Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹15.5 LRejected-Finance 1814 NARSING NAGAR RANJHI JABALPUR MP 482005 | JABALPUR | JABALPUR | MADHYA PRADESH | 482005 | L1 | Rejected-Finance Due to adm reasons. | |
| 2 | L2₹16.2 L+₹70,499 (4.55%)Rejected-Finance | L2 | Rejected-Finance Not Lowest. |
Tender Value
₹19.4 L
EMD Value
₹38,800
Closing Date
10 Dec 2018, 6:00 pmClosed
GE Kamptee
Garrison Engineer, Military Engineer Services, Kamptee Cantt - 441 001
REPAIR / REPLACEMENT OF LT PANEL, APFC PANEL AND CONVERSION OF LT OH LINE TO UG CABLE AT CERTAIN POCKET AT KAMPTEE.
2018_MES_223724_1
8936/E8
Open Tender
Civil Works
Item Rate
180 days
Kamptee
Class E, Cat b (i)
7 documents required · 7 mandatory
₹500
Yes
GE Kamptee
₹38,800
Yes
11 Jul 2022
16 Nov 2018
11 Dec 2018
17 Nov 2018
10 Dec 2018
29 Nov 2018
17 Nov 2018 - 28 Nov 2018
Amount
Excavation in trenches in any type of soil not exceeding 1.5 meter wide and not exceeding 1.5m in depth for laying of cables, poles, stay and getting out of excavated material complete all as specified and directed by Engineer-in-Charge.
S&F double wall corrugated high density polymer ethyl (HDPE) pipe for laying of electric cable of size 50mm outer diameter and 38mm inner diameter with IS 14930 (part 2):2001 laid in trenches, wall, floor, pole including bends, sockets and other connected accessories complete all as specified and directed by Engineer-in-Charge. Make:- Dura Line / Tijaria / REX.
S&F double wall corrugated high density polymer ethyl (HDPE) pipe for laying of electric cable of size 90mm outer diameter and 76mm inner diameter with IS 14930 (part 2):2001 laid in trenches, wall, floor, pole including bends, sockets and other connected accessories complete all as specified and directed by Engineer-in-Charge. Make:- Dura Line / Tijaria / REX.
S&F double wall corrugated high density polymer ethyl (HDPE) pipe for laying of electric cable of size 120mm outer diameter and 103.5 mm inner Diameter with IS 14930 (part 2):2001 laid in trenches,wall,floor,pole including bends, sockets and other connected accessories complete all as specified and directed by Engineer-in-Charge. Make:- Dura Line / Tijaria / REX.
Returning, filling in, including spreading, leveling, watering and well ramming in layers not exceeding 25cm thick each, excavated soil in trenches after the cables have been laid and tested complete all as specified and directed by Engineer-in-Charge.
Removal of surplus soil to a distance not exc. 50m and deposited where directed at a level not exc. 1.5 m above the starting point all as specified and as directed by EIC.
Dismantling and setting aside existing cross arms of MS channel or angle sections etc from pole 2 pole structure / 4 pole structure for reuse or existing 2 pole structure / 4 pole structure of any size complete all as specified and directed by Engineer-in-charge.
Dismantling of ACSR conductor from site complete all as specified and directed.
Dismantling and setting aside existing pin / shackle / loop / disc HT insulator etc of any size from pole / structure complete all as specified and directed.
Supply and laying in trenches or fixing in walls / poles or drawing through pipe XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) with aluminium conductor, 1100 volts, grade cross sectional area 120 sq mm, 3.5 core including testing after laid and jointed with lugs, nuts, bolts, washers complete all as specified and as directed.
All as per item No 10 above but of size 95 sq mm 3.5 core.
All as per item No 10 above but of size 35 sq mm 3.5 core.
All as per item No 10 above but of size 25 sq mm 4 core.
All as per item No 10 above but of size 16 sq mm 4 core.
All as per item No 10 above but of size 10 sq mm 4 core.
Fabrication, supplying, installing, testing & commissioning of outdoor type feeder pillar box with rain cowl weather / vermin proof, Indoor type, factory made LT panel, from any CPRI approved manufacturer having dismensions of Suitable size with sufficient space between MCCB cable coonection place and body of panel for easily working to workers including necessary incoming & outgoing cable connections, cable glands thimbles of required sizes, made out of CRCA sheet 3.00 mm thick for outer shell and 2mm thick for inner shell duly powder coated paint with inner shutter & outer double door, the cubical shall have a bottom channel of size 75x40x5mm duly coated with zinc metal coating with satinless steel locking handle arrangement both side openable fixed on 50 x 50 x 5 mm MS angle frame fixed 300mm above groud level & 300 mm below the ground grouted in & including PCC 1:3:6 type C1 (using 20mm graded stone aggregate) complete all as specified, directed & comprising of following including refixing existing cables to new panels by proper lugging & cable gland as required. (a) Busbar chamebr for 3 phase & nuetral of capacity 400 Amps (40mm x 10mm) alumunium bus bar duly insulated. (b) Multifunctioning meter to measure Voltage, ampere, KWH, PF - 1 Nos. (c) One set of pilot lamp. (d) Incoming MCCB 250 amps 4 Pole 415 volts 35 KA thermal magnetic setting type - 1 Nos. (e) Outgoing MCCB 160 amps 3 Pole 415 volts 35 KA thermal magnetic setting type - 2 Nos. (f) Outgoing MCCB 100 amps 3 pole 415 volts 10 KA thermal magnetic setting - 2 Nos.
Fabrication, supplying, installing, testing & commissioning of outdoor type feeder pillar box with rain cowl weather / vermin proof, outdoor type, factory made LT panel, from any CPRI approved manufacturer having dismensions of Suitable size with sufficient space between MCCB cable coonection place and body of panel for easily working to workers including necessary incoming & outgoing cable connections, cable glands thimbles of required sizes, made out of CRCA sheet 3.00 mm thick for outer shell and 2mm thick for inner shell duly powder coated paint with inner shutter & outer double door, the cubical shall have a bottom channel of size 75x40x5mm duly coated with zinc metal coating with satinless steel locking handle arrangement both side openable fixed on 50 x 50 x 5 mm MS angle frame fixed 300mm above groud level & 450mm below the ground grouted in & including PCC 1:3:6 type C1 (using 20mm graded stone aggregate) complete all as specified, directed & comprising of following including refixing existing cables to new panels by proper lugging & cable gland as required.including taking down old panel complete all as directed (a) Busbar chamebr for 3 phase & nuetral of capacity 300 Amps (30mm x 10mm) alumunium bus bar duly insulated. (b) Multifunctioning meter to measure Voltage, ampere, KWH, PF - 1 Nos. (c) One set of pilot lamp. (d) Incoming MCCB 160 amps 4 Pole 415 volts 35 KA thermal magnetic setting type - 1 Nos. (e) Outgoing MCCB 63 amps 3 pole 415 volts 10 KA thermal magnetic setting - 6 Nos.
M&L for earthing complete with galvanized steel earth plate electrode 600x600x6mm thick buried directly in ground vertically to a depth not less than 2.25m below ground level with top edge of earth plate not less than 1.5m below ground level connected to galvanized iron earth strip 32 x 6 mm by means of bolts, nuts, check nuts, washers of galvanized iron and connected to main switch/control board upto 7.5m away from the earth electrode including excavation earth work, PCC chamber, RCC cover slab char coal, watering pipe, wire mesh lugs, earth lead protection pipe 40mm bore, light grade 7.5m long as applicable and as per plate No. 3 of SSR 2009 and all as specified. (a) Excavation and earth work in any type of soil. (b) Drilling of holes in electrode (c) PCC pit in cement concrete (1:2:4) type B-1 (d) 40 mm thick Pre-cast RCC cover with suitable handle. (e) Funnel with watering pipe of GI 20 mm nominal bore ,medium grade & copper lug etc. (f) 40mm nominal bore medium grade GI protection pipe 7.50 m long for protection of earthing lead. (g) Requisite quantity of charcoal and common salt. (h) Connection to earthing test point and testing on completion.
NOTE:- SCHEDULE OF CREDIT (Amount shall be deducted offline from the total quoted amount to workout the net contract sum to be considered for acceptance.) [(-) Rs.23,250.00]
M/s T.S.JOHAR
Bidder Name
M/s T.S.JOHAR
TRISHLA CONSTRUCTIONS
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .