Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹23.7 LAccepted-AOC | L1 | Accepted-AOC Being L1 and found in order | |
| 2 | L2₹27.2 L+₹73,111 (2.77%)Rejected-AOC | L2 | Rejected-AOC Not being L1 | |
| 3 | L3₹27.4 L+₹93,000 (3.52%)Rejected-AOC 180 SECTOR 1 CHANNI HIMMAT CHANNI HIMMAT JAMMU JAMMU JAMMU AND KASHMIR 180015 UDYAM JK 07 0006292 | JAMMU | JAMMU AND KASHMIR | 180015 | L3 | Rejected-AOC Not being L1 |
Tender Value
₹25.0 L
EMD Value
₹49,940
Closing Date
29 Sept 2022, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
HQ 135 WE
HQ 135 WE C o 56 APO
COMPREHENSIVE REPAIR MAINT OF 33 by 11 MRS AT SUNDERBANI UNDER GE NORTH AKHNOOR
2022_MES_549472_1
CWE/JA-15/2022-23
Open Tender
Civil Works
Item Rate
180 days
Akhnoor
As per NIT
8 documents required · 8 mandatory
₹500
Yes
GE North
₹49,940
Yes
12 Nov 2022
2 Sept 2022
1 Oct 2022
2 Sept 2022
29 Sept 2022
15 Sept 2022
2 Sept 2022 - 8 Sept 2022
Amount
Complete Overhauling and Servicing of 33/11 KV out door type VCB including disassembly of operating mechanism parts,spring charging motor and mechanism well cleaning with petrol and CRC-226, replacing unserviceable spare parts/accessories i.e incoming jumper connection,bushing holding moving and fixed contact assembly,GO rod,inter connection assembly,spring charge mechanism and oiling and greasing of moving contacts and fixing contact parts and checking of pole insulators,checking of vacuum interrupters, incoming and outgoing terminals,flexible connections,suporting insulators,operating rod, tie bar common operating shift,operating corn, locking cam ,making spring,breaking spring,loading spring,and main linkwell cleaning mechanism linkages drive insulators and fiber reinforced plastic frame around the vacuum interrupters including routine and periodical test,complete all as specified and directed. (Note : Supply only spares will be measured and paid separately)
Supply only the following spares of 33/11KV VCBs and connected control and switchgear accessories.
Supply only spring charging motor with gear and connector for 33/11 KV VCB of voltage 30 Volts DC or as required at site compatible with OD VCB
Supply only Closing and tripping coil for 33/11 KV SF6/VCB as per site requirements.
Supply only Auxillary switch for 33/11 VCB as per site requirements.
Supply only Limit switch for 33 KV VCB as per site requirements.
Supply only Hooter suitable for 33/11 KV breaker as per site requirements
Supply only T&C switch with locking arrangement.suitable for 33 KV breaker
Supply only LED Indicating lamps of desired colour dual input type.
Supply only Vaccum Interrupting unit (bottle type) suitable for SF 6 breaker
Supply only IDMT,IDMTL relays suitable for 33 kv breaker and calibration through primary and secondary testing and connected accessories for functional requirement checking of electrical wiring system and testing complete all as specified and directed.
Supply only Control Cable 8 core armoured control 2.5 sqmm copper for interconnecting from remote panel to VCB outdooor unit all as directed
Supply only Control cable 4 core armoured control cable 2.5 sqmm copper for interconnecting from remote panel to VCB outdooor unit.
Supply and fixing new 33 KV/11 KV CTs outdoor type oil immersed ratio 75-50/5+5A (three core type) Class I & 5P10 VA Burden-15 with first oil filled suitable for 33 KV power supply by providing suitable size of nuts, bolts on existing structure complete including taking out old unserviceable CTs, complete all as specified and directed by Engineer-in-Charge. Make-Jyoti(JSL)/Gyro/Laxmi/ Areva, schneider
Supply, fixing, commissioning and testing of 33000 x 110 volts / √3 outdoor type single pole potential transformer and self air cooled type having 200 VA burden suitable for 33 KV equipment installed on existing structure with suitable fixing arrangement including dismantling of old PTs, complete all as specified and directed by Engineer-in-Charge. Make : Huphen, Areva, schneider
Supply and fixing in replacement of 33 KV rotating , horizontal type, isolator switch 400-600 Amp complete with all fixing arrangements after disconnecting all electric connections, and keeping aside for offering credits, complete all as specified and directed by Engineer-in-Charge.
M&L for scrapping laid out aggregate of any size and removing from site and cleaning of dirt and vegetation from site and relaying of the same in switchyards, complete all as specified and directed by Engineer-in-Charge.
Painting with two coats of aluminium paint of approved make and colour including preparation of chain link iron fencing of length 120 feet and height 6 feet complete around 33 KV grid including iron gates by scrapping of rusted materials, and , complete all as specified and directed by Engineer-in-Charge.
Preparation of old cement based painted surfaces by scrapping of deposited materials, and painting with two coats of cement based paint of approved make and colour, complete all as specified and directed by Engineer-in-Charge.
M&L for painting of HT 33 KV HT grid steel structure including all MS channel isolators, CTs, PTs and MOCBs, VCBs, bus bar and other steel structure with synthetic enamelled aluminium paint on structure abd other colour code for equipment after proper surface preparation, complete all as specified and directed by Engineer-in-Charge.
M&L for Jumpers works in PTs, CTs, MOCBs, isolator, DO fuse by using parallel grove clamp, Tee clamp Tee clamps other connectors required by using ACSR conductor any sizess (Dog/Mouse) including dismantling old conductor and clamp all as specified and as directed by Engr in charge
M&L for repalcement of PG clamps, parallel grove clamps, tee clamps, GI nuts bolts of required size other connectors for connecting ACSR conductor for jumpering all as specified and as directed by Engr in charge
M&L for earthing complete with galvanised steel earth plate electrode 600x600x6mm thick burried directly in ground /earth pit not less than 2.25m deep below the ground level with top edge of the plate not less than 1.5 m below the normal ground level connected to DB/Panel by using GI strip of 32x6 mm sleeved using red colour PVC sleeving as earthing lead soldering/rivetted to earth plate at one end and connected to existing structure by means of nut, bolts etc complete with PCC pit (1:3:6) type PCC cover with handle, funnel with watering pipe wire mess GI protection pipe for earthing lead complete all as specified and as directed.
Supply and fixing Danger notice plate of 1.6 mm thick MS sheet,vitreous enamelled white with letters, figures and conventional skull and bones with MS clamp, bolts and nuts of approved size for HT, 25x20 cm,(3 KV/ 11 KV mark complete all as specified and directed by Engr -in -charge
M&L for steel tubular swaged type poles 11 metrs long,pole weight approximately 227 kgs, pole should be in one piece only and smooth finishing and smooth finishing of pole,ISI marked complete with all accessories such as cast iron base plate, finial taper plug,bolts, nuts, screws,washers and drilling of holes for continious GI earth wire as specified type 410 SP-55 including applying two coats of aluminium paint over one coat of red oxide zinc chrome primer and embedded portion shall be painted with two coats of black paint after preparation of surface complete all as specified and directed make as approved by GE.
M&L for steel tubular swaged type poles 12 metrs long,pole weight approximately 292 kgs, pole should be in one piece only and smooth finishing and smooth finishing of pole,ISI marked complete with all accessories such as cast iron base plate, finial taper plug,bolts, nuts, screws,washers and drilling of holes for continious GI earth wire as specified type 410 SP-64 including applying two coats of aluminium paint over one coat of red oxide zinc chrome primer and embedded portion shall be painted with two coats of black paint after preparation of surface complete all as specified and directed make as approved by GE.
M&L for galvanised cross arms, bracings, supports, clamps, angles, hollow bars square/round,flat irons etc and back plates fabricated in structural steel sections including nuts, bolts,washers, welding, bending, fabrication, cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat and anti corrosive silver paint one undre coat and one finishing coat and including removing old unserviceable item complete all as specified and directed
Supply and fix and in repair 11 KV out door type Air Break gang operated device of rating 400 Amps, triple pole, vertical type,mechanically operated, mounted on HT insulators 15 Nos, incl drop out fuse assy and steel channel frame with operating machanism worked from ground level with GI tubing 25 mm dia medium grade with operating handle and locking arrangement including seven lever navtal lock and providing ACSR conductor jumpers duly crimped with lugs, connecting to existing 11 KV supply cand testing complete all as specified and directed. Make :- Atlas/Elpro/ECE/Pactil/Oblum
Supply and fix and in repair 11 KV out door type Air Break gang operated device of rating 200 Amps, triple pole, vertical type,mechanically operated, mounted on HT insulators 15 Nos, incl drop out fuse assy and steel channel frame with operating machanism worked from ground level with GI tubing 25 mm dia medium grade with operating handle and locking arrangement including seven lever navtal lock and providing ACSR conductor jumpers duly crimped with lugs, connecting to existing 11 KV supply cand testing complete all as specified and directed..Make :- Atlas/Elpro/ECE/Pactil/Oblum
M & L for PCC 1:2:4 type B1 (using 20 mm graded aggregate). For foundation, filling, mass concrete, coping etc incl finishing of external surfaces without applying extra cement incl dismantaling old PCC
M & L for PCC 1:3:6 type C-2 (using 40 mm graded aggregate). For foundation, filling, mass concrete, coping etc incl dismantling old PCC
Supply and lay cable XLPE insulated screened PVC bedded, galvanised steel strip or wire armored, electric power cables (heavy duty) 11000 volts grade with stranded aluminium conductor of size 95 Sq mm, 3 core.
Supply and lay cable XLPE insulated screened PVC bedded, galvanised steel strip or wire armored, electric power cables (heavy duty) 11000 volts grade with stranded aluminium conductor of size 120 Sq mm, 3 core.
M & L for excavation in trenches,for laying under ground cable,pipe lines, errection of poles and stays in any type of soil not exc 1.5 Mtr wide and not exc. 1.5 m in depth for foundation and getting out complete all as specified and as directed.
M & L for excavation in trenches,for laying under ground cable,pipe lines, errection of poles and stays in any type of soil not exc 3.0 Mtr wide and not exc. 3.0 m in depth for foundation and getting out complete all as specified and as directed.
M & L for returning filling in including spreading, levelling, watering and ramming in layers not exceeding 25 cm thick with earth obtained from excavation all as specified and as directed.
M & L for removal of surplus soil to a distance not exceeding 50 mtrs and depositing where directed at a level not exceeding 1.5 mtr above the starting point all as specified and as directed.
M & L for unwashed sand cushioning below and around cable in trenches with river sand all as specified and as directed by EIC. (Punned thickness will be measured)
Supplying and laying un-reinforced precast concrete cable cover HV, Type 1, flat, size 300mmx l80mm x 40mm complete all as directed by EIC.
S & F 80mm bores of tubes 'light grade' galvanised with all fittings and fixed complete with electric pole, laid in trenches for passing of XLPE cable all as specified and as directed by EIC.
S & F 100 mm bores of tubes 'light grade' galvanised with all fittings and fixed complete with electric pole, laid in trenches for passing of XLPE cable all as specified and as directed by EIC.
Supply and fixed cable jointing kit for 11 KV grade cable for in door termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium condcutor cable of size but 50 sqmm to 95 sqmm
Supply and fixed cable jointing kit for 11 KV grade cable for out door termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium condcutor cable of size but 120 sqmm to 185 sqmm
Supply and fixed cable jointing kit for 11 KV grade cable for out door termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium condcutor cable of size but 50 sqmm to 95 sqmm
Supply and fixed cable jointing kit for 11 KV grade cable for out door termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium condcutor cable of size but 120 sqmm to 185 sqmm
Supply and fixed cable straight through jointing kit for 11 KV grade cable for out door termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium condcutor cable of size but 50 sqmm to 95 sqmm
Supply and fixed cable straight through jointing kit for 11 KV grade cable for out door termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium condcutor cable of size but 120 sqmm to 185 sqmm
Supply insatallation, testing and commissioing of maintenance free earthing based on 300mm long GI earthing Electrode (Met -Chem) 80mm outer dia and inner rod with 10mm thickness 3000mm long duly filled with ITPC-EECP15 fixed with nuts an bolts incl excavation/ earth work in any strata & PCC chamber with CI Frame and cover (Earth pit not less than 2.25 mtrs below ground level). The electrode is surrounded by chemical (ITPC-EECP15) a mixture of sulphate, silica, Iron Oxide etc, magnesium oxide, sodium oxide, zinc oxide etc. Each Earth electrode should have resistance <2 Ohm by using earth electrode is used as per the site requirements. Chemicals compound powder to be provided minimum 50Kg per site. The inspection joint provide for earthing reference incl the man hole cover with locking facility be provided. (Make: ITPC/KEGS/TERRAFILL)
S&F Copper strip of size 20x3 mm as in earth continiuty conductor fixed to wall on batten or recess or cases or buried in ground or any other situation for loop earthing as required at site al as specified and directed by engr in charge
Disconnecting electrical connections from HT 33/11 KV, 1.25 MVA transformer of any descriptions by opening of earth & control connections of any type, sealing of oil leakage, replacement of unserviceable parts and filtration of oil, cleaning the transformer, including making all HT connections, control cable connection, earth connection etc including testing the transformer after necessary repairs, complete all as specified and as directed by Engineer-In-Charge. Note: Spares required for repair/ replacement of unserviceable parts shall be measured and paid separately under relevant items
Supply and fixing in replacement of primary coil of HT 33/11 KV , 1.25 MVA transformer of any capacity, made of super enameled copper winding wire/ strip of existing insulation, gauge and specifications, complete all as specified and as directed by Engineer-In-Charge. Note: Primary coil shall have same number of turns of winding wire and with matching to manufacturer design.
Supply and fixing in replacement of secondary coil of 33/11 KV , 1.25 MVAtransformer of any capacity, made of super enameled copper winding wire/ strip of existing insulation, gauge and specifications, complete all as specified and as directed by Engineer-In-Charge. Note: Secondary coil shall have same number of turns of winding wire and with matching to manufacturer design.
Supply and fixing out door type suitable for 33KV meter, 3 phase,incl providing CT &PT units,copper wound type,oil cooled having following specification for potential Transformer of ration 33KV/110V and current transformer of ration 30/5A (PT) primary voltage 33000volts,secondary voltage 110V,rated burden 25 VA,accuracy class 0.5,frequency 50Hz,insulation class-A,IS No:3156&2705 confirming for PT& CT,(CT) Primary current 30A,secondary current 5A,3Ph, insulation class-A and including providing outdoor fixing arrangements,control wiring and all connected operational accessories and testing and including removing old unserviceable meter and deposit to MES yard complete all as specified and as directed by Engineer-In-Charge.
Disconnecting electrical connections from HT and LT sides of old unserviceable/ damaged/ burnt step down transformers of any descriptions, capacity upto 400 KVA, any type and taking down from the platforms or mounted on exisiting position (four poles/ two pole structure) by hydraulic cranes of suitable capacity and transporting by truck/ lorry to the workshop, opening top cover, draining out the transformer oil in clean barrels, cleaning of sludge from oil tank and conservator tank, cleaning and polishing of tapping contact point, opening carefully copper wire/ strip wound LT coils and rewinding the same after providing new necessary insulating packing material by using the same old strip/ wire, refitting top cover with replacement of studs, nuts, bolts, washers and gasket after repairs/ replacement of unserviceable parts and cleaning the transformer and making the transformer absolutely leak proof, pouring in the insulating oil in the transformer, placing in original position on four pole/ two pole structure/ platform at site and making all HT/LT connections including testing the transformer after necessary repairs, complete all as specified and as directed by Engineer-In-Charge. Note: Spares required for repair/ replacement of unserviceable parts shall be measured and paid separately under relevant items of BOQ.
Replacement of old unserviceable/ damaged 33 KV HT bushing assembly with new HT bushing assembly (Set of three) with insulated brass stud including nuts, bolts and washers, suitable for transformer of any type, any capacity complete all as specified and as directed by Engineer-In-Charge.
Replacement of old unserviceable/ damaged 11 KV HT bushing assembly with new HT bushing assembly with insulated brass stud including nuts, bolts and washers, suitable for transformer of any type, of any capacity, complete all as specified and as directed by Engineer-In-Charge.
Replacement of old unserviceable/ damaged cork sheet gasket with new cork sheet gasket, suitable for transformer of any capacity, complete all as specified and as directed by Engineer-In-Charge.
M&L for collection of sample of old transformer oil from top and bottom of transformer of different capacity of installed at 33KV sub station and testing for acidity and submission of test report in duplicate for each sample and all as directed.
Dehydration and filtration of 33 / 11 KV transformer oil after draining out oil from transformer by the dehydration machine at site or nearby transformer workshop to achieve di-electric strength 50 KV at 4mm gap, complete all as specified and as directed by Engineer-In-Charge. Note: (i) Cost of transportation of dehydration machine and other required materials and tools, plants shall be deemed to be included in the quoted rates. (ii) Test certificate of di-electric strength from Govt auth Lab shall be produce before and after dehydradation and filtration process for each transformer.
Replacement of old unserviceable/ damaged air breather assembly with new air breather assembly with silica gel suitable for 33/11 KV transformer including nuts, bolts and washers complete all as specified and as directed by Engineer-In-Charge.
Replacement of old unserviceable/ damaged air breather assembly with new air breather assembly with silica gel capacity 500 gm suitable for 11/.440 KV transformer including nuts, bolts and washers complete all as specified and as directed by Engineer-In-Charge.
Supply only fresh transformer oil to top-up and filling in the existing transformer, di-electric strength not than 45 KV, meeting Bureau of Indian Standards: IS 335-1993 (Reaffirmed-2005) specification, examined in a 100mm thick layer at 270°C, clear, transparent and free from all type of suspended matter or sediment, complete all as specified and as directed by Engineer-In-Charge. Make: IOCL/ HPCL/ BPCL/ Reliance.
Preparation of old, external surface of 33/11 KV transformers of any capacity , by removing the scrap, rust, washing including cleaning and spray painting with two coats of synthetic enamel paint including numbering MES No in white colour synthetic enamel paint, at site or at workshop, complete all as specified and as directed by Engineer-In-Charge.
Preparation of old, external surface of 11/0.44 KV transformers any capacity, by removing the scrap, rust, washing including cleaning and spray painting with two coats of synthetic enamel paint including numbering MES No in white colour synthetic enamel paint, at site or at workshop, complete all as specified and as directed by Engineer-In-Charge.
M&L Lightening arresters expulsion type complete with all fittings, transmission class, discharge capacity 65 kilo amp, 33000 volts, complete all as specified and directed by Engineer-in-Charge.
M&L Lightening arresters expulsion type complete with all fittings, transmission class, discharge capacity 12 kilo amp, 11000 volts, complete all as specified and directed by Engineer-in-Charge.
Supply and fixing Electrical accident / shock treatment chart mounted on wodden frame, complete all as specified and directed by Engineer-in-Charge.
M&L for guarding cradles, made to shape hexagonal/rectangular or any other shape fabricated with GI 4 mm dia wire including binding wire, complete all as specified and directed by Engineer-in-Charge.
S&F Disc type insulator porcelain, vitrous 145 mm high and 255 mm dia ball and socket type, (white, brown or green) complete single disc assembly for ACSR conductor having working pressure 11000 volts grade, complete all as specified and directed by Engineer-in-Charge.
S&F Pin type, porcelain, vitreous, white, brown or green insulator including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut,150mm height, 150mm dia for 11000 volts grade, complete all as specified and directed by Engineer-in-Charge.
S&F loop type, porcelain, vitreous, white, brown or green insulator including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut, 150mm height, 150mm dia for 33000 volts grade, complete all as specified and directed by Engineer-in-Charge.
S&F Pin type, porcelain, vitreous, white, brown or green insulator including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut, for 33000 volts grade, complete all as specified and directed by Engineer-in-Charge.
S&F disc type, porcelain, vitreous, white, brown or green insulator including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut, for 33000 volts grade, complete all as specified and directed by Engineer-in-Charge.
S&F loop type, porcelain, vitreous, white, brown or green insulator including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut, for 33000 volts grade, complete all as specified and directed by Engineer-in-Charge.
M&L for Hardcore Aggregate of guage n. exc 25mm deposited, spread and levelled in layers n exc. 15 cm thick, to a true surface, complete all as specified and directed by Engineer-in-Charge.
Servicing and complete overhauling of VCB 11 KV Indoor type 630 Amps capacity including disassembly of operating mechanism parts, well cleaning with petrol & CRC-226, replacing of moving parts, re-assembly, fine setting of mechanism, replacement of unserviceable parts and re-assembly of parts including well cleaning the complete panel board main bus bar, de-carbonizing all joints, bus bar, CTs’ PTs spouts, metal parts and making VCB perfect operation in manual and electric mode including all routine and preventive maintenance, complete all as specified and directed by Engineer-in-Charge.
Routine preventive and annual maintenance of RTCC Panel, dismantling complete and cleaning, repair / replacement of burnt out electrical accessories, checking of connections , repair and replacement of complete internal wiring, current and earth fault relay, voltmeter, ammeter, tripping coil with system, burnt out elecrical parts etc. as existing specification, setting of relays with provided values, complete all as specified and directed by Engr-in-charge. All minor/ Burnt spares/works, bolts, nuts, washers, connectors, pins, panel hinges, locks, allignment, lubricants etc shall also be included in quoted rates.
Supply and fixing by stringing stretching and strengthening on insulators ACSR conductor of desired size including aluminium binding wire of suitable cross sectional area including joints sleeve for jointing conductors of equal or unequal size and for jumpers connections including treatment of connector and ACSR conductor joints/jumpers with conducting jelly, and taking down of UNSV conductors, complete all as specified and directed.
Material and labour for tree branches/vegitation cutting around the 2/4 pole structure and HT lines and installations from line conductor to tree distance up to 4 mtrs and cutted wood pieces/vegitation materials disposal upto distance not exc 100 mtr at defence land location where as directed and including providing safety eqpts & cutting tools,ladders etc will be own arrangement by the contractor and complete all as specified and directed.Note:- (1) Safety measures will be fully responsibility of tenderer (2) During tree /branches/vegitation cutting any damages if occour on OH lines/installation should be reuniform is responsibility of the tenderer with out any extra cost.(3) Approximately distance covered both side for the HT lines/installatons not exc 100 mtr measured as a one Job only
Material and labour for paintng of 4 pole structure of any type/size/length and removing from existing pole painting by using wire brush and using with emary paper and cleaning with chemical agents after cleaning of steel tubular pole and GI brackets and cross arms in two coats of red oxide primer and two coats of silver oil painting upto smooth finishining and painting to satisfactorly by engr-in-charge and painting work carryout at any height and including marking of pole numers as directed and safety eqpts & tools will be own arrangement of tenderer and complete all as specified and directed.Note:- Cost of painting material is deemed to be included in quoted rate only.
All as per item No.70.00 but 2 pole structure and complete all as specified and directed
Material and labour for fault finding on 11 KV HT cables in trenches of any size and any length with fault detective(fault finding) machine by thumbing method and injection suitable high voltage proper fault finding equipment and all as testing device instructions and including necessary excavation,returning filling,removing surplus soil,sand, existing bricks etc where find the cable faulty complete all as directed by Engineer-in-charge.
Supply and fixing glow sign board made of sheeting having lighting arrangement of superior quality of size 5'x2' showing installation Nomenclature as approved marked all as specified and directed. Note: Installation line diagram to be enfaced will be approved by AGE E/M and no extra will be paid of any addition and alteration of words or marking of colours.
Material and labour for scraping of old paint of 33/11KV substation (02 Nos bay) steel structure posts by using emery/iron brush and painting with two coats of aluminium to complete 33/11KV substation including entire steel structure upto height of mtr,spray painting of 02 Nos 33/11KV,1.25MVA transformer as per existing incl aluminium painting of XPM jalli around transformer,spray painting to CT/PT units all as specified and directed Note:- Contractor has to take complete shut down and contractor shall not be provided working periods more than 02 Hrs/day
M/S SHREE KRISHANA ENERPRISES
Tawi Constructions
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .