Loading…
Loading…
Tender Value
₹71.0 L
EMD Value
₹1.4 L
Closing Date
14 Apr 2025, 3:00 pmClosed
Electrical work in connection with upgradation / modernization of infrastructure at Sirsa Goods Shed and Raman Goods Shed over Bikaner Division and electrical work in connection with expansion of traffic facilities in RKK (Ratangarh Kanakwal) yard for smooth movement of HMEL traffic.
09-EL-BKN-E-Tender-24-25R
09-EL-BKN-E-Tender-24-25R
Open
Works - General
6 Months
Bikaner, Rajasthan
₹0
₹1.4 L
22 Mar 2025
22 Mar 2025
A-Goods Platform (Sirsa)
Supply, erection, testing & commissioning of 12.50 mtr highmast shaft totally hot dip galvanized and suitable for wind velocity as per IS 875 Part-3. The mast shaft shall be in two finished section. It shall also include accessories for 12.5 Mtrs high mast including head frame, steel wire rope 6 mm dia (7/19 construction) double arm winch, galvanized lantern carriage arrangement suitable for 1 6 luminaires systematically and its control gear boxes and lighting finial with integral power tool. The work also include design & casting of suitable foundation bolts with M-20 concrete mixture for high mast considering the safe soil bearing capacity at site as 10T per sqmm at 2 mtrs depth. The foundation should be casted with foundation bolt manufactured with special steel along with nuts, washers, anchors plates and templates are required make: Bajaj/Philips or similar. The mast shall have one longitudinal weld and single dipping (hot dip galvanized) per section (as per specification attached).
Supplying fixing and commissioning of street light fitting accessories e.g. GI pipe of bore 25mm, clamps, nuts, bolts, cable etc as per instruction of site engineer.
Supply and fixing of new head frame with aluminium pulley for high mast tower as per tender specs
Supply and fixing of new 1 HP 3 phase motor for high mast tower as per tender specs. Motor shall be of reputed make.
Supply and fixing of 6 mm Stainless Steel rope wire for high mast tower as per tender specs.
Supply and fixing of ERP PVC sheathed copper cable 5 core 2.5 sqmm for high mast as per tender specs.
Supply and fixing of new junction box on top of the high mast as per tender specs.
Supply and fixing of LED aviation light luminaires of BGAV 302 LED of Bajaj or similar comprising of aluminium housing with polycarbonate enclosure, (1 fitting per mast is necessary if no taller structures are in the vicinity). Fitting should be of reputed make and as per tech. spec.
Supply and fixing of LED 400W flood light complete with all accessories and integral electronic driver. LED luminaries to be suitable for outdoor installation on high mast and of reputed make and as per tech. spec.
Supply, fixing and commissioning of Switching Panel with electromechanical time 10 switch with two daily dial/electronic time switch & two suitably rated contactors for operating 6/12 x 150/250/400 W LED flood lamps, suitable control gear for operation of lowering and lifting mechanism of 12.5 mtr mast necessary cable etc. for commissioning of the Mast. All the accessories should be of reputed make and the switch also incorporates electronic over current trip and latch mechanism.
Supply, installing, testing and commissioning earth electrode complete in all respect with perforated GI pipe medium "B" class (Blue) confirming to IS 1239 part-I length of 4 mtr., bore 11 50mm with all accessories like nut bolt, reducer nipple, wire meshed funnel and CC finished chamber covered by CI/RCC frame etc. Digging pit and refilling it with charcoal and salt in successive layers and connection with 25x3 mm GI strip as per IS:3043 and drawing and testing of earth resistance as reqd.
Laying, connecting, testing and commissioning of 4x16 sqmm, 1.1KV grade, LT XLPE insulated PVC outer sheathed aluminum conductor armoured cable in trench/pipe/air as per spec
Laying, connecting, testing and commissioning of 4x50 sqmm, 1.1KV grade, LT XLPE insulated PVC outer sheathed aluminum conductor armoured cable in trench/pipe/air as per spec
Laying, connecting, testing and commissioning of 4x70 sqmm, 1.1KV grade, LT XLPE insulated PVC outer sheathed aluminum conductor armoured cable in trench/pipe/air as per spec
Laying, connecting, testing and commissioning of 4x120 sqmm, 1.1KV grade, LT XLPE insulated PVC outer sheathed aluminum conductor armoured cable in trench/pipe/air as per spec.
Supply of HDPE pipe conforming to IS 4984:1995, 75/80 mm dia, wall thickness minimum 3 mm, PN 6, for under the road.
Laying of HDPE pipe conforming to IS 4984:1995, 75/80 mm dia, under the road
Supply of HDPE pipe conforming to IS 4984:1995, 50 mm dia, wall thickness minimum 3 mm, PN 6, for laying under the road.
Laying of HDPE pipe conforming to IS 4984:1995, 50 mm dia, under the road
Digging and filling of trench size 0.4 x 0.8 mtr as per spec. (trench work may be on kuchha/pucca land and all type of soil as per site requirement and without protective layer of brick) Surface of trench shall be made good in all respect and satisfaction of site engineer.
Supply and fixing of junction box size 390x305x170mm comprising of SMP/FRP 21 material with rubber gasket, padlock arrangement, zinc passivated earth bolt, etc. similar to Sintex model no. GSJB 3525 or similar with 4 no. aluminium busbar cap 200 Amp., suitable for 415 volt supply requirement. The box shall be fixed robustly with clamps at pole/ wall as per requirement. Material should be of good quality & as per spec.
Providing SH rail post 1.5 / 2.5 mtrs. Long for EFT & supporting cable tray. Work includes cutting of 50 / 60 / 75 / 90 lbs capacity rails in pieces of desired length (1.5/2.5 mtrs.), digging of pit and erection of rail pole (Rails will be supplied by railway and is to be collected by contractor from concerned SSE). The rail pole shall be erected over a cement concrete bed (1:3:6) of 15 cm thickness and back filling of pit with excavated earth soil. The depth of the pit shall be 0.5 mtrs. or as directed by Site Engineer. These rail poles should be grouted properly so that cable tray / EFT box are fixed in truly vertical position.
Supply, laying and fixing of GI pipe medium "B" class (Blue) confirming to IS 1239 part-I for passing incoming and outgoing cable from ground through it size 50 mm dia. Pipe should be of reputed make and as per tech. spec.
Supply, laying and fixing of GI pipe medium "B" class (Blue) confirming to IS 1239 part-I for passing incoming and outgoing cable from ground through it size 100 mm dia. Pipe should be of reputed make and as per tech. spec.
Supply and fixing of 4 pole MCCB 63 amp. 35 kA with adjustable thermal and fix magnetic release complete with box. MCCB should be of reputed make and as per tech. spec.
Drilling of horizontal bore below Track/Road by pushing method for laying of RCC/HDPE/DWC pipe of various sizes up to 450 mm dia.
Supply & erection of 5 m high with single / double arm model no. BOP-5030 of Bajaj or similar, hot dip galvanized steel octagonal pole with galvanized base plate of 200x200x12 mm, 27 junction box with 6 Amp. MCB and stud terminals (for mounting inside the base compartment of pole), foundation bolt size 4x16mm dia. 600 mm in length including excavation and making foundation as per spec. and drawing. It shall be galvanized internally and externally by single dipping methods. The pole and foundation shall be made as per specification and drawing attached.
Supply of compact body LED street light 70/72 W complete with all accessories and integral electronic driver. LED shall be of reputed make and as per tech. spec.
Fixing of LED street light complete. (Fitting is not included in it).
Removal of existing Rail/Swage poles from station area. Rail are to be cut 0.5m below 30 the ground level & making the ground level good by suitable cement concrete and transportation of rail pole and all accessories with fitting etc. complete from site to place located at that station by concern SSE/Elect.
Removal of existing Octagonal pole. & making the ground level good by suitable cement concrete and transportation of rail/swage/octagonal pole and all accessories with fitting etc complete from the site to place located at the station by concern SSE/Elect
Fabrication, supply, fixing, testing and commissioning of OFF delay timer panel comprising of analogue multifunction timer with OFF delay/Signal OFF delay function with timing range adjustable upto 30 minutes minimum for OFF delay (L&T GIC model no. Micon 175 - 1CMDT0 or similar of reputed make), 3 Pole power contactor AC3-40A / AC1-55A, 240 VAC coil, 2 nos. LED based 32 illuminated flush type push switch with 2 NC/NO contact for ON/OFF, SP MCB 6A, 10 kA 'C' series for control wiring, four terminal connecting strip 63 A min. for incoming and outgoing and other accessories including power (min. 10 sqmm copper wire) and control (min. 1.0 sqmm copper wire) wiring. Panel should have good finishing in all respect to the satisfaction of Railway authority. Panel should be as per tech spec. and it should be got approved by competent authority prior to supply and commissioning.
B-Building & Shed Wiring (Sirsa)
Supply, installation, testing & commissioning of concealed / surface modular wiring of Light/Fan/Exhaust/Call bell points in PVC rigid conduit pipe size 25mm dia medium class minimum 1 thickness approx 1.6mm to 1.8mm of ISI mark with 1.5 sq mm multistrand PVC insulated copper conductor cable confirming to IS:694-1990 or latest with one holder / ceiling rose on junction box with round plate and modular switch with 2.5sq mm PVC insulated copper wire green coloured for earthing along with connection etc.
Supply of material & fixing of flush metal box of 2 module with connection used for concealed modular flush metal box wiring.
Supply of material & fixing of plate inner & outer 2 module used for concealed modular wiring.
Supply of material & fixing of flush metal box of 4 module with connection used for concealed modular flush metal box wiring.
Supply of material & fixing of plate inner & outer 4 module used for concealed modular wiring.
Supply of material & fixing of flush metal box of 6 module with connection used for concealed modular flush metal box wiring.
Supply of material & fixing of plate inner & outer 6 module used for concealed modular wiring.
Supply of material & fixing of flush metal box of 8 module with connection used for concealed modular flush metal box wiring.
Supply of material & fixing of plate inner & outer 8 module used for concealed modular wiring.
Supply of material & fixing of flush metal box of 12 module with connection used for concealed modular flush metal box wiring.
Supply of material & fixing of plate inner & outer 12 module used for concealed modular wiring.
Supply of material and fixing of 6/16 Amp 6-pin combined shuttered socket (2- module) used for concealed modular wiring.
Supply of material and fixing of 6 Amp 3/5 pin socket (2-module) used for concealed modular wiring.
Supply and fixing of blank plates (1-module) used for concealed modular wiring.
Supply of material and fixing of 6/16 Amp 6-pin combined shuttered socket (2- module) used for concealed modular wiring.
Supply of material and fixing of S.P. switch 16 Amp one way (1-module) used for concealed modular wiring.
Supply and fixing of MS board manufactured by 1.6mm MS sheet duly finished with two coats of red oxide, earth terminal, 3mm sunmica sheet, zinc plated/ brass screw, cup washer etc in recessed, as reqd. 100x100x50mm
Supply and fixing of modular ceiling rose. Ceiling rose should be of reputed make and as per tech. spec.
Supplying and drawing 2.5 sq. mm PVC insulated multistrand copper conductor cable 19 as submain and 1.5 sq. mm PVC insulated multistrand earth copper cable voltage grade 1.1 kV as earthing wire conforming to IS: 694-1990 in existing conduit/casing caping. Wire should be of reputed make and as per tech. spec.
Supplying and drawing 6.0 sq. mm PVC insulated multistrand copper conductor cable 20 as submain and 1.5 sq. mm PVC insulated multistrand earth copper cable voltage grade 1.1 kV as earthing wire conforming to IS: 694-1990 in existing conduit/casing caping. Wire should be of reputed make and as per tech. spec.
Supplying and drawing 4.0 sq. mm PVC insulated multistrand copper conductor cable 21 as submain and 1.5 sq. mm PVC insulated multistrand earth copper cable voltage grade 1.1 kV as earthing wire conforming to IS: 694-1990 in existing conduit/casing caping. Wire should be of reputed make and as per tech. spec.
Supply and fixing of PVC conduit/casing caping (as per instruction of site supervisor) and its accessories, size 25 mm, thickness 1.6 mm As per IS 9537
Supply & fixing of Galvanized Perforated Cable Tray sized 1.2mm thick, 50mm width, side wall 50mm covered Electrical Ventilated Channel Type Cable Trunking Tray as per site requirement.
Supply and fixing of PVC Trunking size 35x30mm and heavy thick, compounded high 24 impact rigid polyvinyl chloride, non-flammable confirming to UL 94 V0 standards, warp-proof and non- brittle, high dielectric strength and withstands temperature up to 60C. These should not be peel, chip or crack and resists oil, salt solution and fungus as per spec.
Making and filling of chase for 25 mm dia PVC/MS conduit. Surface of chase shall be made good in all respect and satisfaction of engineer incharge.
Fixing of LED lubelight four feet complete with accessories.
Supply & installation of Recess / ceiling mounted 36W (2feet X 2feet) LED Luminaire 27 having system wattage of 36W and system lumen efficacy of 100 Lumens/watt, complete with Electronic driver, operating voltage range 140 to 270 volt. Frame around the light shall be provided by firm if light is mounted on ceiling for aesthetic looks as per site requirement.
Supply of ISI marked 5 Star BLDC ceiling Fan 1200 mm sweep, Rated voltage 140-285 Volt, Power consumption 25W to 35W as per spec.
Supply of material and fixing of modular fan regulator 5-step (2- module) suitable for BLDC fan, used for concealed modular wiring.
Fixing and commissioning of ceiling fan with nut, bolt, rod, etc. ensuring all safety aspects. Contractor is responsible for falling of fan within a period of 12 month.
Supply and installation of PVC Electric Ceiling Fan Box Optimum Quality to be used in Fan installation as per site requirement.
Supply, fixing, testing and commissioning of single phase, 230 volt 50 Hz operating ventilation fan of 300 mm. sweep with louver shutters. Fan should be of reputed make and as per tech. spec.
Supply, fixing, testing and commissioning of single phase, 230 volt 50 Hz wall mounting/bracket fan of sweep 400 mm. Fan should be of reputed make and as per tech. spec.
Supply of unit maintenance free earth material as per RDSO Specification No. RDSO/PE/SPEC/PS/0/0109 (REV.0) 2008 or Latest
Installation of unit maintenance free earth as per RDSO Specification No. RDSO/PE/SPEC/PS/0/0109 (REV.0) 2008 or Latest
Supply and fixing of Double Door MCB TPN DB SP (8+12 module), neutral and earth 36 link, 4 way with one no four pole MCB 63 amp, one no Four Pole RCCB 63 amp 30 mA and twelve no SP MCB 32/25/16/10/6 amp. 'C' series. Breaking capacity not less than 10 kA. MCB, RCCB and DB should be as per tech spec. and of same make.
Supply and fixing of single phase Double Door MCB DB SP (4+2) way, with DP MCB 40 amp 'C' series one number & SP MCB 32/25 amp. 'C' series four number. Breaking capacity not less than 10 kA. MCB and DB should be as per tech spec. and of same make.
Supply, fixing, testing and commissioning of RCBO 63A, 4 pole, 8 module, 30mA with Earth leakage, overload and short circuit protection as per spec
Supply and fixing of Potable water purification system with inbuilt water cooler. UV Hot, Cold & Ambient UV Water Purifier as per the specifications.
Supply, fixing, testing and commissioning of RCBO 25A, double pole, four module, 30mA with Earth leakage, overload and short circuit protection as per spec
Supply and fixing of 4 module metal enclosure for fixing of RCBO as per IEC 61439-3, Suitable for flush mounting and surface mounting with door for IP 54, similar to Legrand model no. 5077 91/93 of reputed make
Transportation, installation, testing and commissioning of water cooler including with water connection angle valve as per site requirement over BKN division
Supply, fabrication and fixing of MS cage made of suitable size MS angle and MS jali 43 1"X1" to provide protection of electrical equipment with two nos of key locks & 2 nos hinges including one coat of red oxide and two coats of enamel paint along with fixing arrangement on existing wall / rail / pipe / foundation by nutbolt / clamp / washer etc. as per site requirement
Provision of suitable foundation with concrete and cement (size 1Mtr x 1Mtr) for water cooler as per instructions of site supervisor and site requirement.
Supply, fixing, testing & commissioning of UPS cum invertor 900VA 24 months 45 warranty with single tubular battery 12 volt 150AH, 36 months warranty, single phase input, single phase output with indication panel, alarm complete with rack & stand as per requirement. Make of battery & invertor / UPS - Exide, Sukam, Luminous, Microtek or similar reputed make.
Fixing and commissioning of split AC 1.5 ton with all accessories and proper MS stand as per site requirement.
Supply and fixing of MCB DP 32 amp with box. Breaking capacity not less than 10 KA.
Supply and fixing of copper tube 3/8" or 1/2" with insulating material as per site requirement.
Supply and fixing of copper tube 1/4" with insulating material as per site requirement.
Supply and fixing of CPVC Pipe SDR 11 Class 1 3/4" Inch size with all accessories required for AC water drainage.
C-Goods Platform (Raman)
Supply, erection, testing & commissioning of 12.50 mtr highmast shaft totally hot dip galvanized and suitable for wind velocity as per IS 875 Part-3. The mast shaft shall be in two finished section. It shall also include accessories for 12.5 Mtrs high mast including head frame, steel wire rope 6 mm dia (7/19 construction) double arm winch, galvanized lantern carriage arrangement suitable for 1 6 luminaires systematically and its control gear boxes and lighting finial with integral power tool. The work also include design & casting of suitable foundation bolts with M-20 concrete mixture for high mast considering the safe soil bearing capacity at site as 10T per sqmm at 2 mtrs depth. The foundation should be casted with foundation bolt manufactured with special steel along with nuts, washers, anchors plates and templates are required make: Bajaj/Philips or similar. The mast shall have one longitudinal weld and single dipping (hot dip galvanized) per section (as per specification attached).
Dismantling of 11 mtr. / 12.5 mtr. high mast with the help of suitable equipments. The dismantled high mast to be shifted to desired location as per instructions of site supervisor. It includes cost of hiring of machinery / vehicle required for shifting.
Supply of set of 06 nos. foundation bolts for 12.5 Mtr. High Mast. The diameter of each bolt not less than 27 mm and length 750 mm shall be manufactured from special steel with exposed portion hot dip galvanized and with galvanized washers and nuts complete with anchor plate of suitable size and template.
Design and casting of open raft shallow footing foundation suitably designed for the reaction arising out of the dynamic loading of the 12.5 mtr. high-mast, with M-20 concrete mixture, 4 considering the safe soil bearing capacity at site as 10 T/sqmtr., at 2 mtrs. depth. Muffing around high mast tower is to be made for safety from vehicles. Size of muffing 1 m radius 0.3 m height GI pipe 6/8 no 0.6 m long 50 mm dia with suitable chain to cover corner of muffing. Mechanical vibrator is to be used for setting of cement concrete for foundation.
Erection and commissioning of the 12.5 mtr. high mast tower along with accessories with the help of suitable equipments at desired location. It includes cost of equipments / machinery required for erection of high mast.
Supply and fixing of LED aviation light luminaires of aluminium housing with polycarbonate enclosure, (1 fitting per mast is necessary if no taller structures are in the vicinity). Fitting should be of reputed make and as per tech spec.
Fixing & commissioning of 240W / 250W outdoor type LED flood lights on high mast towers.
Supply, fixing and commissioning or replacement of Switching Panel with 8 electromechanical timer switch with two daily dial & two suitably rated contactors for operating 6/12X250 W LED flood lights, suitable control gear for operation of lowering and lifting mechanism of 12.5 mtr mast necessary cable etc. for commissioning of the Mast as per detailed specification. All the accessories should be of reputed make and as per technical specification.
Supply, installing, testing and commissioning earth electrode complete in all respect 9 with perforated GI pipe medium "B" class (Blue) confirming to IS 1239 part-I length of 4 mtr., bore 50mm with all accessories like nut bolt, reducer nipple, wire meshed funnel and CC finished chamber covered by CI/RCC frame etc. Digging pit and refilling it with charcoal and salt in successive layers and connection with Strip and as per IS:3043 and drawing and testing of earth resistance as reqd.
Laying, connecting, testing and commissioning of 4X16sqmm, 1.1KV grade, LT XLPE/PVC insulated PVC outer sheathed aluminium conductor armoured cable in trench/pipe as per spec.
Laying, connecting, testing and commissioning of 4X50sqmm, 1.1KV grade, LT XLPE/PVC insulated PVC outer sheathed aluminium conductor armoured cable in trench/pipe as per spec.
Laying, connecting, testing and commissioning of 4X70sqmm, 1.1KV grade, LT XLPE/PVC insulated PVC outer sheathed aluminium conductor armoured cable in trench/pipe as per spec.
Digging and filling of trench size 0.4 X 0.8 mtr as per spec. (trench work may be on kuchha/pucca land and all type of soil as per site requirement and without protective layer of brick). Surface of trench shall be made good in all respect and satisfaction of site engineer.
Supply of HDPE pipe 50mm dia, wall thickness minimum 3mm, PN-6, conforming to IS 4984: 2016.
Laying of HDPE pipe, 50 mm dia, wall thickness minimum 3mm, conforming to IS 4984: 2016. The work involves laying of HDPE pipe under road/track.
Supply and fixing of junction box size 390x305x170mm comprising of SMP/FRP 16 material with rubber gasket, padlock arrangement, zinc passivated earth bolt, etc. similar to Sintex model no. GSJB 3525 or similar with 4 no. aluminium busbar cap 200 Amp., suitable for 415 volt supply requirement. The box shall be fixed robustly with clamps at pole / wall as per requirement. All the material should be of good quality and as per tech. spec.
Providing SH rail post 1.5 / 2.5 mtrs. Long for EFT & supporting cable tray. Work includes cutting of 50 / 60 / 75 / 90 lbs capacity rails in pieces of desired length (1.5/2.5 mtrs.), 17 digging of pit and erection of rail pole (Rails will be supplied by railway and is to be collected from concerned SSE and transported by contractor). The rail pole shall be erected over a cement concrete bed (1:3:6) of 15 cm thickness and back filling of pit with excavated earth soil. The depth of the pit shall be 0.5 mtrs. or as directed by Site Engineer. These rail poles should be grouted properly in vertical position.
Supply, laying and fixing of GI pipe medium "B" class (Blue) confirming to IS 1239 part-I for passing incoming and outgoing cable from ground through it size 38 mm dia. Pipe should be of reputed make and as per tech. spec.
Supply of HDPE pipe, 160 mm dia, PN-6, conforming to IS 4984: 2016 as per site requirement.
Supply, laying and fixing of GI pipe medium "B" class (Blue) confirming to IS 1239 part-I for passing incoming and outgoing cable from ground through it size 100 mm dia. Pipe should be of reputed make and as per tech. spec.
Supply and fixing of 4 pole MCCB 63Amp 35kA with adjustable thermal and fix magnetic release complete with box. MCCB should be of reputed make and as per tech spec.
Laying of Spun/MS/GI/DWC/HDPE pipe 100mm to 200 mm by drilling of Horizontal bore by machine in Railway yard/below track/Road.
Supply & erection of 5 m high with double arm model no. BOP-5030 of Bajaj or similar, pole shaft material S355J0 or equivalent as per IS, hot dip galvanized steel octagonal pole with 23 galvanized base plate of 200x200x12 mm, junction box with 6 Amp. MCB and stud terminals (for mounting inside the base compartment of pole), foundation bolt size 4x16mm dia. 600 mm in length including excavation and making foundation as per spec. and drawing. It shall be galvanized internally and externally by single dipping method. The pole and foundation shall be made as per specification and drawing attached.
Fixing of LED street light / LED high bay light complete with accessories as per requirement. (Fitting is not included in it).
Supplying and drawing 2.5 sq. mm PVC insulated multistrand copper conductor cable 25 as submain and 1.5 sq. mm PVC insulated multistrand earth copper cable voltage grade 1.1 kV as earthing wire conforming to IS: 694-1990 in existing conduit/casing caping. Wire should be of reputed make and as per tech. spec.
D-Building & Shed Wiring (Raman)
Supply and fixing of Ceiling rose complete. Ceiling rose should be of reputed make and as per tech. spec.
Supply and fixing of PVC conduit / casing caping (as per instructions of site supervisor) and its accessories, size 25 mm, thickness 1.6 mm as per IS 9537.
Supply and fixing of Rigid PVC conduit size 25 mm, Heavy mechanical stress (HMS) type including all fixing accessories, as per IS: 9537
Making and filling of chase for 25 mm dia PVC/MS conduit. Surface of chase shall be made good in all respect and satisfaction of engineer incharge.
Supplying and drawing 6.0 sq. mm PVC insulated multistrand copper conductor cable 8 as submain and 1.5 sq. mm PVC insulated multistrand earth copper cable voltage grade 1.1 kV as earthing wire conforming to IS: 694-1990 in existing conduit/casing capping. Wire should be of reputed make and as per tech. spec.
Supplying and drawing 4.0 sq. mm PVC insulated multistrand copper conductor cable 9 as submain and 1.5 sq. mm PVC insulated multistrand earth copper cable voltage grade 1.1 kV as earthing wire conforming to IS: 694-1990 in existing conduit/casing capping. Wire should be of reputed make and as per tech. spec.
Supplying and drawing 2.5 sq. mm PVC insulated multistrand copper conductor cable 10 as submain and 1.5 sq. mm PVC insulated multistrand earth copper cable voltage grade 1.1 kV as earthing wire conforming to IS: 694-1990 in existing conduit/casing caping. Wire should be of reputed make and as per tech. spec.
Fixing of LED four feet fitting complete with tube. (Fitting will be supplied by Railway).
Supply and fixing of flush mounted electronic step fan regulator, socket size (suitable for BLDC fan).
Fixing and commissioning of ceiling fan with nut, bolt, rod and other accessories ensuring all safety aspects. Contractor is responsible for falling of fan within a period of 12 month.
Supply, installing, testing and commissioning earth electrode complete in all respect with perforated GI pipe medium "B" class (Blue) confirming to IS 1239 part-I length of 4 mtr., bore 14 50mm with all accessories like nut bolt, reducer nipple, wire meshed funnel and CC finished chamber covered by CI/RCC frame etc. Digging pit and refilling it with charcoal and salt in successive layers and connection with 25x3 mm GI strip and as per IS:3043 and drawing and testing of earth resistance as reqd.
Supplying fixing and commissioning of street light fitting accessories e.g. GI pipe of bore 25mm, clamps, nuts, bolts, cable etc as per instruction of site engineer
Supply and fixing of MCB DP 32 amp with box. Breaking capacity not less than 10 KA.
Supply and fixing of Double Door MCB DB SP 12 way (10+2 module), neutral and 17 earth link, with one no. DP MCB 40 amp, one no. DP RCCB 40 amp 30 mA and eight no. SP MCB 32/25/16/10/6 amp. 'C' series. Breaking capacity not less than 10 kA. MCB, RCCB and DB should be as per tech spec. and of same make.
Supply and fixing of DD DB (4+2) way 1 no. DP MCB 40A "C" series, 4 nos. SP MCB 25/32A "C" series. Box and MCB to be of same make. Breaking capacity not less than 10kA.
Supply, fixing, testing and commissioning of RCBO 25A, double pole, four module, 30mA with Earth leakage, overload and short circuit protection as per spec
Supply and fixing of 4 module metal enclosure for fixing of RCBO, Suitable for flush mounting and surface mounting with door for IP-54, Enclosure & RCBO shall be of reputed and similar make.
E-Ratangarh Kanakwal Yard
Installation and commissioning of 1.5 Ton split AC with all accessories as per the site requirement and site engineer instructions (AC will be supplied by the Railways).
Dismantling of 1.5 / 2 Ton AC complete with all accessories as per the site requirement and site engineer instructions.
Supply, fixing, testing and commissioning of microprocessor based energy efficient sequence AC controller for controlling simultaneous running 04 Nos. / 03 Nos. / 02 Nos. ACs, which works on 230 volt, 50 Hz AC supply
Supply and fixing of MCB DP 32 amp with box. Breaking capacity not less than 10 KA.
Supply and fixing of copper tube 3/8" or 1/2" with insulating material as per site requirement.
Supply and fixing of copper tube 1/4" with insulating material as per site requirement.
Supply and fixing of MS board manufactured by 1.6mm MS sheet duly finished with two coats of red oxide , earth terminal, 3mm sunmica sheet, zinc plated/ brass screw, cup washer etc. in recessed, as reqd.
Supply and fixing of PVC conduit / casing caping (as per instructions of site supervisor) and its accessories, size 25 mm, thickness 1.6 mm as per IS 9537.
Making and filling of chase for 25 mm dia PVC/MS conduit. Surface of chase shall be made good in all respect and satisfaction of engineer incharge.
Supplying and drawing 2.5 sq. mm PVC insulated multistrand copper conductor cable 13 as submain and 1.5 sq. mm PVC insulated multistrand earth copper cable voltage grade 1.1 kV as earthing wire conforming to IS: 694-1990 in existing conduit/casing caping. Wire should be of reputed make and as per tech. spec.
Supplying and drawing 4.0 sq. mm PVC insulated multistrand copper conductor cable 14 as submain and 1.5 sq. mm PVC insulated multistrand earth copper cable voltage grade 1.1 kV as earthing wire conforming to IS: 694-1990 in existing conduit/casing capping. Wire should be of reputed make and as per tech. spec.
Supplying and drawing 6.0 sq. mm PVC insulated multistrand copper conductor cable 15 as submain and 1.5 sq. mm PVC insulated multistrand earth copper cable voltage grade 1.1 kV as earthing wire conforming to IS: 694-1990 in existing conduit/casing capping. Wire should be of reputed make and as per tech. spec.
Fixing of LED four feet fitting complete with tube. (Fitting will be supplied by Railway).
Supplying fixing and commissioning of street light fitting accessories e.g. GI pipe of bore 25mm, clamps, nuts, bolts, cable etc as per instruction of site engineer
Fixing of LED street light complete with accessories as per requirement. (Fitting is not included in it).
Supply and fixing of flush mounted electronic step fan regulator, socket size (suitable for BLDC fan).
Fixing and commissioning of ceiling fan with nut, bolt, rod and other accessories ensuring all safety aspects. Contractor is responsible for falling of fan within a period of 12 month.
Supply and fixing of Ceiling rose complete. Ceiling rose should be of reputed make and as per tech. spec.
Supply and installation of PVC Electric Ceiling Fan Box Optimum Quality to be used in Fan installation as per site requirement.
Supply, installing, testing and commissioning earth electrode complete in all respect with perforated GI pipe medium "B" class (Blue) confirming to IS 1239 part-I length of 4 mtr., bore 23 50mm with all accessories like nut bolt, reducer nipple, wire meshed funnel and CC finished chamber covered by CI/RCC frame etc. Digging pit and refilling it with charcoal and salt in successive layers and connection with 25x3 mm GI strip as per IS:3043 and drawing and testing of earth resistance as reqd.
Supply, laying and fixing of GI pipe medium "B" class (Blue) confirming to IS 1239 part-I for passing incoming and outgoing cable from ground through it size 50 mm dia. Pipe should be of reputed make and as per tech. spec.
Supply and fixing of Double Door MCB TPN DB SP (8+12 module), neutral and earth 25 link, 4 way with one no four pole MCB 63 amp, one no Four Pole RCCB 63 amp 30 mA and twelve no SP MCB 32/25/16/10/6 amp. 'C' series. Breaking capacity not less than 10 kA. MCB, RCCB and DB should be as per tech spec. and of same make.
Laying, connecting, testing and commissioning of 4x120 sqmm, 1.1KV grade, LT XLPE insulated PVC outer sheathed aluminum conductor armoured cable in trench/pipe/air as per spec.
Laying, connecting, testing and commissioning of 4x50 sqmm, 1.1KV grade, LT XLPE insulated PVC outer sheathed aluminum conductor armoured cable in trench/pipe/air as per spec
Supply of HDPE pipe conforming to IS 4984:1995, 75/80 mm dia, wall thickness minimum 3 mm, PN 6, for under the road.
Laying of HDPE pipe conforming to IS 4984:1995, 75/80 mm dia, under the road
Supply of HDPE pipe conforming to IS 4984:1995, 50 mm dia, wall thickness minimum 3 mm, PN 6, for laying under the road.
Laying of HDPE pipe conforming to IS 4984:1995, 50 mm dia, under the road
Digging and filling of trench size 0.4 x 0.8 mtr as per spec. (trench work may be on kuchha/pucca land and all type of soil as per site requirement and without protective layer of brick) Surface of trench shall be made good in all respect and satisfaction of site engineer.
Supply and fixing of junction box size 390x305x170mm comprising of SMP/FRP 33 material with rubber gasket, padlock arrangement, zinc passivated earth bolt, etc. similar to Sintex model no. GSJB 3525 or similar with 4 no. aluminium busbar cap 200 Amp., suitable for 415 volt supply requirement. The box shall be fixed robustly with clamps at pole / wall as per requirement. Material should be of good quality & as per spec.
Dismantling of 20 mtr. / 30 mtr. high mast with the help of suitable equipments. The dismantled high mast to be shifted to desired location as per instructions of site supervisor. It includes cost of hiring of machinery / vehicle required for shifting.
Design and casting of open raft shallow footing foundation suitably designed for the reaction arising out of the dynamic loading of the 20 / 30 mtr. high-mast, with M-20 concrete mixture, 35 considering the safe soil bearing capacity at site as 10 T/sqmtr., at 2 mtrs. depth. Muffing around high mast tower is to be made for safety from vehicles. Size of muffing 1 m radius 0.3 m height GI pipe 6/8 no 0.6 m long 50 mm dia with suitable chain to cover corner of muffing. Mechanical vibrator is to be used for setting of cement concrete for foundation.
Supply of set of foundation bolts for 20 /30 Mtr. High Mast. The size of foundation 36 bolts shall be suitable for existing high mast towers at site. It shall be manufactured from special steel with exposed portion hot dip galvanized and with galvanized washers and nuts complete with anchor plate of suitable size and template.
Erection and commissioning of the 20 / 30 mtr. high mast tower along with accessories with the help of suitable equipments at desired location. It includes cost of equipments / machinery required for erection of high mast.
Supply, erection, testing & commissioning of 30 meters highmast shaft totally hot dip galvanized and suitable for wind velocity as per IS 875 Part-3. The mast shaft shall be in three finished section. It shall also include 12 nos. 350W LED flood lights and accessories for 30 Mtrs high mast including head frame, steel wire rope, double arm winch, galvanized lantern carriage 38 arrangement suitable for 12 luminaires systematically and its control gear boxes and lighting finial with integral power tool. The work also include design & casting of suitable foundation bolts with M- 20 concrete mixture for high mast considering the safe soil bearing capacity at site. The foundation should be casted with foundation bolt manufactured with special steel along with nuts, washers, anchors plates and templates are required. Make: Bajaj/Philips/Crompton or similar. (as per specification attached).
Supply and fixing of LED aviation light luminaires of BGAV 302 LED of Bajaj or similar comprising of aluminium housing with polycarbonate enclosure, (1 fitting per mast is necessary if no taller structures are in the vicinity). Fitting should be of reputed make and as per tech. spec.
Supply, fixing and commissioning of Switching Panel with electromechanical time 40 switch with two daily dial/electronic time switch & two suitably rated contactors for operating 6/12 x 150/250/400 W LED flood lamps, suitable control gear for operation of lowering and lifting mechanism of 20/30 mtr mast necessary cable etc. for commissioning of the Mast. All the accessories should be of reputed make and the switch also incorporates electronic over current trip and latch mechanism.
Providing SH rail post 1.5 / 2.5 mtrs. Long for EFT & supporting cable tray. Work includes cutting of 50 / 60 / 75 / 90 lbs capacity rails in pieces of desired length (1.5/2.5 mtrs.), 41 digging of pit and erection of rail pole (Rails will be supplied by railway and is to be collected by contractor from concerned SSE). The rail pole shall be erected over a cement concrete bed (1:3:6) of 15 cm thickness and back filling of pit with excavated earth soil. The depth of the pit shall be 0.5 mtrs. or as directed by Site Engineer. These rail poles should be grouted properly so that cable tray / EFT box are fixed in truly vertical position.
Drilling of horizontal bore below Track/Road by pushing method for laying of RCC/HDPE/DWC pipe of various sizes up to 450 mm dia.
Supply, fixing, testing and commissioning of fabricated feeder pillar distribution box made from MS sheet 1.6mm thick size 600X300X600mm with suitable MS stand, copper bus bar of 200A capacity and 2X63A MCB 4 pole as per spec
Item Breakup - D-Building & Shed Wiring (Raman)
Long point Total 35760.00 Item- 2 Supply and fixing of socket as per specification. S No. Item Description of Item Unit Qty Rate Amount No
5/6 amp. 3/5 pin with switch on existing MS board. BIKANER DIVISION-ELECTRICAL/NORTH WESTERN RLY
15/16 amp. 6 pin with switch on existing MS board. Total 3060.00 Supply and fixing of MS board manufactured by 1.6mm MS sheet duly finished with two coats of red Item- 3 oxide, earth terminal, 3mm sunmica sheet, zinc plated/ brass screw, cup washer etc. in recessed, as reqd. S No. Item Description of Item Unit Qty Rate Amount No
Item Breakup - E-Ratangarh Kanakwal Yard
Long Point Total 26370.00 Item- 9 Supply and fixing of socket as per specification. S No. Item Description of Item Unit Qty Rate Amount No
5/6 amp. 3/5 pin with switch on existing MS board.
15/16 amp. 6 pin with switch on existing MS board. Total 4635.00 Supply and fixing of MS board manufactured by 1.6mm MS sheet duly finished with two coats of red Item- 10 oxide , earth terminal, 3mm sunmica sheet, zinc plated/ brass screw, cup washer etc. in recessed, as reqd. S No. Item Description of Item Unit Qty Rate Amount No
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .