Loading…
Loading…
Tender Value
₹13 L
Closing Date
18 Sept 2026, 2:00 pm
Competent Authority
C8 8th Floor RBI BKC Office
Electrical works for Renovation of Staff canteen at RBI BKC
2026_RBI_287840_1
RBI/Mumbai Regional Office/Estate BKC/26-27/1
Limited
Electrical Works
Works
RBI BKC OFFICE
Please refer Tender documents.
2 documents required · 2 mandatory
₹0
Exempted
18 Aug 2026
18 Aug 2026
21 Sept 2026
18 Aug 2026
18 Sept 2026
8 Sept 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | MCCBDB: Main DB
Supply, Installation, Testing and commissioning of approved make 12 Way, VTPN double door (metallic door) MCCBDB (IP 43) complete with 250 A Copper Busbar for each phase, 2 Neutral bar, 2 Earth bar and Cable ties for Cable management and fully insulated busbar & shrouded Neutral bars, required hardwares for mounting of MCBDB on wall with MS angle frame of minimum 35 mm x 35 mm x 5 mm size and required hardwares and following accessories
Incomer:
FPMCCB Qty 01 No.
Rated current: 160 Amp
Category: 36 KA
Thermal and Magnetic O/L and SC protection,
Outgoing, “C” curve MCBs:
TPMCB 32 Amp Qty 09 Nos.
TP MCB 63 Amp Qty 02 Nos.
SP MCB 63 AMP Qty 03 Nos. | - | Set | - | - |
| 2 | Cable End box:
Supply and Installation of respective make metallic cable end box suitable for above 12 Way VTPN MCCBDB stated at Sr. No. 1 of this BOQ. | - | No | - | - |
| 3 | MCBDB: Lighting and RAW
Supply, Installation, testing and commissioning of approved make 8 Way, per phase isolation, ETPN PPI double door (metallic door) MCBDB (IP 43) complete with minimum 100 A copper busbar for each phase, neutral bar, earthbar and cable ties for cable management, fully insulated busbar & shrouded neutral bars, per phase isolation kit, required hardwares for mounting of MCBDB and following respective make ‘C’ curve MCBs, RCCBs on wall, with MS angle frame of minimum 35 mm x 35 mm x 5 mm size and required hardwares and following accessories
Incomer:
FPMCB 63 Amp Qty 01 No.
Outgoing:
RCCB (two pole two module)
40 Amp 100 mAmp Qty 03 Nos
SPMCB 6 Amp to 32 Amp Qty 18 Nos. | - | Set | - | - |
| 4 | Cable End box:
Supply and Installation of respective make metallic cable end box suitable for above 8 Way ETPN MCBDB stated at Sr. No. 3 of this BOQ. | - | No | - | - |
| 5 | MCBDB: Critical Load Raw Power
Supply, Installation, testing and commissioning of approved make 8 Way, SPN double door (metallic door) MCBDB suitable for flush mounting and surface mounting complete with minimum 100 A copper busbar for each phase, neutral bar, earthbar and cable ties for cable management, fully insulated busbar & shrouded neutral bars, required hardwares for mounting of MCBDB and following respective make ‘C’ curve MCBs, RCCBs.
Incomer:
RCCB (two pole two module)
40 Amp 100 mAmp Qty 01 No.
Outgoing:
SPMCB 16 Amp to 32 Amp Qty 06 Nos. | - | Set | - | - |
| 6 | Cable End box:
Supply and Installation of respective make metallic cable end box suitable for above 8 Way SPN MCBDB stated at Sr. No. 6 of this BOQ. | - | No | - | - |
| 7 | Supply, Installation, testing and commissioning of approved make C series 32 Amp FPMCB in respective make metal enclosure in surface manner | - | Set | - | - |
| 8 | PVC conduits:
Supply and laying of approved make HMS grade of minimum 25 mm size PVC conduit along with required pipe fittings including required support, on wall in surface manner for vertical drop/horizontal looping of wiring upto MCBDB and on wall in concealed manner by providing chase cutting in wall for installation of PVC conduit and refilling the gap surrounding it by mortar making the good damages for vertical drop of wiring upto switch plates and on true ceiling in surface manner with required saddle and hardwares as directed by Bank’s Engineer as per site conditions. | - | Mtrs | - | - |
| 9 | Circuit wiring
Supply, Installation, Testing and Commissioning (SITC) of approved make 3 Nos. 2.5 Sq mm copper conductor Heat resistance Flame retardant Low smoke Halogen (HR-FR-LSH) insulated wire (Red/Yellow/Blue colour for Phase, Black colour for Neutral and Green colour for earth) partly in existing floor trunking/ PVC conduits from MCBDB to switch boards/ switch board to switch boards. | - | Mtrs | - | - |
| 11 | false ceiling, and gear wire assembly and main support from true ceiling, as directed by Bank s Engineer as per site condition.ßLED downlighter:
Supply, Installation, Testing and Commissioning of approved make wireless remote operated round shape LED dimmable and tuneable downlighter of minimum 18 watt, minimum 100 lumens per watt, white colour bodyìLED Linear light fitting:
Supply & Installation of approved make minimum 40 Watt, 1200 mm, minimum 100 lumens per watt aluminium body LED linear light fitting with required hardwares and gear wire set and main support from true ceiling.Supply, Installation, Testing and commissioning of approved make LED rope light of 8 Watt per mtr, 700 Lumens per watt, 120 LED per mtr.ÇSupply, Installation, Testing and Commissioning of approved make Direct Online (DOL) starter suitable for 5 HP 3 Phase 415 Volt 50 HZ Induction motor having overload range suitable for motor current.zCable Tray:
Supply and installing 150 mm x 50 mm x 1.6 mm size of perforated Hot deep Galvanized Iron cable tray (Galvanization thickness not less than 50 micron), bend, Tees, cross members, reducer etc, with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from ceiling with GI suspenders including G.I. bolts and nuts etc as required.«Rebate for carefully dismantling of existing old electrical wiring, conduits, cables, switchboards etc and taking away. The lighting fixtures shall be handed over to bank.Job/Tender Inviting Authority: RBI Estate Cell, BKCXName of Work: Electrical work for the Staff Canteen in the Bank s Office Building at BKC:Contract No: RBI/Mumbai Regional Office/Estate BKC/26-27/1
| - | No | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.23 MB
Tender.pdf
Tender Documents • 0.88 MB
BOQ_335809.xls
BOQ • 0.34 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at [email protected].