Loading…
Loading…
Tender Value
₹4.4 Cr
EMD Value
₹8.8 L
Closing Date
25 Jun 2026, 1:00 pm
Construction of Station Service Building along with associated miscellaneous works at NYN station and Construction of S&T Service Buildings in section & other miscellaneous civil works in the jurisdiction of Dy.CSTE/PU/CNB in Prayagraj Division of North Central Railway
PU-CNB-W-03-2026
PU-CNB-W-03-2026
Open
12 Months
Prayagraj, Uttar Pradesh
₹0
₹8.8 L
2 Jun 2026
2 Jun 2026
11 Jun 2026
B-Non SOR Building Electrical work 6369646.75 Below/P
Supplying and laying PVC conduct pipe at 25mm dia in recess including cutting, 1 chase of requested size in brick walls earthling of conduct Pipe with 14 SWG GI wie run out grade along the conduct Pipe with all accessories like Juction box conduit bend and joints as per requirement with cover the Chage made for condurt will be made gered and required plaster by the contractor. Conduit shall be ISI mark as approved sample as a complete job.
Wiring for light/fan/exhaust fan/call bell points with 1.5 sqmm (22/.3 mm) PVC insulated single core unsheathed stranded Copper conductor ISI marked cable in recessed PVC pipe of ISI mark, MS switch box having wall thickness 16 SWG with 3 mm thick phenolic laminated sheet 2 cover including running of 16 SWG(1.5sqmm PVC insulated single core unsheathed stranded Copper of make Havells/Plaza/Grandley or similar) copper earth wire along with the pipe duly clamped as required and as per relevant technical specification No.Sr.DEE /G/ALD/IE/94/ 104/Rev and additional specification. (a) Medium Point Note: All accessories including Switches to be provided by the contractor.
Wiring for circuit with 2.5 sqmm (36/0.3mm) PVC insulated single core unsheathed stranded Copper conductor ISI marked cable in recessed PVC pipe of ISI marked and running of 16 3 SWG (1.5 sqmm PVC insulated single core unsheathed stranded Copper conductor approved make) copper earth wire duly clamped with pipe and providing multiway connector on MS switch box for neutral looping etc. as required and as per relevant technical specification. (a)2 x 2.5 sq mm of make Havells/Plaza/ Grandley or similar
Wiring for submain with 4 sqmm (56/0.3 mm) PVC insulated single core unsheathed stranded Copper conductor ISI marked cable in recessed PVC pipe of ISI marked and unning of 16 4 SWG/ (1.5 sqmm PVC insulated single core unsheathed stranded Copper conductor approved make) copper earth wire duly clamped with pipe and providing multiway connector on MS switch box for neutral looping etc. as required and as per relevant technical specification. (a) 2 x 4 sq mm of make Havells/Plaza/Grandley or similar
Wiring for submain with 6 sqmm (84/0.3 mm) PVC insulated single core unsheathed stranded Copper conductor ISI marked cable in recessed PVC pipe of ISI marked and running of 16 5 SWG (1.5sqmm PVC insulated single core unsheathed stranded Copper conductor approved make)copper earth wire duly clamped with pipe and providing multiway connector on MS switch box for neutral looping etc. as required and as per relevant technical specification.( a ) 2 x 6 sq mm of make Havells/Plaza/Grandley or similar
Wiring for luminaries and fans with 2 x 1 sqmm (14/0.3mm) PVC insulated single core 6 unsheathed stranded Copper conductor along with 16 SWG (1.5sqmm PVC insulated single core unsheathed stranded Copper conductor approved make)copper earth wire through PVC pipe 20mm including connecting, testing & commissioning as required and as per relevant technical specification.Make Havells/Plaza/Grandley or similar
Supply, replacement, fixing, testing, connecting and commissioning of 72 Watt or above LED street lights fittings.LED Luminaries:-(1) A complete LED lighting unit consisting of a light source and driver together with parts of distribute lights,to position and protect the light source,and to connect the light source to a branch circuit.The light source itself may be an LED array and LED module, or an LED lamp. (2):-Supplied LED luminaries shall confirm to IS:16101(2012) IS :16106(2012).Light Source(LED) in the Luminaries should be of make:- (1):-NICHIA/ CREE/OSRAM/ SEOUL/ PHILIPS/LUMILEDS /LEDNIUM. (2):- LEDs to IS:16105(2012).IS:16108 (2012), IEC: 62471. Type LED:
Supply, replacement, fixing, testing, connecting and commissioning of energy efficient luminaries complete with all accessries of capacity 20 watt, 4 feet length, T8 LED lamps with sutable current control driver circuit ,suitable for surface/recessed mounting.LED Luminaries:- (1) A complete LED lighting unit consisting of a light source and driver ogether with parts of 8 distribute light,to position and protect the light source,and to connect the light source to a branch circuit.The light source itself may be an LED array and LED module, or an LED lamp. (2):-Supplied LED luminaries shall confirm to IS:16101(2012) IS :16106(2012).Light Source(LED) in the Luminaries should be of make:- (1):-NICHIA/ CREE/OSRAM/ SEOUL/PHILIPS/LUMILEDS /LEDNIUM. (2):- LEDs to IS:16105 (2012).IS:16108 2012),IEC: 62471.1.Input operating voltage :-105- 295 V AC.2:-Normal Voltage-220V. (a)1x20 watt.Make- Philips, Bajaj, Crompton or similar
Wiring for submain with 10 sqmm PVC insulated single core unsheathed stranded Copper conductor ISI marked cable in recessed PVC pipe of ISI marked and running of 16 SWG/ 9 (1.5sqmm PVC insulated single core unsheathed stranded Copper conductor approved make) copper earth wire duly clamped with pipe and providing multi-way connector on MS switch box for neutral looping etc. as required and as per relevant technical specification. 2 x 10 sq mm of make Havells/Plaza/Grandley or similar
Supply, fixing, testing, connecting and commissioning of Ceiling Fan 1200/1400mm 10 sweep , 230V AC ,white/brown colours of Make: Philips/Bajaj/Crompton greaves or similar and electronic regulator with wiring the down rod of 762mm length upto 30mm including assembling & C/W twisted flexiblechord of minimum size 16/0.2mm Cu conductor as per technical specification.
Wiring for 3/5 pin, 5 Amp. Plug point with 1.5 sqmm (22/.3mm) PVC insulated single 11 core unsheathed stranded Copper conductor ISI markedcable including providing and fixing 3/5 pin 5 Amps. Socket out let with switch on same board and earthing the 3rd pin with 16 SWG/ (1.5sqmm PVC insulated single core unsheathed stranded Copper conductor approved make) copper earth wire etc. as required and as per relevant technical specification.Make: Havells/Plaza/Grandley or similar
Wiring for 3/5 pin 15 amps plug points with 2.5 sqmm (36/0.3mm) PVC insulated single core unsheathed stranded Copper conductor ISI marked in recessed PVC pipe of ISI marked 12 and MS switch box having wall thickness 16 SWG with 3 mm thick phenolic laminated sheet cover including providing and fixing 3/5 pin 5/15 Amps socket outlets and 5/15 Amps piano type switch and earthing the 3rd pin with 16 SWG/(1.5sqmm PVC insulated single core unsheathed stranded Copper conductor approved make) Copper earth wire along with pipe duly clamped as required and as per relevant technical specification. (5pin 15Amp). Make: Havells/ Plaza/ Grandley or similar
Supply, fixing, testing, connecting and commissioning of 300 mm sweep Exhaust Fan suitable for 230 volts, 50 Hz AC supply, 900 RPM heavy duty with wiring and flexible PVC pipe as required .Make: Almonard, Bajaj, Havell's or similar.
Supply, erection, testing and commissioning of approved make standard size of following Distribution board recessed in wall having earth terminal block and neutral terminal block 14 to enable termination of conductors incoming as well as outgoing individually by screwed connections and without twisting complete in all respect as per relevant technical specification. DP distribution board of standard size confirming to technical specification No. Sr.DEE/G/ALD/94/104 comprising of one No. 2 pole 63 Amps MCB of make: Crompton/Havells/L&T or similar.(a) 8 way spare MCB's of 6/10 Amps as required. Make: Crompton/ Havells/ L&T or similar "
"Supply and installation of earth electrode as per standard practice and as per NCR Drawing no. S&T/CONST/6.4/97. It includes supply of GI pipe of 3m length. It includes connecting the earth electrode to the equipments which are required to be earthed including digging of earth pit 3 mtr deep and fixing earth electrode pipe, casting of cement concrete enclosure with cover (cover as per drawing no. S&T/CONST/6.3/97. It includes installation of 7 strand GI wires as earth lead wires, supported on MS flat size 5mm x 40 mm, soldering and nut bolt both, one end of both earth lead wire and MS flat to earth electrode and other end to Location boxes, block equipments, power equipments, cable sheath, signals etc. as per site requirement and as per instructions given by engineer incharge. "
Preparation and submission of structural design & Architectural Drawing of the 16 Proposed work between Panki-SB section includy survey at the site of the work and determination of bearing capacity of the sail as per the instructions of the engineer in charge. NOTE. The Architectural drawing & structural design should be done by a reputed Architect and qualified structural Engg.
Supply and erection of fencing panels at LSC buildings. As per RDSO Drawing no ETI/C/0186 SH-1 and SH-2.
Supply and erection of fencing uprights. As per RDSO Drawing no ETI/C/0186 SH-1 and SH-2.
Supply and erection of gates for fencing. As per RDSO Drawing no ETI/C/0186 SH-1 and SH-2.
Supply and erection of Anti climbing device at LSC Buildings. As per RDSO Drawing no ETI/C/0186 SH-1 and SH-2.
Providing and placing on terrace (at all floor levels) polyethylene water storage tank, IS : 12701 marked, with cover and suitable locking arrangement and making necessary holes for inlet, outlet and overflow pipes but without fittings and the base support for tank.
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
HTML
nit.pdf
NIT
2026_03_13IRStandardGCCApril2022ACSNo_11_compressed.pdf GCC Correction Slip no 11
ATTACHMENT
Tender_Document_NYN__Other_Misc_Works.pdf
ATTACHMENT
GCCApril-2022_2_1.pdf
ATTACHMENT
GCCCS1to10.pdf
ATTACHMENT
NameofBrandforNCR1.pdf
ATTACHMENT
TenderDocumentNYN.pdf
ATTACHMENT
Standard_Layout_of_Station_Building_compressed.pdf
ATTACHMENT
2026_03_13IRStandardGCCApril2022ACSNo_11_compressed.pdf
ATTACHMENT
Download all tender documents and submit your bid