Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹58,800Accepted-Finance | L1 | Accepted-Finance ACCEPTED | |
| 2 | L2₹60,000+₹1,200 (2.04%)Accepted-Finance | L2 | Accepted-Finance ACCEPTED | |
| 3 | L3₹62,000+₹3,200 (5.44%)Accepted-Finance | L3 | Accepted-Finance ACCEPTED | |
| 4 | Not Admitted-PreQual/Technical | - | Not Admitted-PreQual/Technical Not Complied with technical specification |
Tender Value
₹60,000
EMD Value
₹1,000
Closing Date
25 Apr 2025, 11:00 amClosed
EE ETD I KANPUR
EE ETD I KANPUR
Complete Overhauling and Repairing work of 132 KV Circuit Breaker of 40MVA Transformer at 132 KV Sub Station Dada Nagar Kanpur under ETD I Kanpur
2025_UPTCL_1027534_1
ET-01/ETD-I (K)/2025-26
Open Tender
Electrical Works
Fixed-rate
120 days
EE ETD I KANPUR
Please refer Tender documents.
3 documents required · 3 mandatory
₹590
PNB ACCOUNT 0746002100006255
₹1,000
29 Apr 2025
11 Apr 2025
25 Apr 2025
11 Apr 2025
25 Apr 2025
11 Apr 2025
Amount
Complete Overhauling & Repairing work of 132 KV Circuit Breaker of 40MVA T/F at 132 KV s/s Dada Nagar, Kanpur
Complete overhauling & repairing work of 132 KV circuit breaker of 40 MVA Transformer Bay including cleaning and lubrication of horizontal assembly, its various part, linkage bar pin and replacement of nuts & bolt, split pin wherever required opening and dismantling of control valve assembly, cleaning and lubrication replacement of cap seal assembly control valve seal O-ring and adjustment for necessary refixing of control valve assembly, opening and cleaning of closing spring shock absorber and reassemble after proper adjustment, checking of gas pressure switch air governor switch, air alarm and air lockout with proper adjustment and calibration, replacement of gas pipeline O-ring, checking and tighting of control wiring marshalling box, check and report of close and trip timing by digital timer. All consumable items cap seal assembly control valve seat, O-ring, P7 roller C&D are to be provided by Contractor. *After completion of overhauling of 132KV CB, the problems arising within six months will be rectified by the firm without any cost.
Refilling of SF6 Gas (12KG) with maintained rated gas pressure 7Kg/cm2 (at 20 Degree C.) in 132KV Circuit Breaker of CGL Make 40 MVA T/F Bay with required associated work to complete the job.
TAJ ENTERPRISES (BID ID -5144361)
M/S T R TRADERS (BID ID -5144623)
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .