Loading…
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹89.0 LAccepted-AOC 29 MODEL TOWN BEHIND GURUDWARA PATHANKOT | PATHANKOT | PATHANKOT | PUNJAB | 145001 | L1 | Accepted-AOC Due to L1 rate quoted | |
| 2 | L2₹89.5 L+₹56,808 (0.64%)Rejected-Finance B XXIII 56 A PREM NAGAR SAINGARGH PATHANKOT 145001 PUNJAB | PATHANKOT | PATHANKOT | PUNJAB | 145001 | L2 | Rejected-Finance Other than L1 rate quoted. | |
| 3 | L3₹89.7 L+₹75,974 (0.85%)Rejected-Finance | L3 | Rejected-Finance Other than L1 rate quoted. | |
| 4 | L4₹92.7 L+₹3.7 L (4.15%)Rejected-Finance 195 MAHESH NAGAR AMBALA CANTT 133001 | AMBALA | HARYANA | 133001 | L4 | Rejected-Finance Other than L1 rate quoted. | |
| 5 | L5₹1.0 Cr+₹13.6 L (15.3%)Rejected-Finance 11 GURU NANAK MARKET AMBALA ROAD SAHARANPUR 247001 | SAHARANPUR | UTTAR PRADESH | 247001 | L5 | Rejected-Finance Other than L1 rate quoted. |
| Sl No | Description | Qty | Unit | Raman Electric Trading Co L4 | SATISH AND CO L2 | kailu construction co L1 | Leo Air and Power Solution pvt Ltd. L6 | M/s Trade Linker Associates L3 | Rajan Traders L5 | Roy and Sons Infrastructures L7 |
|---|---|---|---|---|---|---|---|---|---|---|
| .10Note:- Please refer Sch 'A" notes on Srl Page No 14 to 17 on tender documents. | ||||||||||
| 1.00 | Supply, installation, testing and commissioing of HT Indoor VCB Panel 11 KV, 50 Hz, 3 phase min rupturing cap 350 MVA, indoor type totally enclosed metal clad switchgear with-drawable type with copper bus bar of suitable ratings complete with provision of 02 x vaccum circuit breakers (as incommer) having min rupturing capacity 350 MVA and 800 Amp rated horizontal isolation horizontal drawout type with over load and earth fault protection relays, ammeter, voltmeter, 08 x VCB (outgoing) having rupturing capacity 350 MVA and 630 Amps rated horizontal isolation horizontal drawout type, over Load, earth fault protection, ammeter and the 01 x VCBs as bus coupler but without over load and earth fault protection relays, ammeter, voltmeter and necessary provision for future expansion, incl all required mechanical and electrical works for testing and commossioning of 11 KV HT Panel, complete all as specified and directed. The switchgear panel shall be made up of CRCA steel sheet not less than 2.5 mm thick for load bearing section and not less than 2 mm thickness for non-load bearing duly powder coated and shall be IP-54 Protection (totally dust and vermin proof). The VCB panel shall consist of the following:-
(A) VCB:
(i) The metal clad indoor type VCB's shall be horizontal draw out and horizontal isolation type floor mounted manually and motor operated (230 V AC, 50 Hz) spring charged type for 3 pole simultaneous operation VCB of rating 800 A as incomer 2 Nos, 8 x VCBs shall be horizontal draw out and horizontal draw out and horizontal isolation type floor mounted manually and motor operated (230 V AC, 50 Hz) spring charged type for 3 pole simultaneous operation VCB of rating 630 A rating as outgoing VCB and 1 x 800 Amp rating VCB's shall be horizontal draw out and horizontal isolation type floor mounted manually and motor operated (230 V AC, 50 Hz) spring charged type for 3 pole simultaneous operation VCB of rating 800 A as bus coupler, 11 KV nominal voltage and rated voltage 12 KV. | 1 | Each Job | 80,00,000 ₹80,00,000 | 75,95,000 ₹75,95,000 | 75,50,000 ₹75,50,000 | 88,45,280 ₹88,45,280 | 75,25,000 ₹75,25,000 Lowest | 85,00,000 ₹85,00,000 | 1,16,60,000 ₹1,16,60,000 |
| 1.01(ii) The breakers shall be capable of making and breaking the short time current in accordance with the requirement of IEC 62271-200/IS 13118 (1991) or latest amendments thereof and shall have three phase rupturing capacity of minimum 25 KA for 1 second at 11 KV. (iii) Digital Ammeters with suitable size CT for RYB and Digital voltmeters including selector switch all as per latest IS. (iv) Arrangement of breakers bus bars main connections and aux wiring shall be as per IS- 375. (v) Aux. contactor 6 NO + 6 NC. (vi) Arcing contacts and bus bars shall be rated for min 25 KA for 1 Sec for 11 KV system. (vii) VCB shall have mechanical interlocking and safety shutters and isolating plug and sockets. (viii) VCB shall have feature of anti pumping relays. (ix) All control wiring shall not be less than 1.5 Sqmm copper FRLS and CT & PT wiring with 2.5 Sqmm copper FRLS for VCBs. (x) The VCB enclosure shall be type tested for E2/C2 /M2 class. (xi) Shunt Trip/close coils 220 V DC. (B) EPOXY RESIN CAST, 1-PH CT: Epoxy resin cast 1-PH CTs set of three as per IS-2705 (1992) -10 set of CTs (Two set of 2 x incomer VCBs and 8 sets for outgoing VCBs as per detailed specification given here under Makes of CTs: CGL/ABB/Siemens/Schenider. (i) Epoxy resin cast 1-Ph (set of three), CT 400-200/5-5-0.577A, CL-1/5P10, Burden-15 VA (for 02 Nos incoming VCB's). (ii) Epoxy resin cast 1-Ph (set of three), CT 200-100/5-5A, CL-1/5P10, Burden-15 VA (for all outgoing 8 VCB's). (C) EPOXY RESIN CAST, 3 PH PT: (i) Epoxy Resin Cast PTs : 3-Ph, Drop out type as per IS-3156 (1992) (Ratio: 11 KV/110 V, class-1, Burden-100 VA) -02 Nos for 2 x Incomer VCB. (D) METERS: (i) Digital Ampere Meter with selector Switch (For All VCB's). (ii) Digital Voltmeter Meter with selector Switch (For Incomer VCB's), Makes of Meters : L&T/Schenider/AE/Conserv. | ||||||||||
| 1.02(E) INDICATING LAMP LED TYPE: (i) Breaker On – Red. (ii) Auto trip indication – Amber. (iii) Breaker Off – Green. (iv) Trip Circuit healthy – Clear/white. (v) Spring Charged - Blue. (vi) R,Y,B indication. (F) RELAYS: (i) Incomer VCB's: Main Protection Relay shall be numerical Relay confirming to IEC- 61850 with microprocessor based protection scheme for tripping the breaker on various fault like (a) Directional over- current and Earth-fault protection, over voltage, under voltage, over current, the relay should have breaker failure protection, negative sequence, over current , broken conductor and inrush blocking functions communicable, non drawn out. IEC-61850- for incomer VCBs. (b) The main protection relays should be SCADA compatible with IEC 61850 Edition 2 on 2 Nos FO ports. (c) The relay should generate GOOSE massage as per IEC 61850 standard for interlocking and also interoperability with third party relays. (ii) Outgoing VCBs: Numerical relay should be communicable, Non Drawn out, IEC-61850 for all 08 x VCB’s with over current and earth fault protection, the relay should have breaker failure protection, negative sequence over current, broken conductor, under current and inrush blocking functions. The main protection relays should be SCADA compatible with IEC 61850 Edition 2 on 2 Nos FO ports. The relay should generate GOOSE massage as per IEC 61850 standard for interlocking and also interoperability with third party relays. (iii) Auxiliary relay for transformer (3 Elements) for outgoing VCB's. (iv) Master trip relay (for all incomer and outgoing VCB's). (v) Trip circuit supervision relay (for all incomer and outgoing VCB's). (vi) Power Pack for all VCB as per OEM recommendation. | ||||||||||
| 1.03NOTES:- (i) VCB's Panels should be manufactured, designed & supplied by OEM only. VCB Panels from the channel partners will not acceptable. (ii) All the main components Like VCB/Relays/vacuum interrupter should be of same manufacturer. (iii) VCBs should be Type Tested for E2/C2/M2 Class. All type test should be as per IEC 62271-100-2021. (iv) The VCB's shall be fitted on existing platform. Necessary modification/repair if any required as per recommendation of OEM is under scope of work and cost thereof is deemed to be included in quoted rates by the contractor. (v) All parts and accessories, fittings necessary for efficient operation of 11 KV VCB's shall be deemed to be within the scope of specification weather mentioned or not specifically mentioned herein. (vi) Pre-dispatch inspection shall be carried out by nominated rep of Accepting Officer. The arrangement for pre dispatch factory inspection & testing of VCB's will be responsibility of the contractor & cost thereof is deemed to be including in quoted rate. (vii) Make & drawings of VCBs shall be approved by the CWE. (viii) Pre-commissioning shall be carried out by SEI HQ CEWC within overall cost quoted. (ix) Defect liability period shall be of 2 years after entire completion of work. Make:- CG Power and Industrial Solutions Limited, ABB or equivalent. | ||||||||||
| 2.00 | Material and labour for dismantling of existing set of VCBs/Bus coupler (11 Nos) including disconnecting of existing HT cables from bus bar/VCBs and shifting to MES store yard, complete all as specified and directed. | 1 | Each Job | 7,000 ₹7,000 Lowest | 49,867 ₹49,867 | 25,000 ₹25,000 | 50,000 ₹50,000 | 50,000 ₹50,000 | 50,000 ₹50,000 | 10,000 ₹10,000 |
| 3.00 | Supply and fixing Battery Charger of size 220 Volt DC/30 A, float cum boost charger with Voltmeter, Ammeter and indicators complete with following specification:-
(a) Constant current Constant Voltage (CCCV).
(b) Powder Coated Metal enclosure.
(c) Rated Input Volts - 415 V AC.
(d) Rated Output Volt - 220 V DC ± 1%
(e) The system should have the following protections:
(i) Alarm on fuse blowing.
(ii) Short circuit.
(iii) Battery reverse indication.
(iv) MCB protection.
(f) The output Voltage regulation to be better than 1% and load regulation better than 2%. Make: Sinetrac/Amara Raja/Exide/Statcon. | 1 | Each Set | 3,07,000 ₹3,07,000 | 3,20,000 ₹3,20,000 | 3,50,000 ₹3,50,000 | 4,24,210 ₹4,24,210 | 2,00,000 ₹2,00,000 | 1,50,000 ₹1,50,000 Lowest | 2,75,000 ₹2,75,000 |
| 4.00 | Supply and fixing Battery Bank consisting of 110 Nos of Sealed maintenance free batteries each of 2 volts, 120 Ah connected in series with single core Copper wire and terminals and cabinet, complete all as specified and directed. Make:- Exide/Amara Raja/HBL. | 1 | Each Job | 4,15,000 ₹4,15,000 | 4,15,000 ₹4,15,000 | 4,50,000 ₹4,50,000 | 4,00,964 ₹4,00,964 | 4,85,000 ₹4,85,000 | 3,00,000 ₹3,00,000 Lowest | 5,50,000 ₹5,50,000 |
| 5.00 | Supply, laying, jointing and testing cable HT XLPE cable cross sectional area 185 Sqmm, 3 core, 11000 V screened suitable for earthed system PVC insulated bedded, galvanized steel (heavy duty) strip or wire armoured with stranded aluminium conductor 11 KV (Earthed) conforming to IS 7098 (Part-I) 1977 and Part-II of 1985 laid in pipes/ducts/trenches, under floor and roads or fixed to wall etc incl any type, complete all as specified and directed.
Note:- A BOO shall be conveyed by the CWE FZR to check the actual requirement of HT cable on ground and old serviceable/unserviceable cable deposit to MES store yard. Rate is included in quoted rate. | 250 | RM | 1,560 ₹3,90,000 | 1,475 ₹3,68,750 | 1,350 ₹3,37,500 Lowest | 1,528 ₹3,82,000 | 1,880 ₹4,70,000 | 3,500 ₹8,75,000 | 1,540 ₹3,85,000 |
| 6.00 | Excavation in trenches in soft/loose soil not exceeding 1.5 meter wide and not exceeding 1.5 meter deep for laying of cable, pole foundation, etc including taking out old brick cable protection cover and getting out forming bottom surface to required gradient, complete all as specified and directed. | 86 | Cum | 100 ₹8,600 Lowest | 180 ₹15,480 | 130 ₹11,180 | 250 ₹21,500 | 200 ₹17,200 | 300 ₹25,800 | 250 ₹21,500 |
Tender Value
₹1.3 Cr
EMD Value
₹2.1 L
Closing Date
7 Jul 2025, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Chief Engineer Jalandhar Zone Jalandhar Cantt
HQ Chief Engineer Jalandhar Zone Jalandhar Cantt
Provn of conversion of old vintage outdated VCBs at 66 KV MES and connected items under GE (East) Ferozepur
2025_MES_711933_1
81082/E8
Open Tender
Electrical and Maintenance Works
Item Rate
365 days
Jalandhar Cantt
As per NIT
9 documents required · 9 mandatory
₹1,000
Garrison Engineer (East) Ferozepur Cantt
₹2.1 L
Yes
2 Sept 2025
2 Jun 2025
15 Jul 2025
2 Jun 2025
7 Jul 2025
23 Jun 2025
Amount
Note:- Please refer Sch 'A" notes on Srl Page No 14 to 17 on tender documents.
Supply, installation, testing and commissioing of HT Indoor VCB Panel 11 KV, 50 Hz, 3 phase min rupturing cap 350 MVA, indoor type totally enclosed metal clad switchgear with-drawable type with copper bus bar of suitable ratings complete with provision of 02 x vaccum circuit breakers (as incommer) having min rupturing capacity 350 MVA and 800 Amp rated horizontal isolation horizontal drawout type with over load and earth fault protection relays, ammeter, voltmeter, 08 x VCB (outgoing) having rupturing capacity 350 MVA and 630 Amps rated horizontal isolation horizontal drawout type, over Load, earth fault protection, ammeter and the 01 x VCBs as bus coupler but without over load and earth fault protection relays, ammeter, voltmeter and necessary provision for future expansion, incl all required mechanical and electrical works for testing and commossioning of 11 KV HT Panel, complete all as specified and directed. The switchgear panel shall be made up of CRCA steel sheet not less than 2.5 mm thick for load bearing section and not less than 2 mm thickness for non-load bearing duly powder coated and shall be IP-54 Protection (totally dust and vermin proof). The VCB panel shall consist of the following:- (A) VCB: (i) The metal clad indoor type VCB's shall be horizontal draw out and horizontal isolation type floor mounted manually and motor operated (230 V AC, 50 Hz) spring charged type for 3 pole simultaneous operation VCB of rating 800 A as incomer 2 Nos, 8 x VCBs shall be horizontal draw out and horizontal draw out and horizontal isolation type floor mounted manually and motor operated (230 V AC, 50 Hz) spring charged type for 3 pole simultaneous operation VCB of rating 630 A rating as outgoing VCB and 1 x 800 Amp rating VCB's shall be horizontal draw out and horizontal isolation type floor mounted manually and motor operated (230 V AC, 50 Hz) spring charged type for 3 pole simultaneous operation VCB of rating 800 A as bus coupler, 11 KV nominal voltage and rated voltage 12 KV.
(E) INDICATING LAMP LED TYPE: (i) Breaker On – Red. (ii) Auto trip indication – Amber. (iii) Breaker Off – Green. (iv) Trip Circuit healthy – Clear/white. (v) Spring Charged - Blue. (vi) R,Y,B indication. (F) RELAYS: (i) Incomer VCB's: Main Protection Relay shall be numerical Relay confirming to IEC- 61850 with microprocessor based protection scheme for tripping the breaker on various fault like (a) Directional over- current and Earth-fault protection, over voltage, under voltage, over current, the relay should have breaker failure protection, negative sequence, over current , broken conductor and inrush blocking functions communicable, non drawn out. IEC-61850- for incomer VCBs. (b) The main protection relays should be SCADA compatible with IEC 61850 Edition 2 on 2 Nos FO ports. (c) The relay should generate GOOSE massage as per IEC 61850 standard for interlocking and also interoperability with third party relays. (ii) Outgoing VCBs: Numerical relay should be communicable, Non Drawn out, IEC-61850 for all 08 x VCB’s with over current and earth fault protection, the relay should have breaker failure protection, negative sequence over current, broken conductor, under current and inrush blocking functions. The main protection relays should be SCADA compatible with IEC 61850 Edition 2 on 2 Nos FO ports. The relay should generate GOOSE massage as per IEC 61850 standard for interlocking and also interoperability with third party relays. (iii) Auxiliary relay for transformer (3 Elements) for outgoing VCB's. (iv) Master trip relay (for all incomer and outgoing VCB's). (v) Trip circuit supervision relay (for all incomer and outgoing VCB's). (vi) Power Pack for all VCB as per OEM recommendation.
NOTES:- (i) VCB's Panels should be manufactured, designed & supplied by OEM only. VCB Panels from the channel partners will not acceptable. (ii) All the main components Like VCB/Relays/vacuum interrupter should be of same manufacturer. (iii) VCBs should be Type Tested for E2/C2/M2 Class. All type test should be as per IEC 62271-100-2021. (iv) The VCB's shall be fitted on existing platform. Necessary modification/repair if any required as per recommendation of OEM is under scope of work and cost thereof is deemed to be included in quoted rates by the contractor. (v) All parts and accessories, fittings necessary for efficient operation of 11 KV VCB's shall be deemed to be within the scope of specification weather mentioned or not specifically mentioned herein. (vi) Pre-dispatch inspection shall be carried out by nominated rep of Accepting Officer. The arrangement for pre dispatch factory inspection & testing of VCB's will be responsibility of the contractor & cost thereof is deemed to be including in quoted rate. (vii) Make & drawings of VCBs shall be approved by the CWE. (viii) Pre-commissioning shall be carried out by SEI HQ CEWC within overall cost quoted. (ix) Defect liability period shall be of 2 years after entire completion of work. Make:- CG Power and Industrial Solutions Limited, ABB or equivalent.
Material and labour for dismantling of existing set of VCBs/Bus coupler (11 Nos) including disconnecting of existing HT cables from bus bar/VCBs and shifting to MES store yard, complete all as specified and directed.
Supply and fixing Battery Charger of size 220 Volt DC/30 A, float cum boost charger with Voltmeter, Ammeter and indicators complete with following specification:- (a) Constant current Constant Voltage (CCCV). (b) Powder Coated Metal enclosure. (c) Rated Input Volts - 415 V AC. (d) Rated Output Volt - 220 V DC ± 1% (e) The system should have the following protections: (i) Alarm on fuse blowing. (ii) Short circuit. (iii) Battery reverse indication. (iv) MCB protection. (f) The output Voltage regulation to be better than 1% and load regulation better than 2%. Make: Sinetrac/Amara Raja/Exide/Statcon.
Supply and fixing Battery Bank consisting of 110 Nos of Sealed maintenance free batteries each of 2 volts, 120 Ah connected in series with single core Copper wire and terminals and cabinet, complete all as specified and directed. Make:- Exide/Amara Raja/HBL.
Supply, laying, jointing and testing cable HT XLPE cable cross sectional area 185 Sqmm, 3 core, 11000 V screened suitable for earthed system PVC insulated bedded, galvanized steel (heavy duty) strip or wire armoured with stranded aluminium conductor 11 KV (Earthed) conforming to IS 7098 (Part-I) 1977 and Part-II of 1985 laid in pipes/ducts/trenches, under floor and roads or fixed to wall etc incl any type, complete all as specified and directed. Note:- A BOO shall be conveyed by the CWE FZR to check the actual requirement of HT cable on ground and old serviceable/unserviceable cable deposit to MES store yard. Rate is included in quoted rate.
Excavation in trenches in soft/loose soil not exceeding 1.5 meter wide and not exceeding 1.5 meter deep for laying of cable, pole foundation, etc including taking out old brick cable protection cover and getting out forming bottom surface to required gradient, complete all as specified and directed.
Returning, filling in, earth including spreading, leveling watering and well ramming in layers each not exceeding 25cm thick each layer, complete all as specified and directed.
Removal of surplus soil to a distance not exc. 50 meter and depositing where directed at a level not exc. 1.5 meter above the starting point, complete all as specified and directed.
Material and labour for Precast reinforced cement concrete cable cover factory made class HV, type-I, flat, size 300mm x 180mm x 40mm for HT cable ISI marked, laid flat across the cable, complete all as specified and directed.
Material and labour for sand cushioning using river fine sand for the underground cables in trenches/ existing cable trenches, in layers of 8 cm thickness before laying the cable and 15 cm thickness after laying and stretching cable punned down to 10 cm complete all as specified and directed. Note:- Only punned thickness shall be measured for purpose of payment.
Material and labour for Cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminum conductor cable of size 185 Sqmm, complete all as specified and directed.
Earthing complete with galvanized mild steel earth plate electrode size 600mm x 600mm x 6mm thick buried directly in ground (Preferably in vertical position) earth pit not less than 2.25 metre below normal ground level with top edge of the earth plate not less 1.5 metre (BGL) connected to galvanized iron earth strip 32 x6 mm by means of bolts, nuts, check nut and washer of galvanized iron including Cement concrete chamber of PCC (1:3:6) type C-2 using 40 mm graded stone aggeregate, precast RCC cover with suitable handle, excavation and earth work in any type of soil, 15 mm bore “Light grade” galvanized iron water tubing fixed with cast iron funnel and wire mesh and 40 mm bore “light grade” galvanized iron protection pipe for earth strip 32 x6 mm upto 7.5 m length, charcoal, common salt, connected to test point and testing on completion, complete all as specified and directed. Note:- On getting unsatisfactory result of earthing should be redone by the contractor without no extra payment.
Material and labour for earthing connected to gavanised earth strip 32 x 6 mm size by means of nut bolts, check nuts and washers of gavanised iron or steel, complete all as specified and directed.
SATISH AND CO (BID ID -3341536)
M/s Trade Linker Associates (BID ID -3350476)
Raman Electric Trading Co (BID ID -3340382)
Rajan Traders (BID ID -3350640)
Leo Air and Power Solution pvt Ltd. (BID ID -3349614)
Roy and Sons Infrastructures (BID ID -3350567)
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .