Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹2.7 CrAccepted-AOC SCF 15 HUDA COMPLEX 184 NEW IDC 124001 | ROHTAK | HARYANA | 124001 | ₹2.7 Cr | L1 | Accepted-AOC L1 |
Tender Value
₹2.7 Cr
EMD Value
₹5.4 L
Closing Date
11 May 2020, 5:00 pmClosed
Ravi Ladwal, EE
Executive Engineer Elect. Division PWD B and R Hisar
Pdg. Compact Substation in Lala Lajpat Rai University of Veterinary and Animal Sciences at Hisar RECALL
2019_HRY_110467_2
PWD/Elect-GGR/Elect-HSR/16689
Open Tender
Construction Works
Works
180 days
Hisar
Please refer Tender documents.
3 documents required · 3 mandatory
₹10,000
Executive Engineer, Elect. Division PWD B and R Br
₹5.4 L
18 Dec 2020
21 Mar 2020
12 May 2020
21 Mar 2020
11 May 2020
21 Mar 2020
Amount
1 : - (Q) Earthing (HSR 31.22) iii) Earthing with GI earth plate 600 mm x 600 mm x 6 mm thick including accessories and providing masonry enclosures with cover plate having locking arrangement and watering pipe etc. ( but without charcoal or coke and salt ) complete as required.
: - iv) Earthing with tinned copper earth plate 600 mm x 600 mm x 3 mm thick including accessories and providing masonry enclosures with cover plate having locking arrangement and watering pipe etc. ( but without charcoal or coke and salt ) comlete as equired.
: - v) Extra for charcoal or coke and salt for G.I. Plate or copper plate earth electrode.
: - x) Pdg. and fixing 25 mm x 5 mm copper strip in 40 mm dia G.I. pipe from earth electrode as required .
: - xi) Pdg. and fixing 25 mm x 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode as required .
2 : - Lightning conductor Copper (HSR 31.23) vii) Supply and erection of copper tape 32 mm x 6 mm thick from earth electrode directly in ground and surface , fixed with suitable copper stapples of same size.
3 : - Supply and erection of underground cable ,loose in existing pipe or trenches complete with necessary connections. (HSR 31.26) MAKE - POLYCAB / HAVELLS / RR KABEL / GRANDLAY / KEI xxvii) 50 Sq. mm 3.5 Core Ard. Cable .
: - xxviii) 70 Sq. mm 3.5 Core Ard. Cable .
: - xxix) 95 Sq. mm 3.5 Core Ard. Cable .
: - xxx) 120 Sq. mm 3.5 Core Ard. Cable .
: - xxxiii) 240 Sq. mm 3.5 Core Ard. Cable .
: - xxxv) 400 Sq. mm 3.5 Core Ard. Cable .
4 : - Supply and erection of suitable compression type brass cable glands for underground Cable. (HSR 31.28) iii) 25 Sqmm to 50 Sqmm Cable 2 to 4 Core.
: - iv) 70 Sqmm to 95 Sqmm Cable 3 to 3.5 Core .
: - v) 120 Sqmm to 185 Sqmm Cable 3 to 3.5 Core
: - vi) 240 Sqmm Cable 3 to 3.5 Core .
: - vii) 300 Sq mm to 400 Sqmm Cable 3 to 3.5 Core .
5 : - Street Light. (HSR 31.30 ( vi -ii ) 9 mteres long 105 mm * 115 mm at top and 105 * 315 mm at bottom with working load of 200 kg buried 1.6 mtr in ground
6 : - S/E of mark double walled corrugated (DWC) HDPE pipe laid 1 mtr. below ground level including diging and refilling of earth including cost of suitable size socket / cuppler for HDPE pipe including the cost of labour and material required to complete the job in all respect upto the entire satisfaction of Engineer-incharge of the work (HSR 31.67) ii) HDPE pipe 145/123 mm outer dia/inner dia.
1 : - Non Schedule Items Three VCB Panel Board ( Compact Type) Supply, installation, testing and commissioning of 11 KV, 630 Amps, Non-Extensible indoor fixed type, RMU (Ring main unit) 3 way comprising of 3 No 630 Amps, Vaccum Circuit Breaker (Comprising One No. Incomer & Two Nos. as outgoing) inside robotically welded stainless steel (Non Ferrite Non Megnetic Grade) tank having min thickness 3 ± 0.5 mm having IP 67 degree of protection. RMU should be provided with Copper busbars internal, external as well as earthing busbars should be of copper, Resin cast ring core protection CT on cables 150-75/1 Amp, SP 10, 2.5 VA-03 Nos & Resin cast ring core metering CT 150-75/1 Amp, CI 1.0, 2.5 VA-3 No's on cables, one number fault passage indicator per unit, padlock provisions & complete with all accessories. The RMU shall be type tested for internal arc test of 20RA/I sec as per IEC62271-200. The unit shall include the following with all necessary standard fitting as required at site. (a) 1 No. 630 Amps motorised Vacumm Circuit Breaker triple pole, single break 3 position as incomer (On, Off and earth having STC capacity 20 KA for 3 seconds with copper bus bar and copper earth bar fitted with fixed type voltage indicator device as per IEC 61958-1, fully rated with earth switch, spring assisted mechanism, Red/ Green Push Button for On/ Off operation. Arc proof hinged type cable cover interlocked with earth switch. Air insulated cable boxes and boots suitable for bottom entry front termination of 3 core cable 95/120/185 Sqmm. (b) 2 Nos. 630 Amps manual Vacumm Circuit Breaker triple pole, single break 3 position as outgoing (On, Off and earth having STC capacity 20 KA for 3 seconds with copper bus bar and copper earth bar fitted with fixed type voltage indicator device as per IEC 61958-1, fully rated with earth switch, spring assisted mechanism, Red/ Green Push Button for On/ Off operation. Arc proof hinged type cable cover interlocked with earth switch. Air insulated cable boxes and boots suitable for bottom entry front termination of 3 core cable 95/120/185 Sqmm.(c) 3O/C + IE/F self powered relay with low and high set for over current and earth fault. Relay should have LCD (16 x 2). Relay should have facility to trip the breaker from remote commands without shunt trip coil, Last 5 fault record with time stamp, battery pack replaceable from front. Make of RMU : ABB/siemens/Schneider/ Voltamp. Interconnection between HT switchgear & transformer using AI. Armoured XLPE single core cable & interconnection between transformer & LT switchgear using copper bus bars. Internal earthing connections by 50 x 6mm Copper strips = 1 Set.
2 : - LT Panels and APFC Panels Note: All panel shall be completed as per the specifications and schematic diagram. The ventilation fans shall be provided in each capacitor banks TSM compartment. All meters shall be of digital type with LED display. All Multifunction meters shall have the communicating ports with LED display in the Main LT Panel. All TP MCCB shall have the neutral link. All MCCB shall be with operating handle. The provision of dedicated UPS, battery bank and the DC supply for Protection circuit and indication lamps shall be included in the cost of Main LT Panel. LT Panel for CODST Building ( MAKE - Siemens / Schneider / ABB / L&T / C&S / Havells / Advance Power Control System , Sudhir/ Dhillon Fabricators and Engineers/ Highlight) Supplying of 415V, 3 Phase, 50 Hz., 4 wire system, sheet steel clad, dust and vermin proof cubical and indoor type floor mounted, Free standing extendible type M.V. Panel with IP - 42 protection, compartmentalized design and fabricated out of 2 mm / 1.6 mm CRCA sheet steel complete with Copper Bus bars, Providing & Fixing of base plate / channel, P/F the following Switchgears, complete with earth Bus bar throughout the length of the panel, terminal arrangement for Incomings / Outgoings cables and also outgoing terminations for various sizes of cables, The incoming and outgoing feeders shall be accommodated in a modular multi-tier arrangement, adequate size bus duct/cable alley, Sign writing, Painting, Earthing, Numbering, Danger plate etc. complete as required as per specifications and drawing. (Make of LT Switchgear in LT panel : ABB/ Schiender/ Siemens/ L&T / C&S / Havells ) INCOMING: 1 nos. 2000A 415V, 4P 50kA EDO ACB with Microprocessor based release having O/L, S/C/ , E/F, RPR , O/V, U/V , Phase Sequence and Phase Loss Protection and ON /OFF/TRIP Indications , annuciator with MCB.- Incomer From CSS-1 (1250KVA) , 1 nos. 2000A 415V, 4P 50kA EDO ACB with Microprocessor based release having O/L, S/C/ , E/F, RPR , O/V, U/V, Phase Sequence and Phase Loss Protection and ON /OFF/TRIP Indications, annuciator with MCB.- Incomer From CSS-2 (1250KVA) , 1 nos. 1000A 415V, 4P 50kA EDO ACB with Microprocessor based release having O/L, S/C/ , E/F, RPR , O/V, U/V, Phase Sequence and Phase Loss Protection and ON /OFF/TRIP Indications, annuciator with MCB.- Incomer from DG-1 , 3 nos. Digital type Multifunction Meters to show (V, A, kWh, KVAh, KW, KVA, KVAR, PF, Hz.) with Communicating ports and cast resin CTs. 3 Set of LED phase indicating lamps with MCB protection for R,Y,B Indication. 3 Set of LED phase indicating lamps with MCB protection for On/Off/Trip Indication. 3 nos. Trip Circuit Supervision relays. 3 nos. Restricted earth fault realys with set of CT's PS Class. 1 no. Dual source Electronic type elecronic Auto matic power factor correction relay ( to sense the sifgnal from both Transformers feeder. 2 nos. TPN surge protection device of Class 1 & 2. BUSBARS: 1 Set of TPN Copper bus bar of minimum of 2000 A capacity with heat shrinkable coloured sleeves and i/c DMC/SMC bus bars supports at required intervals complete for cross section, size supports & their spacing etc, for withstanding fault level of 50 KA for 1 Sec. Electrical Interlocking between all incomers and Bus Couplers through PLC BUS COUPLER : 2 no. 2000A 415V, 4P 50kA EDO ACB with inbuilt O/L, S/C Protection and ON /OFF/TRIP Indications with MCB- Buscouplar , OUTGOINGS 1 no. 2000A 415V, 4P 50kA EDO ACB with Microprocessor based release having O/L, S/C/ , E/F, RPR , O/V, U/V Protection and ON /OFF/TRIP Indications with MCB.- HVAC Load , 1 no. 630A 415V, TP+Neutral Link MCCB of 50kA with Microprocessor based release, O/L and S/C protection and a set of CT's., Multi Function meter (V+A+Hz.)- Power Load , 1 no. 400A 415V, TP+Neutral Link MCCB of 50kA with Microprocessor based release, O/L and S/C protection and a set of CT's., Multi Function meter (V+A+Hz.)- Light Load , 1 no. 250A 415V, TP+Neutral Link MCCB of 50kA with Microprocessor based release O/L and S/C protection and a set of CT's., Multi Function meter (V+A+Hz.)- Fire Fighting Panel , 1 no. 200A 415V, TP+Neutral Link MCCB of 35kA with Microprocessor based release O/L and S/C protection and a set of CT's., Multi Function meter (V+A+Hz.)- Plubing Panel , 1 no. 125A 415V, TP+Neutral Link MCCB of 35kA with Microprocessor based release O/L and S/C protection and a set of CT's., Multi Function meter (V+A+Hz.)- Other Load , 1 no. 100A 415V, TP+Neutral Link MCCB of 35kA with thermal magnetic release, O/L and S/C protection and a set of CT's., Multi Function meter (V+A+Hz.)- Street Lighting , 1 no. 160A 415V, TP+Neutral Link MCCB of 35 kA with thermal magnetic release, O/L and S/C protection and a set of CT's., Multi Function meter (V+A+Hz.)- Spare , 2 nos. 100A 415V, TP+Neutral Link MCCB of 35kA with thermal magnetic release, O/L and S/C protection and a set of CT's., Multi Function meter (V+A+Hz.)- Spare ,
3 : - LT Panel for Admin Building + VC Building ( MAKE - Siemens / Schneider / ABB / L&T / C&S / Havells / Advance Power Control System , Sudhir / Dhillon Fabricators and Engineers/ Highlight ) Supplying of 415V, 3 Phase, 50 Hz., 4 wire system, sheet steel clad, dust and vermin proof cubical and indoor type floor mounted, Free standing extendible type M.V. Panel with IP - 42 protection, compartmentalized design and fabricated out of 2 mm / 1.6 mm CRCA sheet steel complete with Copper Bus bars, Providing & Fixing of base plate / channel, P/F the following Switchgears, complete with earth Bus bar throughout the length of the panel, terminal arrangement for Incomings / Outgoings cables and also outgoing terminations for various sizes of cables, The incoming and outgoing feeders shall be accommodated in a modular multi-tier arrangement, adequate size bus duct/cable alley, Sign writing, Painting, Earthing, Numbering, Danger plate etc. complete as required as per specifications and drawing.(Make of LT Switchgear in LT panel : ABB/ Schiender/ Siemens / L&T / C&S / Havells ) INCOMING: 1 nos. 1600A 415V, 4P 50kA EDO ACB with Microprocessor based release having O/L, S/C/ , E/F, RPR , O/V, U/V, Phase Sequence and Phase Loss Protection and ON /OFF/TRIP Indications, annuciator with MCB.- Incomer From CSS-4 (1000KVA) , 1 no. 800A 415V, 4P 50kA EDO ACB with Microprocessor based release having O/L, S/C/ , E/F, RPR , O/V, U/V, Phase Sequence and Phase Loss Protection and ON /OFF/TRIP Indications, annuciator with MCB.- Incomer from DG , 1 no. 800A 415V, 4P 50kA EDO ACB with Microprocessor based release having O/L, S/C/ , E/F, RPR , O/V, U/V, Phase Sequence and Phase Loss Protection and ON /OFF/TRIP Indications, annuciator with MCB.- Incomer From CSS-3 (500KVA) , 1 nos. 400A 415V, 4P MCCB of 50kA with Microprocessor based release O/L and S/C E/F, RPR , O/V, U/V, Phase Sequence and Phase Loss protection, annuciator and a set of CT's.- Incomer from DG , 4 nos. Digital type Multifunction Meters to show (V, A, kWh, KVAh, KW, KVA, KVAR, PF, Hz.) with Communicating ports and cast resin CTs. , 4 Set of LED phase indicating lamps with MCB protection for R,Y,B Indication , 4 Set of LED phase indicating lamps with MCB protection for On/Off/Trip Indication , 4 nos. Trip Circuit Supervision relays , 4 nos. Restricted earth fault realys with set of CT's PS Class , 1 no. Dual source Electronic type elecronic Auto matic power factor correction relay ( to sense the sifgnal from both Transformers feeder , 2 nos. TPN surge protection device of Class 1 & 2. BUSBARS: 1 Set of TPN Copper bus bar of minimum of 1600 A capacity with heat shrinkable coloured sleeves and i/c DMC/SMC bus bars supports at required intervals complete for cross section, size supports & their spacing etc, for withstanding fault level of 50 KA for 1 Sec , Electrical Interlocking between all incomers and Bus Couplers through PLC BUS COUPLER : 3 nos. 1600A 415V, 4P 50kA EDO ACB with inbuilt O/L, S/C Protection and ON /OFF/TRIP Indications with MCB.- Buscouplar OUTGOINGS 1 no. 800A 415V, 4P 50kA EDO ACB with Microprocessor based release having O/L, S/C/ , E/F, RPR , O/V, U/V Protection and ON /OFF/TRIP Indications with MCB.- HVAC Load , 1 nos. 250A 415V, TP+Neutral Link MCCB of 50kA with Microprocessor based release O/L and S/C protection and a set of CT's., Multi Function meter (V+A+Hz.)- Lighting , 1 nos. 250A 415V, TP+Neutral Link MCCB of 50kA with Microprocessor based release O/L and S/C protection and a set of CT's., Multi Function meter (V+A+Hz.)- HVAC Load , 1 nos. 250A 415V, TP+Neutral Link MCCB of 50kA with Microprocessor based release O/L and S/C protection and a set of CT's., Multi Function meter (V+A+Hz.)- Plumbing Panel , 1 nos. 250A 415V, TP+Neutral Link MCCB of 50kA with Microprocessor based release O/L and S/C protection and a set of CT's., Multi Function meter (V+A+Hz.)- Fire Fighting Panel , 1 nos. 200A 415V, TP+Neutral Link MCCB of 35kA with Microprocessor based release O/L and S/C protection and a set of CT's., Multi Function meter (V+A+Hz.)- Power , 1 no. 125A 415V, TP+Neutral Link MCCB of 35kA with thermal magnetic release, O/L and S/C protection and a set of CT's., Multi Function meter (V+A+Hz.)- Light Load , 1 nos. 100A 415V, TP+Neutral Link MCCB of 35kA with thermal magnetic release, O/L and S/C protection and a set of CT's., Multi Function meter (V+A+Hz.)- Power Load , 1 nos. 100A 415V, TP+Neutral Link MCCB of 35kA with thermal magnetic release, O/L and S/C protection and a set of CT's., Multi Function meter (V+A+Hz.)- Street Light , 1 nos. 125A 415V, TP+Neutral Link MCCB of 35kA with thermal magnetic release, O/L and S/C protection and a set of CT's., Multi Function meter (V+A+Hz.)- Other Load 1 nos. 160A 415V, TP+Neutral Link MCCB of 35kA with thermal magnetic release, O/L and S/C protection and a set of CT's., Multi Function meter (V+A+Hz.)- Spare ,
7 : - Supply, erection, testing & commissioning of 11 KV indoor H.T. Metering panel complete with CTs, PTs cubical and electronics meter with accuracy class 0.5 as per requirement / approved by HVPN Consisting of the following :- Cubical panel free standing floor mounting type made of sheet steel 14-G SWG CRCA sheet with channel iron base frame spray paintd with strong Synthetic grey channel paint as per size & design approved by HVPN . 3 Nos. 11 KV CTs of rating as approved by HVPN for indoor installation of approved make of HVPN. One No. 11 KV PT 11000/110 Volts 10 KA burden 0.5 accuracy oil filled suitable for indoor installation of approved make of HVPN. Digital electronic meter 3 Phase 4 wires 0.5 accuracy for recording reading operating system for difference kind of readings. The cubical panel will be complete in all respect including interconnection, internal wiring with PVC copper cable its testing and approved of all items by HVPN including cost of all testing/approved charges of all items of HVPN including cost of all labour & material required to complete the job in all respect upto the entire satisfaction of the Engineer-in-Charge ofthe work.
8 : - RUBBER MAT Supply and erection of Rubber Mat 1mx2mmx 3mm thick suitable for 11/33 KVA as per IS No. 15652C/M/L 3017739 as per approved by Chief Electrical inspector, Govt. of Haryana
9 : - Supply and erection of indoor type end termination jointing box heat shrinkable type suitable for 240 sqmm 3 core 11 K.H.V.T. XPLE cable with epoxy cast bushing including making necessary connection with all labour and material required to complete the job in all respect up to the entire satisfaction of the Engineer-in-charge of the work.(Make:- 3-M/ Densons/ Rachyem.) Suitable for 240 sqmm. 3 core XLPE cable
10 : - Supply and erection of outdoor type end termination jointing box heat shrinkable type suitable for 240 sqmm 3 core 11 K.H.V.T. XPLE cable with epoxy cast bushing including making necessary connection with all labour and material required to complete the job in all respect up to the entire satisfaction of the Engineer-in-charge of the work. (Make:- 3-M/ Densons/ Rachyem.) Suitable for 240 sqmm. 3 core XLPE cable
11 : - Supply & erection of fire extinguisher ISI marked ABC type 6 Kg. Capacity powder base with square grip Gavle duly erected/hung on wall with hook including the cost of hook, screw etc. with all the labour and material required to complete the job in all respect up to the entire satisfaction of the Engineer-In-Charge of the work.(Make:- Safex/Ceasefire/ Minimax).
12 : - Supply & Installation of CO2 type fire Extinguisher 4.5 KG capacity made from brand new seamless cylinder as per ISI mark IS: 7285 and CCE approval fitted with discharge hose and horne and squeeze grip /wheel type valve with initial charge as per IS 15683 : 2006 specification bearing ISI marks and EIL approved complete in all respect (Safex/ Minimax Make) with Three year warranty.
13 : - S/E of fire bucket of G.I. sheet of 24 gauge write with " FIRE" as per fire specification.
14 : - S/E of MS bucket stand suitable for six Nos. fire buckets (but without buckets) including the cost of welding & painting with all cost of red oxide and two coat of enameled paint of red colour completion all respect.
15 : - Supply and erection of stay wire suitable for 9/11 M. long RCC pole make out of 7/8 SWG GI wire with U type MS rod 5/8" dia duly threaded by means of angle iron of size 50 mm x 6 mm x 30 cm and 6 ft. long MS rod 5/8" dia 5' buried in the ground after fixing with cross channel size 75 mm x 40 mm x 60 cm. The stay wire will be binded on the top of the pole with help of suitable size of double U type MS clamps and stay fixed with nuts& bolts. The stay wire shall be insulated in the middle point with the help of egg. Insulator and complete with all labour and material required to complete the job in all respect up to the entire satisfaction of the Engineer-in-Charge of the work.
16 : - Supply and erection of 11 KV pin insulator with pin make with all labour and material required to complete the job including fixing the same on existing channels up to the entire satisfaction of Engineer-in- Charge of the work.
17 : - Supply and erection of 11 KV gang operated switch make conforming to IS with latest amendment including suitable size of copper blade erection of same on the existing 'H' pole with the help of 3 No. channels of size 75 mm x 40 mm x 6 mm, 1.8 M long fixed with suitable size of MS clamp, nuts and bolts including cost of 6 No. 11 KV insulator with GI pin R.D. fuses and painting with 2 coat of approved paint and one cost of red oxide and material required to complete the job in all respect up to the entire satisfaction of the Engineer-in-Charge of work.
18 : - Supply and erection of 11 KV disk insulator with all labour and material required to complete the job including fixing the same on existing channels up to the entire satisfaction of Engineer-in- Charge of the work
19 : - Supply and erection of lightening arrester module suitable for 11 KV G.O. switch with all labour and material required to complete the job in all respect upto the entire satisfaction of the Engineer-in-Charge of the work.
20 : - S/E angle iron, channel & clump with nut & bolts of various sizes required for made the platform & G.O. switch etc.
21 : - Supply and erection of fencing of transfer for safety precaution made out with the help to 50 cm x 50 cm x 6 mm angle iron, M.S. plate 50 mm x 6 mm, M.S. Jaal the perportionate quantities required in 1 sqm duly painted with red enameled paint including one coat of red oxide. The fencing angle shall be embedded in ground with C.C. mixture at least 60 cm in ground level including all labour and material required to complete the job up to the entire satisfaction of Engineer-in-charge of the work.
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .