Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹20.9 LAccepted-AOC | L1 | Accepted-AOC Being lowest bidder | |
| 2 | L2₹26.8 L+₹5.4 L (25.0%)Rejected-Finance | L2 | Rejected-Finance Being higher bidder | |
| 3 | L3₹27.6 L+₹6.1 L (28.6%)Rejected-Finance | L3 | Rejected-Finance Being higher bidder | |
| 4 | L4₹31.5 L+₹10.1 L (46.9%)Rejected-Finance 60 310A 3 KHERIA MOD JAGNER ROAD AGRA 01 | AGRA | UTTAR PRADESH | 282001 | L4 | Rejected-Finance Being higher bidder | |
| 5 | L5₹33.3 L+₹11.9 L (55.4%)Rejected-Finance 29 7 KACHERI ROAD NEAR DISTRICT HOSPITAL PRATAPGARH PRATAPGARH UTTAR PRADESH 230001 | PRATAPGARH | UTTAR PRADESH | 230001 | L5 | Rejected-Finance Being higher bidder |
Tender Value
₹38 L
EMD Value
₹76,000
Closing Date
8 Mar 2023, 6:00 pmClosed
GE AF TECH AREA AGRA
GE AF TECH AREA AGRA
REPAIR AND MAINT OF DG SET AND AMF PANEL FOR STAND BY DG SET IN ZONE B AND C OF AF STN AGRA UNDER GE AF TECH AREA AGRA
2023_MES_581215_1
8200-1494/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE AF TECH AREA AGRA
AS PER NIT
9 documents required · 9 mandatory
₹500
GE AF TECH AREA AGRA
₹76,000
Yes
10 Apr 2023
16 Feb 2023
10 Mar 2023
16 Feb 2023
8 Mar 2023
1 Mar 2023
17 Feb 2023 - 22 Feb 2023
Amount
M&L for servicing of upto 40 KVA DG set including replacement Engine oil and all type of filters as per manufacturers manual. Opening, adjusting, tightening of tappet cover complete by torque wrench by applying proper pressure , cleaning of complete sump from sludge of dirt, oil etc. and refitting for DG set including drain out (used) engine oil and filling and topping of new engine oil complete all as specified and directed. (Note:- (a) Engine oil will be measured and paid separately under respective items of schedule 'A'. (b) Each servicing of DG Set will be required after 6 months or 250 hours working. ( c ) servicing of DG Set shall be carried out by the authorised workshop.
M&L for servicing 50 KVA to 82.5 KVA DG set including replacement Engine oil and all type of filters as per manufacturers manual. Opening, adjusting, tightening of tappet cover complete by torque wrench by applying proper pressure , cleaning of complete sump from sludge of dirt, oil etc. and refitting for DG set including drain out (used) engine oil and filling and topping of new engine oil complete all as specified and directed. (Note:- (a) Engine oil will be measured and paid separately under respective items of schedule 'A'. (b) Each servicing of DG Set will be required after 6 months or 250 hours working. ( c ) servicing of DG Set shall be carried out by the authorised workshop.
M&L for servicing of 100 to 180 KVA DG set including replacement Engine oil and all type of filters as per manufacturers manual. Opening, adjusting, tightening of tappet cover complete by torque wrench by applying proper pressure , cleaning of complete sump from sludge of dirt, oil etc. and refitting for DG set including drain out (used) engine oil and filling and topping of new engine oil complete all as specified and directed. (Note:-(a) Engine oil will be measured and paid separately under respective items of schedule 'A'. (b) Each servicing of DG Set will be required after 6 months or 250 hours working. ( c ) servicing of DG Set shall be carried out by the authorised workshop.
M&L for servicing of 200 to 320 KVA KVA DG set including replacement Engine oil and all type of filters as per manufacturers manual. Opening, adjusting, tightening of tappet cover complete by torque wrench by applying proper pressure , cleaning of complete sump from sludge of dirt, oil etc. and refitting for DG set including drain out (used) engine oil and filling and topping of new engine oil complete all as specified and directed. (Note:-(a) Engine oil will be measured and paid separately under respective items of schedule 'A'. (b) Each servicing of DG Set will be required after 6 months or 250 hours working. ( c ) servicing of DG Set shall be carried out by the authorised workshop.
M&L for servicing of 400 KVA DG set including replacement Engine oil and all type of filters as per manufacturers manual. Opening, adjusting, tightening of tappet cover complete by torque wrench by applying proper pressure , cleaning of complete sump from sludge of dirt, oil etc. and refitting for DG set including drain out (used) engine oil and filling and topping of new engine oil cleaning of fuel tank by taking out the existing fuel in container and keeping aside and refilling the same after cleaning the fuel tank complete all as specified and directed. (Note:-(a) Engine oil will be measured and paid separately under respective items of schedule 'A'. (b) Each servicing of DG Set will be required after 6 months or 250 hours working. ( c ) servicing of DG Set shall be carried out by the authorised workshop.
M&L for servicing of 500 KVA KVA DG setincluding replacement Engine oil and all type of filters as per manufacturers manual.Opening, adjusting, tightening of tappet cover complete by torque wrench by applying proper pressure , cleaning of complete sump from sludge of dirt, oil etc. and refitting for DG set including drain out (used) engine oil and filling and topping of new engine oil cleaning of fuel tank by taking out the existing fuel in container and keeping aside and refilling the same after cleaning the fuel tank complete all as specified and directed. (Note:- (a) Engine oil will be measured and paid separately under respective items of schedule 'A'. (b) Each servicing of DG Set will be required after 6 months or 250 hours working. ( c ) servicing of DG Set shall be carried out by the authorised workshop.
Supply and filling of Engine oil 15 W / 40 complete all as specified and directed. Make :Castrol / HP / Bharat Petrolium / Valvoline
Supply and filling of coolant suitable for radiater of DG sets complete all as specified and directed. Make: HP/TVS / Valvoline / KIRLOSKAR
S&F in renewal battery terminal brass(heavy duty)with nuts & bolts (as per sample) complete all as specified and directed.
Supply and filling distilled water suitable for DG set complete all as specified and directed.
Disconnecting of self starter 12/24 volts DC, dismantling and repairing with renewal of bendex pinion , rewinding of armature , bushes set , rewinding of field coil assembly, reassembling and refilled including testing of the complete self starter for capacity upto 125 KVA DG Set Complete all as specified and directed.
Disconnecting of self starter 12/24 volts DC, dismantling and repairing with renewal of bendex pinion, rewinding of armature, bushes set,rewinding of field coil assembly, reassembling and refilled including testing of the complete self starter of DG set for capacity from 321-400 KVA Complete all as specified and directed.
Disconnecting of self starter 24 volts DC, dismantling and repairing with renewal of bendex pinion,rewinding of armature, bushes set, rewinding of field coil assembly, reassembling and refilled including testing of the complete self starter DG set for capacity from 200 to 320 KVA Complete all as specified and directed.
Disconnecting of self starter 24 volts DC, dismantling and repairing with renewal of bendex pinion,rewinding of armature, bushes set, rewinding of field coil assembly, reassembling and refilled including testing of the complete self starter DG set for capacity from 401 to 500 KVA Complete all as specified and directed.
Taking down old repairable Radiator by opening nut/bolt from foundation and loading and transportation to local market for checking, unloading testing for any defects and repairing as below : - Cleaning, washing the copper tubes and Top to bottom Copper Fins Frame of the radiator by acid process. Checking the leakage if any and repairing the same by Soldering and Testing radiator, loading transportation and unloading including refixing to its old position with proper accuracy and correct situation for DG set Capacity up to 200 KVA including renewal of GI/MS nut/bolt, hose pipe sets with MS/ GI clamps and testing complete all as specified and directed.
Taking down old repairable Radiator by opening nut/bolt from foundation and loading and transportation to local market for checking, unloading testing for any defects and repairing as below : - Cleaning, washing the copper tubes and Top to bottom Copper Fins Frame of the radiator by acid process. Checking the leakage if any and repairing the same by Soldering and Testing radiator loading, transportation and unloading including refixing to its old position with proper accuracy and correct situation for DG set Capacity up to 100 KVA including renewal of MS/GI nut/bolt, hose pipe sets with MS/GI clamps and testing complete all as specified and directed.
Taking down old repairable Radiator by opening nut/bolt from foundation and loading and transportation to local market for checking, unloading, testing for any defects and repairing as below : - Cleaning, washing the copper tubes and Top to bottom Copper Fins Frame of the radiator by acid process. Checking the leakage if any and repairing the same by Soldering and Testing radiator unloading and transportation and unloading & including refixing to its old position with proper accuracy and correct situation for DG set Capacity from 200 KVA to 320 KVA including renewal of MS/GI nut/bolt, hose pipe sets with MS/ GI clamps and testing complete all as specified and directed.
Taking down old repairable Radiator by opening nut/bolt from foundation and loading and transportation to local market for checking, unloading testing for any defects and repairing as below : - Cleaning, washing the copper tubes and Top to bottom Copper Fins Frame of the radiator by acid process. Checking the leakage if any and repairing the same by Soldering and Testing radiator with loading and transportation & unloading including refixing to its old position with proper accuracy and correct situation for DG set capacity from 400 KVA to 500 KVA including renewal of MS/GI nut/bolt, hose pipe sets with MS/GI clamps and testing complete all as specified and directed.
Taking down old Radiator by opening nut/bolt from foundation and supply, installing and testing new Radiator with proper accuracy and correct situation for DG sets capacity from upto 200 KVA including MS/GI nut/bolt, hose pipe sets with MS/GI clamps and testing complete all as specified and directed.
M & L for disconnection & taking down of After cooler assembly from foundation of DG set engine including repairing, soldering & cleaning of Radiator assembly complete by acid process and refixing to its old position with proper accuracy and correct situation including transportation charges for DG set of capacity 200 to 320 KVA complete all as specified and directed.
M & L for disconnection, taking down and repairing of alternator DC from DG set engine with rewinding of armature ,renewal of carbon brushes, renewal of bearings, rewinding of field coil assembly, renewal of connection plate, reassembling and refixing to DG set engine after necessary repair for following sizes complete all as specified and directed:-
M & L for repairing of automatic battery charger of 12 Volt / 24 Volts including rewinding of transformer unit and renewal of diode plates, rectifier plates, auto cut mosfet circuit , fuses etc. and testing for following sizes complete all as specified and directed:-
M & L for repairing of canopy doors complete with renewal of following itmes including denting and necessary welding of doors complete all as specified and directed:-
Stain less Steel Door lock of size 5.75" x 4.5" and of 08 levers
Stain less Steel .door handle of 150mm size
Stain less Steel Butt hinges of 100 mm size heavy duty of having 08 holes for screwing all asmspecified
M & L for flywheel ring in renewal with proper setting and alignment for 100 to 160 KVA DG set complete all as specified and directed.
M & L for painting of DG set, panels, diesel tank, silencer by applying two coats of synthetic enamel paint over one coat of primer and writing SM.MES No, Make and capacity with super enamel paint including scrapping of old paint for DG set Capacity from 100 KVA to 160 KVA complete all as specified and directed.
M & L for painting of DG set of capacity 20 KVA & 30 KVA DG Set with trolly frame including panels, diesel tank by applying two coats of super sythentic enamel paint over one coat of primer complete all as specified and directed.
M & L for renewal of Magnetic Pickup suitable for 100 KVA & 200 KVA DG set complete all as specified and directed. Make:- Cummins / KIRLOSKAR / GREAVES COTTON
S&F in renewal Shut down valve solenoid suitable for all capacities of DG set complete all as specified and directed.
S&F in renewal Thermostat of suitable for water temprature reading and engine temperature reading fitting with existing network along with minor modifications of existing system for any capacities of DG set complete all as specified and directed.
S&F in renewal Hose Sil D100 X 90 for DG set upto 200 KVA capacity complete all as specified and directed.
S&F in renewal Switch temperature (Water Safety) suitable for all capacities of DG set complete all as specified and directed.
S&F in renewal Separator fuel and water suitable for all capacities of DG set complete all as specified and directed.
S&F in renewal Air Cleaner Assembly for DG set upto 62.5 KVA capacity complete all as specified and directed.
S&F in renewal copper Battery lead of 25 Sqmm, 2mtr long suitable for all capacities of DG set complete all as specified and directed.
S&F in renewal Feed pump suitable for all capacities of DG set complete all as specified and directed.
S&F in renewal V Belt / Fan belt suitable for all capacities of DG set complete all as specified and directed.
S&F in renewal Fuel pipe (525 mm) for all capacities of DG set complete all as specified and directed.
M&L for disconnecting, dismantling and overhauling of fuel injector pump of DG set of capacity 15 KVA to 82.5 KVA including overhauling, calibration and testing at admissible pressure properly complete all as specified and directed.
Supply & fix in renewal Nozzle for 15 KVA to 82.5 KVA capacity DG set complete all as specified and directed.
Supply & fix in renewal F.I.P. Elements for 15 KVA to 82.5 KVA capacity DG set complete all as specified and directed.
M&L for disconnecting, dismantling and overhauling of fuel injector pump of DG set of capacity 100 KVA to 200 KVA including repair, overhauling, calibration, testing complete and refixing to its original position properly complete all as specified and directed. Note:- FIP shall be calibrated by authorised work shop of manufacturer company Contractor has to submit documentary evidense for over hauling carried out from authorised work shop.
Supply & fix in renewal Nozzle & Holder Assembly of DG Set capacity 100 KVA to 200 KVA complete all as specified and directed.
Supply & fix in renewal Gasket injection pump mount of DG Set of capacity 100 KVA to 200 KVA complete all as specified and directed.
Supply & fix in renewal of A.V.R suitable for 20 KVA to 200 KVA capacity of DG set complete all as specified and directed. Make:- KIRLOSKAR / AE / NATIONAL.
M & L for dismantling of defective water pump assembly by disconnecting of hose pipe connections, fanbelt, radiator connection and supply and fixing of new water pump assembly suitable for DG set capacity for 40 KVA to 200 KVA including renewal of u/s hose pipes, fan belt, nut/bolts etc complete all as specified and directed. Make:-- KIRLOSKAR / Cummins / GREAVES COTTON
Supply & fix in renewal fully automatic battery charger (input 230V AC SMPS based and out put 24V DC) for 24 volt battery complete all as specified and directed. Make :- KIRLOSKAR / ELECT INDIA / Cummins / UNITEK INDIA .
Supply & fix in renewal fully automatic battery charger (input 230V AC SMPS based and out put 12V DC) for 12 volt battery complete all as specified and directed. Make :- KIRLOSKAR / ELECT INDIA / Cummins / UNITEK INDIA
Supply & fix in renewal of maintenance free type battery- 12 Volts,180 AH for DG set of suitable capacity complete all as specified and directed with 18 month replacement warrantty Make: EXIDE / AMARON / or equillvant as approved.
Supply & fix in renewal of maintenance free type battery- 12 Volts,120 AH for DG set complete all as specified and directed with 18 month replacement warranty. Make: EXIDE / AMARON as approved
Supply & fix in renewal of maintenance free type battery- 12 Volts,100 AH for DG set complete all as specified and directed with 18 month replacement warranty. Make: EXIDE / AMARON as approved.
M&L for checking of AMF panel & DG set for detecting any kind of fault and attending the fault immediately at any time round the clock and carry out certain repair as per site requirement and checking of AMF panel and DG set for power suply from DG set through AMF panel and replace the worn out parts of AMF panel & DG set by expert engineer complete all as specified and directed. Notes :- Note: (a) Replaced worn out parts of AMF panel/DG set shall be measured and paid separately under relevant items of schedule 'A'. (b) Charges for detecting the fault in AMF Panel/electric system/DG set are included in the quoted item rate.
M & L for flywheel ring ( 3246713 ) in renewal with proper setting and alignment for the DG set capacity 400 to 500 KVA complete all as specified and directed.
M & L taking down old Flywheel ring from DG set and provideng of new flywheel ring ( 3166605 ) with proper setting and alignment for the DG set of capacity 320 KVA DG set complete all as specified and directed.
M & L for disconnecting, dismantling and overhauling with repairing of PT pump complete including renewal of drive accessories, Plunger Air fuel control, Oil seal , Gasket set fuel pump etc including machinery work for 500 KVA capacity DG SET complete all as specified and directed (Location 50 Sqn). Note:- PT pump shall be calibrated by authorised work shop of manufacturer company Contractor has to submit documentary evidense for the repairing carried out from the authorised work shop
M & L for shifting of trolly mounted DG set capacity up to 250 KVA from location to another location (with in 05 kilometer) complete including disconnection of cable, earth strip including transportation with using necessary chain pulley & HYDRAULIC jack etc including reconnection of cable and earth strip and other etc. at new location complete all as specified and directed.
S & F in renewal Genset Controller Panel suitable upto 125 KVA capacity DG Set, make and model of Genset controller panel shall be as per site or directed by Enginer -in- charge
S & F in renewal Genset Controller Panel suitable DG Set of capacity 126 to 320 KVA capacity DG set make and model Genset controller panel shall be as per site or directed by Enginer -in- charge
S & F in renewal Genset Controller Panel sutiable upto 400 KVA to 500 KVA make and model as per site or directed by Enginer -in- charge
Supply & fix in replacement Indicater lamp with holder set of three colours of R,Y & B (LED type) suitable for DC/AC supply.
Supply & fix in replacement aluminum bus bar of suitable length,width & thickness with suitable size of porcelain insulator duly insulated with coloured insulation tape R,Y,B and neutral Black laminated with respective colour code fitted on existing LT panels with minor modifications by cuttung/welding al all as specified and directed.
Supply & fix in replacement Relay-24 VDC/ 12 VDC / 220 VAC / 240 VAC for AMF panel of DG set. Make: CUMMINS( AX1012821 ) / OMRON / SALZER / PLA.
Supply & fix in replacement Contactor- 3/4 Pole,150 Amps/ 140 AMPS for 62.5 KVA capacity DG Set AMF panel with replacement of lugs and checking of all connections etc. Make:- LEGRAND ( 4162 66 ) / L &T / SCHNEIDER / C & S .
Supply & fix in replacement Contactor- 3/4 Pole, 225 Amp/ 200 Amp for 125 KVA capacity DG set AMF panel with replacement of lugs and checking of all connections etc. Make:- LEGRAND ( 4162 96 ) / L &T / SCHNEIDER / C & S .
Supply & fix in replacement Contactor 4 Pole, 250 Amps for AMF PANEL of DG Set with replacement of cable lugs and checking of all connections etc. Make:-SCHNEIDER ( LC1F1504 ) / L &T / C & S .
Supply & fix in replacement Contactor of 4 Pole, 400 Amps, for AMF PANEL of DG Set with replacement of lugs and checking of all connections etc. Make:- SCHNEIDER ( LC1F3304 ) / L &T / C & S .
Supply & fix in replacement Spare Contact Kit for Contactor-250 Amps suitable capacity 100 to 125 KVA capacity DG set. Make:- L & T ( CS94084) / SCHNEIDER / C & S .
Supply & fix in replacement Spare Contact Kit for Contactor-400 Amps suitable 110 to 200 KVA capacity DG set AMF panel. Make:- L & T ( CS94297 ) / SCHNEIDER / C & S
Supply & fix in replacement Spare Contact Kit for Contactor-600 Amps suitable for 320 KVA capacity DG SET. Make:- L & T ( CS94299 ) / SCHNEIDER / C & S
Supply & fix in replacement MCCB, 400 Amp, 4 pole, 36 KA ,thermal magnetic adjustable type from 80-110% of 415 Volt including taking out existing connections, cable lugs etc all as specified and directed. Make:-L & T ( CM94153OOOOAG ) / Legrand / HAVELLS .
Supply & fix in replacement Microprocessor base MCCB of capacity 630 Amp, 4 pole, 36 KA , 415 Volt including taking out existing connections, cable lugs etc all as specified and directed. Make:- L & T ( CM94179OOOOAG ) / Legrand / HAVELLS .
Supply & fix in replacement Micro processor based type MCCB, 800 Amp current carrying capacity, 4 pole, 50 KA , 415 Volt including taking out existing connections, cable lugs etc all as specified and directed. Make:- L & T( CM96115OOOOAG ) / Legrand / HAVELLLS
Supply & fix in replacement DIN Type Fuse Links Type HN (160 amps ) suitable for 100 KVA capacity DG set AMF panel. Make: L & T ( SF94231 ) / STANDARD OR Equivalent as approved
Supply & fix in replacement DIN Type Fuse Links Type HN ( 100 amps ) suitable for 63 KVA capacity DG set AMF panel. Make: L & T ( SF94129 ) / STANDARD OR Equivalent as approved
Supply & fix in replacement Fuse Bases ( HN-Size 2 & 3 ) suitable for 63 KVA capacity DG set AMF panel. Make: L & T ( SK91051 ) / STANDARD OR Equivalent as apprpved.
Supply & fix in replacement Self Engine Stop Relay Device for 63 KVA to 180 KVA capacity DG set AMF panel . Make: Automation Electronics / Elect India
Supply & fix in replacement AMF Controller device for Auto/ Manual function for 200 KVA to 500 KVA capacity DG set. Make: Automation Electronics / ELECT INDIA OR Equivalent as apprpved
Supply & fix in replacement Solenoid stopper ( Solenoid Fuel Pump ) upto 125 KVA capacity DG set . Make:--Cummins ( 3928160 ) / Kirloskar / or Eqivalent as apprpved
M & L for dismantling of defective water pump assembly by disconnecting of hose pipe connections, fanbelt, radiator connection. Supply and fixing of new water pump assembly suitable for DG set capacity for 100 KVA to 200 KVA including replacement of u/s hose pipes, fan belt, nut/bolts etc complete all as specified and directed. Make:-- Kirloskar ( KL6.176.05.0.00 ) / Cummins or Eqivalent as apprpved
Supply & fix in replacement Electronic Timer, auxilary supply-240 VAC/24 VDC for 125 KVA to 200 KVA capacity DG set. Make: AE/ EAPL / MINILEC t
Supply & fix in replacement Undervolt/overvolt relay-ON/OFF delay time (1 to 15 sec ),sensing supply 415 Volt for 63 to 400 KVA capacity DG set. Make-AE/ PIC / MINILEC
Supply & fixing new in replacement ON-Load Changeover switch (Open Execution, Front operated) of 630 Amps, 4 Pole, 415 V, 50 Hz fitted in existing LT Panels with minor modifications by cutting/welding to fix the change over switch along with terminaton of LT cable with copper lugs of heavy duty ,including MS/GI nut bolts all as specified and dirceted. Make: HPL ( BP06304POAV ) / HAVELLS .
Supply & fix in replacement ON-Load Changeover switch (Open Execution, Front operated) of 400 Amps, 4 Pole, 415 V, 50 Hz fitted in existing LT Panels with minor modifications by cutting/welding to fix the change over switch along with terminaton of LT cable with copper lugs of heavy duty , including MS/GI nut bolts all as specified and dirceted. Make: HPL ( BP06304POAV ) / HAVELLS .
Supply & fix in replacement ON-Load Changeover switch (Open Execution, Front operated) of 250 Amps, 4 Pole, 415 V, 50 Hz fitted in existing LT Panels with minor modifications by cutting/welding to fix the change over switch along with terminaton of LT cable with copper lugs of heavy duty , including MS/GI nut bolts all as specified and dirceted. Make: HPL ( BP06304POAV ) / HAVELLS .
Supply & fix in replacement ON-Load Changeover switch (Open Execution, Front operated) of 125 Amps, 4 Pole, 415 V, 50 Hz fitted in existing LT Panels with minor modifications by cutting/welding to fix the change over switch along with terminaton of LT cable with copper lugs of heavy duty , including MS/GI nut bolts and all as specified and dirceted. Make: HPL ( BP06304POAV ) / HAVELLS .
Supply & fix in replacement OFF-Load Changeover switch (Side Handle) of 400 Amps, 4 Pole, 415 V, 50 Hz. Make: HAVELLS / HPL.
Supply & fix in replacement Rectifier Assembly for 40 to 160 KVA capacity DG set. Make: KIRLOSKAR ( KV280108000) / CUMMINS OR Equivalent as approved .
Supply & fix in replacement Three Phase Multifunction Digital meter . Make: Automation Electronics / HPL / National
Supply & fix in replacement AMF Relay Box for Auto/ Manual function including voltage monitor system and fully auto and manual system for 63 to 110 KVA capacity DG set. Make: AE/ ELECT INDIA as approved.
Supply & fix in replacement starter (Self Starter) for 200 KVA capacity DG set. Make: KIRLOSKAR ( KL6.140.12.0.00 ) / AUTOLEK / LUCAS.
Supply & fix in replacement Tube injector fuel supply for 100 to 200 KVA capacity DG set. Make: CUMMINS ( 3964706 ) / KIRLOSKAR
Supply & fix in replacement CONTROL GOVERNOR ( MECHANICAL GOVERNOR ) for 160 KVA capacity DG set. Make: CUMMINS ( 3037359 ). .
M & L for repairing PT pump complete with replacement of drive accessories, plunger and barrel, weight/courier,oil sheets etc including machinery work for 125 to 160 KVA capacity DG set complete all as specified and directed. Note :- PT pump shall be calibrated by authorised workshop of manufacturer company Contractor has to submit documentary evidense for the repairing carried out from the authorised workshop.
Supply & fix oil seal (3006738) for repairing of PT pump for 125 to 160 KVA capacity DG set complete all as specified and directed.
Supply & fix gasket set fuel pump (3010242) for repairing of PT pump for 125 to 160 KVA capacity DG set complete all as specified and directed.
M & L for dismantling turbo charger of DG set of capacity 100 to 200 KVA including repair, overhauling, testing complete and fixing to its original position properly complete all as specified and directed.
S&F in repair Kit Turbo (KIT3801101) for repairing of Turbo charger of DG set capacity 100 to 200 KVA complete all as specified and directed.
S&F in repair shaft (01320360) for repairing of Turbo charger of the DG set capacity 100 to 200 KVA complete all as specified and directed.
M & L for dismantling and replacement of Injector assembly (3239796) of DG set of capacity 62.5 to 200 KVA complete all as specified and directed.
Taking out alternator of DG Set of capacity 125 to 200 KVA of any make, including material of labour for rewinding by using super enamelled copper wire of suitable gauge, varnishing, changing insulating material, assembling, testing and reconnecting to DG set complete all as specified and directed by Engr-in-Charge Note:- Rates quoted by contractor deemed to be included the rates for tranportation of alternator from site to workshop.
M&L for Field coil rewinding of alternator of 125 to 200 KVA capacity DG sets of any make, including material and labour for rewinding with super enamelled copper wire of suitable gauge, varnishing, changing insulating material, assembling, testing and reconnecting to DG set complete all as specified and directed by Engr-in-Charge Note:- Rates quoted by contractor deemed to be included the rates for tranportation of alternator from site to workshop.
Taking out alternator of 62.5 to 100 KVA capacity DG sets of any make, including material of labour for rewinding with super enamelled copper wire of suitable gauge, varnishing, changing insulating material, assembling, testing and reconnecting to DG set complete all as specified and directed by Engr-in-Charge Note:- Rates quoted by contractor deemed to be included the rates for tranportation of alternator from site to workshop.
M&L for field coil rewinding of alternator of DG set of capacity 62.5 to 100 KVA of any make, including material of labour for rewinding with super enamelled copper wire of suitable gauge, varnishing, changing insulating material, assembling, testing and reconnecting to DG set complete all as specified and directed by Engr-in-Charge Note:- Rates quoted by contractor deemed to be included the rates for tranportation of alternator from site to workshop.
Taking out alternator of DG set of capacity 20 KVA to 50 KVA of any make including materials and labour for, rewinding with super enamelled copper wire of suitable gauge, varnishing, changing insulating material, assembling, testing and reconnecting to DG set complete all as specified and directed by Engr-in-Charge Note:- Rates quoted by contractor deemed to be included the rates for tranportation of alternator from site to workshop.
M&L for field coil rewinding of alternator of DG set of capacity 20 to 50 KVA of any make, including material of labour for rewinding with super enamelled copper wire of suitable gauge, varnishing, changing insulating material, assembling, testing and reconnecting to DG set complete all as specified and directed by Engr-in-Charge Note:- Rates quoted by contractor deemed to be included the rates for tranportation of alternator from site to workshop.
S&F MCCB 4 Pole Thermal adjustable breaker type of following capacity complete all as specified and directed.
63 AMP, 36 KA
125 AMP, 36 KA
160 AMP, 36 KA
250 AMP, 36 KA
Supply, fabricating and testing of factory made/fabricated cubical automatic main failure panel indoor type with degree of protection IP-42 conforming to IS-2147, suitable for 125KVA capacity DG Set, fabricated by using 14 Gauge CRCA sheet, powder coated comprising of suitable rated copper bus bar,contactors of adequate rating for auto transfer of main/DG supply, internal wiring with control fuse, provn of connecting incoming and outgoing leads/ bus bar as approved with and including following accessories and testing all as specified and directed :- (i) Master switch for auto/manual/reset/off-01 No. (ii) Digital type multifunctional meter for ampere, voltage, power factor, frequency etc -01 No.
(iii) Push button start, stop, reset-01 No. (iv) Set of lamp for indicating load a set, low pressure, high cylinder temperature, load on mains, set fails at start, low oil presure. (v) Battery charger connection to load. (vi) Transformer of adequate rating. (vii) Ractifiers (viii) DC ampere meter and voltmeter. (ix) Fault accept / reset push button. (x) Set of relays and contactor 200 Amp suitable for 125 KVA DG Set for automatic start and automatically shut down of suitable rating and capacity of 2 Nos, MCCB 4 pole, 200 Amp, 25 KA, 4 pole thermal adjustable type of range 70-100% fixed on main supply and DG set supply. (xi) Make of AMF control panel and drawing will be approved by accepting Officer before placing the order.
Supply, fabricating and testing of factory made/fabricated cubical automatic main failure panel indoor type with degree of protection IP-42 conforming to IS-2147, suitable for 62.5KVA capacity DG Set, fabricated by using 14 Gauge CRCA sheet, powder coated comprising of suitable rated copper bus bar,contactors of adequate rating for auto transfer of main/DG supply, internal wiring with control fuse, provn of connecting incoming and outgoing leads/ bus bar as approved with and including following accessories and testing all as specified and directed :- (i) Master switch for auto/manual/reset/off-01 No. (ii) Digital type multifunctional meter for ampere, voltage, power factor, frequency etc -01 No.
(iii) Push button start, stop, reset-01 No. (iv) Set of lamp for indicating load a set, low pressure, high cylinder temperature, load on mains, set fails at start, low oil presure. (v) Battery charger connection to load. (vi) Transformer of adequate rating. (vii) Ractifiers (viii) DC ampere meter and voltmeter. (ix) Fault accept / reset push button. (x) Set of relays and contactor 100 Amp suitable for 62.5KVA DG Set for automatic start and automatically shut down of suitable rating and capacity and 2 Nos, MCCB 4 pole, 100 Amp, 25 KA, 4 pole thermal adjustable type of range 70-100% fixed on main supply and DG set supply. (xi) Make of AMF control panel and drawing will be approved by accepting Officer before placing the order.
Supply and Laying and testing of XLPE insulated PVC and sheathed LT UG cable , bedded armoured heavy duty electric cable 1100 volts grade with aluminum conductor 120 Sqmm 3.5 core IS 7098 (Part-I) laid in trenches or fixed on wall/floor/poles including taking down of old XLPE cablecomplete all as specified and directed.
Supply and Laying and testing XLPE PVC insulated and sheathed LT UG cable, bedded armoured heavy duty electric cable 1100 volts grade with aluminum conductor 95 Sqmm 3.5 core IS 7098 (Part-I) laid in trenches or fixed on wall/floor/poles complete all as specified and directed.
Supply and Laying and testing of XLPE PVC insulated and sheathed LT UG cable , bedded armoured heavy duty electric cable 1100 volts grade with aluminum conductor 150 Sqmm 3.5 core IS 7098 (Part-I) laid in trenches or fixed on wall/floor/poles complete all as specified and directed.
Excavation in trenches in soft/loose soil n. exc 1.5 m wide and n. exc. 1.5 m in depth for laying cables etc complete all as specified and directed.
Return filling in and including spreading, leveling, watering and well ramming in layers n. exc. 25cm thick in soft /loose soil after cable are laid and tested complete all as specified and directed.
Removing excavated surplus soil to a distance n. exc. 50m and deposited where directed at a level n. exc.1.5m above the starting point complete all as specified and directed.
M&L for sand filing with clean dry fine river sand unsashed including gently punning around cables in trenches for cable protection complete all specified and directed. Note : punned thickness sahll be measused and paid.
Supply & Laying sub class 'B' briks old size with axis of the bricks perpendicular to the axis of the cable as in cable protection complete all as specified and directed.
M/s KCL Engines and Machines
Balaji Associate
rohan traders
M/S SINGH ELECTRIC CO
Shri Electrical Enterprises
LAXMI ENTERPRISES
BHARADWAJ BROTHERS
stage.html
html • 0.07 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .