enclosed dust and water proof duly painted with powder coated, fully wired up and ready to connect load & control lines in comprising the followings:- (a) Indication lamp LED type Green (IL1) - 01 No. b) Indication Lamp LED type Green (IL2) - 01 No. c) Control Supply ON/OFF switch (TS1) - 01 No. d) Canopy light ON/OFF Toggle switch (TS2) - 01 No. e) Generator Controller Unit (GCU) - 01 No f) Power contactor, AC-01 Duty, With Wide Band Coil ( 230AC), 2 NO + 2 NC Auxiliary contacts - 01 NO g) Fuse link - 02 Set h) Fuse Holder & Base - 02 Set i) Current transformer - 03 Nos j) DC Ammeter - 01 No k) Hotter – 01 No. l) HTR, CFAR, GCR & MCR Relay - 01 Set m) Glass fuse holder - 08 Nos. n) Glass Fuse - 07 Nos (o) Battery Charger - 01 NO (p) Control Terminals - 02 Nos (q) Miniature Circuit Breaker ( MCB) - 01 No (r) Aluminium Busbar 40 x 10 mm - 01 set (s) Control Connector - 03 Nos (t) ECD Card - 01 No (u) Control Connector with suitable terminals - 01 Set
Material and labour for river washed and screened, dry sand for filling in trenches below and around underground cables for cushioning of cables etc, complete all as specified.
S&F sub class B bricks having minimum compressive strength 75 Kg/ Sqcm laid in trenches for cable protection etc complete all as directed by Engineer-in-Charge.
Supply, laying, testing and comissioning cable XLPE insulated screende, PVC bedded flexible electric power cable heavy duty with copper conductor 1100 Volt grade of size 3.5 Core , 35 Sqmm
Supply, laying, testing and comissioning cable XLPE insulated screende, PVC bedded flexible electric power cable heavy duty with copper conductor 1100 Volt grade of size 3.5 Core , 25 Sqmm
Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required 4 mm dia galvanised iron or steel wire all as specified and directed by Engg -in-charge.
All as item Srl item No 102.00 here-in before but earthing strip 25x4mm galvanised iron strip
Material and labour for earthing complete with copper earth plate electrode 60 cm x 60 cm x 3.15 mm thick burried directly in ground ( earth pit not less than 2.25 Mtrs below gorund level) with top edge of the plate not less than 1.5mtr beolw normal ground level, connected to Copper earth strip 20 x 3 mm size upto a distance of 7.5 mtr long by means of bolts , check nuts and washers of galvnised iron or steel all as shown in electrical plate no 5 connected to earthing test point all as specified and indicated and testing complete including execvation earth work drilling holes for electrode PCC pit & cover , funnel , water pipe , lugs etc.
Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required 20x 3 copper strip all as specified and directed by Engg -in-charge.
Steel Tubes, 'light grade' galvanised, with all fitting and fixed complete to walls and ceilings or laid in floors all as specfied and directed by Engg -in-charge.
15 mm bore
40 mm bore
50 mm bore
80 mm bore
M&L shade covering with galvanised, corrugated mild steel sheeting of thickness 0.80mm with two corrugations of side lap, fixed with L type and J type hook and washers, in roofs wall with grade of zinc coating 275 complete all as specified and directed.
Boring of holes under road pavement hard standing by trenchless technology With manual boaring technologly 80 mm dia bore including incerting 80 mm dia GI tubing medium grade all as specified and directed by Engg -in-charge
Supply and fix HT route indicator made out of cast iron plate 80 mm dia emborcing with MES HT cable 11000 volt fixed on MS channel 40 x40 x 5mm , 3 ft height duly painted with one coat of red oxide primer and two coat of synthetic enamel paint fixed 1 ft of Angle inside ground with concrete 1:2:4 squre in shape all as specified and directed by Engg -in-charge
Supply and fix LT route indicator made out of cast iron plate 80 mm dia emborcing with MES HT cable 1100 volt fixed on MS channel 40 x40 x 5mm , 3 ft height duly painted with one coat of red oxide primer and two coat of synthetic enamel paint fixed 1 ft of Angle inside ground with concrete 1:2:4 square in shape all as specified and directed by Engg -in-charge
Shifting of Trasnformer 400 KVA from power house to CPL lab Appx distance 2.5 Km with necessary T & P, Manpower and transport vehical making necessery plat form 3 Ft Height, 6 ft width & 6 Ft length with use of Brick, Mourm filling and necessary plastering around platform wall , Contractor should cast PCC layer of 30 mm thick on top of plat form with ratio of 1:2:4 all as specified and directed by Engg-in-charge.
Supply, laying, testing and comissioning cable XLPE insulated screened, PVC bedded galvanised steel strip or wire armoured, electric power cable heavy duty with stranded aluminium conductor 1100 Volt grade of size 630 Sqmm single core complete all as specified and as directed.
Supply, laying, testing and comissioning XLPE insulated screened, PVC bedded galvanised steel strip or wire armoured, electric power cable heavy duty with stranded aluminium conductor 1100 Volt grade of size 400 Sqmm single core complete all as specified and as directed.
M/s JAIMAA ASSOCIATES
AMIT ASSOCIATES
M/s VINOD KUMAR SHARMA
SANJEEV ENTERPRISES
V r traders
M/s R. K. Bhambri
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .