Superintending Engineer
Office of the Superintending Engineer, Western Electrical Circle , PWD, Purta Bhavan, 1st floor, Burdwan-713103
Construction of Multistoried building at Tertiary Cancer Care Centre (TCCC) at Burdwan Medical College and Hospital, Purba Bardhaman. -- SITC of Fire Detection System in AC plant Zone..
2022_WBPWD_408044_1
WBPWD/SEWEC /BED /NIQ-31/2021-22-2nd Call
Open Tender
ELECTRICAL WORKS ORG
Item Rate
45 days
Purba Bardhaman
Please refer Tender documents.
5 documents required · 5 mandatory
₹31,000
Office of the Superintending Engineer, Western Ele
16 Dec 2022
19 Sept 2022
7 Dec 2022
19 Sept 2022
5 Dec 2022
23 Sept 2022
19 Sept 2022 - 22 Sept 2022
22 Sept 2022
Amount
Supply, Installation, Testing & Commissioning of Microprocessor controlled. IP Addressable Multi-sensor detector IP 54 (VDS / UL /ERTL/ LPCB / FM approved) with inbuilt optical smoke Sensors and heat detector sensor with inbuilt short circuit fault Isolator as per NFPA style 7 wiring complete with base (Note Detectors without built-in fault isolator is also acceptable Provided one independent short circuit fault isolator per detector is to be provided extra without extra cost) the detectors should have built in response indicator with LED indicator. Thedetector should have 360 degree optical view with single/ multiple LED that blinks on actuation of detector. Reverse polarity or faulty zone wiring shall not damage the detectors. (Approved Make : Cerberus Pro / Johnson Controls/ Edward/ Secutron/Securiton /Honeywell/ Apollo/ Morley/ Eaton/GST/ Ravel)
Supply, Installation, Testing & Commissioning of Microprocessor controlled IP Addressable Heat detector IP 54 ( VDS / UL/ ERTL / LPCB / FM approved ) with combination of fixed type & Rate of Rise of Temperature feature. Detector shall have minimum triggering temperature programmable from 60 deg. C to 80 deg. C., having high level of immunity to electromagnetic influences and show alarm signal limit temperature is reached. Detector shall have inbuilt short circuit fault isolator as per NFPA style 7 wiring complete with base (Note : Detectors without built-in fault isolator is also acceptable provided one independent short circuit fault isolator per detector is to be provided extra without extra cost) the detectors should have built in response indicator with LED indicator. (Approved Make : Cerberus Pro / Johnson Controls/ Edward/ Secutron /Securiton /Honeywell/ Apollo/ Morley/ Eaton/GST/ Ravel)
Supply, Installation,Testing & Commisioning of IP Addressable Manual Call Point ( VDS / UL / ERTL / LPCB / FM approved ) with in built short circuit fault isolator as per NFPA style 7 wiring complete as required. (Approved Make: Cerberus pro/ Johnson Controls/ Edward /Secutron/ Securiton/Honeywell/ Apollo / Morley I Eaton/ GST /Ravel
Supply, Installation, Testing & Commissioning of IP Addressable Loop Powered Hooter (sound output of minimum 90 db ) cum strobe (strength of iight 10 cd) complete with inbuilt short circuit fault isolator. Degree of protection IP 65 ( VDS / UL / ERTL / LPCB / FM approved) approved. (Approved Make: cerberus Pro I Johnson controls / Edward/ Secutron / Securiton/ Honel.wett/ Apotlo / Morley / Eaton/ GST/Ravel
Supply, Installation, Testing & Commissioning of Microprocessor based intelligent, addressable and network connected Repeater panel ( VDS / UL /ERTL/ LPCB/ FM approved), should have all the controls and monitoring as on the main fire alarm panel, functioning as a controller, shall allow remote command in the system reset, trouble and alarm silence and manual alarm. It shall be programmable to display information for the entire system i.e. all panels in the network, having minimum 80 characters LCD display (display system status). The system text displays shall include: Alarm missing point trouble; system test, service, local system test, extra custom test by polling circuit and address. The repeater panel should annunciate alarm and trouble conditions in the occasion of signal actuation. (Approved Make : Cerberus Pro / Johnson Controls/ Edward/ Secutron /Securiton/Honeywell/ Apollo/ Morley/ Eaton/GST/ Ravel)
Supply, Installation, Testing & Commissioning of Addressable Monitor Modules ( VDS / UL /ERTL/ LPCB / FM approved ) for monitoring Flow switches / Fire exit doors / AHU I Lift etc. with inbuilt short circuit fault isolator and minimum (04) four potential free contact with adjustable setting parameter likes of Input or output, complete in single or multiple housing with degree of protection IP 54 with flash LED indicator that conforms module is operational and integrated buzzer signaling maintenance alarm, complete as required. (Approved Make : cerberus pro I Johnson controls/Edward/ secutron/ securiton/ Honeywerl/ Apollo/ Morley/Eaton/GST/Ravel
Supplying, installation, testing and Commissioning of LED type Response indicator (VDS / UL /ERTL/ LPCB/ FM approved) having 2 Nos. red colored LED lamps including connections etc. (Approved Make : Cerberus Pro / Johnson Controls/ Edward/ Secutron/ Securiton /Honeywell/ Apollo/ Morley/ Eaton/GST/ System Sensor /Agni Suraksha / Ravel)
Supply & Laying of 2 Core 1.5 sq.mm FRLS copper Cable (For Loop) (Make. Finolex / Polycab / RR Kable ) with 19 mm dia PVC 'FR' type rigid conduit pipe with necessary aeeangement (Make: Precision/ AKG/ Medium / Polycab) on the surface of the wall.
Supply, Installation, Testing & Commissioning of Microprocessor based addressable fully networkable fire alarm control panel (VDS / UL /ERTL/ LPCB/ FM approved) suitable for the devices as stated in the previous items of this BOQ along with 20% spare capacity with each loop loading not exceeding 80 % of the full capacity of detectors and devices taken together, complying to IS 2189:2008 or its latest amendments, and with minimum 600 character alpha - numeric liquid crystal display The panel shall be soft addressable type and shall be able to give pin point location of all fire/ fault conditions. Further, the panel must be able to automatically switch off respective control switches with help monitor module whenever any alarm is triggered. The Panel should be able to store sufficient numbers of log events in its Memory as per recommended standards.
The panel should have extra loop card slot for expansion of capacity twice. The panel shall have in built rectifier, provision for external & internal printer ( if required ), Loop cards, L C D unit to indicate Fire/Fault Signal with address and analog output, complete in all respects, inbuilt Surge protection facility, integral SMF lead acid batteries with sealed cells of 24V capable of running for 24 hours normal working and then be capable of operating the system for 60 minutes during Emergency condition, with integral battery charger complete in all respect as required. The FACP shall be capable of being networked (future expansion) with other similar FACP located at different part of the premises through single RS 485 modbus. The FACP shall have provision for interfacing with the public address system, remote computer and BMS interface. The system must be preloaded with licensed software. (Approved Make : Cerberus Pro / Johnson Controls/ Edward/ Secutron /Securiton /Honeywell/ Apollo/ Morley/ Eaton/GST/ Ravel)
NOTE :- 1) The Fire Alarm system shall comply with latest requirements of -- (i) National Fire Protection Association (NFPA) standards, (ii) IS 2189 (iii) NFPA 7O National Electric Code, (iv) NFPA 72 National Fire Alarm & Signaling Code (v) Local Statutory Regulations , (vi) Manufacturer Recommendation vii) System should be integrated with the components like FACP, Detectors, MCP, Hooter, Monitor Module, Relay Module, etc. and all these components should be of same brand.
TESTS :- 1) The system shall be tested and commissioned by a qualified competent, trained engineer or technician authorized by the manufacturer of the fire alarm equipment to technically supervise and participate during all of the adjustments and tests for the system. 2) Before energizing the cables and wires, inspection and check for correct connections, and test for short circuits, ground faults, continuity, and insulation and other tests as per applicable Indian/International standards must be done.
TERMS & CONDITIONS:- The Agency must procure the materials from the Manufacturer / OEM or from their authorized sales channel so that the standard warranty / support of the Manufacturer / OEM becomes applicable to the products to be delivered and installed by them. Documents that authenticates such procurement from the Manufacturer / OEM or from their authorized sales channel and standard warranty / support should be sent from the e-mail of the Manufacturer / OEM / authorized sales channel to the email of Engineer-in-Charge and hard copy of it to be submitted during execution, of work/ submission of bill. If any refurbished material is supplied and installed, penal action will be taken as per existing rules
NRD Global
TESLA ENGINEERING SOLUTION
MAGNUM SAFETY INDIA
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .