Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹1.9 CrAdmitted-Finance | ₹1.9 Cr | L1 | Admitted-Finance |
| 2 | L2₹2.2 Cr+₹23.0 L (11.8%)Admitted-Finance | ₹2.2 Cr+₹23.0 L (11.8%) | L2 | Admitted-Finance |
| 3 | L3₹2.2 Cr+₹30.5 L (15.7%)Admitted-Finance | ₹2.2 Cr+₹30.5 L (15.7%) | L3 | Admitted-Finance |
| Sl No | Description | Qty | Unit | J.L. Enterprises L1 | M/S-Sonkar Enterprises L2 | NIKHIL ENTERPRISES L3 |
|---|---|---|---|---|---|---|
| 1.00Supply of Materials and Erection for Construction of 33/ 11 KV New Sub Station (1X5) MVA Pure Iswarnathpur Distt. Pratapgarh and its associated 33 KV and 11 KV Line in Nagar Nikay Plan 2024-25 on "Turnkey Basis" (Without Transformer) under EDC, Pratapgarh ( As per RESSPO Norms.) | ||||||
| 2.00A - Supply of Centralised Materials | ||||||
| 3.00 | PCC POLE 09 MTR. LONG | 179 | NO. | 8,05,500 ₹9,50,490 | 8,51,503 ₹10,04,773.54 | 17,900 ₹21,122 Lowest |
| 4.00 | STP POLE 11 MTR. LONG | 39 | NO. | 7,80,000 ₹9,20,400 | 7,93,884 ₹9,36,783.12 | 3,900 ₹4,602 Lowest |
| 5.00 | 33 KV V TYPE CROSS ARM | 181 | No | 2,53,400 ₹2,99,012 | 2,37,834 ₹2,80,644.12 | 18,100 ₹21,358 Lowest |
| 6.00 | 33KV MS TOP CHANNEL | 25 | No | 47,500 ₹56,050 | 48,150 ₹56,817 | 2,500 ₹2,950 Lowest |
| 7.00 | 33KV DISC FITTING (B&S) DOG/RACOON 70 KN | 102 | No | 35,700 ₹42,126 | 35,802 ₹42,246.36 | 10,200 ₹12,036 Lowest |
| 8.00 | COMPOSITE POLY. DISC INSULATOR 70KN B&S | 102 | No | 30,192 ₹35,626.56 | 30,192 ₹35,626.56 | 10,200 ₹12,036 Lowest |
| 9.00 | 33 KV COMPOSITE POLYMER PIN INSULATOR | 600 | No | 2,40,000 ₹2,83,200 | 2,51,400 ₹2,96,652 | 60,000 ₹70,800 Lowest |
| 10.00 | STAY WIRE GI(7/4.0MM) 7/8 SWG | 714 | KG | 60,690 ₹71,614.2 Lowest | 60,690 ₹71,614.2 Lowest | 71,400 ₹84,252 |
Tender Value
₹1.7 Cr
EMD Value
₹1.7 L
Closing Date
29 Mar 2025, 12:00 pmClosed
Superintending Engineer
Superintending Engineer, E.W.C., 177, Alenganj, Prayagraj
Supply of Materials and Erection for Construction of 33/ 11 KV New Sub Station (1X5) MVA Pure Iswarnathpur Distt. Pratapgarh and its associated 33 KV and 11 KV Line in Nagar Nikay Plan 2024-25 on Turnkey Basis (Except Transformer) under EDC, Prata
2025_PVVNV_1016448_1
18/EWCP/2024-25
Open Tender
Electrical Works
Turn-key
360 days
Pratapgarh
Supply of Materials and Erection for Construction of 33/ 11 KV New Sub Station (1X5) MVA Pure Iswarnathpur Distt. Pratapgarh and its associated 33 KV and 11 KV Line in Nagar Nikay Plan 2024-25 on Turnkey Basis (Except Transformer) under EDC, Prata
2 documents required · 2 mandatory
₹11,800
Account Number 914020010003107
₹1.7 L
2 Apr 2025
12 Mar 2025
29 Mar 2025
12 Mar 2025
29 Mar 2025
12 Mar 2025
Supply of Materials and Erection for Construction of 33/ 11 KV New Sub Station (1X5) MVA Pure Iswarnathpur Distt. Pratapgarh and its associated 33 KV and 11 KV Line in Nagar Nikay Plan 2024-25 on "Turnkey Basis" (Without Transformer) under EDC, Pratapgarh ( As per RESSPO Norms.)
A - Supply of Centralised Materials
PCC POLE 09 MTR. LONG
STP POLE 11 MTR. LONG
33 KV V TYPE CROSS ARM
33KV MS TOP CHANNEL
33KV DISC FITTING (B&S) DOG/RACOON 70 KN
COMPOSITE POLY. DISC INSULATOR 70KN B&S
33 KV COMPOSITE POLYMER PIN INSULATOR
STAY WIRE GI(7/4.0MM) 7/8 SWG
STAY ROD 20X1800 M.M.
G.I.WIRE 6 SWG
G.I.WIRE 8 SWG
T-OFF channel (100X50X50X6mm)for 33 kv L
33KV GAURDING ANGLE
EARTH ROD 2500X20 MM
33KV BRACING ANGLE
Dropper Channel for 33 KV Line
33KV XLPE Al. Cable 3x300mm2
A.C.S.R. DOG CONDUCTOR
A 1 - Supply of De-Centralised Materials
33 KV Cross arm holding clamps with N&B
Cable jointing kit for 3x300 XLPE 33 KV
33 KV STRAIGHT THROUGH 3X300 XLPE CABLE
E- BRACKET WITH BOLT & NUTS FOR 11 Mtr. STP
F-BRACKET
NUT BOLT WITH WASHER OFF SIZE
G.I.PIPE 6" DIA
P.G. CLAMP FOR DOG TO DOG CONDUCTOR
33 KV BRACING CLAMP WITH NUT & BOLT
TOP CHANNEL CLAMP FOR 11 MTR. ST POLE
PG CLAMP DOG TO PANTHER CONDUCTOR
DANGER BOARD WITH CLAMP FOR 33 KV LINE
BARBED WIRE
Aluminium Paint
Red oxide Paint
A 2 - Carriage of following material
PCC Pole 9 Mtr. Long-179 No., ST Pole 11 Mtr. Long-39 No. 33 KV V-type cross arm, 33 KV M.S Top channel, 33 KV Disc Fitting, 33 KV Disc Insulator, 33 KV Pin Insulator, 3x300 sqmm 33 KV XLPE Cable, ACSR Dog Cond. 33 KV Cable jointing kit 3x300 sqmm, 33 KV Bracing clamp, 33 KV P.G Clamp etc.
A 3 - Erection work
Digging of pits of size 0.45x1.25x 1.50 mtr. for erection of STP pole 11 mtr. Long.
Erection of single STP pole of 11 mtr long.
Mounting and fitting of V-type cross arm, 33 KV pin, pin insulator, earth clamp complete in all respect as per drawing of RESPO on single STP pole 11 mtr long.
Mounting and fitting T-off Channel with clamp
Fabrication, mounting and fitting of top channel, bracing made of m.s. angle, earth clamp, 33 KV pin & pin insulators, disc insulator and disc fitting on STP . double pole.
Fabrication, mounting and fitting of M.S Channel ,33 KV disc insulator and disc fitting on STP . double pole for riser
Fabrication, mounting and fitting of top channel, bracing made of m.s. angle, earth clamp, 33 KV pin & pin insulators, disc insulator and disc fitting on STP . Tri pole.
Fabrication, mounting and fitting of top channel, bracing made of m.s. angle, earth clamp, 33 KV pin & pin insulators, disc insulator and disc fitting on STP . Four pole.
Painting of single STP pole 11 mtr long .
Grouting of ST pole 11 Mtr. long with cement, sand and brick bllast ratio 1:4:8 size 0.45x 0.45x 1.5 mtr deep under the ground as per drawing No. RES-6. Cement, sand, brick, ballast shall be provided by the contractor.
Digging of pits of size 0.60x 0.60x1.2 mtr and grouting the stay rod anchor plates 0.45x 0.45x 0.45 mtr with cement, Ganga sand and brick ballast ratio 1:4:8 as per drawing No. RES-16. Cement, sand, brick, ballast shall be provided by the contractor.
Complete fitting of stay rod and fastening stay wire including fitting of stay clamp, turn buckle, and making ring of stay wire on both ends in seven strands 9” to 12” long. all material provided by the contractor.
Earthing of single STP pole by digging 1.00 mtr deep pit and driving the electrodes of MS earth rod and connecting all the metallic parts of poles with earthing rod by G.I. wire and filling pits with soil after completion of earthing.earth wire/all materials shall be provided by the Contractor
Laying of A.C.S.R. Dog conductor with the help of aluminium roller by hanging three nos. on each support in a manner taking sufficient care to ensure safety of A.C.S.R. Dog conductor against rubbing on ground, precaution for safety of crops is also to be taken. The work includes jointing of Conductor by providing jointing sleaves, stringing of conductor upto correct sag and binding of conductor with insulators on each support. All material shall be provided by Contractor such as jointing sleeve binding wire, armour rod etc.
Hanging of 3x300 Sqmm 33 KV XLPE Cable for Loop & Air All Materials Provided by the Contractor.
Laying 3x300 Sqmm 33 KV XLPE Cable for Along the Road & Road Crossing 33 KV XLPE Cable All material shall be provided by Contractor.
Laying 3x300 Sqmm 33 KV XLPE Cable for 33 KV Line Intrench
Installation and Fixing of 33 KV Cable Box Jointing Kit 3x300 Sqmm
Guarding of 33 KV Line for Road Crossing and Marcket All material shall be provided by Contractor
Trimming of tree branch big/small branch which is laying in alignment of 33 KV line.
Jumpring of 33 KV line on 33 KV Bay using P.G. Clamp dog to dog & dog to Panther & binding of jumper and other accessories on terminal gantry at 132 KV S/S Distt. Pratapgarh All material shall be provided by Contractor
B - Supply of Centralised Materials (Excl. T/F)
Terminal Gantry
Main Bus Bar with Complete Structure
90 Lbs Rail Pieces for T/F (44.64 Kg)/M
33 KV Post Insulator
Structure for Post Insulator
33 KV Bus Isolator
Structure for Bus Isolator
33 KV Line Isolator
Structure for Line Isolator
33 KV VCB with structure
33 KV Single T/F control Pannel
33 KV CT 200/100/1A
Structure for CT
33 KV PT Outdoor (33 KV/110 volt)
Structure for PT
Lighting Arrester
Structure for Lighting Arrester
11 KV 3x185 mm2 XLPECable
11 KV 3x120 mm2 XLPECable
11 KV Switch gear 600/300/5A 350 MVA I/C
11 KV Switch gear 200/100/5A 350 MVA O/G
24 Volt Battery & Battery Charger
Fire Bucket (04 no.) with stand
M.S.Channel 125x65x4000mm for cable stand
M.S. Earthing Rod 2540x20 mm.
M.S Top Channel 100x50x5x2240 mm.
M.S. Dropper Channel 100x50x5x2028 mm.
PCC Pole 8.5 Mtr. Long
G.I. wire 8 swg
Stay wire
Stay Set
Bracing of PCC double pole
ACSR Dog Conductor
63 KVA T/F
11 KV Fuse set with fixing clamp
11 KV TPMO
Sub Station Base Angle
B 1 - Supply of De-Centralised Materials
Control cable 4x2.5 mm2
Control cable 2x2.5 mm2
11 kv Cable Jointing kit 120 mm.sq.
11 kv Cable Jointing kit 185 mm.sq.
LT PVC Armoured Al. Cable (4x24 sqmm)
Rabber Matting
Earth Wire Clamp for PCC Pole
Stay Clamp for PCC Pole
Top channel Clamp for PCC Pole
Dropper channel Clamp for PCC Pole
G.I. Strips of size 35x6 mm
G.I. Strips of size 50x6 mm
G.I. Pipe 2" dia
PG Clamp for dog conductor
T&P Instruments for s/s (Meggar plire hand gloves etc.)
Table (Wooden)
Chair (Wooden)
Street Light shed flat
B 2 - Carriage of following material
PCC Pole 8.5 Mtr. Long-06 No., Structure of LA-01 No., 33kv Isolator-02 No., 33 KV CTs-03 No., Single T/F Control Pannel-01 No., 33kv VCB -01 No. Incoming Pannel-01 no, Battery & Battery Charger-01 no and other associated accessiories etc.
B 3 - Erection work
Laying of Earth Mat (Outdoor) as per Resp.
Laying of Earth Mat (Indoor) as per Resp.
Construction of Terminal Gantry and Bus Bar Gantry as per resp.
Construction of complete T/F plinth size 3mx3m x1.05 Mtr. (0.3 Mtr. above the ground level and 0.75 Mtr. deep foundation made as per drawing.) Top of plinth is to be C.C. work in the ratio of 1:3:6 fitted with 3 Mtr. long, 90 lbs, 2Nos. rail pieces. Cement mortar is to be used in 1:3 ratio. Cement, concrete material, bricks used in plinth shall be supplied by the contractor. 6” stone grit is to be laid before foundation start for whole plinth. Except rail pieces all material shall be provided by the contractor .
Erection of complete structure and 33 KV Bus Isolator (before and after bus bar as required) in switch yard as per RESPO drawing. Work also includes construction of plinth of size 0.45x0.45x1.05 cum (0.3 Mtr. above the ground level and 0.75 Mtr. deep foundation made as per drawing.) with cement,coarse sand and ballast in ratio 1:3:6 and plastaring of plinth with cement & sand in ratio 1:4 including digging of pits & backfilling. All concreting material like cement, ballast, sand labour & T&P etc.shall be provided by the contractor.
Erection of complete structure and 33 KV lightening arrestor in switch yard as per RESPO drawing. Work includes erection of 3 Nos.33 KV lightening arrestor, its fitting and mounting with care. Grouting of structure with cement, coarse sand and ballast in ratio 1:3:6, construction of plinth size 0.45x 0.45x1.05 cum. (0.3 Mtr. above the ground level and 0.75 Mtr. deep foundation made as per drawing.) Plastering the plinth with cement mortar with cement and sand in ratio 1:4. All concreting material like cement, ballast, sand labour & T&P etc.shall be provided by the contractor.
Erection of 33 KV post Insulators with complete structure in Switch yard as per RESPO drawing. Work includes Installation of 1X3 Nos. 33 KV Post Insulator on structure complete as per schedule, grouting of Structure with Ist class brick ballast in the ratio of 1:3:6, plastering in the ratio of 1:3 on plinth size 0.45x0.45x1.05 Cum. (0.3 Mtr. above the ground level and 0.75 Mtr. deep foundation made as per drawing.) The work is to be done strictly as per RESPO drawing. All the material like post Insulator cap, Cement, concrete material used for above work will be provided by the Contractor.
Erection of complete 33 KV VCB with structure 0.7x0.7x1.05 cum. (0.3 Mtr. above the ground level and 0.75 Mtr. deep foundation or made as per requirement.) in switchyard and grouting of VCB structure by cement, sand, brick ballast mortar in ratio 1:3:4. Work includes complete fitting of VCB on structure carefully with making all connections of control cable for operating the VCB . All other item like cement, concrete material, T&P shall be provided by the contractor.
Erection of complete 33 KV C.T (03 NO) with structure (0.45x0.45x1.05) cum. (0.3 Mtr. above the ground level and 0.75 Mtr. deep foundation made as per drawing.) in switchyard and grouting of C.T. structure by cement, sand, brick ballast mortar in ratio 1:3:4. Work includes complete fitting of C.T. on structure carefully with making all connections of control cable . All other item like cement, concrete material, T&P shall be provided by the contractor.
Installation of 33 KV single transformer control pannel, 1 No. Incoming and 2 No. Outgoing in the switchgear room and grouting the pannel by rag bolt using cement, sand mortar in ratio 1:3. Work includs fitting of all accessories in all respect with complete connection of control cable with pannel. All material will be provided by the Contractor except VCB and CRP.
Construction of cable trenchs with top cover and laying of control cable for VCB, C.T. & T/F Control Pannel etc. as per direction of engineer. trenchs to be 12” wide and 9” deep. work includes digging, of trench, concreting of the foundation in the ratio 1:3:6 R.B. wall 9” wide with cement mortar 1:4 and plastering inside the trench in the ratio 1:3 and sand filling in the trench. All material will be provided by the contractor.
Earthing of all Structures (as LA. CT, VCB, Isolator, etc.) erected in the yard with 35x6 mm. G.I. strip fully welded at both ends and to be connected with earthmat, .
Earthing of 11 KV indoor equipments, switchgears as per RESSPO Drawing. with G.I. Strip of Size 35x6 mm. G.I. strip fully welded at both ends and to be connected with earthmat,
Earthing of T/F neutral with G.I Pipe (Specification - 2" dia 60 feet depth) Up to wet earth, making delta with space of 02 feet and connecting it with 50x6 mm. G.I. strip to T/F neutral giving half round turn at the T/F.
Two Separate body Earthing of T/F with G.I Pipe (Specification - 2" dia 60 fit depth) Up to wet earth and connecting it with 50x6 mm. GI strip.
Erection of DP with PCC pole 8.5 mtr long with all accessaries and Grouting of the PCC Pole with cement, sand and brick ballast ratio 1:4:8 size 0.45x 0.45x 1.5 mtr deep under the ground as per drawing No. RES-6.(Cement, sand, brick, ballast shall be provided by the contractor.)
Laying and stringing of ACSR Dog conductor from bus to bar L.A, VCB, C.T., Post insulator and 33/11 KV T/F, Isolator etc. properly with jumpering with P.G. Clamp, . PG Clamp shall be provided by the contractor except ACSR Dog conductor.
Painting of all structure and equipment inside the switch yard with two coats of red oxide primer and thereafter two coats of aluminium paint, giving silver white finish, painting is to be done after proper cleaning of the structures. paint, primer, thinner etc. required shall be provided by the contractor himself.
Installation of 24 Volt Battery and Battery Charger with cabinet in the switch gear room, by grouting base channel 100 x 50 x 6 x 1000mm. Fixing of rag bolt.
Laying of 11 KV 3x300/3x185/ 3x120 Sqmm. XLPE cable by digging 0.75 Mtr. deep trench, putting layer of sand in the bottom, ramming it, laying of cable over it RMT and covering the cable from sides and top by laying bricks, finally covering the same by earth and levelling of the same, all the materials, except cable, will be pvovided by the contractor.
Fixing and termination of Outdoor/ Indoor Heat shrinkable Cable boxes of size 3 x300/3x185/3x120 sqmm. XLPE cable. Boxes will be supplied by the Contractor
Commissioning of the Power transformer protection33KV VCB's and 11KV VCB's CT&CRP.
Fabrication and grouting of cable stand for power transformer
Sundries ( as per site requirement/emergency work)
C- Supply of Centralised Materials
8.5 Mtr PCC Pole
11 Mtr STP
11 KV "V" type cross arm 65x65x6 mm, M S Angle
Bracing Angle with clamkp for 11 KV
Polymeric 11KV Pin Insulator
T off Channel
11 KV Top Channel
Stone Pad (300x300x75 mm)
11 KV Disk Fitting 45 KN
Weasel Conductor 5x3+3% Sag
G.I. Wire 6 SWG
G.I. Wire 8 SWG
11 KV Disk Insulator 45 KN
Stay Set
Stay Wire
11 KV 3x120 sqmm XLPE Cable
Earthing of Pole by M S Earthing Rod 20 x 2500 mm and 6 SWG earthing wire etc
Guarding Angle for PCC Pole
C 1 - Supply of De-Centralised Materials
11 KV Jointing Kit 3x120 sqmm
11 KV E Bracket
11 KV F Bracket
G.I. Pipe
Number Plate with clamp and Nut & Bolt
Danger Plate with clamp and Nut & Bolt
G I Barbed Wire
Stay Clamp
Nut Bolt and washer all sizes
Clamp for 11 KV "V" type Cross arm with bolts and nuts
Earthing of Pole by M S Earthing Rod 20 x 2500 mm and 6 SWG earthing wire etc
Concreting of Support (0.268CuM)
HDPE Pipe 6" dia
C 2 - Carriage of following material
ST Pole 11 Mtr. Long-04 No. 11 KV V-type cross arm, 11 KV M.S Top channel, 11 KV Disc Fitting, 33 KV Disc Insulator, 11 KV Pin Insulator, ACSR Weasel Cond. 11 KV Cable jointing kit 3x120 sqmm, 11 KV Bracing clamp etc.
C 3 - Erection work
Digging of pits of size 0.45x1.25x 1.50 mtr. for erection of PCC pole 09 mtr. Long.
Erection of single PCC pole of 8.5 mtr long.
Mounting and fitting of V-type cross arm, 11 KV pin, pin insulator, earth clamp complete in all respect as per drawing of RESPO on single PCC pole 8.5 mtr long.
Mounting and fitting T-off Channel with clamp
Fabrication, mounting and fitting of top channel, bracing made of m.s. angle, earth clamp, 11 KV pin & pin insulators, disc insulator and disc fitting on PCC . double pole.
Fabrication, mounting and fitting of M.S Channel , 11 KV disc insulator and disc fitting on PCC . double pole for riser
Painting of single STP pole 11 mtr long .
Grouting of PCC pole 8.5 Mtr. long with cement, sand and brick bllast ratio 1:4:8 size 0.45x 0.45x 1.5 mtr deep under the ground as per drawing No. RES-6. Cement, sand, brick, ballast shall be provided by the contractor.
Digging of pits of size 0.60x 0.60x1.2 mtr and grouting the stay rod anchor plates 0.45x 0.45x 0.45 mtr with cement, Ganga sand and brick ballast ratio 1:4:8 as per drawing No. RES-16. Cement, sand, brick, ballast shall be provided by the contractor.
Complete fitting of stay rod and fastening stay wire including fitting of stay clamp, turn buckle, and making ring of stay wire on both ends in seven strands 9” to 12” long. all material provided by the contractor.
Earthing of single PCC pole by digging 1.00 mtr deep pit and driving the electrodes of MS earth rod and connecting all the metallic parts of poles with earthing rod by G.I. wire and filling pits with soil after completion of earthing.earth wire/all materials shall be provided by the Contractor
Laying of Weasel conductor with the help of aluminium roller by hanging three nos. on each support in a manner taking sufficient care to ensure safety of Weasel conductor against rubbing on ground, precaution for safety of crops is also to be taken. The work includes jointing of Conductor by providing jointing sleaves, stringing of conductor upto correct sag and binding of conductor with insulators on each support. All material shall be provided by Contractor such as jointing sleeve binding wire, armour rod etc.
Hanging of 3x120 Sqmm 11 KV XLPE Cable for Loop & Air All Materials Provided by the Contractor.
Laying 3x120 Sqmm 11 KV XLPE Cable for Along the Road & Road Crossing 11 KV XLPE Cable All material shall be provided by Contractor.
Installation and Fixing of 11 KV Cable Box Jointing Kit 3x120 Sqmm
Guarding of 11 KV Line for Road Crossing and Marcket All material shall be provided by Contractor
Trimming of tree branch big/small branch which is laying in alignment of 11 KV line.
M/S-Sonkar Enterprises (BID ID -5088749)
NIKHIL ENTERPRISES (BID ID -5089454)
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .