Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹2.1 LAccepted-AOC 00 MAA KALI ENTERPRISE NEW ROAD KULTI BARDHAMAN WEST BENGAL 713343 | PASCHIM BARDHAMAN | WEST BENGAL | 713343 | L1 | Accepted-AOC lowest rate | |
| 2 | L2₹2.1 L+₹2,134.51 (1.04%)Rejected-Finance | L2 | Rejected-Finance Higher than L1 | |
| 3 | L3₹2.1 L+₹3,236.93 (1.57%)Rejected-Finance 77 2 1 LENIN SARANI KOLKATA 700013 | KOLKATA | KOLKATA | WEST BENGAL | 700013 | L3 | Rejected-Finance Higher than L1 |
Tender Value
Refer Docs
EMD Value
₹4,300
Closing Date
1 Aug 2023, 6:00 pmClosed
Executive Engineer Electrical Division PHED
P16 India Exchange Place CIT Annexe Bldg Extn 2nd floor Kolkata 700073
E/M works
2023_PHED_546986_34
WBPHED / EE / ED / 14 / 2023-24
Open Tender
Electrical Work/ Equipment
Item Rate
30 days
Office of the Executive Engineer ED PHED
Please refer Tender documents.
6 documents required · 6 mandatory
₹4,300
19 Feb 2025
15 Jul 2023
4 Aug 2023
15 Jul 2023
1 Aug 2023
15 Jul 2023
Amount
Supply & delivery of wall mounted M.S. febricated by 2 mm thick CRCA steel enclosure hinged type front door powder coated motor control cubical panel (for 7.5 to 10 H.P, Star Delta, 3 phase) having internal wiring. The panel consisting of the following accesorries:-
Incomer:
4P MCCB (63.Amp., 25KA) fixed O/L, S/C protection, (Make- Siemens / ABB/L&T) - 1 no.
Spreader Link for above MCCB (ABB/L & T) 1 No.
Digital Ammeter, CL-1, 96mmx96mm (Make- AE/Rishav) - 1 no.
Digital Voltmeter, CL-1, 96mmx96mm (Make- AE/Rishav) - 1 no.
C.T. 60/5, 15 VA, CL-1, Tape wound type (Make-ECS/Kappa) - 3 nos.
SP MCB (6 Amp, 10KA), (Make- Siemens/ABB/L&T) - 3 nos.
Phase Indicating Lamp (R/Y/B) LED type 230V, AC (Make-ABB/Siemens/Sumo) - 3 nos.
Voltage monitoring relay (Phase failure, Unbalance, Phase sequence, under Voltage and over voltage protection with digital display) (Make - Siemens/ Minelec/PHE Approved
Voltage Trip Indicator (Yellow) - LED Type, 230V, AC (Make- ABB/Siemens) - 1 no.
Surge Protection (DS440-280)DUAL.(CITEL) 1 No.
TPN MCB, 25Amp, 10KA (ABB/L &T) 1 No.
Auto Phase Correction Device .(ECS/Kappa) 1 No.
Outgoing Feeder:
For Star-Delta Starter(7.5-10 HP)
Motor Protection Relay (3-30Amp, Over Current, Locked Rotor, Phase Reversal and Phase Loss Protection) [Make-BOCR-BCH] - 2 no.
Power Contactor, AC-3 Duty (18Amp., 230V, AC), (Make- Siemens/ABB/ L&T) - 6 nos.
TP MCB (10 Amp, 10KA), (Make- Siemens/ABB/L&T) - 2 no.
SP MCB (6 Amp, 10KA), (Make- Siemens/ABB/L&T) - 2 no.
Phicap ROU 440V 50/60Hz-4/4.8KVAr 3 PH, (Make- Epcos) - 2 no.
Contactor for Capacitor (9 Amp., 230 V AC), (Make- Siemens/ABB/L&T) - 2 no.
Star-Delta Timer (3-120Sec, 240 V AC), (Make- Siemens/GIC/PHE Approved) - 2 no.
On Delay Timer (0.5Sec.-30Hrs., 240 V AC), (Make- Siemens/GIC/PHE Approved) - 2 no.
Start/Stop Push Button, 1NO/1NC Contact (Make- ABB/Siemens) - 4 nos.
ON/OFF/Trip Indicator (R/Y/G) LED type, (Make- ABB/Siemens) - 6 nos.
CHLORINATOR:
TP MCB 16 Amp, 10KA. (Make-ABB/Siemens/L&T) - 1 no.
Power Contractor, AC-3 Duty, 9Amp., 230V, AC (Make-ABB/Siemens/L&T) - 1 no.
Tharmal overload Relay (1.3 to 1.8 Amp.) (Make-ABB/Siemens/L&T/PHE Approved) - 1 no.
Over Load Relay Mounting Kit (Make - ABB/Siemens/L&T) 1 No.
Start/Stop Push Button, 1NO/1NC Contact (Make- ABB/Siemens) - 2 nos.
ON/OFF/Trip Indicator (R/Y/G) LED type, (Make- ABB/Siemens) - 3 nos.
Liquid Level Controler,240V,AC (ECS/GIC).
Panel make : RNR Industries / PCE Projects / OPG Power System / ECS. [TC & GC should be submitted at the time of delivery].
Existing Panel dismantle & Installtion of panel by drawing power line with dismantling from temporary connected panel and other fixing materials required to complete the job including necessary in all respect including successfull operation along with testing of the whole installation as per entire satisfaction of EIC with out hampering the water supply.
Add: 18% GST
Add: 1% CESS
MOITRA ENGINEERING CO
D K ELECTRIC
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .