| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹9.3 CrAccepted-AOC | ₹9.3 Cr | L1 | Accepted-AOC BEING LOWEST |
| 2 | L2₹10.3 Cr+₹1.0 Cr (11.0%)Rejected-Finance AT MAIN ROAD DANDAI PO PS DANDAI DIST GARHWA | LATEHAR | JHARKHAND | 822112 | ₹10.3 Cr+₹1.0 Cr (11.0%) | L2 | Rejected-Finance Not lowest |
| 3 | L3₹10.7 Cr+₹1.4 Cr (14.9%)Rejected-Finance A 153 HQ CE EC KOLKATA LEKHAPANI POST TINSUKIA DIST ASSAM STATE | ₹10.7 Cr+₹1.4 Cr (14.9%) | L3 | Rejected-Finance Not lowest |
| 4 | L4₹11.7 Cr+₹2.4 Cr (26.2%)Rejected-Finance | ₹11.7 Cr+₹2.4 Cr (26.2%) | L4 | Rejected-Finance Not lowest |
Tender Value
₹9.8 Cr
EMD Value
₹8.1 L
Closing Date
23 Aug 2022, 6:00 pmClosed
CE SHILLONG ZONE
HQ CE Shillong, Spread Eagle Falls, Shillong, Meghalaya 793011
PROVN OF CENTRAL ENGINEERING SERVICES AT TEZU AND OUTPOCKETS UNDER GE LEKHAPANI
2022_MES_535879_1
CESZ/TEZU/ OF 2022-23
Open Tender
Civil Works
Lump-sum
720 days
LEKHAPANI
All as per NIT
2 documents required · 2 mandatory
₹3,000
GE LEKHAPANI
₹8.1 L
Yes
12 Sept 2022
5 Jul 2022
25 Aug 2022
5 Jul 2022
23 Aug 2022
11 Aug 2022
Amount
NOTE:- (Applicable for all parts/items/):- The bidders/contractors are advised to read tender document, all drawings & all corrigendum/ amendments and General conditions of contracts before entry/quoting the rates.
Lumpsum price workedout by the tenderer for BUILDING & STRUCTURE WORKS as listed in Schedule ‘A’ Part-I
Lumpsum price worked out by the bidder/ tenderer for SITE CLEARANCE, SITE DEVELOPMENTS & EARTH WORKS as listed in Schedule 'A' Part-II.
Lumpsum price worked out by the bidder/ tenderer for INTERNAL WATER SUPPLY as listed in Schedule 'A' Part-III.
Lumpsum price worked out by the bidder/ tenderer for INTERNAL ELECTRIFICATION as listed in Schedule 'A' Part-IV.
Lumpsum price worked out by the bidder/ tenderer for ROAD, PATH & CULVERT as listed in Schedule 'A' Part-V.
Lumpsum price work EXTERNAL WATER SUPPLY as listed in Schedule 'A' Part-VI.
Lumpsum price worked out by the bidder/ tenderer for EXTERNAL ELECTRIFICATION as listed in Schedule 'A' Part-VII.
Lumpsum price worked out by the bidder/ tenderer for SEWAGE DISPOSAL as listed in Schedule 'A' Part-VIII.
Lumpsum price worked out by the bidder/ tenderer for AREA DRAINAGE as listed in Schedule 'A' Part-IX.
Lumpsum price worked out by the bidder/ tenderer for CHAIN LINK FENCING as listed in Schedule 'A' Part-X.
Sch 'A' Sec-XII (Miscellaneous Items) Note : This schedule is not pre-priced by MES and the pre-priced rate indicated as "Rs 0.00" under Col. 5 siginifies this fact only.
Bringing approved earth (as approved by Garrison Engineer) from sources outside defence land including all cost such as royalty if any , transportation ,taxes,etc. for area filling / area development upto MGL level including raising of original ground level upto MGL by approved earth and including spreading in layers not exc 30cm thick each layer ,watering , compaction with 8 tonne to 12 tonne power roller and finished to required size and shape etc. Notes: (i) Earth required for the item, shall be supplied by contractor, from out side MOD land of any lead, at his own own arrangement. (ii) All cost of procurement of earth including cost of transportation, compaction, royalties, tax etc shall be deemed to be included in the unit rate quoted by the contractor. (iii) With reference to clause 3.6 of MES part-II on serial page No-21 it is clarified that measurement of the above item shall be of finished embankment /traverse of filled earth after consolidation /compaction and 5% deduction shall be made from measured and calculated volume to allow for increase in bulk. (iv) Total quantity /partial quantity of earth may not be available in Tezu Area. The contractor has to bring the earth from out side area and it is advised to quote the rate considering availability of soil and its lead involved.
Supplying and laying of 32 mm outer dia CPVC pipes SDR 11 & Plain CPVC SDR 11 fittings on walls/ceiling or laying in floors/trenches including special fittings like CPVC Brass fittings (Brass elbow, Brass Tee, Male threaded brass adaptor, Female threaded brass adaptor) complete all as specified and directed.
Supplying and laying of 20 mm outer dia CPVC pipes SDR 11 & Plain CPVC SDR 11 fittings on walls/ceiling or laying in floors/trenches including special fittings like CPVC Brass fittings (Brass elbow, Brass Tee, Male threaded brass adaptor, Female threaded brass adaptor) complete all as specified and directed.
Supply & fix cromium plated health faucet suitable for 20 mm outer dia of CPVC pipe with 1.2m long flexible tube and wall hook including making connections complete all as specified and directed.
Stone dust in floors or paving laid in layers spread thickness 75mm thick, spread, levelled and rammed including watering complete all as specified and directed.
Material, labour and applying road marking paint 3mm thick, retro-reflective type of specified shade / colour using hot thermoplastic material by automatic thermoplastic paint applicator machine fitted with profile shoe, glass beads dispenser, propane tank heater and profile shoe heater, driven by experienced operator on road surface including cleaning the road surface and remove all dirt, seals, oil, grease and foreign material etc. complete all as per manufacturer's instructions and as per direction.complete all as specified and directed.
Supply and fix reflective polycarbonate road stud/Cat Eye made from ABS material, dynamically designed having high impact strength of size 100 x 100 x 18.5mm and fitted with 2 Nos. highly reflective reflectors and two Nos Eye balls each on both side, fixed with adhesive in road surface as per manufacturer's instructions complete all as specified and directed.
Supply & Fix solar road studs/cat eye of minimum size 125mm x 125mm x 25mm made from aluminium alloy and powered by mono crystaline solar panel with one high capacity Ni-Cd rechargeable battery, provide with LED's -10mm, 03 pieces on each side and total 6 pieces are used for high brightness with backup 12 hours of continuous light and fixed with adhesive or as per manufacturers instruction complete all as specified and directed.
Supply and installation of rubberized speed breakers curve type made by natural rubber of size 500 x 350 x 50mm installed alternately in black and yellow colour, installation done by anchor fastener and adhesive or as per manufacturers instruction.
Material and labour for Drilling trial bore hole by ODEX full casing method through any kind of soil, boulder rock for a bore of 200mm dia tube well as required as per site condition upto 150m depth as per IS-2800 including disposal of soil from the site complete all as specified and directed. (Note: This item will be considered for payment if borewell is not successfull at site as directed by the Engr-in-charge)
Material and labour for Drilling and development of trial bore hole by ODEX full casing method through any kind of soil, boulder rock for a bore of 200mm dia tube well as required as per site condition upto 60 m from ground level as per IS-2800 including disposal of soil from the site complete all as specified and directed.
Material and labour for Drilling and development of trial bore hole by ODEX full casing method through any kind of soil, boulder rock for a bore of 200mm dia tube well as required as per site condition depth exceeding 60 m but not exceeding 120m below ground level as per IS-2800 including disposal of soil from the site complete all as specified and directed.
Material and labour for Drilling and development of trial bore hole by ODEX full casing method through any kind of soil, boulder rock for a bore of 200mm dia tube well as required as per site condition depth exceeding 120 m but not exceeding 150m below ground level as per IS-2800 including disposal of soil from the site complete all as specified and directed. (for 2 nos borewell, 30 mtr for each borewell) (Note for serial item Nos: 11.11 to 11.13: (I) Unit Quoted rate shall deemed to be inclusive of arrangement and shifitng of drilling rig of suitable capacity boring machine to work site with all accessories and necessary tools including necessary transportation and removing of the same from the site work after completion of work complete. (II) Boring to any depth beyond 150 mtrs if required at site shall be carried out with prior approval of Accepting Officer and shall be paid under item No.11.13 above. (III) Electrical Geographical logging of the bore holes under item Sl No. 11.11 to 11.13 shall be done after completion of driling but before lowering the assembly and cost for same shall deemed to be included in unit quoted rates under item Nos 11.11 to 11.13 above. (IV) Aquifer samples to be collected during drilling and preserve in sample box for analysis and preparation of lithological log and cost for same shall deemed to be included unit quoted rates under item Nos 11.11 to 11.13 above. (v) Depth of boring at each location will be decided by the GE based on recommendation of Central Ground Water Board report. (VI) Lowering of tube well assembly shall be done by welding collar rings or by screwed and socketed ends as directed by GE.
Material and labour for assembling, lowering and fixing into bore holes, 200 mm bore, mild steel ERW (ISI marked), casing pipe having wall thickness 6mm as per IS-4270-2001 (Steel tube or water well), heavy grade, plain end, blank jointed with collar through electric resistance of high frequency induction welding for increasing of length of pipe including necessary fittings and cleaning internal and external surfaces of pipe and painting inside and outside of pipe with two coats of anti corrosive black bituminous paint suitable for drinking purpose water over a coat of zinc oxide primer complete all as specified and directed.
Material and labour for assembling, lowering and fixing into bore holes, 150 mm bore, mild steel ERW (ISI marked), casing pipe having wall thickness 6mm as per IS-4270-2001 (Steel tube or water well), heavy grade, plain end, blank jointed with collar through electric resistance of high frequency induction welding for increasing of length of pipe including necessary fittings and cleaning internal and external surfaces of pipe and painting inside and outside of pipe with two coats of anti corrosive black bituminous paint suitable for drinking purpose water over a coat of zinc oxide primer complete all as specified and directed.
Material and labour for assembling, lowering and fixing in position, 150mm bore low carbon Glavanised Steel (LCG) Strainer with continuous slot screen (V-Wire Strainer) of 0.75 to 1.00mm slot width to give an open area of 30.4% conforming to relevant IS including cleaning internal and external surfaces of pipe and painting inside and outside of pipe with two coats of anti corrosive black bituminous paint suitable for drinking purpose water over a coat of zinc oxide primer complete all as specified and directed.
Collecting water sample in clean bottle from borewell after development by compressor for testing of physical, chemical and bacteriological test as per IS -10500 (2012) from NEIST JORHAT or any other government recognized institute and submitting the test report complete all as specified and as directed.
Supply and fixing well cap in two parts out of MS plate 6mm thick for covering tube well internal dia 200mm & 150mm depth duly welded with locking arrangement, including making holes for passing submersible cable & one run of support chain complete all as specified and directed. Note:- After complition of the work well cap will be used to keep the borewell closed untill the submersible pumping set is installed.
Material & Labour for development of tube well with air compressor as per IS : 11189-1985 of suitable capacity till sand/mud free water of potable quality is obtained and to achieve minimum discharging capacity of 61000 LPH/ Max yield complete all as specified and directed by GE. Note: - Compressor with accessories and fuel shall be arranged by the contractor at the own cost.
Material & Labour for carrying out yield test for the above bore well by continuously pumping for 16 hours to determine safe pumping yield and preperation of test sheet per hour specifying necessary parameters of testing complete all as specified and directed. (Note :- Yield test of bore well shall be carried out in presence of rep of accepting officer)
Supply, fixing, commissioning and testing Pumping sets, centrifugal monoblock, electric driven, of capacity 10 HP head not less than 65 metre and discharge 650 LMP (min) operated on AC 3 phase, voltage range 380 V-433V, 50 Hz complete inclusive of starter and PCC foundation of suitable size as specified and directed.
BLANK
Supply & Fix submersible cable 3 core multi stranded copper conductor PVC insulated, water proof, (ISI marked) of size 6 sqmm for connecting from starter to bore well submersible pump sets all as specified and as directed
Supply and fixing chain pully block, triple spur gear, 2 ton capacity with 3 mtr lift, manually operated completed with hooks high tensile forged steel confirming to IS : 3815 and load confirming to IS: 6216 and hand chain to IS: 2429 (Part-I) complete all as specified and as directed.
Supply and fixing steel rope flexible 10 mm dia with GI clamps, nuts, bolts, washer etc for fixing of submersible pump set complete all as specified and as directed.
Supply and fixing 80mm bore, cast iron Non return valve, flange type with by pass arrangement class PN 1.6 complete all as specified and as directed.
Supply and lowering jointing and testing MS black column pipe 3 mtr long heavy duty 80 mm bore, wall thickness 5.4 mm, both end flanged, (ISI marked) with heavy duty MS flanged not less than 16 mm screwed and welded in side and out side. The flange end making surface shall be made smooth including welding of 04 strip of 5.04 mm thick 25 mm wide and 50 mm long covering pipe and flanged, both end flanged having 08 Nos predrilled hole not less than 16 mm including rubber gasket, nut bolts and washer, pipe should be duly painted with anti corrosive paint complete.
Supply and fix 80mm bore sluice valve (operation-cap) both side flanged, ISI marked (IS No 14846-2000 class PN-1.6) having cast iron body, cast iron hand wheel, brass spindle, cheek nuts and sliding gate and body width including testing against leakage and supply of nuts & bolts complete all as specified and as directed.
Supply and fix 100mm bore sluice valve (operation-cap) both side flanged, ISI marked (IS No 14846-2000 class PN-1.6) having cast iron body, cast iron hand wheel, brass spindle, cheek nuts and sliding gate and body width including testing against leakage and supply of nuts & bolts complete all as specified and as directed.
Supply and fix 150mm bore sluice valve (operation-cap) both side flanged, ISI marked (IS No 14846-2000 class PN-1.6) having cast iron body, cast iron hand wheel, brass spindle, cheek nuts and sliding gate and body width including testing against leakage and supply of nuts & bolts complete all as specified and as directed.
Supply and fix Cast iron Reflux valve of 100 mm bore with by pass arrangement complete all as specified and directed
Supply & Fix Cast Iron Air Valves with two air Outlets, 100 mm dia bore and fixing Up in cast iron water supply mains complete all as specified and directed
Supply & Fix Cast Iron Air Valves with two air Outlets, 150 mm dia bore and fixing Up in cast iron water supply mains complete all as specified and directed
Supply, laying and jointing of ductile iron pipes of 100mm bore with spigot and socket ends conforming to IS 8329 : 2000, suitable for push on rubber joint centrifugally cast, class (K-9), inner side cement lining and outer side black bitumen coating and any length, laid in trenches or fixed in floors or on walls including push on rubber (EPDM) ring with ISI marked complete all as specified and directed. Note: Ductile iron fitting such as Bends (any type, radius and angle) tapers any type, (straight, bend, increasing, decreasing or double socket etc.) Tee pieces single branch. "Y" junction, double branch, cross (all sockets or socket and spigot) collars, caps and plugs of suitable size shall be measured and paid separately under relevant item.
Supply, laying and jointing of ductile iron pipes of 150mm bore with spigot and socket ends conforming to IS 8329 : 2000, suitable for push on rubber joint centrifugally cast, class (K-9), inner side cement lining and outer side black bitumen coating and any length, laid in trenches or fixed in floors or on walls including push on rubber (EPDM) ring with ISI marked complete all as specified and directed. Note: Ductile iron fitting such as Bends (any type, radius and angle) tapers any type, (straight, bend, increasing, decreasing or double socket etc.) Tee pieces single branch. "Y" junction, double branch, cross (all sockets or socket and spigot) collars, caps and plugs of suitable size shall be measured and paid separately under relevant item.
Supply, install, testing and commissioning of cubical housing cabinet type LT panel board indoor type, platform/wall mounted factory made, totally enclosed dust and vermin proof openable from front side made out of 2.0 mm thick CRCA MS Sheet of suitable size and built upon suitable size angle iron frame work, having front hinged door, earthing strips at rear side, bottom/side detachable gland plate complete with suitable size zinc plated and passivated nut, bolts, spring and washers. The cabinet and all members should be chemically treated with MSR solution for anticorrosive treatment. The panel shall be Epoxy Powder coated and the control circuit diagram shall be with colour code multi standered conductor copper 1.5 Sqmm. The panel should be suitable for 415 volts, 50Hz, 3 phase 4 wire system and internal connection should be provided with aluminium busbar 150 Amps rated of suitable size and necessary foundation work and comprising following:-
(Sr. Item No. 11.36 Condt/...) Incoming Side (i) MCCB 4 Pole 100 Amp ,breaking capacity 25 KA with thermal release-01 No (ii) on load Change lever 100 Amps , 4P -01 Nos (iii) Digital type Voltmeter 0-500 volts, 3 Phase, 4 digit, high resolution, LED type with one side programmability -1 Nos . (iv) Ammeter digital type three phase CT operated onsideprogramable with copper wound CT coil for three phases of suitable ratio & size class I accuracy, 0.5 VA burden, -01 Nos (v) Indicator lamp with holder key flush mounted,LED type Red, yellow, blue with toggle switch-2 Sets Outgoing Side (i) MCCB 4 Pole of capacity 40 Amp, breaking capacity 16 KA with thermal release-04 Nos (ii) MCB 2 Pole of capacity 32 Amp breaking capacity 10 KA-2 Nos (iii) Star delta starter suitable for 10 HP submersible Motor and monoblock pump with all type of protection-04 Nos
Supply and Fixed Glow signs Board of size 1.5m x 0.75m made of 2 mm aluminium sheet pasted with retro reflective sheet and mounted on MS pipe of 60 mm dia of duly painted with two coats of synthetic enamel paint over red oxide primer including foundation in PCC 1:3:6 type C2 and excavation and earthwork complete all as specified and directed.
M&L for construction of brick masonry valve pit of size 1200 X 1200 X 1000 mm (internal dimension) one brick thick wall in CM 1:4 on 100mm thick PCC 1:4:8 type D-2 (40mm graded aggregate) as in foundation, and 15mm thick rendering in cement mortar (1:4) internally, externally up to 15cm below GL, providing valve pit cover made of 3mm thick MS sheet/plate, welded including provision of hinges, handle and locking arrangement including 50 X 50 X 6mm angle iron frame fixed on top of valve pit by means of hold fast 150mm long, embedded in PCC block 1:2:4 type B-1 (20mm graded aggregate) of size as shown in drawing, including two coats of anti-corrosive paint over a coat of red oxide zinc Chrome primer and necessary earth work in soft/loose soil complete all as specified & directed and as per TD no. TD/EM/6 sheet No 1/2 & 2/2.
M&L for construction of brick masonry valve pit of size 600 X 600 X 800 mm (internal dimension) one brick thick wall in CM 1:4 on 100mm thick PCC 1:4:8 type D-2 (40mm graded aggregate) as in foundation, and 15mm thick rendering in cement mortar (1:4) internally, externally up to 15cm below GL, providing valve pit cover made of 3mm thick MS sheet/plate, welded including provision of hinges, handle and locking arrangement including 50 X 50 X 6mm angle iron frame fixed on top of valve pit by means of hold fast 150mm long, embedded in PCC block 1:2:4 type B-1 (20mm graded aggregate) of size as shown in drawing, including two coats of anti-corrosive paint over a coat of red oxide zinc Chrome primer and necessary earth work in soft/loose soil complete all as specified & directed and as per TD no. TD/EM/6 sheet No 1/2 & 2/2.
Supply, install, testing & commissioning of single deck iron removal cum pressure filtration plant of 8000 GPH of size 2500mm dia x 1500mm height (approximate dimensions) with shell/body thickness 8mm (minimum), bed plate 12mm & dish end 12mm complete with oxidation chamber of size 1000mm dia x 1200mm height (approximate dimensions), shall / body thickness 6mm, bed plate & dish end 8 mm. Material construction : Mild steel as per IS : 2062 so as to meet Test Pressure of 5.00 Kg/Cm2 & Working Pressure of 3.5 Kg/Cm2 as per IS : 2825, duly painted internally with 2 coated of potable quality anticorrosive bituminous black paint and externally 2 coats of red oxide primer before dispatch.The final painting will be of synthetic enamel paint 2 coats minimum at site after commissioning complete with suitable civil platform with foot stool foundation including drain and pit to accommodate the entire plant etc.Incl the following accessories: 1) Frontal pipe line of suitable dia ERW ( medium grade ) pipes in required length incl misc fittings such as tees,bends, etc & running welding to connect filter plant with existing raw water line. 2) Cast iron slimseal butterfly valves of suitable dia confirming to IS : 13095 - as required at site for controlling of incoming supply, bypass supply, outlet supply complete all as required at site. 3) Filter media (sand,gravels) & catalytic media of required qty. 4) Underbed plate system fitted with PVC (Double nut Type) strainers.
(Sr Item No. 11.40 Contd/...) 5) Pressure gauge & sampling cock - 02 sets (01 each for raw water & fresh water) 6) Cagulation sytem, air vent system & back washing facilities 7) Operation & maintenance manual - 01 No. 8) Air compressor of suitable capacity not less than 10 cfm fitted with suitable capacity 3 phase, 440 volts, 1440 RPM TEFC motor including starter. 9. Necessary plateform made out of PCC 1:2:4, 20mm graded stone aggregate of suitable length, width and height as per manufacturer's guide lines complete all as directed in and including necessary earth work complete Note. 1. The treatment plant shall be capable of removal of all organic/inorganic materials/salts/iron etc from the water & make the water potable as per IS : 10500-2012- Drinking water specifications 2. The contractor shall submit the design of filteration plant for approval by the GE prior to placing of order/procurement 3. Necessary chemical & bacteriological analysis report shall be provided by the contractor to the GE after commissioning of the treatment plant 4. Any other items/accessories inadvertently missed out but trechnically required for proper function of the plant is deemed to be included in the quoted rates for the item.
Supply, installation, testing and commissioning chlorine pressure feed, high pressure single head gear motorised adjustable dozing pump with accessories including lead tubing, connecting nuts, injection check valves, clay weight and ferrules, multi stage centrifugal pumps, startor control cabling etc of capacity upto 1000 grams/ hr with 100 ltr FRP tank and other connected accessories complete all as specified and as directed.
Supply, installation, testing and commissioning of silent type Direct injection, water cooled Diesel engine driver Generating set of capacity 60 KVA comprising of 3 cylinder in line, 4 strokes rated at 1500 RPM in line not less than 80.10 BHP, with AMF Control panel with necessary protection & meters and accessories complete as per the standard design of original OEM of D. G. Set including sound proof canopy confirming to BS-5514 and has the following specifications :- (i) In line fuel pump with mechanical governor suitable for 60 KVA D. G. Set (ii) Stainless steel exhaust flexible coupling and exhaust pipe to insulated with glass fire wool to be claded with plain GI sheet & extended out side the building (iii) Silencer extended out side to the building complete. (iv) Radiator
(Sr Item No. 11.42 Cond/....) (v) Coolant inhabitor, (vi) Plate type lubricant oil cooler (vii) Spin-on-filters-coolant, fuel & lubricant oil. (viii) Dry type, heavy duty, replaceable paper element air cleaner with restriction indicator. (ix) Flywheel housing and flywheel to suit single bearing alternator (x) Electrical starter motor (xi) Battery charging alternator (xii) 12 Volts, 80 Ah battery with multistranded copper cable for connecting wire and terminals complete (xiii) First fill lub oil B. ALTERNATOR (i) Self excited, self regulated (ii) Voltage regulation plus/minus 1 percent (iii) Class 'H' insulation (iv) Silent pole revolving field (v) Digital automatic voltage regulator (vii) Telephone interference factor - 50 (viii) Total harmonic factor Better than 2% ix) Supplying power to variable electrical load for unlimited hours. Prime power (PRP) is in accordance with ISO 8528. Ten percent over load capacity for one hour every 12 hrs of operation and will be suitable tropical conditions
(Sr Item No. 11.42 Cond/....) C. FUEL TANK (a) Fuel tank suitable capacity for minimum 12 hrs run with provision for supply and return lines, level indicator, drain valve, cleaning cover, vent pipe & locking devices shall be provided (b) Fuel pipe line from fuel tank to FIP of suitable size (c ) The fuel tank has to be mounted/located in side the cubicle. D. ACOUSTIC ENCLOSURE I) Designed to meet stringent MoEF/CPCB norms 75dBA @ 1 meter. ii) Air inlet louvers to be designed to operate at rated load even at 50 degree centrigrade air inlet temp. iii) Cubical to be powder coated for long lasting service life and super finish with UV resistent powder coating, it has to with stand extreme environment. Has to be use stainless steel hardware. iv) Insulation material has to meets exacting IS 8183 speces for better sound (v) Provision of Genset controller for Engine & alternator E. ACCESSORIES i) Periodical maintenance tools as per manufacture ii) Minimum two years spares as manufactures design. iii) Operational, spare parts & installation guide line catalogue F. AMF CONTROL PANEL FOR DG SET (I) MCCB 100 Amps, 4 pole, 415 volts, 25 KA, 50 Hz with thermal magnetic and electronic earth leakage module - 01
(Sr Item No. 11.42 Cond/....) (ii) Power contactors of suitable sizes, Air breake type - 02 Nos (iii) Digital type multi functional meter -01 Nos (iv) Current transformer (CT) of rating 100/5, tape wound, rated burden 5 VA - 03 Nos (v) Micro processor based relay of suitable size/ratings-01 Nos vi) Battery charger auto/manual switch - 01 Nos (vii) Suitable annunciation with features of following protections :- Over current, overvoltage, under voltage, under frequency, Low pressure oil. (viii) Change over switch four pole-two way with Centre off- 400 volts, 100 amps, open execution type, CAT part No. CO 11000 OOOO of L&T or as equivalent in specified makes Note : (a) Provision of PCC plateform as per manufacturer guidelines/specifications, the cost of the same shall be deemed to be included in the unit quoted rates. Nothing shall be admissible on this account (b) Testing of the DG set shall be carried out by the rep of the accepting office/IEM (c ) The contractor shall submit the drawing for approval of the GE before procurement of the DG set (d) Resistive load whether water load or strip heaters of suitable capacity and POL/DHPP for testing of DG set to be made available during test by the contractor. The cost of the same shall be deemed to be included in the unit quoted rates. (e) The DG set shall be procured from authorized OEM and of same group. The accoustic panel shall also be manufactured by the same OEM (f) Anything missed out above but is required for efficient working of DG set is deemed to be included in the unit quoted rate (g) Earthings, LT cable and other connected works shall be measured and paid seperately under relevant schedule
M & L for earthing complete with galvanised steel plate earth electrode 600 mm X 600 mm X 6 mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metres below normal ground level, connected to earthing lead of 32 mm x 6 mm galvanised mild steel strip by means of bolts, nuts, check nuts and washers of galvanised iron from earth plate to test point upto 7.5 metre including all as shown in electrical plate No. 3 of SSR Part I (2009) including necessary concrete chamber in cement concrete M-15 (Nominal Mix) using 20 mm nominal size coarse aggregate, precast RCC cover slab in cement concrete M-15 (Nominal mix) using 20 mm nominal size coarse aggregate of size 40 cm X 40 cm X 5 cm reinforced with 8 mm dia TMT bars @ 150 mm c/c with one handle for lifting made out of 8 mm dia bar, GI funnel, GI wire mesh filter, 20 mm dia GI pipe medium grade for watering, 40 mm dia GI pipe medium grade for protection of earthing lead, charcoal or coke dust and salt in alternate layers including necessary excavation and earth work in any type of soil/ strata and testing complete all as specified and as directed.
Supply and fix elastome Rubber mat of 1 m x 2 m x 2 mm as per IS 15652: 2000, suitable upto 3.30 KV AC (RMS) complete all as specified and directed.
Supply, fixing and testing DI fittings for spigot & socketed or flanged pipes i.e. bends, reducers, tail pieces, tapers, tees, collars, caps, plugs with MS plate, nuts, bolts, washers gaskets etc of sizes 100mm to150mm dia complete all as specified and directed .
Supply, fixing and commissioning of Aviation obstruction light, lighting fixtures including Neon spiral lamp, built in 75 Watt stepup transformer, heat resistant clear thick glass and accessories. Fixtures shall have die cast alluminium alloy including suitable MCBs complete all as specified and directed.
Supply and fix Air termination, single pointed aluminium rod 12mm dia and 300mm long all as specified and directed.
Supply, fixing, connecting and testing 200 KVA step down transformer, outdoor type 11/0.433 KV, AC double wound core type, copper wound, oil immersed, air naturally cooled with external cooling tubes, transformer delta connetion of HV side and star connection on LV side in accordance with vector symbol DyN-11 (vector group 4) and having tapping of ±7.5% in equal step of 2.5% off load tap changing arrangement. The voltage regulation shall be as per IS including first fill of transformer oil as per IS-335 and including all fittings/accessories as specified in SSR Part-1 and the transformer should be ISI marked and certified as per BIS ISI: 1180 (Part-1)for EEL 3, (mandatory quality control order latest version) the transformer should have cable box on LT side and brass bushing on HT side. The limit of temp rise after continuous full laod run as specified in SSR Part-1 and IS-1180 for EEL 3 shall be suitably adjusted to suit the maximum ambient temp prevailing at site all as specified comprising with and including the following specifications :- i) 01 Nos Cable box on LT side consisting of 03 Nos porcelain bushing with bushing brass rods and nuts washers and cable glands of suitable for reception of cable LT 1100 Volts grade XLPE insulated heavy duty including gland joint complete. ii) HV bushing with arching horn on 11 KV side. iii) Oil conservator with filter type drain valve and oil level guage. iv) Explosion Vent.
(Sr. Item No. 11.48 Contd/....) v) Thermometer Pocket. vi) Two Earthing Terminal on tank body to facilitate fixing of 32x6 GI strips. vii) One No Thermometer Dail type vapour pressure type having range 0-120 degree centigrade with maximum temperature indicator and re-setting device to maximum temperature including needle of temperature guage : Max reading pointed terminal. viii) Rating plate with terminal marking plate. ix) Oil level guage. x) Oil drain filter valve. xi) Oil filling pot on top cover with plug. xii) Air release valve/plug. xiii) First fill of transformer oil confirming to relevant to IS and tested upto 60 KV dielectric strength. xiv) Inspection cover. xv) Lifting lugs and jack lifting pad support. xvi) Bi-directional plain / flanged rullers. xvii) Explosion vent with double diaphragm and sight glass. xviii)Breather assembly with silica gel or with connecting pipe, first fill of dehdrating agent. xiv) Hand hole of sufficient size to assess the interior of the tank. xx) Cover lifting eyes. xxi) Oil temperature indicator of approved range, including shut off valve between conservator and main tank. xxii) Drain valve with threaded adaptor. xxiii) Filter valve with threaded adaptor.
(Sr. Item No. 11.48 Contd/....) xxiv) Sample valve. xxv) Extra bushing for neutral out side the LV side. xxvi) Platform for mounting of transformer made up of PCC 1:2:4 , 20mm graded stone aggregate, solid block and making all faces fare using extra cement as per manufacturer design of required length, width and hight including providing of 02 nos ISMC 100 chanel embedded in PCC of suitable length as directed at site by the engr-in-charge and including earth work complete Note : (i) Anything missed out above but technically required for proper operation of transformer is deemed to be included in the quoted rate.
Supply, fixing, connecting and testing 100 KVA step down transformer, outdoor type 11/0.433 KV, AC double wound core type, copper wound, oil immersed, air naturality cooled with external cooling tubes, transformer delta connetion of HV side and star connection on LV side in accordance with vector symbol DyN-11 (vector group 4) and having tapping of ±7.5% in equal step of 2.5% off load tap changing arrangement. The voltage regulation shall be as per IS including first fill of transformer oil as per IS-335 and including all fittings/accessories as specified in SSR Part-1 and the transformer should be ISI marked and certified as per BIS ISI: 1180 (Part-1)for EEL 3, (mandatory quality control order latest version) the transformer should have cable box on LT side and brass bushing on HT side. The limit of temp rise after continuous full laod run as specified in SSR Part-1 and IS-1180 for EEL 3 shall be suitably adjusted to suit the maximum ambient temp prevailing at site all as specified comprising with and including the following specifications :- i) 01 Nos Cable box on LT side consisting of 03 Nos porcelain bushing with bushing brass rods and nuts washers and cable glands of suitable for reception of cable LT 1100 Volts grade XLPE insulated heavy duty including gland joint complete. ii) HV bushing with arching horn on 11 KV side. iii) Oil conservator with filter type drain valve and oil level guage. iv) Explosion Vent.
(Sr Item No.11.49 Condt/…) v) Thermometer Pocket. vi) Two Earthing Terminal on tank body to facilitate fixing of 32x6 GI strips. vii) One No Thermometer Dail type vapour pressure type having range 0-120 degree centigrade with maximum temperature indicator and re-setting device to maximum temperature including needle of temperature guage : Max reading pointed terminal. viii) Rating plate with terminal marking plate. ix) Oil level guage. x) Oil drain filter valve. xi) Oil filling pot on top cover with plug. xii) Air release valve/plug. xiii) First fill of transformer oil confirming to relevant to IS and tested upto 60 KV dielectric strength. xiv) Inspection cover. xv) Lifting lugs and jack lifting pad support. xvi) Bi-directional plain / flanged rullers. xvii) Explosion vent with double diaphragm and sight glass.
(Sr Item No.11.49 Condt/…) xviii)Breather assembly with silica gel or with connecting pipe, first fill of dehdrating agent. xiv) Hand hole of sufficient size to assess the interior of the tank. xx) Cover lifting eyes. xxi) Oil temp indicator of approved range, including shut off valve between conservator and main tank. xxii) Drain valve with threaded adaptor. xxiii) Filter valve with threaded adaptor. xxiv) Sample valve. xxv) Extra bushing for neutral out side the LV side. xxvi) Platform for mounting of transformer made up of PCC 1:2:4 , 20mm graded stone aggregate, solid block and making all faces fare using extra cement as per manufacturer design of required length, width and hight including providing of 02 nos ISMC 100 chanel embedded in PCC of suitable length as directed at site by the engr-in-charge and including earth work complete Note : (i) Anything missed out above but technically required for proper operation of transformer is deemed to be included in the quoted rate.
Materials and labour for earthing complete with galvanised iron earth plate electrode 600 mm x 600 mm x 6 mm thick, burried directly and preferably vertically in ground, earth pit not less than 2.25 Mtr deep below ground level with top edge of the plate not less than 1.5m below ground level connetced with galvanised wire of 4mm dia by means of nuts, bolts, check nuts and washers made of galvanised iron or steel earthing lead to be protected by galvanised iron pipe of 15mm bore (light grade) and other end connected to earthing test point or lightening arrestor or main controlling switch as directed including providing funnel with 20mm bore galvanised iron pipe (medium grade), wire mesh, charcoal or coke dust and common salt in alternate layer of 15cm (compacted thickness) all round the earth electrode, concrete earth pit in PCC (1:3:6) type C-1 (with 20mm graded aggregate), 50mm thick precast RCC (1:2:4) cover slab (re-inforced with 8mm dia TMT bar @ 15 cm C/C bothways and suitable handle made of 10mm dia) including necessary earth work in excavation, returning filling and removal of surplus earth upto a distance not exceeding 50 m etc all as shown on electrical plate No. 3 of MES Schedule Part-I(2009) complete including testing on completion all as specified and as directed.
Supply and fixing LED street light fitting 60 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with potted type driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection complete all as specified and directed.
Supply and fix junction box made out of polycarbonate with IP 65 protection suitable for 25 Sqmm 4 core cable termination of size 200 x 160 x 98 mm including - 02 Nos of cable terminal, 02 Nos of polycarbonate cable gland , 01 Nos of DIN rail and 01 No of MCB SP, 'C' curve 10 KA 6 Amps complete all as specified and directed.
Supply and fix three single core FR PVC insulated sheathed stranded copper conductor cable drawn into steel pole of size 2.5 sq mm for connection or security/street light fitting from junction box all as directed and specified
Material & Labour for Street light bracket made out of 40 mm bore GI pipe Medium grade 1.5 mtr long including fixing with clamps and nuts & bolts complete all as specified and directed.
Supply & Fix HT /LT Cable route indicator of size height 1.0m, width 0.5m and thickness 0.1 m made of Plain Cement Concrete 1:2:4 (type B-1) using 20 mm graded stone aggregate including necessary fair finish formwork, excavation & earthwork and marking showing LT/HT type of cable on PCC block complete all as specified and directed.
Supply and install triple pole air break switch mechanically operated, mounted on insulator and steel frame with operating mechanism worked from ground level, current rating upto 200 Amps HT 11 KV outdoor type gang operated air break switch suitable for horizontal or vertical mounting fixed type complete with 12 insulators of rating 200 Amps in and including expulsion fuse single pole for each phase in and including necessary operating pipe, clamps for fixing and operating handle complete all as specified and as directed.
Supply and fix lightning arrestors non linear resistor type confirming to IS 3070 (Part-3) 1993 complete line discharge class-3m, nominal discharge current 10 KA (Peak), 12 KV rated system, voltage peak valve high current impulse of 4/10 micro sec. Wave shape 100 KA (Peak), assembly suitable for 11 KV, long duration discharge class-ll with insulation level 28/75 KV and mounted on hot dip galvanised steel structure including all clamps, nuts, bolt and washers and connecting to earth with 32x6 mm Gl strip complete all as specified and directed
Supply, installing, testing and commissioning out door type LT feeder piller box of suitable size, padestal mounted, CPRI type tested factory made totally enclosed, dust and vermin proof, double leaf shutter in front and rear side made of 3.00 mm thick CRCA sheet, framing with 75 x 75 x 6 mm thick MS angle iron duly fabricated and having proper locking arrangement in both front and rear door with 4 side slanting roof duly projected and painted to both internal and External surfaces with powder coating paint in heat process of sheet and suitable for 433 volts, 50 Hz, 3 phase 4 wire system and comprising with and including following accessories and mounted on PCC Plat form made out of PCC 1:2:4, 100 mm thick, 1 Mtr all round the panel board complete with the following items housed in : (Main Panel 200 KVA Transformer 205 Fd wksp') Note :- 1. Danger notice plate should be fixed on both side of LT Panel 2. After installation of Panel each MCB should be indicated by painted that connection goes to which building 3. Rate of Earthwork and PCC platform shall be deemed included in quoted rate.
Sr. Item No. 11.58 Cond/…. A) BUSBAR :- 400 Amps rated Aluminium bus bar TPN duly insulated with coloured PVC sleeve as per standard colour code and rigidly mounted on bakelite/DMC insulator bus bar support (Square/round) insulators of suitable size and good insulation resistance. B) INCOMING:- (i) MCCB 4P of capacity 250 Amps, 415 Volts, 50 Hz, 3 phase breaking capacity 36 KA thermal magnetic type with O/L and S/C protection -01 No (ii)3 Ph digital volt meter Class 1, 0-500 volts, 3 Phase, 4 digi twith LED display-- 01 No (iii)3 Ph digital Ampere meter Class 1 accuracy , 0.5 VA burden with LED display-- 01 No (iv) Modular indicator lamp with integral circuit (230V) and cluster LED (RED, YELLOW, BLUE) -01 set (v) Current Transformer 300/5A -03 Nos C) OUTGOING:- (i) MCCB 4 Pole of capacity 160 Amp, breaking capacity 25 KA with thermal release - 1 Nos (LTP-3) (ii) MCCB 4 Pole of capacity 100 Amp, breaking capacity 25 KA with thermal release - 2 Nos (LTP-4 AND LTP-2) (iii) MCCB 4 Pole of capacity 80 Amp, breaking capacity 25 KA with thermal release - 1 Nos (FPB 2 ) (iv) MCCB 4 Pole of capacity 63 Amp, breaking capacity 16 KA with thermal release - 1 Nos (LTP-4 ) (v) MCCB 4 Pole of capacity 40 Amp, breaking capacity 16 KA with thermal release - 2 Nos (FP-4, one spare) (vi) MCB TPN of capacity 32 Amp, breaking capacity 10 KA with thermal release -2 Nos (vii) MCB 2 Pole of capacity 16-32 Amp, breaking capacity 10 KA with thermal release - 4 Nos (Spare for future use) (viii) Time Switches astro type (having longitude and latitude of indian cities in memory) 250 V single phase of 20 Amp Rating With 3 phase 63A Contactor
Supply, installing, testing and commissioning out door type LT feeder piller box of suitable size, padestal mounted, CPRI type tested factory made totally enclosed, dust and vermin proof, double leaf shutter in front and single leaf shutter in rear side made of 3.00 mm thick CRCA sheet, framing with 50 x 50 x 6 mm thick MS angle iron and legs of size 0.5m long . duly fabricated and having proper locking arrangement in both front and rear door with 4 side slanting roof duly projected and painted to both internal and External surfaces with powder coating paint in heat process of sheet and suitable for 500 volts, 50 Hz, 3 phase 4 wire system and comprising with and including following accessories and mounted on PCC Plat form made out of PCC 1:2:4, 100 mm thick, 1 Mtr all round the panel board complete with the following items housed in : (LTP-5 near 200 KVATransformer 11 Compo) Note :- 1. Danger notice plate should be fixed on both side of LT Panel 2. After installation of Panel each MCB should be indicated by painted that connection goes to which building 3. Rate of Earthwork, Excavation and PCC platform shall be deemed included in quoted rate.
Sr. Item No. 11.59 Contd/... A) BUSBAR :- 400 Amps rated Aluminium bus bar TPN duly insulated with coloured PVC sleeve as per standard colour code and rigidly mounted on bakelite/DMC insulator bus bar support (Square/round ) insulators of suitable size and good insulation resistance B) INCOMING:- (i) MCCB 4P of capacity 250 Amps, 415 Volts, 50 Hz, 3 phase breaking capacity 36 KA thermal magnetic type with O/L and S/C protection - 01 No (ii) 3 Ph digital volt meter Class 1, 0-500 volts, 3 Phase, 4 digit with LED display - 01 No (iii) 3 Ph digital Amphere meter Class 1 accuracy , 0.5 VA burden with LED display - 01 No (iv) Modular indicator lamp with integral circuit (230V) and cluster LED (RED,YELLOW,BLUE) -01 set (v) CT (100/5A) -03 Nos C) OUTGOING:- (i) MCCB 4 Pole of capacity 80Amp, breaking capacity 16 KA with thermal release - 2 Nos (LTP-6, FP-10) (ii) MCCB 4P of capacity 100 Amps, 415 Volts, 50 Hz, 3 phase breaking capacity 25KA with thermal magnetic release - 02 No (for petrol pump, FP-8) (iii) MCCB 4 Pole of capacity 40 Amp, breaking capacity 16 KA with thermal release -1 Nos (FPB11) (iv) MCCB 4 Pole of capacity 63 Amp, breaking capacity 16 KA with thermal release - 2 Nos ( FPB-9 and Spare) (v) MCB 2 Pole of capacity 16-32 Amp, breaking capacity 10 KA with thermal release - 5Nos (spare for future use) (vi ) Spare pocket fo MCCB - 1
Supply,installing, testing and commissioning out door type LT feeder piller box of suitable size, padestal mounted, CPRI type tested factory made totally enclosed, dust and vermin proof, double leaf shutter in front and single leaf shutter in rear side made of 3.00 mm thick CRCA sheet, framing with 50 x 50 x 6 mm thick MS angle iron and legs of size 0.5m long . duly fabricated and having proper locking arrangement in both front and rear door with 4 side slanting roof duly projected and painted to both internal and External surfaces with powder coating paint in heat process of sheet and suitable for 500 volts, 50 Hz, 3 phase 4 wire system and comprising with and including following accessories and mounted on PCC Plat form made out of PCC 1:2:4, 100 mm thick, 1 Mtr all round the panel board complete with the following items housed in : (LTP-6 100KVA Tfr P/H main Panel) Note :- 1. Danger notice plate should be fixed on both side of LT Panel 2. After installation of Panel each MCB should be indicated by painted that connection goes to which building 3. Rate of Earthwork, Excavation and PCC platform shall be deemed included in quoted rate.
Sr. Item No. 11.60 Contd/.... A) BUSBAR :- 200 Amps rated Aluminium bus bar TPN duly insulated with coloured PVC sleeve as per standard colour code and rigidly mounted on bakelite/DMC insulator bus bar support (Square/round ) insulators of suitable size and good insulation resistance B) INCOMING:- (i) MCCB 4P of capacity 125 Amps, 415 Volts, 50 Hz, 3 phase breaking capacity 25 KA with thermal magnetic release - 01No (ii) on load changelever 4P, capacity125A , 415V,50Hz breaking capacity 25KA - 01 Nos (iii) 3 Ph digital volt meter Class 1, 0-500 volts, 3 Phase, 4 digit with LED display - 01 No (iv) 3 Ph digital Amphere meter Class 1 accuracy, 0.5 VA burden with LED display - 01 No (v) Modular indicator lamp with integral circuit (230V) and cluster LED (RED, YELLOW, BLUE) -01 set (vi) Current Transformer (100/5A) -03 Nos C) OUTGOING:- (i) MCCB 4 Pole of capacity 63 Amp, breaking capacity 16 KA with thermal release -1 Nos (for P/H panel ) (ii) MCCB 4 Pole of capacity 40 Amp, breaking capacity 16 KA with thermal release - 3 Nos (street light perimeter 2 side and units street light) (iii) MCB 4 Pole of capacity 32 Amp, breaking capacity 10 KA with thermal release -2 Nos (Spare) (iv) MCB 2 Pole of capacity 32 Amp, breaking capacity 10 KA with thermal release -1Nos (v) Spare pocket fo MCCB - 1 (vi) Time Switches astro type (having longitude and latitude of indian cities in memory) 250 V single phase of 20 Amp Rating With 3 phase 63A Contactor fitted inside steel enclosure - 03 Nos (vii) Spare MCCB 80 Amp,16KA, 4P - 1 Nos
Supply, installing, testing and commissioning out door type LT feeder piller box of suitable size, padestal mounted, CPRI type tested factory made totally enclosed, dust and vermin proof, double leaf shutter in front and rear side made of 3.00 mm thick CRCA sheet, framing with 50 x 50 x 6 mm thick MS angle iron . duly fabricated and having proper locking arrangement in both front and rear door with 4 side slanting roof duly projected and painted to both internal and External surfaces with powder coating paint in heat process of sheet and suitable for 500 volts, 50 Hz, 3 phase 4 wire system and comprising with and including following accessories and mounted on PCC Plat form made out of PCC 1:2:4, 100 mm thick, 1 Mtr all round the panel board complete with the following items housed in : ( 205 Wksp FPB-2 ) Note :- 1. Danger notice plate should be fixed on both side of LT Panel 2. After installation of Panel each MCB should be indicated by painted that connection goes to which building 3. Rate of Earthwork, Excavation and PCC platform shall be deemed included in quoted rate.
Sr Item No. 11.61 Contd/... A) BUSBAR :- 120 Amps rated Aluminium bus bar TPN duly insulated with coloured PVC sleeve as per standard colour code and rigidly mounted on bakelite/DMC insulator bus bar support (Square/round ) B) insulators of suitable size and good insulation resistance B) INCOMING:- (i) MCCB 4P of capacity 80 Amps, 415 Volts, 50 Hz, 3 phase breaking capacity 16 KA with thermal magnetic release - 01 No (ii) 3 Ph digital volt meter Class 1, 0-500 volts, 3 Phase, 4 digit with LED display - 01 No (iii) 3 Ph digital Amphere meter Class 1 accuracy, 0.5 VA burden with LED display - 01 No (iv) Modular indicator lamp with integral circuit (230V) and cluster LED (RED, YELLOW, BLUE) - 01 set (v) CT (100/5A) - 03 Nos C) OUTGOING:- (i) MCCB 4 Pole of capacity 40 Amp, breaking capacity 16 KA with thermal release - 4 Nos (ii) MCB 2 Pole of capacity 32 Amp, breaking capacity 10 KA with thermal release -12 Nos
Supply, installing, testing and commissioning out door type LT feeder piller box of suitable size, padestal mounted, CPRI type tested factory made totally enclosed, dust and vermin proof, double leaf shutter in front and rear side made of 3.00 mm thick CRCA sheet, framing with 50 x 50 x 6 mm thick MS angle iron . duly fabricated and having proper locking arrangement in both front and rear door with 4 side slanting roof duly projected and painted to both internal and External surfaces with powder coating paint in heat process of sheet and suitable for 500 volts, 50 Hz, 3 phase 4 wire system and comprising with and including following accessories and mounted on PCC Plat form made out of PCC 1:2:4, 100 mm thick, 1 Mtr all round the panel board complete with the following items housed in : ( 205 Wksp FPB-3 ) Note :- 1. Danger notice plate should be fixed on both side of LT Panel 2. After installation of Panel each MCB should be indicated by painted that connection goes to which building 3. Rate of Earthwork, Excavation and PCC platform shall be deemed included in quoted rate.
Sr Item No. 11.62 Contd/…. A) BUSBAR :- 100 Amps rated Aluminium bus bar TPN duly insulated with coloured PVC sleeve as per standard colour code and rigidly mounted on bakelite/DMC insulator bus bar support (Square/round ) insulators of suitable size and good insulation resistance. B) INCOMING:- (i) MCCB 4P of capacity 63 Amps, 415 Volts, 50 Hz, 3 phase breaking capacity 16 KA with thermal magnetic release - 01 No (ii) 3 Ph digital volt meter Class 1, 0-500 volts, 3 Phase, 4 digit with LED display - 01 No (iii) 3 Ph digital Amphere meter Class 1 accuracy , 0.5 VA burden with LED display - 01 No (iv) Modular indicator lamp with integral circuit (230V) and cluster LED (RED, YELLOW, BLUE) -01 set (v) CT (100/5A) -03 Nos C) OUTGOING:- (i) MCCB 4 Pole of capacity 40 Amp, breaking capacity 16 KA with thermal release - 2 Nos (ii) MCB 2 Pole of capacity 32 Amp, breaking capacity 10 KA with thermal release -12 Nos
Supply, installing, testing and commissioning out door type LT feeder piller box of suitable size, padestal mounted, CPRI type tested factory made totally enclosed, dust and vermin proof, double leaf shutter in front and rear side made of 3.00 mm thick CRCA sheet, framing with 50 x 50 x 6 mm thick MS angle iron . duly fabricated and having proper locking arrangement in both front and rear door with 4 side slanting roof duly projected and painted to both internal and External surfaces with powder coating paint in heat process of sheet and suitable for 500 volts, 50 Hz, 3 phase 4 wire system and comprising with and including following accessories and mounted on PCC Plat form made out of PCC 1:2:4, 100 mm thick, 1 Mtr all round the panel board complete with the following items housed in : ( 205 Wksp FPB-4 ) Note :- 1. Danger notice plate should be fixed on both side of LT Panel 2. After installation of Panel each MCB should be indicated by painted that connection goes to which building 3. Rate of Earthwork, Excavation and PCC platform shall be deemed included in quoted rate.
Sr. Item No. 11.63 (Contd/....) A) BUSBAR :- 100 Amps rated Aluminium bus bar TPN duly insulated with coloured PVC sleeve as per standard colour code and rigidly mounted on bakelite/DMC insulator bus bar support (Square/round ) insulators of suitable size and good insulation resistance B) INCOMING:- (i) MCCB 4P of capacity 40 Amps, 415 Volts, 50 Hz, 3 phase breaking capacity 16 KA with thermal magnetic release - 01 No (ii) 3 Ph digital volt meter Class 1, 0-500 volts, 3 Phase, 4 digit with LED display - 01 No (iii) 3 Ph digital Amphere meter Class 1 accuracy, 0.5 VA burden with LED display - 01 No (iv) Modular indicator lamp with integral circuit (230/240 volt) and cluster LED (RED, ORANGE, BLUE) -01 set (v) CT (100/5A) - 03 Nos C) OUTGOING:- (i) MCB 2 Pole of capacity 32 Amp, breaking capacity 10 KA with thermal release - 12 Nos
Supply, installing, testing and commissioning out door type LT feeder piller box of suitable size, padestal mounted, CPRI type tested factory made totally enclosed, dust and vermin proof, double leaf shutter in front and rear side made of 3.00 mm thick CRCA sheet, framing with 50 x 50 x 6 mm thick MS angle iron. duly fabricated and having proper locking arrangement in both front and rear door with 4 side slanting roof duly projected and painted to both internal and External surfaces with powder coating paint in heat process of sheet and suitable for 500 volts, 50 Hz, 3 phase 4 wire system and comprising with and including following accessories and mounted on PCC Plat form made out of PCC 1:2:4, 100 mm thick, 1 Mtr all round the panel board complete with the following items housed in : ( Engr LTP- 2) Note :- 1. Danger notice plate should be fixed on both side of LT Panel 2. After installation of Panel each MCB should be indicated by painted that connection goes to which building 3. Rate of Earthwork, Excavation and PCC platform shall be deemed included in quoted rate.
Sr Item No.11.64 Condt/... A) BUSBAR :- 150 Amps rated Aluminium bus bar TPN duly insulated with coloured PVC sleeve as per standard colour code and rigidly mounted on bakelite/DMC insulator bus bar support (Square/round ) insulators of suitable size and good insulation resistance B) INCOMING:- (i) MCCB 4P of capacity 100 Amps, 415 Volts, 50 Hz, 3 phase breaking capacity 25 KA with thermal magnetic release - 01 No (ii) 3 Ph digital volt meter Class 1, 0-500 volts, 3 Phase, 4 digit with LED display - 01 No (iii) 3 Ph digital Amphere meter Class 1 accuracy, 0.5 VA burden with LED display - 01 No (iv) Modular indicator lamp with integral circuit (230V) and cluster LED (RED, YELLOW, BLUE) - 01 set (v) CT (100/5A) - 03 Nos C) OUTGOING:- (i) MCCB 4P of capacity 40 Amps, 415 Volts, 50 Hz, 3 phase breaking capacity 16 KA with thermal magnetic release -01 No (ii) MCB 4 Pole of capacity 32 Amp, breaking capacity 10 KA with thermal release - 1 No (iii) MCB 2 Pole of capacity 32 Amp, breaking capacity 10 KA with thermal release - 5 No
Supply, installing, testing and commissioning out door type LT feeder piller box of suitable size, padestal mounted, CPRI type tested factory made totally enclosed, dust and vermin proof, double leaf shutter in front and rear side made of 3.00 mm thick CRCA sheet, framing with 50 x 50 x 6 mm thick MS angle iron . duly fabricated and having proper locking arrangement in both front and rear door with 4 side slanting roof duly projected and painted to both internal and External surfaces with powder coating paint in heat process of sheet and suitable for 500 volts, 50 Hz, 3 phase 4 wire system and comprising with and including following accessories and mounted on PCC Plat form made out of PCC 1:2:4, 100 mm thick, 1 Mtr all round the panel board complete with the following items housed in : ( Engr FP-5) Note :- 1. Danger notice plate should be fixed on both side of LT Panel 2. After installation of Panel each MCB should be indicated by painted that connection goes to which building 3. Rate of Earthwork, Excavation and PCC platform shall be deemed included in quoted rate.
Sr Item No.11.65 Condt/… A) BUSBAR :- 150 Amps rated Aluminium bus bar TPN duly insulated with coloured PVC sleeve as per standard colour code and rigidly mounted on bakelite/DMC insulator bus bar support (Square/round ) insulators of suitable size and good insulation resistance B) INCOMING:- (i) MCCB 4P of capacity 63 Amps, 415 Volts, 50 Hz, 3 phase breaking capacity 16 KA with thermal magnetic release - 01 No (ii) 3 Ph digital volt meter Class 1, 0-500 volts, 3 Phase, 4 digit with LED display - 01 No (iii) 3 Ph digital Amphere meter Class 1 accuracy, 0.5 VA burden with LED display - 01 No (iv) Modular indicator lamp with integral circuit (230V) and cluster LED (RED, YELLOW, BLUE) - 01 set (v) CT (100/5A) - 03 Nos C) OUTGOING:- (i) MCB 2 Pole of capacity 32 Amp , breaking capacity 10 KA with thermal release -7Nos
Supply, installing, testing and commissioning out door type LT feeder piller box of suitable size, padestal mounted, CPRI type tested factory made totally enclosed, dust and vermin proof, double leaf shutter in front and rear side made of 3.00 mm thick CRCA sheet, framing with 50 x 50 x 6 mm thick MS angle iron . duly fabricated and having proper locking arrangement in both front and rear door with 4 side slanting roof duly projected and painted to both internal and External surfaces with powder coating paint in heat process of sheet and suitable for 500 volts, 50 Hz, 3 phase 4 wire system and comprising with and including following accessories and mounted on PCC Plat form made out of PCC 1:2:4, 100 mm thick, 1 Mtr all round the panel board complete with the following items housed in : ( OFFR MESS LTP- 4) Note :- 1. Danger notice plate should be fixed on both side of LT Panel 2. After installation of Panel each MCB should be indicated by painted that connection goes to which building 3. Rate of Earthwork, Excavation and PCC platform shall be deemed included in quoted rate.
Sr Item No.11.66 Condt/… A) BUSBAR :- 150 Amps rated Aluminium bus bar TPN duly insulated with coloured PVC sleeve as per standard colour code and rigidly mounted on bakelite/DMC insulator bus bar support (Square/round ) insulators of suitable size and good insulation resistance B) INCOMING:- (i) MCCB 4P of capacity 100 Amps, 415 Volts, 50 Hz, 3 phase breaking capacity 25 KA with thermal magnetic release - 01 No (ii) 3 Ph digital volt meter Class 1, 0-500 volts, 3 Phase, 4 digit with LED display - 01 No (iii) 3 Ph digital Amphere meter Class 1 accuracy, 0.5 VA burden with LED display - 01 No (iv) Modular indicator lamp with integral circuit (230V) and cluster LED (RED, YELLOW, BLUE) - 01 set (v) CT (100/5A) - 03 Nos C) OUTGOING:- (i) MCCB 4P of capacity 40 Amps, 415 Volts, 50 Hz, 3 phase breaking capacity 16 KA with thermal magnetic release - 01 No (ii) MCB 4 Pole of capacity 32 Amp, breaking capacity 10 KA with thermal release - 2 Nos (iii) MCB 2 Pole of capacity 32 Amp, breaking capacity 10 KA with thermal release -12 Nos
Supply, installing, testing and commissioning out door type LT feeder piller box of suitable size, padestal mounted, CPRI type tested factory made totally enclosed, dust and vermin proof, double leaf shutter in front and rear side made of 3.00 mm thick CRCA sheet, framing with 50 x 50 x 6 mm thick MS angle iron . duly fabricated and having proper locking arrangement in both front and rear door with 4 side slanting roof duly projected and painted to both internal and External surfaces with powder coating paint in heat process of sheet and suitable for 500 volts, 50 Hz, 3 phase 4 wire system and comprising with and including following accessories and mounted on PCC Plat form made out of PCC 1:2:4 100 mm thick, 1 Mtr all round the panel board complete with the following items housed in : ( Transit Camp LTP- 3) Note :- 1. Danger notice plate should be fixed on both side of LT Panel 2. After installation of Panel each MCB should be indicated by painted that connection goes to which building 3. Rate of Earthwork, Excavation and PCC platform shall be deemed included in quoted rate.
Sr Item No.11.67 Condt/… A) BUSBAR :- 250 Amps rated Aluminium bus bar TPN duly insulated with coloured PVC sleeve as per standard colour code and rigidly mounted on bakelite/DMC insulator bus bar support (Square/round ) insulators of suitable size and good insulation resistance B) INCOMING:- (i) MCCB 4P of capacity 160 Amps, 415 Volts, 50 Hz, 3 phase breaking capacity 25 KA with thermal magnetic release -01 No (ii) 3 Ph digital volt meter Class 1, 0-500 volts, 3 Phase, 4 digit with LED display - 01 No (iii) 3 Ph digital Amphere meter Class 1 accuracy , 0.5 VA burdenwith LED display - 01 No (iv) Modular indicator lamp with integral circuit (230V) and cluster LED (RED, YELLOW, BLUE) -01 set (v) CT (100/5A) -03 Nos C) OUTGOING:- (i) MCCB 4 Pole of capacity 63 Amp, breaking capacity 16 KA with thermal release - 1 No (ii) MCCB 4 Pole of capacity 40 Amp, breaking capacity 16 KA with thermal release - 1 No (iii) MCB 4 Pole of capacity 32 Amp, breaking capacity 10 KA with thermal release - 1 No (Spare) (iv) MCB 2 Pole of capacity 32 Amp, breaking capacity 10 KA with thermal release -10 Nos (v) Spare pocket fo MCCB - 1 (vi) Time Switches astro type (having longitude and latitude of indian cities in memory) 250 V single phase of 20 Amp Rating With 3 phase 63A Contactor fitted inside steel enclosure - 01 No
Supply, installing, testing and commissioning out door type LT feeder piller box of suitable size, padestal mounted, CPRI type tested factory made totally enclosed, dust and vermin proof, double leaf shutter in front and single leaf shutter in rear side made of 3.00 mm thick CRCA sheet, framing with 50 x 50 x 6 mm thick MS angle iron and legs of size 0.5m long . duly fabricated and having proper locking arrangement in both front and rear door with 4 side slanting roof duly projected and painted to both internal and External surfaces with powder coating paint in heat process of sheet and suitable for 500 volts, 50 Hz, 3 phase 4 wire system and comprising with and including following accessories and mounted on PCC Plat form made out of PCC 1:2:4, 100 mm thick, 1 Mtr all round the panel board complete with the following items housed in : (FP-6 Transit Camp) Note :- 1. Danger notice plate should be fixed on both side of LT Panel 2. After installation of Panel each MCB should be indicated by painted that connection goes to which building 3. Rate of Earthwork, Excavation and PCC platform shall be deemed included in quoted rate.
Sr Item No.11.68 Condt/… A) BUSBAR :- 80 Amps rated Aluminium bus bar TPN duly insulated with coloured PVC sleeve as per standard colour code and rigidly mounted on bakelite/DMC insulator bus bar support (Square/round ) insulators of suitable size and good insulation resistance B) INCOMING:- (i) MCCB 4P of capacity 40 Amps, 415 Volts, 50 Hz, 3 phase breaking capacity 25 KA with thermal magnetic release -01 No (ii) 3 Ph digital volt meter Class 1, 0-500 volts, 3 Phase, 4 digit with LED display - 01 No (iii) 3 Ph digital Amphere meter Class 1 accuracy, 0.5 VA burden with LED display - 01 No (iv) Modular indicator lamp with integral circuit (230V) and cluster LED (RED, YELLOW, BLUE) -01 set (v) CT (100/5A) -03 Nos C) OUTGOING:- (i) MCB 4 Pole of capacity 32 Amp, breaking capacity 10 KA with thermal release - 1 No (ii) MCB 2 Pole of capacity 10-32 Amp, breaking capacity 10 KA with thermal release - 8 Nos
Supply, installing, testing and commissioning out door type LT feeder piller box of suitable size, padestal mounted, CPRI type tested factory made totally enclosed, dust and vermin proof, double leaf shutter in front and single leaf shutter in rear side made of 3.00 mm thick CRCA sheet, framing with 50 x 50 x 6 mm thick MS angle iron and legs of size 0.5m long. duly fabricated and having proper locking arrangement in both front and rear door with 4 side slanting roof duly projected and painted to both internal and External surfaces with powder coating paint in heat process of sheet and suitable for 500 volts, 50 Hz, 3 phase 4 wire system and comprising with and including following accessories and mounted on PCC Plat form made out of PCC 1:2:4, 100 mm thick, 1 Mtr all round the panel board complete with the following items housed in : (FPB 7 Transit camp ) Note :- 1. Danger notice plate should be fixed on both side of LT Panel 2. After installation of Panel each MCB should be indicated by painted that connection goes to which building 3. Rate of Earthwork, Excavation and PCC platform shall be deemed included in quoted rate.
Sr Item No.11.69 Condt/… A) BUSBAR :- 150 Amps rated Aluminium bus bar TPN duly insulated with coloured PVC sleeve as per standard colour code and rigidly mounted on bakelite/DMC insulator bus bar support (Square/round ) insulators of suitable size and good insulation resistance B) INCOMING:- (i) MCCB 4P of capacity 80Amps, 415 Volts, 50 Hz, 3 phase breaking capacity 16 KA with thermal magnetic release -01 No (ii) 3 Ph digital volt meter Class 1, 0-500 volts, 3 Phase, 4 digit with LED display - 01 No (iii) 3 Ph digital Amphere meter Class 1 accuracy, 0.5 VA burden with LED display - 01 No (iv) Modular indicator lamp with integral circuit (230V) and cluster LED (RED, YELLOW, BLUE) - 01 set (v) CT (100/5A) - 03 Nos OUTGOING:- (i) MCB 2 Pole of capacity 16-32 Amp, breaking capacity 10 KA with thermal release - 8 Nos (ii) MCB 4 Pole of capacity 32 Amp, breaking capacity 10 KA with thermal release - 4 Nos
Supply, installing, testing and commissioning out door type LT feeder piller box of suitable size, padestal mounted, CPRI type tested factory made totally enclosed, dust and vermin proof, double leaf shutter in front and single leaf shutter in rear side made of 3.00 mm thick CRCA sheet, framing with 50 x 50 x 6 mm thick MS angle iron and legs of size 0.5m long . duly fabricated and having proper locking arrangement in both front and rear door with 4 side slanting roof duly projected and painted to both internal and External surfaces with powder coating paint in heat process of sheet and suitable for 500 volts, 50 Hz, 3 phase 4 wire system and comprising with and including following accessories and mounted on PCC Plat form made out of PCC 1:2:4, 100 mm thick, 1 Mtr all round the panel board complete with the following items housed in : (FPB-8, 11 COMPO) Note :- 1. Danger notice plate should be fixed on both side of LT Panel 2. After installation of Panel each MCB should be indicated by painted that connection goes to which building 3. Rate of Earthwork, Excavation and PCC platform shall be deemed included in quoted rate.
Sr Item No.11.70 Condt/… A) BUSBAR :- 200 Amps rated Aluminium bus bar TPN duly insulated with coloured PVC sleeve as per standard colour code and rigidly mounted on bakelite/DMC insulator bus bar support (Square/round ) insulators of suitable size and good insulation resistance B) INCOMING:- (i) MCCB 4P of capacity 100 Amps, 415 Volts, 50 Hz, 3 phase breaking capacity 25 KA with thermal magnetic release - 01 No (ii) 3 Ph digital volt meter Class 1, 0-500 volts, 3 Phase, 4 digit with LED display - 01 No (iii) 3 Ph digital Amphere meter Class 1 accuracy , 0.5 VA burden with LED display - 01 No (iv) Modular indicator lamp with integral circuit (230V) and cluster LED (RED, YELLOW, BLUE) -01 set (v) CT (100/5A) -03 Nos C) OUTGOING:- (i) MCCB 4 Pole of capacity 40Amp, breaking capacity 16 KA with thermal release - 1 No (ii) MCB 2 Pole of capacity 16-32 Amp, breaking capacity 10 KA with thermal release -12 Nos
Supply,installing, testing and commissioning out door type LT feeder piller box of suitable size, padestal mounted, CPRI type tested factory made totally enclosed, dust and vermin proof, double leaf shutter in front and single leaf shutter in rear side made of 3.00 mm thick CRCA sheet, framing with 50 x 50 x 6 mm thick MS angle iron and legs of size 0.5m long . duly fabricated and having proper locking arrangement in both front and rear door with 4 side slanting roof duly projected and painted to both internal and External surfaces with powder coating paint in heat process of sheet and suitable for 500 volts, 50 Hz, 3 phase 4 wire system and comprising with and including following accessories and mounted on PCC Plat form made out of PCC 1:2:4, 100 mm thick, 1 Mtr all round the panel board complete with the following items housed in : (FPB-9, 11 COMPO) Note :- 1. Danger notice plate should be fixed on both side of LT Panel 2. After installation of Panel each MCB should be indicated by painted that connection goes to which building 3. Rate of Earthwork, Excavation and PCC platform shall be deemed included in quoted rate.
Sr Item No.11.71 Condt/… A) BUSBAR :- 100 Amps rated Aluminium bus bar TPN duly insulated with coloured PVC sleeve as per standard colour code and rigidly mounted on bakelite/DMC insulator bus bar support (Square/round ) insulators of suitable size and good insulation resistance B) INCOMING:- (i) MCCB 4P of capacity 63 Amps, 415 Volts, 50 Hz, 3 phase breaking capacity 16 KA with thermal magnetic release -01 No (ii)3 Ph digital volt meter Class 1, 0-500 volts, 3 Phase, 4 digit with LED display - 01 No (iii)3 Ph digital Amphere meter Class 1 accuracy , 0.5 VA burden with LED display - 01 No (iv) Modular indicator lamp with integral circuit (230V) and cluster LED (RED, YELLOW, BLUE) -01 set (v) CT (100/5A) - 03 Nos C) OUTGOING:- (i) MCB 2 Pole of capacity 16-32 Amp, breaking capacity 10 KA with thermal release -12 Nos
Supply,installing, testing and commissioning out door type LT feeder piller box of suitable size, padestal mounted, CPRI type tested factory made totally enclosed, dust and vermin proof, double leaf shutter in front and rear side made of 3.00 mm thick CRCA sheet, framing with 50 x 50 x 6 mm thick MS angle iron . duly fabricated and having proper locking arrangement in both front and rear door with 4 side slanting roof duly projected and painted to both internal and External surfaces with powder coating paint in heat process of sheet and suitable for 500 volts, 50 Hz, 3 phase 4 wire system and comprising with and including following accessories and mounted on PCC Plat form made out of PCC 1:2:4, 100 mm thick, 1 Mtr all round the panel board complete with the following items housed in : ( fpb-10, 11 cOMPO) Note :- 1. Danger notice plate should be fixed on both side of LT Panel 2. After installation of Panel each MCB should be indicated by painted that connection goes to which building 3. Rate of Earthwork, Excavation and PCC platform shall be deemed included in quoted rate.
Sr Item No.11.72 Condt/… A) BUSBAR :- 150 Amps rated Aluminium bus bar TPN duly insulated with coloured PVC sleeve as per standard colour code and rigidly mounted on bakelite/DMC insulator bus bar support (Square/round ) insulators of suitable size and good insulation resistance B) INCOMING:- (i) MCCB 4P of capacity 80 Amps, 415 Volts, 50 Hz, 3 phase breaking capacity 25 KA with thermal magnetic release -01 No (ii) 3 Ph digital volt meter Class 1, 0-500 volts, 3 Phase, 4 digit with LED display-- 01 No (iii) 3 Ph digital Amphere meter Class 1 accuracy , 0.5 VA burden with LED display-- 01 No (iv) Modular indicator lamp with integral circuit (230V) and cluster LED (RED, YELLOW, BLUE) -01 set (v) CT (100/5A) -03 Nos C) OUTGOING:- (i) MCCB 4 Pole of capacity 63 Amp, breaking capacity 16 KA with thermal release - 1 No (ii) MCB 2 Pole of capacity 32 Amp, breaking capacity 10 KA with thermal release -10 Nos
Supply,installing, testing and commissioning out door type LT feeder piller box of suitable size, padestal mounted, CPRI type tested factory made totally enclosed, dust and vermin proof, double leaf shutter in front and single leaf shutter in rear side made of 3.00 mm thick CRCA sheet, framing with 50 x 50 x 6 mm thick MS angle iron and legs of size 0.5m long . duly fabricated and having proper locking arrangement in both front and rear door with 4 side slanting roof duly projected and painted to both internal and External surfaces with powder coating paint in heat process of sheet and suitable for 500 volts, 50 Hz, 3 phase 4 wire system and comprising with and including following accessories and mounted on PCC Plat form made out of PCC 1:2:4, 100 mm thick, 1 Mtr all round the panel board complete with the following items housed in : (FPB-11, ADS) Note :- 1. Danger notice plate should be fixed on both side of LT Panel 2. After installation of Panel each MCB should be indicated by painted that connection goes to which building 3. Rate of Earthwork, Excavation and PCC platform shall be deemed included in quoted rate.
Sr Item No.11.73 Condt/… A) BUSBAR :- 80 Amps rated Aluminium bus bar TPN duly insulated with coloured PVC sleeve as per standard colour code and rigidly mounted on bakelite/DMC insulator bus bar support (Square/round ) insulators of suitable size and good insulation resistance B) INCOMING:- (i) MCCB 4P of capacity 40 Amps, 415 Volts, 50 Hz, 3 phase breaking capacity 16 KA with thermal magnetic release -01 No (ii) 3 Ph digital volt meter Class 1, 0-500 volts, 3 Phase, 4 digit with LED display - 01 No (iii) 3 Ph digital Amphere meter Class 1 accuracy , 0.5 VA burden with LED display - 01 No (iv) Modular indicator lamp with integral circuit (230V) and cluster LED (RED, YELLOW, BLUE) -01 set (v) CT (100/5A) -03 Nos C) OUTGOING:- (i) MCB 4 Pole of capacity 32Amp, breaking capacity 10 KA with thermal release - 1 Nos (ii) MCB 2 Pole of capacity 16-32 Amp, breaking capacity 10 KA with thermal release -14Nos
Supply Installation,Testing & Commissioning of SCADA compatible metal clad floor mounted vermin proof horizontal drawout and Horizontal isolation ,with posibility of future extension, fully interlocked vacuum circuit breaker(VCB) panel board fabricated out of minimum 2mm thick CRCA sheet powder coated of IP4X protection for operation on 11kV, 630Amp, breaking capacity 26.3 kA for 3 Sec and having rupturing capacity 500 MVA, 3 Phase, 50 Hz, AC supply system suitable for indoor installation, manufactured in conformation to IS 3427, IEC 62271-200, BS 5227, complete with power and control wiring, interconnections, three phase Copper Bus bar fully tinned and totally covered with colour coded heat shrinkable sleeves and non-hygroscopic, high dielectric strength, Bus bar support insulators comprising 01 No incomer and 1 Nos outgoing, having cable termination boxes suitable for armoured, aluminium conductor cable for incoming and outgoing feeder, foundation bolts etc. complete as required and as specified below :-
Sr. Item No. 11.74(Contd/...) (a) Incoming -01No (i)11 KV 630 Amps. Electrically/ manually operated draw out type vacuum circuit breaker complete with motor and spring charged closing mechanism. necessary auxiliary relays, control switches, emergency hand trip devices and mechanical ON / OFF indicator. (ii) Multifunction Meter showing all Electrical Parameterie Volt, Ampere, kw, kVA, P.F., kWH. (iii) Phase indication lamps with 2Amp SP MCB for protection (Red, Yellow and Blue). (iv) Double Through Spring Return TNC Switch.(v) Local / Remote Rotary Switch. (vi) Red/ Green indicating lamp for close and open position.(vii)Amber indicating lamp for auto trip.(viii) Clear indicating lamp for trip circuit healthy.(ix) Blue indicating lamp for spring charged.(x) Strip heater to prevent absorption of moisture.(xi) Three phase over current and earth fault digital numeric relay having Instantaneous and Inverse time phase over current protection (50/51),Instantaneous and Inverse time Earth fault protection(51/51N),Phase unbalance Protection(46) with 3 Nos. 11kV Resin Cast CTs of ratio100-50/1-1A CL 5P10, 15VA.(xii) Master Trip Relay.(xiii) Trip circuit supervision relay (xiv) potential transformer of 11 KV /v3/110/v3 V of suitable burden (xv) Power pack (230VAC -110V DC) (b) Out Going -01Nos (i) 11 KV 630 Amps. Electrically/ manually operated draw out type vacuum circuit breaker complete with motor and spring charged closing mechanism. necessary auxiliary relays, control switches, emergency hand trip devices and mechanical ON / OFF indicator etc. (ii) Multifunction meter showing electrical parameter such as, volt, ampere, Kw, Kwa, P.F, Kwh etc (iii) Phase indication lamp with 2Amp SP MCB for protection(Red, Yellow and Blue) (iv) Double Through Spring Return TNC Switch.(v) Local / Remote Rotary Switch. (vi) Red/ Green indicating lamp for close and open position. (vii) Amber indicating lamp for auto trip. (viii) Clear indicating lamp for trip circuit healthy. (ix) Blue indicating lamp for spring charged. (x) Strip heater to prevent absorption of moisture. (xi) Three phase over current and earth fault digital numeric relay having Instantaneous and Inverse time phase over current protection (50/51), Instantaneous and Inverse time Earth fault protection(51/51N),Phase unbalance Protection(46) with 3 Nos. 11kV Resin Cast CTs of ratio 50-50/1-1A CL 5P10, 15VA. (xii) Master Trip Relay. (xiii) Trip circuit supervision relay (xiv) Power pack (230VAC -110V DC) - 01 No for each panel.
Note : The VCB panel shall be of SCADA compatible with communicable port. (i) All meter shall be SCADA compatible having comunicable ports. (ii) The protection relay shall be SCADA compatible with communicable port. (iii) The VCB shall have adequate auxillary contacts(minimum 6 Nos + 6 Nos) wired up to terminal blocks and positioned on the rear side of the VCB panel and clearly identified for SCADA writing. The VCB panel shall have comunication port in front and rear fully prewired to terminal box and position micro switches including all inter connections. (iv) VCB & panels shall be of same make”.
Supply and fix elastomer Rubber mat of 1 m x 2 m as per IS: 15652: 2000, 2.5mm thick suitable for 11 KV AC (RMS) complete all as specified and directed.
Construction of on site LLDPE septic tank designed to carry sewage and sullage water for 50 users, including excavation in any type of soil, plain cement concrete 1:4:8 as in lean concrete, Vent shaft, connections and complete all as specified and as directed.
Construction of on site LLDPE septic tank designed to carry sewage and sullage water for 100 users, including excavation in any type of soil, plain cement concrete 1:4:8 as in lean concrete, Vent shaft, connections and complete all as specified and as directed.
Construction of on site LLDPE septic tank designed to carry sewage and sullage water for 150 users, including excavation in any type of soil, plain cement concrete 1:4:8 as in lean concrete, Vent shaft, connections and complete all as specified and as directed.
Construction of on site LLDPE septic tank designed to carry sewage and sullage water for 10 users, including excavation in any type of soil, plain cement concrete 1:4:8 as in lean concrete, Vent shaft, connections and complete all as specified and as directed.
M & L for soakage well of size 1.8 m dia and 3 m effective depth including Brick masonary intercepting chamber and screen chamber, including excavation in any type of soil earthwork, returning, filling in and removal of soil upto not exceeding 50m and as shown in TD drawing No. CESZ/2020/TD-45, sheet 1/2 & 2/2 complete all as specified and directed.
M & L for soakage well of size 2.4 m dia and 3 m effective depth including Brick masonary intercepting chamber and screen chamber, including excavation in any type of soil earthwork, returning, filling in and removal of soil upto not exceeding 50m and as shown in TD drawing No. CESZ/2020/TD-45, sheet 1/2 & 2/2 complete all as specified and directed.
M & L for soakage well of size 3 m dia and 4.5 m effective depth including Brick masonary intercepting chamber and screen chamber, including excavation in any type of soil earthwork, returning, filling in and removal of soil upto not exceeding 50m and as shown in TD drawing No. CESZ/2020/TD-45, sheet 1/2 & 2/2 complete all as specified and directed.
M & L for soakage well of size 1.2 m dia and 3 m effective depth including Brick masonary intercepting chamber and screen chamber, including excavation in any type of soil earthwork, returning, filling in and removal of soil upto not exceeding 50m and as shown in TD drawing No. CESZ/2020/TD-45, sheet 1/2 & 2/2 complete all as specified and directed.
Material & Labour for Plain Cement Concrete (1:3:6), type C-2 using 40 mm graded stone aggregate as in concrete bed to drain pipes of 180mm dia laid to falls in trenches in any depth including packing under and haunching against the sides of pipes with concrete after they are laid and tested complete all as specified and directed
Material & Labour for Plain Cement Concrete (1:3:6), type C-2 using 40 mm graded stone aggregate as in concrete bed to drain pipes of 240mm dia laid to falls in trenches in any depth including packing under and haunching against the sides of pipes with concrete after they are laid and tested complete all as specified and directed
Cutting into existing manholes for connecting new drains of size 180mm/240mm dia and forming branch channel, including making good to pipe and fixing branch channel with benching of PCC 1:2:4 type B-1 smooth finished, complete all as specified and directed.
Supply & fix DWCPE (SN 8) 180mm outer dia and 163mm inner dia pipe laid in trenches including connections and fittings complete all as specified and directed.
Supply & fix DWCPE (SN 8) 200mm outer dia and 175mm inner dia pipe laid in trenches including connections and fittings complete all as specified and directed.
Material & Labour for concealed point wiring with 1.5 Sq. mm (nominal cross sectional area) PVC insulated and un-sheathed single core FRLSH copper cable 1100 volts grade with multi-stranded copper conductor in and including PVC rigid concealed conduit and conduit accessories alongwith continuous earth wire 1.5 Sq mm PVC insulated and un-sheathed single core FRLSH cable 1100 volts grade with multi-stranded copper conductor and connected to common earth dolly, with and including 1.6 mm thick cadmium plated sunk MS pressed steel terminal boxes with 3 mm thick plastic laminated sheet cover fixed with brass screws complete for one light/fan/bell point controlled by one way switch.
Material & Labour for concealed point wiring with 1.5 Sq. mm (nominal cross sectional area) PVC insulated and un-sheathed single core FRLSH copper cable 1100 volts grade with multi-stranded copper conductor in and including PVC rigid concealed conduit and conduit accessories alongwith continuous earth wire 1.5 Sq mm PVC insulated and un-sheathed single core FRLS cable 1100 volts grade with multi-stranded copper conductor and connected to common earth dolly, with and including 1.6 mm thick cadmium plated sunk MS pressed steel terminal boxes with 3 mm thick plastic laminated sheet cover fixed with brass screws complete for one socket outlet point 6 Amp on same board.
Material & Labour for concealed point wiring with 1.5 Sq. mm (nominal cross sectional area) PVC insulated and un-sheathed single core FRLSH copper cable 1100 volts grade with multi-stranded copper conductor in and including PVC rigid concealed conduit and conduit accessories alongwith continuous earth wire 1.5 Sq mm PVC insulated and un-sheathed single core FRLS cable 1100 volts grade with multi-stranded copper conductor and connected to common earth dolly, with and including 1.6 mm thick cadmium plated sunk MS pressed steel terminal boxes with 3 mm thick plastic laminated sheet cover fixed with brass screws complete for one socket outlet point 6 Amp on independent board.
Material & Labour for concealed point wiring with 4 Sq. mm (nominal area) PVC insulated and un-sheathed single core FRLSH copper cable 1100 volts grade with multi-stranded copper conductor in and including PVC rigid concealed conduit and conduit accessories alongwith continuous earth wire 4 Sq mm PVC insulated and un-sheathed single core FRLSH cable 1100 volts grade with multi-stranded copper conductor and connected to common earth dolly, with and including 1.6 mm thick cadmium plated sunk MS pressed steel terminal boxes with 3 mm thick plastic laminated sheet cover fixed with brass screws complete for one16 Amps socket outlet on independent board.
Sub main wiring with two runs of single core FRLS PVC insulated and unsheathed multistranded, copper conductor cable of size 6.0 Sq mm (nominal area), 1100 volts grade drawn through and including adequate size PVC concealed conduit and accessories (IS-694 marked in PVC conduit) and fittings and one run of 6.0 Sq mm single core FRLS multistranded copper conductor cable as earth continuity conductor. NOTES :- (a) Two runs of copper conductor, one run of earth wire and one run of conduit shall be measured as one run length.
Supply and fix MCB Single Pole and Neutral 240 volts, 32 Amps, 10KA rupturing capacity, 'C' series complete all as specified.
Supply and fix MCB Single Pole 240 volts, 6Amps to 32 Amps, 10KA rupturing capacity, 'C' series complete all as specified.
Preparation & submission of soil investigation report in sixupulate by conducting soil investigation with trial pit of size 1.2 x 1.2 x 1.2m after making bore holes 150 mm dia in any type of soil up to max 6.0 m depth or upto the depth of refusal, collecting, disturbed and undisturbed samples, conducting standard penetration test (SPT) at 1.5 mtr interval thereafter or on change of strata and laboratory test like Direct/Triaxial shear test, Grain distribution curves & pattern in bore holes, Type of soil, C value, Bulk density, Natural moisture content, Dry density, Water table, Specific gravity, Atterberg limit, Hydrometer analysis, Liquid & Plastic limit, Swelling Index, Evaluation of liquifaction potential IS-1893 Part I -2016.
Sr. Item No.11.96 Contd/…. Compilation of Field and Laboratory test results, Preparation of reports, Recommendation for depth of embedment, water table, submission of all report booklets 06 (Six) copies with CD 01 (One) copy including photographs & videography duly indicating the following :- (i) Evaluation of safe bearing capacity of the soil with respect to shear failure test and permissible settlement (Total and Differential) alongwith recommendation about type of foundation and minimum depth of foundation to be adopted for subject work. (ii) Evaluation of liquefaction potential. (iii) Evaluation of K-value. (iv) Specific suggestions if any for Soil Treatment if required below foundation /ground floor / roads and type of treatment to be carried out. (v) Bore log diagram duly showing the different layers of strata met alongwith their depths. Note : (i) Each bore hole will be measured upto depth of refusal or 6.00 m whichever is earlier. (ii) Rate includes mobilsation of T&P as per requirement and direction of the Engr-in-Charge. (iii) Rate includes Vetting of geotechnical investigation report from any NIT(National Institute of Technology)/IITs(Indian Institute of Technology) and submit hard copy & soft copy in Six numbers/sets for approval of accepting officer.
Preparation & submission of soil investigation report in sixupulate by conducting soil investigation with trial pit of size 1.2 x 1.2 x 1.2m after making bore holes 150 mm dia in any type of soil up to max 15.0 m depth or upto the depth of refusal, collecting, disturbed and undisturbed samples, conducting standard penetration test (SPT) at 1.5 mtr interval thereafter or on change of strata and laboratory test like Direct/Triaxial shear test, Grain distribution curves & pattern in bore holes, Type of soil, C value, Bulk density, Natural moisture content, Dry density, Water table, Specific gravity, Atterberg limit, Hydrometer analysis, Liquid & Plastic limit, Swelling Index, Evaluation of liquifaction potential IS-1893 Part I -2016.
Sr. Item No.11.97 Contd/…. Compilation of Field and Laboratory test results, Preparation of reports, Recommendation for depth of embedment, water table, submission of all report booklets 06 (Six) copies with CD 01 (One) copy including photographs & videography duly indicating the following :- (i) Evaluation of safe bearing capacity of the soil with respect to shear failure test and permissible settlement (Total and Differential) alongwith recommendation about type of foundation and minimum depth of foundation to be adopted for subject work. (ii) Evaluation of liquefaction potential. (iii) Evaluation of K-value. (iv) Specific suggestions if any for Soil Treatment if required below foundation /ground floor / roads and type of treatment to be carried out. (v) Bore log diagram duly showing the different layers of strata met alongwith their depths. Note : (i) Each bore hole will be measured upto depth of refusal or 15.00 m whichever is earlier. (ii) Rate includes mobilsation of T&P as per requirement and direction of the Engr-in-Charge. (iii) Rate includes Vetting of geotechnical investigation report from any NIT(National Institute of Technology)/IITs(Indian Institute of Technology) and submit hard copy & soft copy in Six numbers/sets for approval of accepting officer.
Material and Labour for 80mm thick factory made chamfered edge cement concrete paver block with grey cement and pigments of M-40 grade with approved colour, design & pattern as in footpath, parks, lawns, drive ways or light traffic parking etc., of required strength & size/ shape, made by table vibratory method using PU mould, laid in required colour & pattern, compacting and proper embedding/ laying of inter locking paver blocks into the sand bedding layer through vibratory compaction by using plate vibrator, filling the joints with fine sand and cutting of paver block as per required size and pattern, finishing and sweeping extra sand complete all as specified and directed. Note: Sand filling shall be measured and paid separately.
Material and Labour for 80mm thick factory made chamfered edge cement concrete paver block with grey cement and no pigments of M-40 grade with approved colour, design & pattern as in footpath, parks, lawns, drive ways or light traffic parking etc., of required strength & size/ shape, made by table vibratory method using PU mould, laid in required colour & pattern, compacting and proper embedding/ laying of inter locking paver blocks into the sand bedding layer through vibratory compaction by using plate vibrator, filling the joints with fine sand and cutting of paver block as per required size and pattern, finishing and sweeping extra sand complete all as specified and directed. Note: Sand filling shall be measured and paid separately.
SCHEDULE 'A' PART-XII ( PRIME COST SUM) Note : This schedule is not pre-priced by MES and the pre-priced rate indicated as "Rs 0.00" under Col. 5 siginifies this fact only.
Rate worked out by the tenderer for Prime cost sum of Rs.1,41,000/- for following items of work: Prime cost sum for provision of 2 Nos of multi stage submersible pump set with suitable electric motor, starter, discharge pressure gauge, depth gauge and all connected accesories. Note: (i) The motor casing shall be of stainless steel, pump shaft/ motor shaft shall be of stainless steel, (ii) Pump bowls shall be of high graded cast iron. (iii) The capacity of pump set can be ascertained after yield testing of borewell. (iv) Contactor shall be quote, contractors percentage(amount) plus/minus pre-prices amount.
ms singh construction
M/s Singh enterprises
M/s NARAYAN MUKHERJEE & CO
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .