Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹8.2 LAccepted-AOC | L1 | Accepted-AOC L1 Bidder lowest | |
| 2 | L2₹12.8 L+₹2.8 L (28.3%)Rejected-Finance 712 GORAKHPUR JABALPUR 482001 MP | JABALPUR | MADHYA PRADESH | 482001 | L2 | Rejected-Finance Other than L1 | |
| 3 | L3₹13.8 L+₹3.8 L (38.5%)Rejected-Finance 37A 115 MADHU NAGAR AGRA 282001 UP | AGRA | AGRA | UP | 282001 | L3 | Rejected-Finance Other than L1 | |
| 4 | L4₹18.8 L+₹8.8 L (87.8%)Rejected-Finance MAIN ROAD RANJHI BAZHAR JABALPUR MP PIN 482005 | JABALPUR | MADHYA PRADESH | 482005 | L4 | Rejected-Finance Other than L1 |
Tender Value
₹20 L
EMD Value
₹40,000
Closing Date
17 Dec 2019, 6:00 pmClosed
GE (West) Jabalpur
Garrison Engineer (West) Jabalpur Supply Marg Post Box No. 54 Jabalpur Cantt-482001 (MP)
REPAIR MAINTENANCE AND REPLACEMENT OF CEILING FANS, EXHAUST FANS GEYSER AND OTHER RELATED WORKS UNDER GE (WEST) JABALPUR
2019_MES_295452_1
8194/E8
Open Tender
Electrical and Maintenance Works
Item Rate
150 days
GE (West) Jabalpur
AS per Tender documents
6 documents required · 6 mandatory
₹500
GE (West) Jabalpur
₹40,000
8 Jan 2020
6 Nov 2019
19 Dec 2019
6 Nov 2019
17 Dec 2019
20 Nov 2019
Amount
M&L for Rewinding of ceiling fans including opening of fan, Removing the burnt copper winding of ceiling fan after testing and cutting the rotor coil complete and making clean the rotor & the stator and rewinding with and including super enamelled copper wire of approved quality of existing gauge, over-hauling, lubricating with fresh grease including assembling with replacement of unserviceable parts (to be measured & paid seperately) and testing for satisfatory operation complete for the following .
(a). 1200mm sweep .
(b) 1400mm sweep
M&L for Rewinding of Exhaust fans including opening of fan,Removing the burnt copperwinding of ceiling fan after testing and cutting the rotor coil complete and making clean the rotor & the stator and rewinding with and including super enamelled copper wire of approved quality of existing gauge, over-hauling,lubricating with fresh grease including assembling with replacement of unserviceable parts (to be measured & paid seperately) and testing for satisfatory operation complete for the following
(a). 450mm sweep .
(b) 375/300 mm sweep
M&L for Rewinding of Tablet/Bracket fans including opening of fan, removing the burnt copper winding of ceiling fan after testing and cutting the rotor coil complete any make cleaning the rotor & the stator and rewinding with and including super enamelled copper wire of approved quality of existing gauge, over-hauling, lubricating with fresh grease including assembling with replacement of unserviceable parts (to be measured & paid seperately) and testing for satisfatory operation complete for 400mm sweep.Note for item No 1 to 3: Contractor shall to collect fans from AGE E/M Electric store yard & deposit the repaired fans in AGE E/M Store yard
M & L for Opening of ceiling fan of any make and any sweep for over-hauling complete including providing fresh clean lubricating Oil/ grease, reassembling for proper functioning , with replacement of unserviceable parts (to be measured & paid seperately) and testing for satisfatory operation complete for the following .
(a). 1200mm sweep .
(b) 1400mm sweep
M & L for Opening of Exhaust fan of any make and any sweep for over-hauling complete including providing fresh clean lubricating Oil/ grease, reassembling for proper tunning, with replacement of unserviceable parts (to be measured & paid seperately) and testing for satisfatory operation complete for the following :
(a). 450mm sweep .
(b) 375/300 mm sweep
Supply only in replacement of ball bearing of 6201/120 for ceiling fan/ exhaust fan of any size and make complete. Make : NBC, SKF, TATA
Ditto all as per above items but 6202/115 complete. Make : NBC, SKF, TATA
Ditto all as per above items but 6203/117 complete. Make : NBC, SKF, TATA
Ditto all as per above items but 6204/118 complete. Make : NBC, SKF, TATA
Supply only in replacement of condenser 2.5 MFD of apporved make forceiling fan complete. Make : ED cos, Scimanse, Unic
Ditto all as per above items but 4.0 MFD for exhaust fan complete. Make : ED cos, Scimanse, Unic
Supply only in replacement of self lubricating bush of gun metal of same make for ceiling fan/exhaust fan complete.
Supply only in replacement of shaft of approved quality for ceiling fan/Exhaust fan any make and type & size complete.
S&F in replacement of split pin suitable for ceiling fan/ exhaust fan any make and type & size complete.
S&F in replacement of PVC flexible 3 core cable with copper con-ductor of size 16/0.20 mm from ceiling rose to fan including connection complete.-
Supply & Fixing in repairs ceiling Fan 1200mm sweep with electronic fan regulator, down rod , canopy, rubber reel etc including provision of three single core 0.5 sqmm copper conductor flexible cable connected from ceiling rose to fan and suitable size MS bolts, nuts for fixing ceiling fan complete all as specified and directed. Make : Usha, Bajaj, Havells Note :- Old U/S Fan shall be diposited in MES Store yard
M&L for painting of ceiling fan including preparing the surface of body/blades of ceiling fan of any sweep and make and painting with 2 coats of synthetic enamel white paint and writing the MES No. with black paint 2.5 cm height letters comlete.
M&L for painting of exhaust fan including preparing the surface of body/blades/frame of of exhaust fan of any sweep and make and painting with 2 coats of synthetic enamel Grey paint and writing the MES No. with black paint 2.5 cm height letters comlete.
M&L for Hanging only ceiling fan and connecting up with point wiring complete for satisfactory functioning complete with PVC flexible 3 core copper conductor cable. Note: (i) Ceiling fans for hanging in the buildings with regulator shall be issued by Engineer-in-charge on proper issue voucher & receipt voucher after repair.
S&F in repairs rubber seal suitable for ceiling fan of any make and size.
S&F in repairs GI pipe medium grade with all fitting and fixed complete for ceiling fan as down rod of 15 mm bore.
S&F in replacement GI pipe 40mm medium grade with all fitting and fixed complete for hanging of ceiling fan .
M&L in replacement for clamps and back plates fabricated from steel section conforming to Gde Fe 410-0 or Fe 310-0 includingnuts, bolts, washers, drilling holes for bolts in any shape or size for fixing ceiling fan complete weighing not more than 2Kg.
Supply & Fixing in replacement Wall mounting fan 400mm sweep complete. Make Almonard/Bajaj/ Havells. Note :- Old UNSV Fan shall be dipossited in MES store yard .
M& L for comprehensive maintenance and overhauling of ceiling fans at site of any make and size including following works (a) Checking proper working of ceiling fans. (b) Checking of safety pin/sockets/clamps including replacement of unseviceable part (c) Replacement of unserviceable condenser/bearings. (d) Cleaning of ceilingfan/overhauling with fresh grease. ( e). Note : 1.Contractor has to depute Two electricians daily who will report to JE /Fan incharge. 2 Unserviceable parts to be measured & paid seperately under relevant item of Sch A..3.All T & P and ladder provide to electrician at site by contractor.
Taking down carefully storage type water heater any make and capacity from clamps/bolts including disconnection water and electric connection and refixing the same and connecting up after cleaning of geyser and repairs complete.
Repair of inner flange of 25/50 Ltrs geysers and replacement of worn-out stud brazing with gas welding not exceeding 5mm thick complete.
Supply and fix in replacement geyser flange assembly (any make/type) copper alloy chromium plates suitable for 25 Ltrs capacity including rubber gasket, clamps and nuts/bolts etc complete. Make : Recold ditz, Bajaj ISI mark.
Ditto all as per above item but 50 Ltrs complete. Make : Recold,Ditz, Bajaj ISI mark.
Supply and fix and connecting heating element ( triangular or circular base type) 1.5 KW 230 volts suitable for 25 ltrs capacity geysers in replacement of old unserviceable heating element complete.Make : Hot Pace, Power Pace, Das Pass ISI mark.
Supply and fix and connecting heating element ( triangular or circular base type) 2 KW, 230 volts suitable for 50 ltrs capacity geysers in replacement of old unserviceable heating element complete ,Make : Hot Pace, Power Pace, Das Pass ISI mark.
Supply only in replacement thermostat of existing type/make complete
Supply only in replacement indicating lamp, 230 volts rectangular type complete.
Fixing and connecting only geyser 25/50 ltrs capacity including necessary GI fittings and electric connection complete Note: Geysers shall issued under schedule 'B' free for fixing
S&F in replacement GI tube medium grade 15mm bore fixed to wall/geyser into short places including cutting, screwing, threading and all GI fittings (including union, socket if required) complete.
S&F in replacement geyser bottom cover complete including machine screws etc. as per original size and shape of any make of geyser 25 ltrs capacity complete.
Ditto all as per above item but 50 ltrs capacity complete.
S&F brass chromium plated flexible pipe connection heavy duty suitable for hot water supply with two Nos brass chromium plated union 450 mm long in replacement of PVC pipe connection complete
S&F in replacement non return valve of 15mm size of brass for geyser (weight of valve shall not be less than 400 grams) complete.
M&L for painting of geyser with two coats of synthetic enamel white paint and writing the MES No. (letter not less than 1.5 cm height)for 25 ltrs capacity geyser of any make and type complete.
Ditto all as per above item but 50 ltrs capacity complete.
S&F in replacement stop valve cast copper alloy 15mm bore a tinlet or outlet connection of geysers.
S&F in replacement PVC insulated over all PVC sheathed three core copper cable of size 40/0.193 including disconnection of old cable complete.
S&F Pressure release valve suitable for 25/50 ltrs any make any type of geyser complete in replacement of dead weight.
Removing old glass wool for the geysers and providing new glass wool of equal thickness and specification :-
(a) Capacity 25 Ltrs
(b) Capacity 50 Ltrs
S&F in repair three pin top15 Amp 240 volts complete all as specified directed
S&F in repair Top for ;earth plug socket 20 Amps AC 240 Volts complete all as specified and dierected by Engineer in charge/
S&F in repair single pole and neutral enclosure with a two pin and earth plug and socket complete with one MCB SP 20/32 Amps complete all as directed by Engineer-in-Charge.
Supply ,fixing, connection and testing exhaust fan single phase 240 Volts AC 50 Hz with louvers of size 300 mm sweep including cutting holes in wall and 3 core copper wire of size 0.50 sqmm for connection complete all as specified and directed of Make : Usha, Bajaj, Philips Note :- Old UNSV Exhaust Fan shall be diposited in MES Store yard
M&L for making opening by cutting/chasing existing PCC/Masonary wall for fixing of exhaust fan of 300mm/450 mm sweep capacity including grouting of foundation bolts complete plastering and making good distrubed surface good complete all as specified and directed.
S & F in repair Water heater storage type, electric supplied and installed complete capacity 25 litres. Make : Bajaj, Recold Note :- Old UNSV water heater shall be deposited in MES Store yard
S&F in repair safety valve suitable for geyser 25/50 liters as per sample
Taking down carefully any type of old unserviceable point wiring copper or aluminium conductor (light, fan, socket, bell or power) point complete with fittings such as switches ceiling roses, lamp holders, sockets, fan regulators, call bell, light fittings with PVC conduit surface / concealed or wooden battens including sunken cast iron / pressed steel terminal boxes etc and making good the disturbed surfaces of walls, roof, floors etc to match with the existing surfaces complete all as specified & directed by Engineer-in-Charge.
Taking down carefully old unserviceable main switches / distribution boards complete of any size complete all as specified & directed.
Taking down carefully and re-fixing ceiling fan / Exhaust fan of any sweep with 1.5 Sqmm new copper wire upto ceiling rose complete all as specified and directed.
S& F in repair Sub main wiring with two single core PVC Insulated cable two run of size 6.0 Sqmm multi-strand copper conductor FRLS cable 1100 volts grade drawing in and including PVC conduit, medium grade not less than 25 mm dia with all conduit accessories and one run of 4.0 Sqmm multi-strand copper conductor FRLS cable as continuous earth wire complete all as specified and directed. Note : - Two run of 6.0 Sqmm & one run of 4.0 Sqmm cable shall be measured as one unit run.
S&F in repair Sub main wiring with two single core PVC Insulated cable two run of size 4 Sqmm multi-strand copper conductor FRLS cable 1100 volts grade drawing in and including PVC conduit, medium grade not less than 25 mm dia with all conduit accessories and one run of 2.5 Sqmm multi-strand copper conductor FRLS cable as continuous earth wire including making good disturbed surface to match existing complete all as specified & directed. Note : - Two run of 4 Sqmm & one run of 2.5 Sqmm cable shall be measured as one unit run.
Supply & fixing in repair 25 mm dia non mettalic Rigid PVC conduit, ISI Marked conforming to IS : 9537 medium grade Including all fittings like bends, elbow reducer, junction boxes, tee bell mouth fixing accessories such as coupler lock, nuts, saddles pipe hooks etc complete including cutting & chasing required on brick wall not exceeding 10 CM girth for concealed conduit wiring and making good to disturbed surface with cement mortar 1:3 and treated with distemper or colour wash to match with existing surfaces complete all as specified & directed.
Material & Labour for concealed Point wiring with three layer PVC Insulated 1.5 Sqmm multi-strand copper conductor FRLS cable 1100 Volts grade drawn into and including concealed PVC conduit medium grade not less than 20mm (ISI marked) including all fitting and fixing accessories including 1.25 mm thick sunken pressed steel terminal boxes duly painted with two coats of anti-corrosive paint outside and two coats of aluminium paint inside with and including 3mm thick hylam brand laminated white bakelite sheet cover for mounting switches, sockets, fan regulators fixed with CP screws with cup washers and PVC insulated 1.5 Sqmm multi-strand copper conductor cable as earth wire and making good the disturbed surfaces with cement sand mortar 1:3 to match with the existing surfaces complete all as specified & directed by Engineer-in-charge.
(a) One light point controlled by one switch.
(b) One fan point controlled by one switch.
(c) One socket point 5 Amp controlled by one switch on same board.
(d) One socket point 5 Amp controlled by one switch on Independent board.
(e) One socket point 5 Amp controlled by one switch on Independent board below the switch board.
(f) One bell point controlled by one bell push button independent board.
Description same all as per item No. 10 here in above but with 1100 Volts grade copper stranded conductor FRLS cable of size 2.5 Sqmm main & with 1.5 Sqmm earth multi-strand copper conductor cable as earth wire for 3 pin switch socket outlet 15 Amp on Independent board complete all as specified & directed by Engineer-in-Charge.
Supply & Fixing switch piano flush button type single pole one way 5 Amps of polycarbonate complete all as specified & directed.
Supply & fixing of call bell ding dong sound type suitable for AC 240 volt single pole complete all as specified & directed.
Supply & Fixing switch bell push flush type suitable for 5 Amp 230 Volt of polycarbonate body complete all as specified & directed.
Supply & Fixing socket outlet 2 in 1, 5 Pin 5 Amp flush type of polycarbonate body complete all as specified & directed.
Supply & Fixing Switch socket combination 2 in 1, 3 pin / 5 Amp and 15 Amps flush type universal of polycabonate body complete all as specified & directed.
Supply & Fixing lamp holder / batten or angle holder Insulated body with back plate suitable for batten fittings complete all as specified & directed.
Supply & Fixing in repair 9 Watt capacity LED lamp fixed in lamp holder complete all as specified & directed.
Supply & Fixing Ceiling rose surface type 60x30 mm three terminals of polycarbonate body complete all as specified & directed.
Supply & Fixing Ceiling Fan regulator electronic ROTARY / Step type 120 / 280 Watt capacity of ploycarbonate body ISI marked complete all as specified & directed.
Supply & Fixing in repair 20 watt LED tube light fitting four feet long box type high efficiency aluminum linear batten type along with fixed on surface / wall or Pendent mounting Luminaires connector block etc, with all accessories internally pre-wired and connecting up with three core flexible flexible copper conductor cable suitable size complete all as specified & directed. Make : Wipro Cat Part No. LL20-281-65AL1 or equivalent make & model in Philips / Crompton
S&F in repair LED Mirror light fitting 12 watt along with fixture Surface mounted suitable for indoor aplication , connector block, etc . Complete with all accessories internally pre-wired and including round wood block, connecting up with three core flexible flexible copper conductor cable suitable size complete all as specified and directed by Engineer in charge. Make Luker code no LMR 10 or Wipro or equvalent philips/syaska
Supply and fixing in repair of decorative wall light fitting 1x14 watt made up of Polycarbonate, Cylindrical shape , with LED lamp complete with fixing arrangements on wall all as specified and directed. make luker light code no LWL-110-2 or equivalent Havells or equivalents Bajaj/Philips/CG as approved by GE(I)
Supply & Fixing in repair Bulk head endura LED light fitting complete with10 watt LED and making necessary electric connection to ceiling rose with copper conductor of suiyable size & length complete all as specified & directed. Make : Havells Cat Part No. RUGBY NEONFT10WLED760SSYMBOPC or Equivalent make & model in Philips / Crompton
Supply & Fixing in repair sheet metal enclosure MCB DB double door [Acrylic], single pole and neutral, 240 volts, 8 way with 200 Amp, 10 KA breaking capacity rated bus bar with blanking plate wherever required and IP-43 degree protection complete all as specified & directed.
Supply & Fixing sheet metal enclosure MCB DB double door [Acrylic], Triple pole and neutral, 440 volts, 4 way with 200 Amp, 10 KA breaking capacity rated copper bus bar with blanking plate wherever required and IP-43 degree protection complete all as specified & directed. Make : Legrand / ABB / Schinider
Supply & Fixing MCB Triple Pole and Neutral 63 Amps,10KA breaking capacity complete all as specified & directed. Make : Legrand / ABB / Schinider
Supply & Fixing MCB Single Pole and Neutral 240Volt, 32 Amps,10KA breaking capacity complete all as specified & directed. Make : Legrand / ABB / Schinider
Supply & Fixing MCB Single Pole 240Volt, 6 to 32Amps,10KA breaking capacity complete all as specified & directed. Make : Legrand / ABB / Schinider
Material & Labour for earthing complete with galvanised steel earth plate electrode of size 600mm x 600mm x 6mm thick burried directly in ground (Earth pit not less than 2.25 m deep below the normal ground level with top edge of earth plate not less than 1.5 m below normal ground level) connected to galvanised earth wire 4 mm dia as earth wire or earthing lead by means of bolts, nuts, check nuts and washers of GI or steel complete as shown in Electrical Plate No. 3 of SSR-2009 (Part-I) including charcoal dust, common salt, 20mm bore GI medium grade watering pipe, MS Sheet funnel with wire mesh, including 15mm dia GI pipe light grade for protection of GI earth wire including PCC pit 1:2:4 type B-1 using 20mm graded crushed stone aggregate with angle iron 40X40X5mm frame 60mm thick RCC cover with 8mm # TMT bars @ 100 mm centre to centre both ways i.e. horizontal and vertical complete all as directed by Engineer-in-charge and testing for required value complete.
RAVI TEJ BUILDERS
M/s Om Infracon
ELCON
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .