Executive Engineer ED Kathua
Office of the Executive Engineer ED Kathua
Supply, Installation, Testing, Commissioning of 63KVA Sub Station and Laying of HT/LT Network for SMF Burmal on Turnkey Basis falling under the jurisdiction of Electric Sub Division Hira Nagar of OM Division, Kathua,JPDCL.
2021_PDD_113415_1
KED/34 of 2020-21 Dt.09.01.2021
Open Tender
Electrical Works
Turn-key
20 days
hiranagar
Please refer Tender documents.
7 documents required · 7 mandatory
₹500
Yes
Executive Engineer Electric Division Kathua
₹12,000
6 Feb 2021
9 Jan 2021
25 Jan 2021
9 Jan 2021
23 Jan 2021
9 Jan 2021
9 Jan 2021 - 13 Jan 2021
Amount
Creation of 63KVA Sub Station for SMF Burmal on Turnkey Basis by way of Supply, Erection/Installation, Testing, commissioning etc of the following material:
11/0.433kV, 63KVA, 3-phase Distribution Transformers with Bimetallic Terminal Connectors Energy Level-2, (Al. wound ).
Gapless Surge Arrestor,9 kV ,10 kA ,LA with polymer housing, Stn. Type
11kV GO, AB Switch 3-Phase, 3-Pole, 200 Amp, Vertical Type
11 kV Horn Gap Fuse Set 3 Phase 200A
70mm² Single Core Cable,1.1K V Grade, PVC Insulated Stranded Conductor FRLS type
9 Mtr. Long ST Pole( 410SP33)
11kV Polymeric composite Disc Insulator 12kV,min failing load 45KN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
GI Channel/Angle/Flat of sizes including clamps(Sizes and quantity as per Drawing No.F-2 of REC Construction Standards)
Galvinized Nuts and Bolts.
Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239.GI Strip for neutral earthing of size 25 mm x 3 mm for connection of transformer body,G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber made of brick masonary with RCC slab cover.
11kV Polymeric composite Pin Insulator 12kV, 5kN, Lightening Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
Galvanised Stay Set with 50x8mm stay clamp, guy insulator(2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
Wedge Connectors / PG Clamps
Danger Plates with Clamps
GI Barbed Wire for Anti Climbing
Prodigy Meter
Cement Bottoming of Pole with 1:2:4 mix as per RE Standard upto 0.25 Mtr above ground and 1.5Mtr below ground width 0.6MtrX 0.6Mtr including plastering and curing of the concrete
LT Distribution Box for 63KVA DTR with MCCBs for Incomer & SFUs for outgoing Circuits
Sundry items like aluminium lugs, Jumpers, binding Tape,
Laying of HT Line on Turnkey Basis by way of Supply, Erection/Installation, Testing, commissioning etc of the following material:
9.0 Mtr PCC Pole(WL-300Kg)
11kV Polymeric composite Pin Insulator 12kV, 5kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
30 mm² ACSR Weasel Conductor
GI Channel X-arm including Clamps and Braces
GI V Cross Arms with Top Bracket including Clamps
Galvanized Nuts and Bolts
Anti-climbing device with clamps
Danger Plates with clamps
Stone Pad(300mm X 300mm X 75mm)
Aluminium Jointing Sleeves
9Mtr PCC Pole Cement bottoming with 1:2:4 mix as per RE Standard upto 0.25 Mtr above ground and 1.5 Mtr below ground width 0.6 Mtr X 0.6 Mtr including plastering and curing of Concrete
Galvanised Stay Set with 50x8mm stay clamp, guy insulator(2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
Pole Earthing complete by GI Pipe of 40mm or GI rod 20mm , 2.5 Mtr long through GI Strip of 25 X 3 mm to each pole( As per J-2 REC Drawing) for 11KV Line
Laying of LT Line on Turnkey Basis by way of Supply, Erection/Installation, Testing, commissioning etc of the following material:
8.0 Mtr PCC Pole(WL-200Kg)
30 mm² ACSR Weasel Conductor
GI U Clamp for Shackle Insulators
16kN Polymer Shackle Insulators
Galvanized Nuts and Bolts.
Anti-climbing device with clamps
Danger Plates with clamps
Stone Pad(300mm X 300mm X 75mm)
Aluminium Jointing Sleeves
Galvanised Stay Set with 50x8mm stay clamp, guy insulator(2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
M/S LUMEN ENGINEERS
ROCKEY SALES CORPORATION
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .