Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹39.2 LAccepted-AOC | L1 | Accepted-AOC Being Lowest | |
| 2 | L2₹40.2 L+₹6,815 (0.17%)Rejected-Finance | L2 | Rejected-Finance Being other than lowest | |
| 3 | L3₹42.0 L+₹1.9 L (4.73%)Rejected-Finance | L3 | Rejected-Finance Being other than lowest | |
| 4 | L4₹42.8 L+₹2.7 L (6.69%)Rejected-Finance B BLOCK 2 3 RAM BACHAN V B NAGAR PIPE ROAD KURLA W MUMBAI 400070 | MUMBAI SUBURBAN | MAHARASHTRA | 400070 | L4 | Rejected-Finance Being other than lowest | |
| 5 | L5₹43.8 L+₹3.7 L (9.26%)Rejected-Finance | L5 | Rejected-Finance Being other than lowest |
| Sl No | Description | Qty | Unit | NOEL ENGINEERS L3 | Ramesh Electrical and Mechanical Works L6 | Panther Facilities L1 | Genius Construction Co. L4 | Sri Krishna Construction L2 | M/S V N ENTERPRISES L5 |
|---|---|---|---|---|---|---|---|---|---|
| 1.00 | Supply, install, testing and commissioning of meter cabin panel mounted on angle iron frame 40x40x5 mm grouted on floor,cubical indoor type for 415V, 3 phase, 4 wire made out of 2 mm thick CRCA sheet weather, vermin proof factory fabricated, CPRI approved, front open hinged door with locking arrangement powder coated, individual compartment for MCCBs and 200 Amps rated copper bus bar(All in equal size), top and bottom cable entry with proper size glands including disconnecting cable connections and electronic meters from old meter cabin panel and fixing & connecting in new installed panel with provisions of thimble/lugs and making provisions of vision glasses for meter readings, one spare MCCB compartment, and including PCC on 1:2:4 type B-1 for fixing meter cabin at old meter cabin place complete all as specified and as directed comprising of the following (a) MCCB 100A, 4 pole, 415 volt, thermal magnatic release type, Ics=100% Icu, 25 kA - 01 Nos, Cat No-4200 55 of Make-Legrand/Siemens/L&T/Schneider. (b) MCCB 63A, 4 pole, 415 volt, thermal magnatic release type, Ics=100% Icu, 25 kA-02 Nos, Cat No-4200 53 of Make-Legrand/Siemens/L&T/Schneider.
(c) Taking out the meter from the existing panel and fix it in new panel along with wiring complete. (d) MCB SPN 32 Amps- 10 Nos Make-Legrand Cat No-4086 17 or eqivalent to L&T/Schnider/ABB. (e) Digital panel meter with LCD multifunction meter with CT/PT and all parameters as V, A, F, PF, KW, kVAR, kWH etc of
make :- L&T, Cat Ref -WL441010OOOO-01 set or equivalent in Legrand/Schnieder/ABB. (f) Phase indicator lamp R,Y & B - (01 Set of three). (g) Copper Bus bar, 200 Amps Rated - R,Y,B & N - (01Set of four). (h) Reconnecting of submain cable 2 core 4/ 6 Sqmm copper conductor with outgoing of energy meter. (i) Making good the disturbed surface of meter cabin room if any damages occures during shifting of panel.
Note :- Before fabrication of panel the contractor has to take approval from accepting officer on drawing. | 9 | Each Job | 1,63,666 ₹14,72,994 | 97,256 ₹8,75,304 | 67,800 ₹6,10,200 Lowest | 1,08,000 ₹9,72,000 | 74,000 ₹6,66,000 | 80,000 ₹7,20,000 |
| 2.00 | All as per Item No 1.00 above but comprising of the following :- (a) MCCB 63A, 4 pole, 415 volt, thermal magnatic release type, Ics=100% Icu, 25 kA-02 Nos, Cat No-4200 53 of Make-Legrand/Siemens/L&T/Schneider (b) MCB SPN 32 Amps- 10 Nos Make-Legrand Cat No-4086 17 or eqivalent to L&T/Schnider/ABB
(c) Taking out the meter from the existing panel and fix it in new panel along with wiring complete.
(d) Digital panel meter with LCD multifunction meter with CT/PT and all parameters as V, A, F, PF, KW, kVAR, kWH etc of
make :- L&T, Cat Ref -WL441010OOOO-01 set or equivalent in Legrand/Schnieder/ABB. (e) Phase indicator lamp R,Y & B - (01 Set of three). (f) Copper Bus bar, 100 Amps Rated - R,Y,B & N - (01Set of four). (g) Reconnecting of submain cable 2 core 4/ 6 Sqmm copper conductor with outgoing of energy meter. (h) Making good the disturbed surface of meter cabin room if any damages occures during shifting of panel.
Note :- Before fabrication of panel the contractor has to take approval from accepting officer on drawing. | 9 | Each Job | 77,700 ₹6,99,300 | 97,256 ₹8,75,304 | 61,800 ₹5,56,200 Lowest | 1,08,000 ₹9,72,000 | 70,000 ₹6,30,000 | 80,000 ₹7,20,000 |
| 3.00 | Taking out old u/s and Supply, installing, testing and commissioning of LT feeder pillar box factory made cubical outdoor type, fabricated out of 2.00 mm thick CRCA sheet with angle iron base frame made of 40x40x6mm, 45cm height, floor mounted duly bolts and nuts grouted, dust and vermine proof, suitable for voltage 415V 3 phase 4 wire weather proof with IP-66 protection, with separate hinge door for each compartment for incoming and out going MCCB etc with locking arrangement, with back door openable (Screwed), legs grouted in PCC complete including painting with two coats of epoxy powder paint over a coat of primer after under going a rigorous metal treatment process involving alkaline degreasing, descaling in dilute sulphuric acid or any other acid and phosphate and with copper busbar (TPN), suitable double compression copper cable glands complete in all respect for bay work station and including provn of the following:- (a) S&F MCCB 100 Amps, 4 Pole, 25 kA, thermal magnetic release, Ics=100% Icu - 01 Nos, (b) S&F MCCB 63 Amps, 4 Pole, 16 kA, thermal magnetic release, Ics=100% Icu - 01 Nos, (c) S&F RCBO's 63 Amps, 4 Pole 300mA - 01 Nos,
(d) S&F MCB SPN 40 Amps, 10 kA, - 01 Nos, (e) Digital panel meter with LCD multifunction meter with CT/PT and all parameters as V,A,F,PF,KW,kVAR,kWH etc of (f) Phase indicator lamp R,Y & B (Set of 3)- 01 Set (g) S&F Copper Bus bar 250 Amps of suitable size, all are in equal size - Set 1(R, Y, B, N) Note: All existing cable connections will be disconnected from old Panel carefully and re-connected with new Panel by providing glands and thimble all as directed by Engr-in-Charge. | 8 | Each Job | 74,160 ₹5,93,280 | 1,81,329 ₹14,50,632 | 39,800 ₹3,18,400 Lowest | 45,000 ₹3,60,000 | 47,400 ₹3,79,200 | 80,000 ₹6,40,000 |
| 4.00 | Supply and installation of Smart Single Phase Meter with the following specifications:
(i) AC Single phase Two Wire, Tamper Proof, Static Meter of Class 1.0, 240 V, 50 Hz, 10 A-60 A conforming to IS-16444 and relevant IEC standards with inbuilt 865-867 MHz Radio Frequency communication facility with self-healing Mesh network with defalult and on demand display, biling date generation facility, anti-tamper features. Microprocessor and LED/LCD based circuitry.
(ii) Meter should support the following data : 30 min instaneous data for voltage, current, power factor, power, cumulative energy and frequency, 30 load survey date for energy, mopntly billing survey for cumulative energy and Max Demand.
(iii) Meter should have connect/disconnect functionality operable from prepaid billing software.(iv) The meter should support open communication protocol DLMS with the software. Note:(a) The contractor would be responsible from removing the existing meter, noting down the reading and depositing it with the MES. (b) It would be possible to run the meter in both prepaid and postpaid . | 40 | Each Job | 5,500 ₹2,20,000 | 3,132 ₹1,25,280 Lowest | 6,800 ₹2,72,000 | 8,000 ₹3,20,000 | 5,000 ₹2,00,000 | 7,000 ₹2,80,000 |
| 5.00 | S & F cable PVC insulated, PVC sheathed, armoured, FRLS, 1100V grade, 2 core 6 sqmm stranded copper conductor electric cable laid on wall/ roof/ duct complete with proper saddling and connecting to DBs with glands including taking out existing unserviceable cable complete all as specified. | 4,000 | RM | 142 ₹5,68,000 | 249 ₹9,96,000 | 280 ₹11,20,000 | 135 ₹5,40,000 Lowest | 160 ₹6,40,000 | 220 ₹8,80,000 |
| 6.00 | Material & Labour for earthing with steel earth plate electrode of size 60x60cmx6mm thick buried directly in ground to a depth not less than 2.25 mtr deep below normal ground level with top edge of the earth plate not less than 1.5 mtr deep below normal ground level connected to galvanized iron strip of size 32x6 mm as earthing lead by means of nuts, bolts and washers of steel after welding of GI strip to earth electrode to the full length of earth plate, GI medium grade pipe 40 mm bore protection pipe upto test point, 20mm dia GI light grade watering pipe with funnel and wire mesh, RCC pit cover of size 300x300x40mm reinforced including 6mm thick MS bar handle made to shape, PCC pit with 1:3:6 type C1 with angle iron frame made of angle iron of size 40x40x4mm, adequate qty of charcoal dust and salt layers all around the earth plate, excavation , earth work in any type of soil, removal of excavated soil and returning filling in all as required at site complete all as specified in plate No 3 of SSR Part-I and all as specified or indicated including testing on completion. NOTE :-Rates inclusive of necessary excavation in any type of soil, earth work, PCC pit, RCC cover, funnel with watering pipe, GI earth wire upto 7.5 m long for connecting to test point etc. all as required at site for complete earthing. | 26 | Each | 3,000 ₹78,000 Lowest | 14,173 ₹3,68,498 | 3,500 ₹91,000 | 3,700 ₹96,200 | 4,000 ₹1,04,000 | 5,000 ₹1,30,000 |
| 7.00 | M&L for aluminium strip 25x3.15mm with saddles and fixing screws etc. for roof conductors above ground. | 250 | RM | 60 ₹15,000 Lowest | 260 ₹65,000 | 170 ₹42,500 | 95 ₹23,750 | 100 ₹25,000 | 150 ₹37,500 |
| 8.00 | M&L of test point terminal block made of gun metal or phosphorus bronze size 75x75x25mm drilled and screwed including 3 Nos 8mm dia 25mm long hex head screw | 26 | Each | 200 ₹5,200 Lowest | 862 ₹22,412 | 800 ₹20,800 | 500 ₹13,000 | 900 ₹23,400 | 500 ₹13,000 |
| 9.00 | M&L scrapping old worn out paint from complete indoor type meter cabin panels and painting with one coats of synthetic enamel paint (incl front door in side and indl compartment outer side etc also) over a coat of primer and spray painting complete including fixing sticker danger sign board suitable for LT panel board and replacement of brocken glass of any size all as specified and as directed by engr-in-charge. | 120 | Each Job | 400 ₹48,000 | 3,403 ₹4,08,360 | 400 ₹48,000 | 300 ₹36,000 Lowest | 500 ₹60,000 | 700 ₹84,000 |
| 10.00 | M & L for snap-on trunking system including cover, angles bends and all accessories and fitting of size 50x80 mm fixing on wall complete all specified and directed. | 820 | RM | 140 ₹1,14,800 Lowest | 1,358 ₹11,13,560 | 400 ₹3,28,000 | 400 ₹3,28,000 | 768 ₹6,29,760 | 200 ₹1,64,000 |
Tender Value
₹47 L
EMD Value
₹94,000
Closing Date
3 Sept 2025, 6:00 pmClosed
GE NW NAVY NAGAR COLABA MUMBAI
GE NW NAVY NAGAR COLABA MUMBAI DR HOMI BHABHA ROAD NAVY NAGAR COLABA MUMBAI
REPAIR MAINTENANCE OF SERVICE CABLE SUBMAIN WIRING ELECTRIC PANEL AT SAILOR MARRIED ACCOMMODATION AND LIFT MACHINE ROOM OF LOW RISE BUILDING OF OLD AND NEW NAVY NAGAR UNDER GE NW NAVY NAGAR
2025_MES_724762_1
8541/E8
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
GE NW NAVY NAGAR COLABA MUMBAI
Class D and Category b(i)
8 documents required · 8 mandatory
₹500
GE NW NAVY NAGAR COLABA MUMBAI
₹94,000
9 Oct 2025
6 Aug 2025
5 Sept 2025
6 Aug 2025
3 Sept 2025
20 Aug 2025
Amount
Supply, install, testing and commissioning of meter cabin panel mounted on angle iron frame 40x40x5 mm grouted on floor,cubical indoor type for 415V, 3 phase, 4 wire made out of 2 mm thick CRCA sheet weather, vermin proof factory fabricated, CPRI approved, front open hinged door with locking arrangement powder coated, individual compartment for MCCBs and 200 Amps rated copper bus bar(All in equal size), top and bottom cable entry with proper size glands including disconnecting cable connections and electronic meters from old meter cabin panel and fixing & connecting in new installed panel with provisions of thimble/lugs and making provisions of vision glasses for meter readings, one spare MCCB compartment, and including PCC on 1:2:4 type B-1 for fixing meter cabin at old meter cabin place complete all as specified and as directed comprising of the following (a) MCCB 100A, 4 pole, 415 volt, thermal magnatic release type, Ics=100% Icu, 25 kA - 01 Nos, Cat No-4200 55 of Make-Legrand/Siemens/L&T/Schneider. (b) MCCB 63A, 4 pole, 415 volt, thermal magnatic release type, Ics=100% Icu, 25 kA-02 Nos, Cat No-4200 53 of Make-Legrand/Siemens/L&T/Schneider. (c) Taking out the meter from the existing panel and fix it in new panel along with wiring complete. (d) MCB SPN 32 Amps- 10 Nos Make-Legrand Cat No-4086 17 or eqivalent to L&T/Schnider/ABB. (e) Digital panel meter with LCD multifunction meter with CT/PT and all parameters as V, A, F, PF, KW, kVAR, kWH etc of make :- L&T, Cat Ref -WL441010OOOO-01 set or equivalent in Legrand/Schnieder/ABB. (f) Phase indicator lamp R,Y & B - (01 Set of three). (g) Copper Bus bar, 200 Amps Rated - R,Y,B & N - (01Set of four). (h) Reconnecting of submain cable 2 core 4/ 6 Sqmm copper conductor with outgoing of energy meter. (i) Making good the disturbed surface of meter cabin room if any damages occures during shifting of panel. Note :- Before fabrication of panel the contractor has to take approval from accepting officer on drawing.
All as per Item No 1.00 above but comprising of the following :- (a) MCCB 63A, 4 pole, 415 volt, thermal magnatic release type, Ics=100% Icu, 25 kA-02 Nos, Cat No-4200 53 of Make-Legrand/Siemens/L&T/Schneider (b) MCB SPN 32 Amps- 10 Nos Make-Legrand Cat No-4086 17 or eqivalent to L&T/Schnider/ABB (c) Taking out the meter from the existing panel and fix it in new panel along with wiring complete. (d) Digital panel meter with LCD multifunction meter with CT/PT and all parameters as V, A, F, PF, KW, kVAR, kWH etc of make :- L&T, Cat Ref -WL441010OOOO-01 set or equivalent in Legrand/Schnieder/ABB. (e) Phase indicator lamp R,Y & B - (01 Set of three). (f) Copper Bus bar, 100 Amps Rated - R,Y,B & N - (01Set of four). (g) Reconnecting of submain cable 2 core 4/ 6 Sqmm copper conductor with outgoing of energy meter. (h) Making good the disturbed surface of meter cabin room if any damages occures during shifting of panel. Note :- Before fabrication of panel the contractor has to take approval from accepting officer on drawing.
Taking out old u/s and Supply, installing, testing and commissioning of LT feeder pillar box factory made cubical outdoor type, fabricated out of 2.00 mm thick CRCA sheet with angle iron base frame made of 40x40x6mm, 45cm height, floor mounted duly bolts and nuts grouted, dust and vermine proof, suitable for voltage 415V 3 phase 4 wire weather proof with IP-66 protection, with separate hinge door for each compartment for incoming and out going MCCB etc with locking arrangement, with back door openable (Screwed), legs grouted in PCC complete including painting with two coats of epoxy powder paint over a coat of primer after under going a rigorous metal treatment process involving alkaline degreasing, descaling in dilute sulphuric acid or any other acid and phosphate and with copper busbar (TPN), suitable double compression copper cable glands complete in all respect for bay work station and including provn of the following:- (a) S&F MCCB 100 Amps, 4 Pole, 25 kA, thermal magnetic release, Ics=100% Icu - 01 Nos, (b) S&F MCCB 63 Amps, 4 Pole, 16 kA, thermal magnetic release, Ics=100% Icu - 01 Nos, (c) S&F RCBO's 63 Amps, 4 Pole 300mA - 01 Nos, (d) S&F MCB SPN 40 Amps, 10 kA, - 01 Nos, (e) Digital panel meter with LCD multifunction meter with CT/PT and all parameters as V,A,F,PF,KW,kVAR,kWH etc of (f) Phase indicator lamp R,Y & B (Set of 3)- 01 Set (g) S&F Copper Bus bar 250 Amps of suitable size, all are in equal size - Set 1(R, Y, B, N) Note: All existing cable connections will be disconnected from old Panel carefully and re-connected with new Panel by providing glands and thimble all as directed by Engr-in-Charge.
Supply and installation of Smart Single Phase Meter with the following specifications: (i) AC Single phase Two Wire, Tamper Proof, Static Meter of Class 1.0, 240 V, 50 Hz, 10 A-60 A conforming to IS-16444 and relevant IEC standards with inbuilt 865-867 MHz Radio Frequency communication facility with self-healing Mesh network with defalult and on demand display, biling date generation facility, anti-tamper features. Microprocessor and LED/LCD based circuitry. (ii) Meter should support the following data : 30 min instaneous data for voltage, current, power factor, power, cumulative energy and frequency, 30 load survey date for energy, mopntly billing survey for cumulative energy and Max Demand. (iii) Meter should have connect/disconnect functionality operable from prepaid billing software.(iv) The meter should support open communication protocol DLMS with the software. Note:(a) The contractor would be responsible from removing the existing meter, noting down the reading and depositing it with the MES. (b) It would be possible to run the meter in both prepaid and postpaid .
S & F cable PVC insulated, PVC sheathed, armoured, FRLS, 1100V grade, 2 core 6 sqmm stranded copper conductor electric cable laid on wall/ roof/ duct complete with proper saddling and connecting to DBs with glands including taking out existing unserviceable cable complete all as specified.
Material & Labour for earthing with steel earth plate electrode of size 60x60cmx6mm thick buried directly in ground to a depth not less than 2.25 mtr deep below normal ground level with top edge of the earth plate not less than 1.5 mtr deep below normal ground level connected to galvanized iron strip of size 32x6 mm as earthing lead by means of nuts, bolts and washers of steel after welding of GI strip to earth electrode to the full length of earth plate, GI medium grade pipe 40 mm bore protection pipe upto test point, 20mm dia GI light grade watering pipe with funnel and wire mesh, RCC pit cover of size 300x300x40mm reinforced including 6mm thick MS bar handle made to shape, PCC pit with 1:3:6 type C1 with angle iron frame made of angle iron of size 40x40x4mm, adequate qty of charcoal dust and salt layers all around the earth plate, excavation , earth work in any type of soil, removal of excavated soil and returning filling in all as required at site complete all as specified in plate No 3 of SSR Part-I and all as specified or indicated including testing on completion. NOTE :-Rates inclusive of necessary excavation in any type of soil, earth work, PCC pit, RCC cover, funnel with watering pipe, GI earth wire upto 7.5 m long for connecting to test point etc. all as required at site for complete earthing.
M&L for aluminium strip 25x3.15mm with saddles and fixing screws etc. for roof conductors above ground.
M&L of test point terminal block made of gun metal or phosphorus bronze size 75x75x25mm drilled and screwed including 3 Nos 8mm dia 25mm long hex head screw
M&L scrapping old worn out paint from complete indoor type meter cabin panels and painting with one coats of synthetic enamel paint (incl front door in side and indl compartment outer side etc also) over a coat of primer and spray painting complete including fixing sticker danger sign board suitable for LT panel board and replacement of brocken glass of any size all as specified and as directed by engr-in-charge.
M & L for snap-on trunking system including cover, angles bends and all accessories and fitting of size 50x80 mm fixing on wall complete all specified and directed.
Material & Labour for repairs/ Servicing to Existing Meter panels Indoor type of each Bldg by taking shut down from appropiate authority including checking loose connections and tight connection and cleaning inside/out side all connection, replacing old/rusted cable glands,thimbles and lugs as per the size of existing cable, repair to broken /hanging doors, glas and cover bolts etc to make it servicable and testing the entire panel board after the completion of servicing up to the satisfication of Engr-in-charge all as directd and specified. Note :- The tenders quoted rate per unit shall deemed to be inclusive of taking out burnt MCB SPN/MCCB/Voltmeter/ Ampiermeter/LED lamps of any type and discription etc and refixing the same, which shall be measured and paid as supply only vide relivent items of this schedule. (i) Cleaning inside the panel and all incoming and out going including MCCB/MCB SPN thorouly with help of Vaccum Cleaner. (ii) Checking the loose connections of incoming and out going cable/wire and rectifify the same.
S&F in repair, MCCBs in existing FP/panel, connecting to bus-bar with all connecting accessories and modification in busbar (if Necessary), connection complete and testing after completion, all as specified and directed, of following capacities :-
MCCB 63 Amps,16 kA,FP, 50 Hz,Thermal magnetic release,lcs=100% lcu.
MCCB 100 Amps,16 kA,FP,50 Hz,Thermal magnetic release,lcs=100% lcu.
MCCB 160 Amps,25 kA,FP,50 Hz,Thermal magnetic release,lcs=100% lcu.
Taking out Old U/S and S&F MCB SPN, 32 Amp, 10 KA, 230 Volt.
Multi Function meters,Digital type 96x96mm, Aux Supply 230Volts AC,Type: EM6436 Conzerv(Schneider Electric).
Indicating Lamps LED type,110Volts AC Make: Teknic
M&L for perforated cable tray of GI Sheet of 150 mm x 50mm and thickness of GI sheet is not less than 1.6 mm and taking including taking out old/enserviceable
Sri Krishna Construction (BID ID -3415536)
NOEL ENGINEERS (BID ID -3403165)
Genius Construction Co. (BID ID -3410269)
M/S V N ENTERPRISES (BID ID -3415606)
Ramesh Electrical and Mechanical Works (BID ID -3406426)
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .