Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹37.0 LAccepted-Finance | L1 | Accepted-Finance BEING LOWEST | |
| 2 | L2₹37.8 L+₹74,376.90 (2.01%)Rejected-Finance | L2 | Rejected-Finance NOT BEING LOWEST | |
| 3 | L3₹39.3 L+₹2.3 L (6.09%)Rejected-Finance | L3 | Rejected-Finance NOT BEING LOWEST | |
| 4 | L4₹40.4 L+₹3.3 L (8.96%)Rejected-Finance SHOP NO 11 18 CITY CENTRE 930 931 SYNAGOGUE STREET PUNE 01 | L4 | Rejected-Finance NOT BEING LOWEST | |
| 5 | L5₹40.4 L+₹3.4 L (9.07%)Rejected-Finance | L5 | Rejected-Finance NOT BEING LOWEST |
| Sl No | Description | Qty | Unit | Sunhari Electricals L3 | KSP ENTERPRISES L2 | Suchit constructions L8 | M/s Harshal Traders L7 | somnath engineering corporation L10 | MUKTI ENTERPRISES L1 | SHRI PLACEMENT AND CONSULTANCY SERVICES L6 | D H L ENTERPRISES L5 | K K ENGINEERING SERVICES L9 | PROLINK COMPUTERS L4 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1.00 | M & L for Checking/ Testing of resistance value of any type of earth pits by disconnecting earth continuity conductor from test terminal block and reconnecting the earth continuity conductor after testing including watering as and when required and all as specified and directed by Engr-In-Charge.
Note:
(i) Temporary earthing connection to be provided while testing.
(ii) Calibrated Earth tester will be bought by contractor and calibration certificate of Earth tester shall be shall be submitted.
(iii) Earth test results shall be recorded in reference to Earth pit No. WRT Each Bldg.
(iv) If earth test result is not satisfactory , earthing test will be carried out again after maintenance and this will be paid separately.
(v) Earth test to be signed by Rep of contractor, Rep of user section and rep of MES , Test reports to be submitted in triplicate. (vi) All T&P, manpower required is deemed to be inclusive in the quoted rates. (vii) Contractor shall provide water to earthing pits fortnightly. (vii) Water shall be arranged by contractor at his end by external source and shall water earthing pits. (viii) Cost of water, manpower and vehicle needed for watering is included in quoted rate of this item and nothing shall be paid extra. | 1,400 | Each Job | 80 ₹1,12,000 | 75 ₹1,05,000 Lowest | 207 ₹2,89,800 | 160 ₹2,24,000 | 100 ₹1,40,000 | 150 ₹2,10,000 | 88 ₹1,23,200 | 110 ₹1,54,000 | 150 ₹2,10,000 | 210 ₹2,94,000 |
| 2.00 | M&L for maintenance of GI Plate/copper plate earthing to improve the earth resistance as following:-
(a) Remove the earth pit carefully and kept at site for reuse. If existing pit is already damaged then new pit will be provided, measured & paid separately.
(b) Excavation in any type of soil and rock 0.5 cum (approx 0.75m x 0.75m x 0.9m depth )
(c) On First day recharge the earth pit with common salt, Magnisium sulphate,back fill compound mixed with water.(Approx salt- 10 kg, Mg sulphate- 10 kg, Charkol - 10 kg )
(d) On the next day recharge the earth pit with water 500 ltrs on next day.
(e) Excavated material to be removed from the site and deposit at the distance not exceeding 50m distance and levelled.
(f) Refill the pit with M&L for black cotton soil 0.5cum.
(g) Refit the earth pit in place.
(h) Testing of earth ( to be measured and paid separately)
Note:-(i) Common salt, Mg sulphate, Charkol will be measured and paid separately.
. | 45 | Each Job | 800 ₹36,000 | 810 ₹36,450 | 720 ₹32,400 | 1,500 ₹67,500 | 2,000 ₹90,000 | 1,200 ₹54,000 | 880 ₹39,600 | 900 ₹40,500 | 150 ₹6,750 Lowest | 600 ₹27,000 |
| 3.00 | M&L for maintenance of GI plate earthing to improve the earth resistance as following:-
(a) Remove the earth chamber carefully and kept at site for reuse. If existing chamber is already damaged then new chamber will be provided, new chamber will be measured & paid separately.
(b) Excavation in any type of soil and rock 1 Cum (approx 0.75m x 0.75m x 2 m depth )
(c) Taking out GI Earth plate , watering pipe , funnel , earth continuty GI strip, cleaning of GI earth plate and GI strip with wire brush and polish paper , cleaning of GI pipe and funnel and renistall the the same (d) GI strip shall be fitted with GI plate by GI nutbolts - 3 nos and in addition welding to be caried out , weld length between GI plate and GI strip not less than 30 CM on both side of strip (e) On First day recharge the earth pit with charcoal ,common salt, back fill compound mixed with water and black cotton soil (Approx charcoal - 25 KG, salt- 25 kg, Magnisium sulphate - 25 kg , black cotton soil 0.5 Cum
(f) On the next day recharge the earth pit with water 500 ltrs on next day.
(g) Excavated material to be removed from the site and deposit at the distance not exceeding 50m distance and levelled
(h) Refill the pit with M&L for black cotton soil 0.5cum.
(j) Refit the earth chamber in place.
(k) Testing of earth ( to be measured and paid separately)
Note:- charcoal , Common salt, Magnasium salphate will be measured and paid separately.
. | 30 | Each Job | 900 ₹27,000 | 720 ₹21,600 | 1,260 ₹37,800 | 1,500 ₹45,000 | 2,000 ₹60,000 | 1,200 ₹36,000 | 780 ₹23,400 | 780 ₹23,400 | 320 ₹9,600 Lowest | 600 ₹18,000 |
| 4.00 | M&L for maintenance of copper plate earthing to improve the earth resistance as following:-
(a) Remove the earth chamber carefully and kept at site for reuse. If existing chamber is already damaged then new chmber will be provided,new chamber will be measured & paid separately.
(b) Excavation in any type of soil and rock 1 Cum (approx 0.75m x 0.75m x 2 m depth )
(c) Taking out Copper Earth plate , watering pipe , funnel , earth continuty copper strip, cleaning of copper earth plate and Copper strip with wire brush and polish paper , cleaning of GI pipe and funnel and renistall the the same (d) copper strip shall be fitted with copper plate by brass nutbolts - 3 nos and in addition brazing to be caried out , brazing length between copper plate and copper strip not less than 30 CM on both side of strip (e) On First day recharge the earth pit with charcoal ,common salt, back fill compound mixed with water and black cotton soil (Approx charcoal - 25 KG, salt- 25 kg, Magnasium sulphate - 25 kg , black cotton soil 0.5 Cum
(f) On the next day recharge the earth pit with water 500 ltrs on next day.
(g) Excavated material to be removed from the site and deposited at the distance not exceeding 50m distance and levelled .
(h) Refill the pit with M&L for black cotton soil 0.5cum.
(j) Refit the earth chamber in place.
(k) Testing of earth ( to be measured and paid separately)
Note:- charcoal , Common salt, Magnesium sulphate will be measured and paid separately.
. | 35 | Each Job | 1,000 ₹35,000 | 900 ₹31,500 | 1,530 ₹53,550 | 1,500 ₹52,500 | 2,000 ₹70,000 | 1,200 ₹42,000 | 980 ₹34,300 | 980 ₹34,300 | 250 ₹8,750 Lowest | 1,200 ₹42,000 |
| 5.00 | M&L for fixing earth indicators made out of 3 mm thick MS sheet of size 200 mm x 300 mm duly fixed in MS angle iron 25 mm x 25mm of 600 mm long fixed to ground by means and including necessary cement concrete foundation and painting with one coat of synthetic enamel paint over a coat of red oxide primer complete for writing earth reading and connected plant/ panel etc. and excavation and earth work complete all as specified and as directed. | 30 | Each Job | 222 ₹6,660 | 210 ₹6,300 Lowest | 540 ₹16,200 | 600 ₹18,000 | 1,500 ₹45,000 | 300 ₹9,000 | 310 ₹9,300 | 230 ₹6,900 | 450 ₹13,500 | 360 ₹10,800 |
| 6.00 | S&F in repair of test point made out of gun metal or phosphorous bronze of size 75x50x5mm duly mounted on epoxy insulator 02 Nos.Drilling of upper & lower portion of test point for incoming & outgoing connections with brass nut bolt to be fitted in and including terminal blockmade out of M.S sheet 2mm thick as per the sample duly painted with two coat of enamel paint over a coat of red oxide primer. | 30 | Each | 500 ₹15,000 Lowest | 510 ₹15,300 | 1,350 ₹40,500 | 720 ₹21,600 | 500 ₹15,000 Lowest | 800 ₹24,000 | 520 ₹15,600 | 540 ₹16,200 | 760 ₹22,800 | 1,230 ₹36,900 |
| 7.00 | Material and labour for supply, installation, testing and commissioning of copper pipe electrode earthing maintenance free earthing based on 6 mtr long copper pipe 75 mm dia(ID) with wall thickness of 2 mm, copper strip in pipe and filled with MFC for improvement of conductivity of electrode duly fixed with connector at top connection of copper strip 25X3 mm riveted /nut bolt after 12 mm boring and further earth continuity conductor made of copper strip 25x3 mm upto 7.5 meter , 150 KGS BFC shall be filled around the copper pipe elecrode ,including providing earth pit chamber size 450x450x300 mm depth outside & 250x250x300 mm depth of PCC (1:3:6) type C1 complete all as specified and directed by Engr-in-Charge.
Note:- (i) Rate included for testing,commisioning including checking of earth continuity and earth result complete all as specified and directed.
(ii) Vendors are bound to get earthing result less than1 Ohm with grid of three earthings and 2 Ohm with grid of two earthing, 3 ohm with single earthing, Any additional work and material required to achive the required result is included in the cost
(iii) Earth strip beyond 7.5m shall be measured and paid separately.
(iv) Rate is included for boring of earthing in any type of soil/rock,minimum dia of bore 150mm.
(v) Continuity of good earth resistance shall maintained upto 1 year and testing will be carried out monthly by MES authority. | 4 | Each Job | 38,000 ₹1,52,000 | 38,100 ₹1,52,400 | 15,300 ₹61,200 | 35,000 ₹1,40,000 | 12,500 ₹50,000 Lowest | 30,000 ₹1,20,000 | 41,500 ₹1,66,000 | 38,500 ₹1,54,000 | 19,500 ₹78,000 | 36,000 ₹1,44,000 |
| 8.00 | Material and labour for supply, installation, testing and commissioning of GI pipe electrode earthing maintenance free earthing based on 6 mtr long GI pipe 80 mm dia(ID) medium grade, GI strip in pipe and filled with MFC for improvement of conductivity of electrode duly fixed with connector at top connection of GI strip 32X6 mm riveted /nut bolt after 12 mm boring and further earth continuity conductor made of GI strip 32x6 mm upto 7.5 meter , 60 KGS BFC shall be filled around the GI pipe electrode including providing earth pit chamber size 450x450x300 mm depth outside & 250x250x300 mm depth of PCC (1:3:6) type C1 complete all as specified and directed by Engr-in-Charge.
Note:- (i) Rate included for testing,commisioning including checking of earth continuity and earth result complete all as specified and directed.
(i) Venders are bound to get earthing result upto 5 Ohm for single earthings and 3 Ohm with the grid of two earthing.Any additional work and material required to achive the required result is included in the cost quoted by the tenderer.
(iii) Earth strip beyond 7.5m shall be measured and paid separately.
(iv) Rate is included for boring of earthing in any type of soil/rock,minimum dia of bore 150mm.
(v) Continuity of good earth resistance shall maintained upto 1 year and testing will be carried out monthly by MES authority. | 6 | Each | 21,000 ₹1,26,000 | 21,000 ₹1,26,000 | 12,600 ₹75,600 | 15,000 ₹90,000 | 6,500 ₹39,000 Lowest | 15,000 ₹90,000 | 22,700 ₹1,36,200 | 21,500 ₹1,29,000 | 13,500 ₹81,000 | 13,500 ₹81,000 |
| 9.00 | M/L for providing earthing complete with Copper earth plate electrode 600 mm x 600 mm x 3.15 mm thick buried directly in ground earth pit not less than 2.25 Mtr deep below ground level with top edge of the plate not less than 1.5 Mtr below normal ground level connected to copper earth strip 20 x 3 mm by means of bolts, nuts, checknuts & washers of copper and connecting to test point , providing charcoal and common salt ,all as shown in electrical plate No. 5 of SSR Part I of 2009 & as specified or indicated and testing on completion including excavation/earth work in any type of strata PCC ( 1:3:6 ) type C1 earthing chamber, pre cast slab 50 mm thick in cement concrete ( 1: 2 : 4 ) type B1 (reinforced with welded steel wire fabric (XPM) weight not less than 4 Kg / Sqm), funnel with wire mesh, watering pipe of 20 mm bore medium grade and lugs, including copper earth strip 20 x 3 mm with GI protection pipe of 25 mm medium grade 7.5 meter long, etc complete all as specified.
Note-- (i) Vendors are bound to get earthing result upto1 Ohm with grid of three earthings and 2 Ohm with grid of two earthing, 3 ohm with single earthing, Any additional work and material required to achive the required result is included in the cost. (ii) Excavated material to be removed from the site and deposit at the distance not exceeding 50m distance and levelled.
(iii) Refill the pit with M&L for black cotton soil 1 cum. | 12 | Each | 24,000 ₹2,88,000 | 21,000 ₹2,52,000 | 15,300 ₹1,83,600 | 15,000 ₹1,80,000 | 14,500 ₹1,74,000 Lowest | 20,000 ₹2,40,000 | 23,500 ₹2,82,000 | 21,500 ₹2,58,000 | 18,500 ₹2,22,000 | 21,000 ₹2,52,000 |
| 10.00 | M&L for providing earthing complete with galvanised iron earth plate electrode 600 mm x 600 mm x 6mm as earthing lead buried directly in ground vertically to a depth not less than 2.25 Mtr deep below ground level with top edge of the plate not less than 1.5 Mtr below normal ground level connected to and including galvanised iron strip 32x6 mm as earthing lead by means of bolts, nuts, check nuts & washers etc made of GI and connected to earthing test point, providing charcoal and common salt all as shown in electrical plate No. 5 of SSR Part I of 2009 & as specified or indicated and testing on completion including exaction/earth work in any type of strata PCC (1:3:6) type C1 earthing chamber, pre cast slab 50 mm thick in cement concrete (1:2:4) type B1 (reinforced with welded steel wire fabric (XPM) weight not less than 4 Kg/sqm), funnel with wire mesh, watering pipe of 20 mm bore medium grade and lugs, including galvanised iron strip 32x6 mm with GI protection pipe of 40 mm medium grade 7.5 meter long, etc complete all as specified.
Note:- (i) Venders are bound to get earthing result upto 5 Ohm for single earthings and 3 Ohm with the grid of two earthing.Any additional work and material required to achive the required result is included in the cost quoted by the tenderer.(ii) Excavated material to be removed from the site and deposit at the distance not exceeding 50m distance and levelled.
(iii) Refill the pit with M&L for black cotton soil 1 cum. | 15 | Each Job | 4,500 ₹67,500 | 4,500 ₹67,500 | 6,003 ₹90,045 | 5,400 ₹81,000 | 6,500 ₹97,500 | 4,000 ₹60,000 Lowest | 4,700 ₹70,500 | 6,500 ₹97,500 | 16,500 ₹2,47,500 | 4,800 ₹72,000 |
Tender Value
₹40 L
EMD Value
₹80,000
Closing Date
30 Sept 2025, 6:00 pmClosed
Garrison Engineer
GE AF LOHEGAON PUNE-411032
REPAIR OF DEFECTIVE ITEMS OF EARTHINGS, LIGHTNING PROTECTION, LT DISTRIBUTION SYSTEMS, DBS, MCBS, CABLES AND ALLIED SERVICES AND MISC ITEMS AT 9BRD AFS PUNE UNDER GE AF LOHEGAON
2025_MES_729968_1
8967
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
9BRD AFS PUNE
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
Yes
GE AF LOHEGAON
₹80,000
Yes
26 Nov 2025
9 Sept 2025
6 Oct 2025
9 Sept 2025
30 Sept 2025
25 Sept 2025
Amount
M & L for Checking/ Testing of resistance value of any type of earth pits by disconnecting earth continuity conductor from test terminal block and reconnecting the earth continuity conductor after testing including watering as and when required and all as specified and directed by Engr-In-Charge. Note: (i) Temporary earthing connection to be provided while testing. (ii) Calibrated Earth tester will be bought by contractor and calibration certificate of Earth tester shall be shall be submitted. (iii) Earth test results shall be recorded in reference to Earth pit No. WRT Each Bldg. (iv) If earth test result is not satisfactory , earthing test will be carried out again after maintenance and this will be paid separately. (v) Earth test to be signed by Rep of contractor, Rep of user section and rep of MES , Test reports to be submitted in triplicate. (vi) All T&P, manpower required is deemed to be inclusive in the quoted rates. (vii) Contractor shall provide water to earthing pits fortnightly. (vii) Water shall be arranged by contractor at his end by external source and shall water earthing pits. (viii) Cost of water, manpower and vehicle needed for watering is included in quoted rate of this item and nothing shall be paid extra.
M&L for maintenance of GI Plate/copper plate earthing to improve the earth resistance as following:- (a) Remove the earth pit carefully and kept at site for reuse. If existing pit is already damaged then new pit will be provided, measured & paid separately. (b) Excavation in any type of soil and rock 0.5 cum (approx 0.75m x 0.75m x 0.9m depth ) (c) On First day recharge the earth pit with common salt, Magnisium sulphate,back fill compound mixed with water.(Approx salt- 10 kg, Mg sulphate- 10 kg, Charkol - 10 kg ) (d) On the next day recharge the earth pit with water 500 ltrs on next day. (e) Excavated material to be removed from the site and deposit at the distance not exceeding 50m distance and levelled. (f) Refill the pit with M&L for black cotton soil 0.5cum. (g) Refit the earth pit in place. (h) Testing of earth ( to be measured and paid separately) Note:-(i) Common salt, Mg sulphate, Charkol will be measured and paid separately. .
M&L for maintenance of GI plate earthing to improve the earth resistance as following:- (a) Remove the earth chamber carefully and kept at site for reuse. If existing chamber is already damaged then new chamber will be provided, new chamber will be measured & paid separately. (b) Excavation in any type of soil and rock 1 Cum (approx 0.75m x 0.75m x 2 m depth ) (c) Taking out GI Earth plate , watering pipe , funnel , earth continuty GI strip, cleaning of GI earth plate and GI strip with wire brush and polish paper , cleaning of GI pipe and funnel and renistall the the same (d) GI strip shall be fitted with GI plate by GI nutbolts - 3 nos and in addition welding to be caried out , weld length between GI plate and GI strip not less than 30 CM on both side of strip (e) On First day recharge the earth pit with charcoal ,common salt, back fill compound mixed with water and black cotton soil (Approx charcoal - 25 KG, salt- 25 kg, Magnisium sulphate - 25 kg , black cotton soil 0.5 Cum (f) On the next day recharge the earth pit with water 500 ltrs on next day. (g) Excavated material to be removed from the site and deposit at the distance not exceeding 50m distance and levelled (h) Refill the pit with M&L for black cotton soil 0.5cum. (j) Refit the earth chamber in place. (k) Testing of earth ( to be measured and paid separately) Note:- charcoal , Common salt, Magnasium salphate will be measured and paid separately. .
M&L for maintenance of copper plate earthing to improve the earth resistance as following:- (a) Remove the earth chamber carefully and kept at site for reuse. If existing chamber is already damaged then new chmber will be provided,new chamber will be measured & paid separately. (b) Excavation in any type of soil and rock 1 Cum (approx 0.75m x 0.75m x 2 m depth ) (c) Taking out Copper Earth plate , watering pipe , funnel , earth continuty copper strip, cleaning of copper earth plate and Copper strip with wire brush and polish paper , cleaning of GI pipe and funnel and renistall the the same (d) copper strip shall be fitted with copper plate by brass nutbolts - 3 nos and in addition brazing to be caried out , brazing length between copper plate and copper strip not less than 30 CM on both side of strip (e) On First day recharge the earth pit with charcoal ,common salt, back fill compound mixed with water and black cotton soil (Approx charcoal - 25 KG, salt- 25 kg, Magnasium sulphate - 25 kg , black cotton soil 0.5 Cum (f) On the next day recharge the earth pit with water 500 ltrs on next day. (g) Excavated material to be removed from the site and deposited at the distance not exceeding 50m distance and levelled . (h) Refill the pit with M&L for black cotton soil 0.5cum. (j) Refit the earth chamber in place. (k) Testing of earth ( to be measured and paid separately) Note:- charcoal , Common salt, Magnesium sulphate will be measured and paid separately. .
M&L for fixing earth indicators made out of 3 mm thick MS sheet of size 200 mm x 300 mm duly fixed in MS angle iron 25 mm x 25mm of 600 mm long fixed to ground by means and including necessary cement concrete foundation and painting with one coat of synthetic enamel paint over a coat of red oxide primer complete for writing earth reading and connected plant/ panel etc. and excavation and earth work complete all as specified and as directed.
S&F in repair of test point made out of gun metal or phosphorous bronze of size 75x50x5mm duly mounted on epoxy insulator 02 Nos.Drilling of upper & lower portion of test point for incoming & outgoing connections with brass nut bolt to be fitted in and including terminal blockmade out of M.S sheet 2mm thick as per the sample duly painted with two coat of enamel paint over a coat of red oxide primer.
Material and labour for supply, installation, testing and commissioning of copper pipe electrode earthing maintenance free earthing based on 6 mtr long copper pipe 75 mm dia(ID) with wall thickness of 2 mm, copper strip in pipe and filled with MFC for improvement of conductivity of electrode duly fixed with connector at top connection of copper strip 25X3 mm riveted /nut bolt after 12 mm boring and further earth continuity conductor made of copper strip 25x3 mm upto 7.5 meter , 150 KGS BFC shall be filled around the copper pipe elecrode ,including providing earth pit chamber size 450x450x300 mm depth outside & 250x250x300 mm depth of PCC (1:3:6) type C1 complete all as specified and directed by Engr-in-Charge. Note:- (i) Rate included for testing,commisioning including checking of earth continuity and earth result complete all as specified and directed. (ii) Vendors are bound to get earthing result less than1 Ohm with grid of three earthings and 2 Ohm with grid of two earthing, 3 ohm with single earthing, Any additional work and material required to achive the required result is included in the cost (iii) Earth strip beyond 7.5m shall be measured and paid separately. (iv) Rate is included for boring of earthing in any type of soil/rock,minimum dia of bore 150mm. (v) Continuity of good earth resistance shall maintained upto 1 year and testing will be carried out monthly by MES authority.
Material and labour for supply, installation, testing and commissioning of GI pipe electrode earthing maintenance free earthing based on 6 mtr long GI pipe 80 mm dia(ID) medium grade, GI strip in pipe and filled with MFC for improvement of conductivity of electrode duly fixed with connector at top connection of GI strip 32X6 mm riveted /nut bolt after 12 mm boring and further earth continuity conductor made of GI strip 32x6 mm upto 7.5 meter , 60 KGS BFC shall be filled around the GI pipe electrode including providing earth pit chamber size 450x450x300 mm depth outside & 250x250x300 mm depth of PCC (1:3:6) type C1 complete all as specified and directed by Engr-in-Charge. Note:- (i) Rate included for testing,commisioning including checking of earth continuity and earth result complete all as specified and directed. (i) Venders are bound to get earthing result upto 5 Ohm for single earthings and 3 Ohm with the grid of two earthing.Any additional work and material required to achive the required result is included in the cost quoted by the tenderer. (iii) Earth strip beyond 7.5m shall be measured and paid separately. (iv) Rate is included for boring of earthing in any type of soil/rock,minimum dia of bore 150mm. (v) Continuity of good earth resistance shall maintained upto 1 year and testing will be carried out monthly by MES authority.
M/L for providing earthing complete with Copper earth plate electrode 600 mm x 600 mm x 3.15 mm thick buried directly in ground earth pit not less than 2.25 Mtr deep below ground level with top edge of the plate not less than 1.5 Mtr below normal ground level connected to copper earth strip 20 x 3 mm by means of bolts, nuts, checknuts & washers of copper and connecting to test point , providing charcoal and common salt ,all as shown in electrical plate No. 5 of SSR Part I of 2009 & as specified or indicated and testing on completion including excavation/earth work in any type of strata PCC ( 1:3:6 ) type C1 earthing chamber, pre cast slab 50 mm thick in cement concrete ( 1: 2 : 4 ) type B1 (reinforced with welded steel wire fabric (XPM) weight not less than 4 Kg / Sqm), funnel with wire mesh, watering pipe of 20 mm bore medium grade and lugs, including copper earth strip 20 x 3 mm with GI protection pipe of 25 mm medium grade 7.5 meter long, etc complete all as specified. Note-- (i) Vendors are bound to get earthing result upto1 Ohm with grid of three earthings and 2 Ohm with grid of two earthing, 3 ohm with single earthing, Any additional work and material required to achive the required result is included in the cost. (ii) Excavated material to be removed from the site and deposit at the distance not exceeding 50m distance and levelled. (iii) Refill the pit with M&L for black cotton soil 1 cum.
M&L for providing earthing complete with galvanised iron earth plate electrode 600 mm x 600 mm x 6mm as earthing lead buried directly in ground vertically to a depth not less than 2.25 Mtr deep below ground level with top edge of the plate not less than 1.5 Mtr below normal ground level connected to and including galvanised iron strip 32x6 mm as earthing lead by means of bolts, nuts, check nuts & washers etc made of GI and connected to earthing test point, providing charcoal and common salt all as shown in electrical plate No. 5 of SSR Part I of 2009 & as specified or indicated and testing on completion including exaction/earth work in any type of strata PCC (1:3:6) type C1 earthing chamber, pre cast slab 50 mm thick in cement concrete (1:2:4) type B1 (reinforced with welded steel wire fabric (XPM) weight not less than 4 Kg/sqm), funnel with wire mesh, watering pipe of 20 mm bore medium grade and lugs, including galvanised iron strip 32x6 mm with GI protection pipe of 40 mm medium grade 7.5 meter long, etc complete all as specified. Note:- (i) Venders are bound to get earthing result upto 5 Ohm for single earthings and 3 Ohm with the grid of two earthing.Any additional work and material required to achive the required result is included in the cost quoted by the tenderer.(ii) Excavated material to be removed from the site and deposit at the distance not exceeding 50m distance and levelled. (iii) Refill the pit with M&L for black cotton soil 1 cum.
S & F GI earth continuity conductor or main earthing lead of size 32x6 mm fixed to wall on batten or recess or chases or buried in ground or drawn in conduit / pipe or fixed to poles or any other indicated situation for earthing etc. as required complete all as directed.
S & F GI earth continuity conductor or main earthing lead of size 25x4 mm fixed to wall on batten or recess or chases or buried in ground or drawn in conduit / pipe or fixed to poles or any other indicated situation for earthing etc. as required complete all as directed.
S & F copper earth continuity conductor or main earthing lead of size 20x3 mm fixed to wall on batten or recess or chases or buried in ground or drawn in conduit / pipe or fixed to poles or any other indicated situation for earthing etc. as required complete all as directed.
S & F copper earth continuity conductor or main earthing lead of size 32x6 mm fixed to wall on batten or recess or chases or buried in ground or drawn in conduit / pipe or fixed to poles or any other indicated situation for earthing etc. as required complete all as directed.
S & F GI wire 4mm dia fixed to wall on batten or recess or chases or buried in ground or drawn in conduit / pipe or fixed to poles or any other indicated situation for earthing etc. as required complete all as directed.
S&F in repair of PVC insulated single core unsheathed multistranded cable FR, green colour with copper conductor size 6 sqmm for voltage grade upto 1100 volts.
S&F in repair of PVC insulated single core unsheathed multistranded cable FR, green colour with copper conductor size 10 sqmm for voltage grade upto 1100 volts.
S&F rigid PVC conduit of 20mm size along with all accessories as required complete all as directed.
S&F in repair for 25 mm bore galvanised steel water tubing 'medium grade' complete all as specified and as directed ( verticle pipe in earth pit for fiiling of water.)
S&F GI Sheet funnel with wire mesh
S&F in repair of GI tubing 20 mm bore 'medium grade' including all necessaory fittings i.e. socket, elbow etc.laid on floor or fixed to wall complete all as specified and directed by Engr-in-charge.
S&F in repair of GI tubing 15 mm bore 'medium grade' including all necessaory fittings i.e. socket, elbow etc.laid in trenches complete all as specified and directed by Engr-in-charge.
S&F Stop valve of 15mm dia complete as directed.
S&F GI elbow & GI plug 15mm dia with 1 mm hole for watering to each pit complete as directed.
Supply and fixing HDPE rotational moulded polyethylene cylindrical vertical water storage tanks 500 Ltr cap (triple layered with closed top), conforming to specification of IS:12701-1996 with amendment No 1 and 2 (covered by fig 1) hoisted and fixed in position, including out let and inlet connection including dismantling/taking down of existing unserviceable water storage tanks of any description and capacity complete complete all as specified and as directed by Engineer-in-Charge.
Note - Item No. 22 to 25 are for watering arrangment to earthings.
Excavation in trenches not exc 1.5 m wide and not exc 1.5 m in depth and getting it out for laying of cable / pole etc.
(a) Soft/loose soil
(b) Hard/dense soil
(c) Soft/ disintegrated rock
Returning/ Refilling of excavated soil including spreading levelling and well ramming in layers for any type of soil.
Removing the surplus soil to a distance not exceeding 50 mtrs from the starting point and depositing at a height not exceeding 1.5 m above ground level.
M&L for Cutting the existing GI pipe upto 80mm for tapping of 25 to 15 mm branch including required fittings complete all as specified and as directed.
S&F epoxy insulators suitable of aluminium strip of 25x3mm size with nut bolts/ screws for fixing of copper/ aluminium / GI strips on stone / PCC block walls etc .
M&L for earthing chamber of size 450x450x300 mm depth outside & 250x250x300 mm depth of PCC (1:3:6) type C1 complete as specified and directed by Engr-in-Charge .
S&F in repair of earthing pit cover 50 mm thick precast slab of RCC 1:2:4 type B1, reinforced with welded steel wire fabric (XPM) weight not less than 4 Kg/sqm incl 6 mm dia bar handle complete all as specified and directed by Engineer-in-charge.
Supply only Common salt for earthing
Supply only charcoal for earthing
Supply only magnasium sulphate for earthing
Taking down carefully from roof / wall of the building loose / hanging / deshaped / GI strip/ aluminium strip / copper strips of any size & type including unserviceable insulators etc all as directed by Engr - in - Charge .
Taking down termination rod .
Supply & fix aluminium strips 25x3 mm on porceline insulator 'T' type not more than 50 cm apart all as directed by Engr - in - Charge . Note: M&L Porcelain insulators with nuts bolts and screws will measured and paid separately
Refixing serviceable aluminium strips of any size and fixing on porecelin insulators 'T' type placed not more than 50 cm apart & fixed with srews & nut bolts . Note : M&L Porcelain insulators with nuts bolts and screws will measured and paid separately
Supply and fix air termination single pointed aluminium 12 mm dia & 300 mm long including nuts & bolts for fixing air termination rod to pole/ pipe duly insulated by providing appropriate insulator all as required at site.
Refixing air termination rod complete all as specified and directed by Engr-in-charge.
Refixing of GI supporting pipe 40/50mm (for termination rod) complete all as specified and directed by Engr-in-charge.
M&L for PCC 1:4:8 type D2 using 40 mm graded stone aggregate as mass concrete for foundation of GI tubing /Air termination rod or as required on site on Electrical installation complete all as specified and directed by Engr-in-charge.
M&L for cement concrete (1:2:4) type B1 in foundation filling and mass concrete and coping of poles incl necessary form work using 20 mm graded stone aggregate etc or as required on site etc complete all as directed by Eng-in-Charge
S&F GI pipe medium grade 40 mm dia all as specified and directed by Engr-in-charge (mounting arrangment for air termination) Note: M&L for PCC work will be measured and paid separately.
S&F porcelian insulators with nut bolts / screws for fixing of copper / aluminium strips / GI strips on walls etc .
Refixing of porcelian insulators with nut bolts / screws for fixing of copper / aluminium strips / GI strips on walls etc . Note For item No 40 to 51 : The lightning protection work has to be carried out in/on Bldg/ Shed/ Hanger at height upto 20 mtrs, all required T&P and safety measures has to be arranged by the contractor, and cost of same is deemed to be included in quoted rates.
M & L tools and machinary required for brazing of copper strip 20/25 mm wide x 3 thick both side by using copper brazing electrode to connecting the strip joints incl taking out/findingout joints below grond and required earth work complete all as required on site and all as directed by engr-in-Charge
All as above item ser No 52 but above ground level
M & L tools and machinary required for brazing of copper strip 32 mm wide x 3 mm thick by using copper brazing electrode to connecting the strip joints incl taking out/findingout joints below grond and required earth work complete all as required on site and all as directed by engr-in-Charge
All as above item ser No 54 but above ground level
M & L tools and machinary required for welding of GI Strip any size by using GI welding electrode to connecting the strip joints incl taking out/findingout joints below grond and required earth work complete all as required on site and all as directed by engr-in-Charge
All as above item ser No 56 but above ground level
M & L for Painting and marking of Earth pit chambers and Earth test points as per direction of user section as required on site complete as directed by Engr-in-Charrge
Comprehensive/ preventive maintanance of spike barrier 6 meter long, on quarterly basis including servicing and greasing all components, repair/ replacement of worn parts checking all electrical connections and testing complete in all respect for smooth functioning of spike barrier etc complete and maintain user satisfaction record all as specified and directed by Engr-In-Charge.Note: Cost of T&P and Spare parts is included in quoted rates.
M& L for washing/ cleaning of solar PV panels mounted on roof of Lab at 9BRD for efficient working of solar plant cap 50KW on monthly basis and recording cleaning date on register with user signature complete all as specified and directed by Engr-In-charge. Note: 1.T&P and washing material shall be provided by the contractor, and cost of same is included in quoted rate of item and nothing extra shall be pain on this account. 2. Non executing the washing for any month during CA period a monthly penalty of 10000.00 Rs shall be recovered from payment due to contractor.
M&L for Attending E-N voltage complaints, checking the wiring circuit for attaining desired E-N voltage, including fine tuning isolation transformer connections , checking all incoming and outgoing circuits, cleaning and servicing of isolation transformer complete upto satisfaction of Engr-In-Charge. (Note : Any minor spare part found faulty during checking and cable lugs , minor wire pieces including cost of T&P, multimeter etc shall be included in quoted rates of this item)
Material and labour for Routine maintenance of Solar water heater plant (including any leakages in GI pipes) of Cap 100/200 ltrs installed at single/ double story bldgs for preventing minor leakage using gasket of nitryl rubber of suitable thickness and size , cleaning of flat plate glass collector, cleaning / drain of water from hot and cold water tank and make up tank clean after disconnecting inlet and out let connections incl replacement of rusted nut bolts and washer of appropriate cap and refixing the same at retrieved position after cleaning for proper functioning of the system to maintain proper water temperature complete all as specified and as directed by Engineer-in-Charge.
Supply and fixing HDPE rotational moulded polyethylene cylindrical vertical water storage tanks 250 Ltr cap (triple layered with closed top), conforming to specification of IS:12701-1996 with amendment No 1 and 2 (covered by fig 1) hoisted and fixed in position, including out let and inlet connection including dismantling/taking down of existing unserviceable water storage tanks of any description and capacity complete complete all as specified and as directed by Engineer-in-Charge.
Supply and fixing in replacement of rubber hose pipe 20 to 25 mm dia between hot water tank & collector fixed with MS clamp complete all as specified and as directed by Engineer-in-Charge.
M&L for Servicing of 3 phase/single phase servo stabliser upto 100KVA including checking of tap changer, servomotor, cleaning of winding coils, tightning incoming and outgoing connections, arresting any minor oil leakage, checking of dimmer, contact relay etc complete upto satisfaction of Engr-In-Charge. (Note : Any minor spare part found faulty during checking such as contact relay and cable lugs , minor wire pieces including cost of T&P, multimeter etc shall be included in quoted rates of this item)
Taking down Old unserviceable LT UG cable of service connection or distribution system of any size and removing from site all as directed.( Excavation and earth work will be measured seperately)
M&L for scrapping of old alum paint of steel tubular pole 9/11 mtr by means of emery paper for preparation of smooth surfaces and painting with two coats of alum paint on pole , brackets old junction boxes channels etc incl alternate 30 cm wide white and blue strip painting up to 1.5 Mtr height from ground level complete all as specified and directed by Engr -in-Charge.
Material & Labour for painting to feeder pillar box / LT panel & duct cover etc, including angle iron frame with two coat of grey synthetic enamel paint including welding of door with proper size new hinges of suitable size and locking arrangements where required complete as specified.
Cutting/trimming of trees upto 150 mm girth including cutting of upper portion of branches above pole clearance up to 10 mtrs and disposal of same at a distance not exc 50 mtr and clearing of site complete as directed.(Note:Tools/ladder required for cutting/trimming of trees will be provided by the contractor at no extra cost and cost of the same be deemed to be included in the quoted rate.) Note:Each Span will be measured from one pole to another pole
Provn of services for cable fault location for LT UG cable, XLPE insulated 1100 Volts, of any size with fault detector machine complete all as specified and as directed.
Material and labour for straight through jointing kits heat shrinkable type LT UG XLPE cable heavy duty armoured sheathed including excavation in any strata, taking out cable, and making disturbed surface after relaying the cable making joints suitable for aluminium conductor of size given below all as specified and directed.
25 to 50 sqmm 3.5 core
70 to 150 sqmm 3.5 core
185-240 sqmm 3.5 core
300-400 sqmm 3.5 core
Supply and fix GI Pipe Light grade with all connected accessories of sizes 100 mm completed as directed
Supply and fix GI Pipe Light grade with all connected accessories of sizes 80 mm completed as directed
Supplying and erecting ( in true vertical position) steel tubular swaged poles complete with cast iron base plate final taper plug, bolts nuts and screws all as specified of type 410-SP-31 (9.0 mtr length) complete all as specifed in IS 2713 (part-II) 1980 including one coat or red oxide primer and two coats of aluminium paint to exposed surfaces and with blach bituminous paint for embedded portion of pole all as specified and directed at site.
Material and labour for cross arms, bracing supports, clamps and back plates fabricated from structural steel sections, including nut bolts, washer welding bending cold/ hot, drilling holes for bolts in any shape or size as indicated or directed and inclusive of one premer coat of red oxide primer, one under coat and one finishing coat of aluminium paint all as directed and as specified.
M& L for danger notice plate 1.6 mm thick mild steel sheet vitreous enamelled white with letter figures and conventional skull and tongue in signal red colour and fixed with MS clamps bolts nuts of approved size LT, 20x15cm all as directed
M&L for cement concrete (1:3:6) type C2 in foundation filling and mass concrete using 40mm graded stone agg for pole/stay foundation or as required on site etc complete all as directed by Eng-in-Charge
Supplying, spreading & leveling stone aggregate size of 40 mm grade to the existing sub station or all as specified and directed by Engineer-in-Charge.
Supplying ,Laying, jointing, testing and commissioning of LT under ground cable 1100 volts grade XLPE (cross linked polythene ) armoured with galvanised round steel wire or steel strip , electric power cable heavy duty, with multi stranded aluminium conductor, laid in trenches, ducts fix on walls/poles with proper size saddles and clamp laid under roads/path/ drain /culverts or enclosed in GI pipe/ fix complete all as specified for following size:-
10 sqmm 2 core
10 sqmm 4 core
16 sqmm 4 core
25 sqmm 3.5 core
35 sqmm 3.5 core
50 sqmm 3.5 core
70 sqmm 3.5 core
95 sqmm 3.5 core
120 sqmm 3.5 core
185 sqmm 3.5 core
300 sqmm 3.5 core
Relaying of old serviceable LT/HT under ground PVC/XLPE cable any grade and any size in trenches/fixed to wall/pole/roof/laid in floor including necessary connections and thimbling complete all as specified and as directed by Engineer-in-charge. (Earth work, brick & sand cushioning shall be measured and paid for separately under appropriate item).
Material and labour for stone dust sand cushioning to under ground cable, provided with a layer 8 cm before and 15 cm after laying and stretching jointing and testing the cable all as specified and directed. [Note : Measuremenet will be done after punning]
M&L for brick protection covers laid over cables of sub class'B' bricks old size all as specified and directed.
Supply and fix in repair / replacement of MCCB FP 630 Amps Adjustable type with breaking capacity 50 KA including connections and testing for proper functioning incl taking out unserviceable complete all as specified and directed.
Supply and fix in repair / replacement of MCCB FP 400 Amps Adjustable type with breaking capacity 36 KA including connections and testing for proper functioning incl taking out unserviceable complete all as specified and directed.
Supply and fix in repair / replacement of MCCB FP 250 Amps Adjustable type with breaking capacity 36 KA including connections and testing for proper functioning incl taking out unserviceable complete all as specified and directed.
Supply and fix in repair / replacement of MCCB FP 200 Amps Adjustable type with breaking capacity 36 KA including connections and testing for proper functioning incl taking out unserviceable complete all as specified and directed.
Supply and fix in repair / replacement of MCCB FP 160 Amps Adjustable type with breaking capacity 36 KA including connections and testing for proper functioning incl taking out unserviceable complete all as specified and directed.
Supply and fix in repair / replacement of MCCB TP 200 Amps Adjustable type with breaking capacity 36 KA including connections and testing for proper functioning incl taking out unserviceable complete all as specified and directed.
Supply and fix in repair / replacement of MCCB TP 160 Amps Adjustable type with breaking capacity 36 KA including connections and testing for proper functioning incl taking out unserviceable complete all as specified and directed.
Supply and fix in repair / replacement of MCCB TP 100 Amps Fixed type with breaking capacity 16 KA including connections and testing for proper functioning incl taking out unserviceable complete all as specified and directed.
Supply and fix in repair / replacement of MCCB TP 63 Amps Fixed type with breaking capacity 16 KA including connections and testing for proper functioning incl taking out unserviceable complete all as specified and directed.
S & F VTPN DB 4 Way sheet metal enclosure double door suitable for MCCB incommer and MCBs outgoing including MCCB 4P 125 Amps 10 KA complete all as speccified and directed including making good disturbed surfaces complete.
Supply and fixing SP 5 To 32 Amps rating 240V, 10KA 'C' curve miniature circuit breaker (MCB) of following poles and current carrying capacity in the MCB DB complete with connection testing and commissioning.
All as per item no 93 but SPN 32 Amps 240V 10KA 'C' Curve.
All as per item no 93 but TP 25 to 63 Amps 415 Volts 10 KA 'C' Curve.
S & F Sub Main Wiring with PVC Insulated multistranded copper conductor wires of size 2x6.0 sq. mm + 1x6.0 sq. mm earth wire including PVC cassing and capping complete all as specified and directed
Opening/disconnecting the electrical connection of defective/burnt out underground LT Cable of any size 2 to 4 core from main switch/DB/ junction box / LT panel /LT OH line etc. Taking out the required length of cable from existing loop, cutting the defective portion of cable, providing required thimbles/ connectors at cable end and reconnecting the cable in previous location with existing main switch/ DB/Junction box /LT Panel/ OH line etc complete all as directed.
Material and labour for Surface excavation n.exc (not exceeding) 30 cm deep and averaging 15cm deep and getting out removing of grass and vegetation grown around the electrical installations like transformers, LT panels, 2 pole structure, HT panels and complete area inside the fencing all as specified and directed by Engr-in-Charge Note : Item may be measured and paid more than one time as per site requirement to clean the E/M Installations
M&L for Cutting the existing road precisely for laying of cable crossing pipe and making good the distubed surface of road as per original after laying of pipe and removal of debries complete all as directed.
M/L for sub main wiring with two runs of single core 2.5 Sq mm FRLS PVC insulated unsheathed multi stranded copper conductor 1100 V grade with colour code and one run of 2.5 Sq mm single core FRLS PVC insulated unsheathed multi stranded copper conductor green colour cable for continuous earthing complete in & including PVC casing & caping with all fttiing & fixtures all as directed and specified. (Note:- Two runs of 2.5 Sqmm copper cable & one run of 2.5 sqmm copper cable including PVC casing & caping shall be mesured and paid as one length)
S&F of Sub main wiring with 4 X 10 sqmm single core cable PVC insulated unsheathed of copper multi strandard conductor cable , 1100 votls grade drawn in PVC casing caping and including PVC casing caping and insulated 1X 10 sqmm unsheathed multistranded FR-LS copper conductor cable for earth continuity and connected to common earth dolly complete all as specified and directed by Engineer-in-charge. (Note:- 4 lengths of 10 Sqmm & 1 length of 10 sqmm cable and PVC casing caping will be measured as one length).
M&L for Servicing of APFC panel of rating upto 200KVA including checking of CTs, control wiring, cleaning of panel and capacitor banks, tightning incoming and outgoing connections, supply and replacement of contactor, checking of capacitor banks, contact relay etc complete upto satisfaction of Engr-In-Charge. (Note : Any minor/major spare part found faulty during checking such as contactor, CTs,contact relay and cable lugs , minor wire pieces including cost of T&P, multimeter etc shall be included in quoted rates of this item)
M & L for servicing of high mast light driving mechanism by checking alll electrical and machnical component, chain, pully, rope,. Motor etc and greasing oiling of chain, motor, pully etc servicing of motor, control panel, auxiliary contacts, replacement of u/s items i.e. toggle switch, indicator light, control wiring complete all as specified and directed.
Labour & Tools incl ladders to attanding general street light complaints for repair / maint of steert light/ flood light fitting any type and capacity after taking out from poles upto 11 mtrs height any place wihin the stn checking throughly function of drivers and connected item, removing carbon on joints, repairing of cable joints/ loose connection, making sholdering etc incl replacement of small parts like wire upto 1.5 mtr long, nut bolts, screws , insulation tape etc fixing on pole after carry out nacessary repairs and testing for smooth functioning complete all as specified and directed. Note : (a) Repairs may be carryed out as an when required basis on site i.e number of times and shall be measured and paid as per site requirement as per satisfaction of Engr-in-Charge and Spare parts like electronic drivers, ballast , lamp , ignator etc shall be measured and paid separately in respective items.
Lowering down of high mast light at any height repairing and replacement of unserviceable parts such as electronic driver, surge protector and internal and external circuit etc as required on site complete all as specified and directed. (Note : Spare / parts required for replacement shall be measured and paid seperately and lowering down work may be carry out as and when required basis for any kind of repair.)
Taking down the existing street light fitting and Supply & fix (in Repalcement) energy saving and environmental frindly long life LED Street light fitting 35 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with impact and corrosion resistant including thermal management in multiple optics IP 65/IP66 road way luminaries with LEDs as light source and lens embedded, toughened glass cover and impact resistance of IK07 and electronic driver fixed on pole on existing bracket including connection complete all as specified and directed.
-ditto- all as per item Ser No 108.00 above but 60 Watt complete all as specified and directed
-ditto- all as per item Ser No 108.00 above but 70 Watt complete all as specified and directed
-ditto- all as per item Ser No 108.00 above but 90 Watt complete all as specified and directed
Taking down the existing Flood lights fitting and Supply & fix (in Repalcement) energy saving and environmental frindly long life exclusive innovative flood light luminaries 70 watt 230 V AC outdoor type with thermal management in multiple optics and equipped with IP66 protection, with impact and corrosion resistant with LEDs as light source and lens embedded on each LED, toughened glass cover and impact resistance of IK07 and electronic driver fixed on high mast pole or any any other place as requird on site incl making all nacessary arrangement for fixing complete with MS flat iron clamps (clamp shall be 40x5 mm MS flat), nuts and bolts and washers complete all as specified and directed.
-ditto- all as per item Ser No 109.00 above but 120 Watt complete all as specified and directed
-ditto- all as per item Ser No 109.00 above but 170/180 Watt complete all as specified and directed
-ditto- all as per item Ser No. 109.00 above but 200/210 Watt complete all as specified and directed
Taking old unserviceable driver from LED light fitting and S&F LED outdoor driver with all Electricals connection as per existing make on site and testing for smooth functioning complete all as specified and directed. For following capacity of light fitting
(a) for LED light fitting 60-72 Watts
(b) for LED light fitting 80-120 Watts
(c) for LED light fitting 150 Watt
(d) for LED light fitting 250 Watt
(e ) for LED light fitting 300 Watt
Supply and fixing LED Post top fitting 40 Watt 5700 K CCT IP 65 powder coated aluminium die cast and spun aluminium with clear diffuser suitable for landscape lighting incl making necessary arrangement for mounting fitting as reqd on site and testing complete all as specified and directed.
Supplying and fixing 1100 Volts grade heavy duty cable PVC insulated aluminium conductor, served with inner sheathing of PVC tape and overall PVC sheathed in service connection, one twin core multistranded cable flat or circulas 4 sqmm incl taking out old unserviceable wire complete all as specified and directed.
-ditto- all as per item Ser No 115.00 above but Service wire of size 6 Sq mm twin core
-ditto- all as per item Ser No 115.00 above but Service wire of size 10 Sq mm twin core
S&F in replacement of PVC insulated 1.5 sqmm copper three core conductor cable between cable loops box to fitting drawn through the pole complete all as specified and directed
S&F along pole PVC non metallic conduit of dia 20 mm medium grade including MS clamps and nut bolts etc for fixing along the pole complete all as specified and directed
Taking down old,rusted, unsv Junction box of any size, type and supply & fix new junction box of size not less than 210 mm x180 mm x 90 mm, made out of Fibre material, shockproof and rustproof, cable entry from bottom. 100% wheather proof and fixing to pole etc using suitable GI clamps of size 25x3mm, nuts, bolts etc for accommodating and including the following complete all as specified and directed:- a) TPN Connector 32 A b) MCB SP 6A-01 Nos
Supply and fixing in replacement of faulty fan 230/300mm sweep of stablizer of rating upto 100KVA 3 Phasecomplete all as specified and as directed by Engineer-in-Charge.
Supply and fixing in replacement of indicator lamp of stablizer as per sample LED source all as specified and directed by Engineer-in-Charge.
S&F in replacement of module control card of single phase of 30 KVA stabliser complete.
Supply and fixing in replacement contactor 4 pole, 440 V, 50 Hz MCX 70 for stablizer complete all as specified and directed by Engineer-in-Charge.
M&L for finding blockage in watering pipe line of 20/25mm dia for earthing system, its clearance and testing complete including identification of broken/rusted piece of pipe complete all as specified and directed. Note: Pipe line required for replacement shall be measured and paid seperately under appropriate item.
KSP ENTERPRISES (BID ID -3439006)
Sunhari Electricals (BID ID -3438872)
PROLINK COMPUTERS (BID ID -3439042)
D H L ENTERPRISES (BID ID -3437784)
SHRI PLACEMENT AND CONSULTANCY SERVICES (BID ID -3438024)
M/s Harshal Traders (BID ID -3439237)
Suchit constructions (BID ID -3439157)
K K ENGINEERING SERVICES (BID ID -3438443)
somnath engineering corporation (BID ID -3439398)
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .