Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹10.5 LAccepted-AOC 3RD FLOOR BHAKTAMAR RESIDENCY SOMNATHNAGAR ROAD PUNE 411014 | PUNE | PUNE | MAHARASHTRA | 411014 | L1 | Accepted-AOC LOWEST BID | |
| 2 | L2₹14.9 L+₹4.2 L (39.4%)Rejected-Finance SHOP NO 259 LOHOGAON ROAD KALWAD KHANDVE NAGAR PUNE 411032 | PUNE | MAHARASHTRA | 411032 | L2 | Rejected-Finance NOT A LOWEST BID |
Tender Value
₹15.6 L
EMD Value
₹31,100
Closing Date
1 Feb 2021, 6:00 pmClosed
GE MH RH KIRKEE
GE MH RH KIRKEE RANGE HILLS ROAD KIRKEE PUNE 411003
REPAIR MAINT INCL REPLACEMENT OF SPARES AND SERVICING OF DG SETS MEDICAL GAS MANIFOLD AND CONNECTED WORKS UNDER GE MH AND RH KIRKEE
2021_MES_411500_1
8177/E8
Open Tender
Civil Works
Item Rate
270 days
KIRKEE AND AUNDH
AS PER TENDER DOCUMENTS
6 documents required · 6 mandatory
₹500
Yes
GE MH RH KIRKEE
₹31,100
Yes
20 Feb 2021
11 Jan 2021
3 Feb 2021
11 Jan 2021
1 Feb 2021
25 Jan 2021
11 Jan 2021 - 18 Jan 2021
Amount
M & L for carrying out "B" check through authorised dealer/ OEM once in six month or 250 Hrs of run which ever is earlier by replacement of diesel filter assembly, bypass filter assembly complete with engine oil filters, air filters including necessary "O" rings, gaskets, packings etc complete and draining out unserviceable engine oil from sump, filling of new oil and checking the proper functiong of the lubrication and coolling system all as directed and as specified for the D.G.set of capacity 500 KVA, of Make : Kirloskar.(PH-I) Note:(a) The cost of Engine oil will be measured and paid seperately. (b) Any item or spare required not catered in schedule but required to carry out "B" check is deemed to be included in the quoted rate.
All as per item No 1 above but D.G.Set 500 KVA, Make :Greaves (PH-II)
All as per item No 1 above but D.G.Set 200 KVA, Make : Kirloskar.(Pump house, Aundh)
All as per item No 1 above but D.G.Set 125 KVA, Make : Greevs.(Pump House West side)
All as per item No 1 above but D.G.Set 125 KVA, Make : Kirlosker.(Fire fighting ,MH)
All as per item No 1 above but D.G.Set 75 KVA, Make : Kirloskar.(STP ,Aundh)
All as per item No 1 above but D.G.Set 62.5 KVA, Make : Kirloskar.( Old Power house,MH)
All as per item No 1 above but D.G.Set 50 KVA, Make : Kirloskar. ( Signal ,Aundh)
All as per item No 1 above but D.G.Set 40 KVA, Make : Kirloskar.(STP ,Aundh)
All as per item No 1 above but D.G.Set 25 KVA, Make : Kirloskar.(STP ,MAP)
All as per item No 1 above but D.G.Set 25 KVA, Make : Kirloskar.(Pump House,MAP)
Supply only of Engine oil suitable for above DG Set Makes all as directed and specfied.
Supply only coolant Additive 5 Lt Pack Part .No.123200198518 all as directed and specfied.
Supply and replace copper conductor of size 50 Sqmm PVC insulated all as specified and directed
Supply and replace battery terminal (copper) incl brazing with multistranded copper conductor all as specified and as directed.
Supply and replace ESU (Engine safety Unit) of 500KVA DG Set directed and specified.
M & L for repair/overhauling of self starter 24 Volts including replacement of carbon, bushes, rewinding of armature and field etc. and varnishing complete all as directed.
Material & labour for taking down the fuel injection pump of 500 KVA of DG set for service & calibration and checking the serviceability of FIP after fixing in position incl replacement of necessary minor parts all as directed
M&L servicing/ repair of dynamo including replacement of carbon brush, brush holders, bushes/bearings, varnishing, scaling etc., as required for above DG Set
M&L servicing/repair of water pump including replacement of repair kit.
Dismantling the leaking radiator from 500KVA DG set and transporting to the workshop for repair by means of gas welding / brazing the copper tubes and reassembleing the same at the authuroised workshop and back to the site and refxing in the engine and testing complete and all as directed
Disconnecting incoming and outgoing cable/busbar connections (as required), taking out the draw out type air circuit breaker of any make, from the cradle for overhauling & servicing through OEM of 3/4 pole, 415 volts, AC, current rating 630A-1600 A by carrying out the following all as specified and as directed. (a) Cleaning of dust, spider web, foreign particles etc. (b). Cleaning of various parts with CRC-2-26. (c). Replacement of damaged parts. (d). Checking, setting and adjusting the spring charging mechanism closing and tripping mechanism operation auxiliary switch contacts. (e) Checking of breaker operation in isolating / test and service position. Note :- 1. The contractor has to replace minor spares like spring washers, locking pin, circlip, spring, nut-bolts etc. 2. The servicing / overhauling of breaker is to be carried out at site. 3. Major spares required to be replace during servicing will be measured and paid under relevant item as specified in the schedule.
All as per item No 12 above but for current rating 2000-2500 A all as specified and as directed.
Supply and replace maintainence free battery of capacity 12V 180AH all as specified and as directed.
Supply and replace maintainence free battery of capacity 12V 200AH all as specified and as directed.
M & L for annual maintanance of AMF cum auto Synchronizing panel for 05 Nos X 500 KVA DG Sets (On call basis or as and when required) including detailed check up, rectification of fault & maintenance /calibration of relays, replacing relays, resistors, contactors etc. to be done for Main power control panel for five DG Set 500 KVA panel to keep the same functional all the time complete as directed.
Supply and replace Under volt Trip Device Part Nos. CS-AUH- V-A 240V AC for 800 A ACB of Make C&S
Supply and replace Under volt Trip Device Part Nos. CS-AUH- V-A 440V AC for 800 A ACB of Make C&S
Supply and replace shunt Trip coil Part Nos. CS-AUH- V-1 240V for 800 A ACB of Make C&S
Supply and replace Closing coil Part Nos. CS-AUH- S-1 240V for 800 A ACB of Make C&S
Supply and replace Spring closing Motor 240 V AC for 800-1200A ACB of Make C&S
Supply and replace Spring Charge Indicater SCIS-M for 800 A ACB of Make C&S
Supply and replace Mechnical Interlocking(D/O -Vertical/ Horizontal) system for 800 A ACB of Make C&S
Supply and replace Arc contacts ,6D-16D/08N-20N for 800 A ACB of Make C&S
Supply and replace triping indicating Switch TIS-1 for 800 A ACBof Make C&S
Supply and replace Main Moving Contact Assembly 16D/16N(AHA) for 800 A ACB of Make C&S
Supply and replace Under volt release (UVR) 220/415V AC Part Nos. SL92720BOOO/DOOO for 800-2500A ACB of Make L&T
Supply and replace Earth fault release Part Nos. SL91340OOO/ SL91341OOO for 800-2500 A ACB of Make L&T
Supply and replace shunt release(SR) 240/415V AC Part Nos. SL92718OBOO/SL92718ODOO for 800-2500 A ACB s of Make L&T
Supply and fix inciuding taking down Power contactor with dust cover of capacity 630 Amp TP,415V ,50Hz, Make C&S Cat part No. LC1FDP630A suitable for existing Panel
Supply and fix inciuding taking down Power contactor with dust cover of capacity 330 Amp TP,415V ,50Hz, Make C&S Cat part No. LC1FDP330A suitable for existing Panel
M&L for servicing of air cooled silenced reciprocating type oil free compressor having 57 cfm FAD (Fulled Air Delivery) capcity unit ( Make:Anest Iwata ) with replacement of recommended spares such as per manufacturers instruction /kit and replacement of compressor oil,air filter,r,oil filter,Beltetc and testing complete as directed by Engr-in-charge Model:FT 3500
M&L for servicing of twin type vaccum pump air cooled type having maximum working pressure 29 inch of Hg or 730 mm of Hg capcity .( Make:Ingersoll Rand ) with replacement of recommended spares such as per manufacturers instruction /kit and replacement of vaccum pump oil,air filter,oil filter,Belt,etc and testing complete as directed by Engr-in-charge Model:15V
M&L for servicing of Reciprocating type Air Compressor unit ( Make:Kirlosker ) with replacement of recommended spares such as per manufacturers instruction /kit and replacement of compressor oil,air filter,Belt,oil filter,etc and testing complete as directed by Engr-in-charge Model:TC-50
M&L for servicing of Air cooled Vacuum pump .( Make:Ingersoll Rand ) with replacement of recommended spares such as per manufacturers instruction /kit and replacement of vaccum pump oil,air filter,oil filter,Belt etc and testing complete as directed by Engr-in-charge Model:7V
M & L for taking out the Vacuum's/comppresor's motors and transporting to reputed work shop , dismantling the motor incl taking out old and U/S burnt winding wire & providing new winding wire of super enameled copper winding of suitable size including insulating materials, varnishing and drying and reassembling and transporting back to site and testing on commissioning all as directed for 15 HP, 3 Phase,440 Volt capacities of motors (make- Kirlosker).
All as per item No 46 but for motor of capacity 10 HP, 3 Phase,440 Volt (make- Kirlosker)
All as per item No 46 but for motor of capacity 7 HP, 3 Phase,440 Volt (make- Crompton Greaves)
S&F following ball bearing No - 6209ZZC3 suitable for Compressor /Vacuum pump motor etc removing of existing unserviceable bearing of any type or make all as specified and directed by Engr-in-charge. Make - SKF or equivalent model of Kirloskar/Tata.
All as per item No 49 but No -6309ZZC3
All as per item No 49 but No - 6208ZZ
All as per item No 49 but No - 6308ZZ
All as per item No 49 but No - 6309
All as per item No 49 but No - 6209
S&F in replacement , MCCB 250A, TP, 415V, 50 Hz 36 KA adjustable type
S&F in replacement , MCCB 125A, TP, 415V, 50 Hz, 25 KA adjustable type.
Supply and Fix in replacement of CTs of 100/5 current rating AC, 415 V, three phase including connecting to supply as per existing all as directed by Engr-in-Charge.
S&F in repair power contactor 3 pole with AC coil 50 Amps along with aux contacts 2NO & 2 NC for 3 phase star delta starter AC 440 V 5 0Hz MNX 32 make L& T /Siemens or equivelent make
S&F in repair power contactor 3 pole 25A with Aux contacts 01 NO & 1 NC .
All as per item No 59 above but 18A with Aux contacts 01 NO & 1 NC .
All as per item No 59 above but 12 A with Aux contacts 01 NO & 1 NC .
S& F in repair themal over load relay range 1 to 1.5 Amps make L& T /Siemens or equivelent make
S& F in repair themal over load relay range 9 to 15 Amps make L& T /Siemens or equivelent make
S& F in repair themal over load relay range 6 to 14 Amps make L& T /Siemens or equivelent make
S& F in repair themal over load relay range 14 to 22 Amps make L& T /Siemens or equivelent make
S & F electronic timer for 3 phase starter of rating 20 to 33 Amps make- Siemens or equivelent approved make
S& F single phase preventor relay SPPR type Sz5(6 wire) 415 V 50 Hz Make Siemens or equevelent approvd make
S&F in repairs phase indicator lamp R.Y.B colour LED type
S&F in repairs voltmeter square dial of range 0-500 volt
Rama Electricals
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .