Loading…
Loading…
Eligibility, documents, scope, Go/No-Go checksEligibility, required documents, scope of work and Go/No-Go checks for this tender, in one click.
Tender Value
Refer Docs
EMD Value
₹8,700
Closing Date
13 Oct 2026, 2:30 pm4d left
Eligibility, documents, scope, Go/No-Go checksEligibility, required documents, scope of work and Go/No-Go checks for this tender, in one click.
Chief Engineer NCTPS-III
Athipattu, Chennai-120
Carrying out Annual Overhaul works in TG Area(Subdivision II) in C and I division
2026_EB_709118_1
CE/SE/ES/CI/07/2026-2027
Open Tender
Maintenance Works
Works
NCTPS-III
Please refer Tender documents.
2 documents required · 2 mandatory
₹0
₹8,700
Yes
29 Sept 2026
29 Sept 2026
14 Oct 2026
29 Sept 2026
13 Oct 2026
29 Sept 2026
29 Sept 2026 - 12 Oct 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Charges for dismantling the Bearing vibration sensors, Axial shift sensors, Rotor expansion sensor, Eccentricity sensor, Casing Expansion Sensor & Speed Sensors of Main turbine, TDBFP's from bearing pedestal, dismantling of proximity probes at senor end , checking healthiness of transducers, calibration of vibration sensor, refixing and sensor alignment checking, signal conditioner modules terminal tightness checking, Gap voltage adjusting and Dressing of proximity probes.(including T&P hire charges and consumable charges) | 50 | NOS | - | - |
| 2 | Charges for dismantling the signal conditioner modules & proximity sensor cables of Turbo supervisory instruments of Main turbine, TDBFP's, checking healthiness of signal conditioner modules, refixing of signal conditioner modules, terminal tightness checking, Gap voltage checking and Dressing of proximity probes (including T&P hire charges and consumable charges) | 101 | NOS | - | - |
| 3 | Charges for dismantling of bearing temperature elements of main turbine,TDBFP, refixing the temperature elements & terminal tightness in transmitters/JB, Control cables loop checking, restoration of healthier value and Dressing of temperature elements cables (including T&P hire charges and consumable charges) | 40 | NOS | - | - |
| 4 | Charges for checking the healthiness of Turbine temperature elements (Main turbine & TDBFP) and terminal tightness at transmitter/JB end, Control cables loop checking and Dressing of temperature elements cables (including T&P hire charges and consumable charges) | 112 | NOS | - | - |
| 5 | Charges for servicing of Temperature transmitter of main turbine and allied areas bearing protection temperature elements and restoring in healthy condition(including T&P hire charges and consumable charges) | 10 | NOS | - | - |
| 6 | Charges for removing, cleaning, flushing and refixing of manifold of Pressure, Differential pressure and flow transmitter in main turbine, TDBFPs, HP bypass, LP bypass and allied areas.(including T&P hire charges and consumable charges) | 30 | NOS | - | - |
| 7 | Charges for dismantling of pressure, temperature, DPT, Flow, level transmitters / switches, gauges of Turbine, BFP & allied areas, transmitter Healthiness checking, terminal tightness checking, impulse line tightness checking, Cable loop checking, refixing of transmitter and restoration of healthier value of pressure, temperature, DPT, Flow, level transmitters / switches,gauges.(including T&P hire charges and consumable charges) | 75 | NOS | - | - |
| 8 | Charges for dismantling the position transmitters and removing of solenoid coil connectors of HP turbine CV / IP Turbine CV / Over load CV / HPT ESV / IPT ESV / HP bypass /LP Bypass/ Extraction NRV/CRH NRV, TDBFP Main CV/Auxiliary CV, checking the cam arrangement tightness, position transmitter response checking, adjusting the zero/span values, refixing of position transmitters, , loop checking of cable, solenoid coil connectors, reconnecting, restoration of healthier position values in DCS.(including T&P hire charges and consumable charges) | 42 | NOS | - | - |
| 9 | Charges for cutting, choke clearing, welding, servicing of damaged root valves, impulse lines, manifolds of pressure, temperature, DPT, Flow, transmitters / switches, gauges of Turbine, BFP & allied areas(including T&P hire charges and consumable charges) | 30 | NOS | - | - |
| 10 | Pneumatic ON/OFF valves without smart positioner:
Charges for removal of instrument air lines, volume booster, air lock relays, AFR, sov, etc of ON/ OFF valves for Cleaning/ servicing the above and healthiness checking of SOVs, checking tightness of power and signal supply lines and restoration of the same for smooth operation of pneumatic valves in Condensate and evacuvation system, Vacuum breaker, NRV, BFPs
(including T&P hire charges and consumable charges) | 26 | NOS | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.19 MB
Spec.pdf
Tender Documents • 0.65 MB
BOQ_852162.xls
BOQ • 0.30 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .