Loading…
Loading…
Tender Value
₹3.0 Cr
EMD Value
₹6.1 L
Closing Date
27 Apr 2026, 3:00 pmClosed
No
No
Single Packet System
Normal Tender
No
Not Applicable
Lowest to Highest
60 days
Expenditure
Capital (Works)
Above/Below/Par
SIG WORKS
14 conditions · 3 needing a document upload
The tenderer must have minimum average annual contractual turnover of V/N or V whichever is less, where: V= Advertised value of the tender in crores of Rupees N=Number of years prescribed for completion of work for which bids have been invited. The average annual contractual turnover shall be calculated as an average of 'total contractual payments" in the previous three financial years, as per the audited balance sheet. However, in case balance sheet of the previous year is yet to be prepared/audited, the audited balance sheet of the fourth previous year shall be considered for calculating average annual contractual turnover. The tenderers shall submit requisite information as per Annexure VIB, along with copies of Audited Balance Sheets duly certified by the Chartered Accountant/ Certificate from Chartered Accountant duly supported by Audited Balance Sheet As per Clause No. 10.2 of Tender Form (second Sheet) of Annex. I of Part-I of GCC 2022,with up to date correction slip.
The tenderer must have successfully completed or substantially completed any of the following categories of work(s) during last 07 (seven) years, ending last day of month previous to the one in which tender is invited: (i) Three similar works each costing not less than the amount equal to 30% of advertised value of the tender, or (ii) Two similar works each costing not less than the amount equal to 40% of the advertised value of the tender, or (iii) One similar work each costing not less than the amount equal to 60% of the advertised value of the tender Work experience certificate from private individual shall not be considered. However, in addition to work experience certificates issued by any Govt. Organisation, work experience certificate issued by Public listed company having average annual turnover of Rs 500 crore and above in last 3 financial years excluding the current financial year, listed on National Stock Exchange or Bombay Stock Exchange,incorporated/registered at least 5 years prior to the date of closing of tender,shall also be considered provided the work experience certificate has been issued by a person authorized by the Public listed company to issue such certificates. In case tenderer submits work experience certificate issued by public listed company, the tenderer shall also submit along with work experience certificate, the relevant copy of work order,bill of quantities, bill wise details of payment received duly certified by Chartered Accountant, TDS certificates for all payments received and copy of final/last bill paid by company in support of above work experience certificate. As per Clause No. 10.1 of Tender Form second Sheet of Annex. I of Part-I of GCC 2022, with up-to-date correction slip.
Definition of similar work: "Any Signalling Work"
62 conditions · 5 needing a document upload
Please enter the percentage of local content in the material being offered. Please enter 0 for fully imported items, and 100 for fully indigenous items. The definition and calculation of local content shall be in accordance with the Make in India policy as incorporated in the tender conditions.
Tenderer should note that tender will be dealt as per GCC 2022 and latest amendments to it.
Rates in the schedule items of work are inclusive of all taxes as per clause 37 of GCC-2022
Wherever there is any ambiguity in SOR Item Description, that particular item description in latest RDSO Specification to be considered as FINAL.
Telecom Circular No. 09/2023 (copy attached) shall be religiously followed for undertaking digging work in the vicinity of Signalling, Electrical and Telecommunication Cables. Zonal Railways issued local instructions/JPO for protection of cables while undertaking works in the vicinity of Railway Tracks in line with Telecom Circular 09/2023.
S&T works for Replacement of 2004 version IPS at various station/LC gates over JP division.
SNT-JP-02-2026-27
SNT-JP-02-2026-27
Open
Works - General
12 Months
Jaipur, Rajasthan
₹0
₹6.1 L
27 Apr 2026
2 Apr 2026
13 Apr 2026
59 items across 2 schedules
| # | Description | Unit | Qty | Rate | Amount |
|---|---|---|---|---|---|
| — | — | — | 2,62,12,788.16 | ||
| — | 14.00 | — | — | ||
| Installation, Wiring and testing of Integrated Power Supply System. This includes power distribution connection to bus bars and relay racks in the room with contractor's own wiring materials and fabrication and fixing of AC/DC power distribution board made on 10mm thick Phenolic hylam sheets or any standard make with connections suitable for 32 A. Wiring to be done considering site requirement, depending upon the load with suitable wires, lugs & glands as per instructions of Engineer-in-charge. The work includes installation of Thermo flasher relay, ELD's, fixing & wiring of change over switch (program switch) for selection of DG set supply (DG1 & DG2) and wiring of change over switch (program switch) for selection of mains or DG supply. This item also includes supply & fixing of ladder along the wall for carrying power supply wires/cables from IPS room to Relay room/power room etc. Any masonry work required will be carried out by contactors own material. It includes transportation of IPS from consignee depot to work site/station/ LC gate. Inspection: Consignee Inspection Charges: None Payment Terms: 100% after execution For Station | — | — | — | 17,43,027.02 | |
| — | 8.00 | — | — | ||
| Installation, Wiring and testing of Integrated Power Supply System. This includes power distribution connection to bus bars and relay racks in the room with contractor's own wiring materials and fabrication and fixing of AC/DC power distribution board made on 10mm thick Phenolic hylam sheets or any standard make with connections suitable for 32 A. Wiring to be done considering site requirement, depending upon the load with suitable wires, lugs & glands as per instructions of Engineer-in-charge. The work includes installation of Thermo flasher relay, ELD's, fixing & wiring of change over switch (program switch) for selection of DG set supply (DG1 & DG2) and wiring of change over switch (program switch) for selection of mains or DG supply. This item also includes supply & fixing of ladder along the wall for carrying power supply wires/cables from IPS room to Relay room/power room etc. Any masonry work required will be carried out by contactors own material. It includes transportation of IPS from consignee depot to work site/station/ LC gate. Inspection: Consignee Inspection Charges: None Payment Terms: 100% after execution For LC gate/IBS/ ALH Hut/ Portacabin | — | — | — | 3,52,309.6 | |
| — | 1.00 | — | — | ||
| Supply of 4 stroke petrol driven, Kerosene operated portable Generator set self-start, 2KVA capacity, and Petrol start kerosene run (Birla Yamaha /Honda). Original Manufacture Certificate to be Submitted. Note: - Contractor takes approval for Make/ Model No. from Engineer In-Charge before supply. Inspection: Consignee Inspection Charges: None Payment Terms: 100% after Supply. | — | — | — | 61,465.44 | |
| — | 200.00 | — | — | ||
| Supply of Class C, Type 2 Protection for 24-60V AC/DC supply as per clause No.3.11.2 of Specification No. RDSO/SPN/165/2023 Ver 4.0 or latest. The Class C shall be with pluggable type, with indication and potential free contact. The supplier should submit OEM certificate, KEMA, UL Certificate with the material, for connection between L1-L2, L1-E & L2-E. Inspection: Consignee Inspection Charges: None. Payment Terms: 100% after supply. | — | — | — | 1,78,600 | |
| — | 20.00 | — | — | ||
| Supply of Self-Regulating Type Battery Charger,230V AC/24V DC,50 Amps as per RDSO Specn.No.IRS:S-86/2000 (Amnd.4) or latest. Inspection: RDSO Inspection Charges: Borne by Railways Payment Terms: 100% on Supply | — | — | — | 22,50,541.4 | |
| — | 10.00 | — | — | ||
| Supply of Self-Regulating Type Battery Charger,230V AC/110V DC, 50 Amps as per RDSO Specn.No.IRS:S-86/2000 (Amnd.4) or latest. Inspection: RDSO Inspection Charges: Borne by Railways Payment Terms: 100% on Supply | — | — | — | 14,72,437.6 | |
| — | 10.00 | — | — | ||
| Supply of Self-Regulating Type Battery Charger,230V AC/110V DC, 60-100 Amps as per RDSO Specn.No.IRS:S-86/2000 (Amnd.4) or latest. Inspection: RDSO Inspection Charges: Borne by Railways Payment Terms: 100% on Supply | — | — | — | 19,18,480.3 | |
| — | 360.00 | — | — | ||
| Supply of uncharged Low Maintenance Lead Acid (LMLA) secondary cell, shelf mounting type conforming to RDSO Specn.No.IRS:S-88/2004 or latest with inter cell connectors, nuts and bolts etc. Inspection: RDSO Inspection Charges: Borne by Railways Payment Terms: 100% after Supply. 2V, 300AH | — | — | — | 30,58,624.8 | |
| — | 300.00 | — | — | ||
| Supply of uncharged Low Maintenance Lead Acid (LMLA) secondary cell, shelf mounting type conforming to RDSO Specn.No.IRS:S-88/2004 or latest with inter cell connectors, nuts and bolts etc. Inspection: RDSO Inspection Charges: Borne by Railways Payment Terms: 100% after Supply. 2V, 500AH | — | — | — | 40,62,426 | |
| — | 660.00 | — | — | ||
| Charging of Lead Acid Batteries with contractors own battery grade sulphuric acid and distilled water with minimum two charge - discharge cycles, installation of charged batteries in groups & their connection & wiring. The work shall be done as per extant practice of N.W.Rly & instruction of Engineer-in-charge. Detailed measurements of initial charging shall be recorded jointly by contractor & Rly's site-in-charge. Inspection: Consignee Inspection Charges: None Payment Terms: 100% after Execution. 2V, 300AH/ 500AH | — | — | — | 7,83,769.8 | |
| — | 20.00 | — | — | ||
| Supply of Steel Plain Almirah with 4 adjustable shelves Size: 1980mm height, 915 mm width and 485 mm depth. Make: Godrej Storewel Plain Large or Similar of reputed brand. Inspection: Consignee Inspection Charges: None Payment Terms: 100% after Supply. | — | — | — | 3,91,653 | |
| — | 600.00 | — | — | ||
| Supply of Track feed Battery Charger as per RDSO Spec. No. IRS: S-89/2013 Ver.1.0 or latest. Charging Capacity Rating 10 Amps for Charging 80 AH Battery. Inspection: RDSO Inspection Charges: Borne by Railways Payment Terms: 100% after Supply | — | — | — | 32,53,146 | |
| — | 20.00 | — | — | ||
| Provision of Ring Earth for EI system which includes supply of all components of earthing & bonding system like earth electrode, earth enhancement material, earth pit, Equi- potential earth busbar, connecting cables and tape/strips and other associated accessories in accordance with RDSO/SPN/197 Version 1.0 dtd. 04.07.2016 or latest, consisting minimum 8 Nos. of earth pits connected in a ring to achieve less than 1 Ohms earth resistance for connecting EI equipments, relay racks, panel, power equipments as per Signal Engineering Practice. Diagram of ring earth should be supplied to Railway for Approval before execution. All related material as recommended by RDSO in Spec. No. RDSO/SPN/197 Version 1.0 dtd. 04.07.2016 or latest, will be supplied by the contractor. basic material for one earth pit is given below: (a) Copper bonded steel electrode of 3.0 m long, 17 mm Dia with copper bonding thickness of minimum macrons and UL listed and marked = 1 no. (b) Earth enhancement material supplied in sealed bags of minimum 10 kg = 3 nos. (c) Copper strip of 150x25x6 mm, to terminate earth rod = 1 no. (d) Copper strip of 300x25x6 mm (MEEB) = 1 no. (e) Copper strip of 150x25x6mm (SEEB) = 1 no. (f) Supply of 35 sq. mm multi strand single core PVC insulated copper cable as per IS: 694 for connecting main earth electrode to MEEB in the equipment room in duplicate.(minimum 10 meter) (g) Supply of 16 sq. mm multi strand single core PVC insulated copper cable as per IS: 694 for connecting MEEB to SEEB and SPD to MEEB (minimum 10 meter ) (h) Supply of 10 sq. mm multi strand single core PVC insulated copper cable as per IS: 694 for connecting various equipments to SEEB (i) Supply of copper lug sleeve for 3/16 cable Note: Earthing arrangement for EI must be as per RDSO guidelines issued by RDSO vide TAN/3006 dated 30.06.2025 or latest. Inspection: RDSO Inspection Charges: Borne by Railways Payment Terms: 100% after Supply. | — | — | — | 36,58,470.8 | |
| — | 20.00 | — | — | ||
| Installation, testing and commissioning of Ring Earth for EI system which includes installation of all components of earthing & bonding system like earth electrode, earth enhancement material, earth pit, Equi- potential earth busbar, connecting cables and tape/strips and other associated accessories in accordance with RDSO Spec. No. RDSO/SPN/197 Version 1.0 dtd. 04.07.2016 or latest consisting minimum 8 Nos. of earth pits connected in a ring to achieve less than 1 Ohms earth resistance for connecting EI equipments, relay racks, panel, power equipments as per Signal Engineering Practice. Diagram of ring earth should be supplied to Railway for Approval before execution. Installation of one earth pit includes ( i ) Digging the earth to the required depth. (ii) Insertion of electrode. (iii) Filling of earth enhancing compound (Approx.30 Kg) (iv) Provision of exothermic weld connections to copper tape of 25 mm x 6 mm x 150 mm to the earth electrodes. All material tools and features required for weld will be arranged by contractor. (v) This also includes CC cover 1.5 ft x 1.5 ft. 1 ft wall thickness 2 inch with cover 3-inch thickness. Cables 35 Sq mm/ 16 Sq mm/10 sq mm for connecting earth to busbar, busbar to busbar and busbars to various equipments. Earth electrode of 17.20 mm Dia and 3.00 meter long high tensile low carbon steel circular rods molecularly bonded with copper and outer surface (minimum copper bonding thickness of 250 microns to made requirement of under writer's laboratories (UL) 467-2007 or latest. Copper strips of 150 mm x 25 mm x 6 mm to be welded with each earth electrode, copper strips of 300 mm x 25 mm x 6 mm for main equip- potential busbar, copper strips of 150 mm x 25 mm x 6 mm sub equip-potential busbar in relay room, power room and panel room. GI strip 25 mm x 2 mm for ring formation of earth pits Earth enhancement material in bags for each Earth Electrode. Inspection chamber of site 300 mm x 300 mm x 300 mm (Inside dimension) of approximate 50 mm thick with pulling hooks to cover the earth pits. Note: Earthing arrangement for EI must be as per RDSO guidelines issued by RDSO vide TAN/3006 dated 30.06.2025 or latest. Inspection: Consignee Inspection Charges: None Payment Terms: 100% after commissioning. | — | — | — | 9,14,617.6 | |
| — | 30.00 | — | — | ||
| Supply of basic material to construct unit maintenance free earth as per RDSO Specs. No. RDSO/SPN/197 Version 1.0 dtd. 04.07.2016 or latest and conforming to RDSO Drg. No. SDO/ RDSO/E&B/001. It consist of following: (a) Copper bonded steel electrode of 3.0 m long, 17 mm Dia with copper bonding thickness of minimum macrons and UL listed and marked = 1 no. (b) Earth enhancement material supplied in sealed bags of minimum 10 kg = 3 nos. (c) Copper strip of 150x25x6 mm, to terminate earth rod = 1 no. (d) Copper strip of 300x25x6 mm (MEEB) = 1 no. (e) Copper strip of 150x25x6mm (SEEB) = 1 no. (ii) Supply of 35 sq. mm multi strand single core PVC insulated copper cable as per IS: 694 for connecting main earth electrode to MEEB in the equipment room in duplicate.(minimum 10 meter) (iii) Supply of 16 sq. mm multi strand single core PVC insulated copper cable as per IS: 694 for connecting MEEB to SEEB and SPD to MEEB (minimum 10 meter ) (iv) Supply of 10 sq. mm multi strand single core PVC insulated copper cable as per IS: 694 for connecting various equipments to SEEB (v) Supply of copper lug sleeve for 3/16 cable Inspection: RDSO Inspection Charges: Borne by Railways Payment Terms: 100% after Supply | — | — | — | 6,32,946.9 | |
| — | 30.00 | — | — | ||
| Installation of Unit Maintenance Free Earth as supplied under item no. 13010300 above It includes: ( i ) Digging the earth to the required depth. (ii) Insertion of electrode. (iii) Filling of earth enhancing compound (Approx.30 Kg) (iv) Provision of exothermic weld connections to copper tape of 25 mm x 6 mm x 150 mm to the earth electrodes. All material tools and features required for weld will be arranged by contractor. (v) This also includes CC cover 1.5 ft x 1.5 ft. 1 ft wall thickness 2 inch with cover 3-inch thickness. Cables 35 Sq mm/ 16 Sq mm/10 sq mm for connecting earth to busbar, busbar to busbar and busbars to various equipments. Earth electrode of 17.20 mm Dia and 3.00 meter long high tensile low carbon steel circular rods molecularly bonded with copper and outer surface (minimum copper bonding thickness of 250 microns to made requirement of under writer's laboratories (UL) 467-2007 or latest. Copper strips of 150 mm x 25 mm x 6 mm to be welded with each earth electrode, copper strips of 300 mm x 25 mm x 6 mm for main equip- potential busbar, copper strips of 150 mm x 25 mm x 6 mm sub equip-potential busbar in relay room, power room and panel room. GI strip 25 mm x 2 mm for ring formation of earth pits Earth enhancement material in bags for each Earth Electrode. Inspection chamber of site 300 mm x 300 mm x 300 mm (Inside dimension) of approximate 50 mm thick with pulling hooks to cover the earth pits. Note: The installation of this item shall be carried out by the contractor as per RDSO/SPN/197 Version 1.0 dtd. 04.07.2016 or latest and conforming to RDSO Drg. No. S DO/RDSO/E&B/001 or latest. Inspection: Consignee Inspection Charges: None Payment Terms: 100% after execution and testing. | — | — | — | 2,83,845.9 | |
| — | 100.00 | — | — | ||
| — | 1000.00 | — | — | ||
| Supply & installation of copper tape 25x3mm for perimeter bonding in S&T rooms as per RDSO Drg. No. SDO/RDSO/E&B/001 or latest. Inspection: Consignee Inspection charges: Borne by Railways Payment terms: 70% after supply, 20% after installation & 10% after commissioning | — | — | — | 3,76,440 | |
| — | — | — | 40,48,065.1 | ||
| — | 5.00 | — | — | ||
| Supply of surge protective device(SPD) life tester, designed for onsitetesting of surge protection devices.It allows checking and indicating thehealth status of GDT/MOV based SPD of voltage range up to 1000V. Itshall indicate the status of SPD bymeasuring its electrical parameters.SPD tester shall be of reputed make JMV or similar. Inspection:-RITES | — | — | — | 5,14,338.4 | |
| — | 1000.00 | — | — | ||
| Casting, transportation and provision of Cement Earth Enclosure As per NWR Drawing Painting and writing work to be done after testing of earth value at site. All materials required for this work will be supplied. by contractor.Inspection:Consignee. | — | — | — | 7,22,650 | |
| — | 4.00 | — | — | ||
| Supply ,Installation , Commissioning and Testing of split core structure, non contactmeasurement, Real In Time testing, high accuracy, high stability, resistance range 0.01-100, resolution 0.001, accuracy ±2% rdg ± 3dgt, working Temp. & humidity -2055, 20% RH 90% RH, Detector Light and Sound Alarm, IP-54 protection, RS485 communication, with extended 4 digit LCD.Display can be mounted up to 2 Mtr.distance from detector unit. (Suitable for Transmission Line/Railway facilities/Communication/Sub Station/Electrical equipment Grounding. Consists of (Model no-KOBLE 2800 KB ver.3.0 or similar) : (a) Main detector unit- 01no., (b) LCD enclosure fitted with Aviation plugs-01no. (c) Set of detector to LCD enclosure connecting two cables each 2mtr. Length fitted with Aviation connector-01 set (d) Rs- 485 connector with 0.5 mtr. Cable -01no (e) RMCU with PFC- 01 no.Make/Brand:KOBLE ( Warranty Period : Upto 30 months from the date of supply).Inspection RITES | — | — | — | 4,33,256 |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
HTML
nit.pdf
NIT
TenderDocumentofTenderNo.SNT-JP-02-2026-27.pdf
ATTACHMENT
MakeInIndiaPolicy2017.pdf
ATTACHMENT
TelecomCircularNo.09_1.pdf
ATTACHMENT
GCC202210NosCorrectionSlipsofGCC_compressed.pdf GCC and 10 Nos Correction Slip
ATTACHMENT
GCCACS-11dated13.03.26.pdf
ATTACHMENT
GCC202210NosCorrectionSlipsofGCC_compressed.pdf
ATTACHMENT
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .