| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹13.5 LAccepted-AOC AZAD COLONY B 90 FEET ROAD SOURA SRINAGAR J K 190011 | SRINAGAR | SRINAGAR | JAMMU AND KASHMIR | 190011 | L1 | Accepted-AOC Being L1 | |
| 2 | L2₹15.2 L+₹1.6 L (12.0%)Rejected-Finance 184 TENGPUNA PULWAMA PULWAMA PULWAMA JAMMU KASHMIR 192301 UDYAM JK 15 0009999 | PULWAMA | JAMMU AND KASHMIR | 192301 | L2 | Rejected-Finance Other than L1 | |
| 3 | L3₹15.4 L+₹1.8 L (13.4%)Rejected-Finance | L3 | Rejected-Finance Other than L1 | |
| 4 | L4₹15.5 L+₹1.9 L (14.1%)Rejected-Finance KOIL KOIL PULWAMA PULWAMA JAMMU KASHMIR 192301 | PULWAMA | JAMMU AND KASHMIR | 192301 | L4 | Rejected-Finance Other than L1 | |
| 5 | L5₹16.7 L+₹3.1 L (23.1%)Rejected-Finance 55 SHALL TOKUNA JANGALNAD PULWAMA PULWAMA JAMMU KASHMIR 192301 | PULWAMA | JAMMU AND KASHMIR | 192301 | L5 | Rejected-Finance Other than L1 |
Tender Value
₹17.9 L
EMD Value
₹35,860
Closing Date
14 Feb 2023, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
GE (AF) AWANTIPUR
GE (AF) AWANTIPUR, 8 FBSU, AF AWANTIPUR
PROVISION OF TAMPER PROOF METERS IN CERTAIN OMQ/SMQs AND SPLIT AC AT GDCC AT 8FBSU
2023_MES_575445_1
GE (AF) AWA-39/2022-23
Open Tender
Civil Works
Item Rate
180 days
GE (AF) AWANTIPUR
AS PER NIT AND TENDER DOCUMENTS
8 documents required · 8 mandatory
₹500
GE (AF) AWANTIPUR
₹35,860
Yes
29 Apr 2023
17 Jan 2023
16 Feb 2023
17 Jan 2023
14 Feb 2023
1 Feb 2023
Amount
S & F electronic meters temper proof LCD display with polycarbonate cover 230 V ,10-60 Amp, accuracy class-I 50 Hz , conforming to IS: 13779, IP-54 with parameters to show data, time, current reading,load,PF,voltage and kWH, complete all as specified and directed. MAKE: HPL,L&T, Elmeasure.
S & F electronic meters temper proof LCD display with polycarbonate cover 415 V 3Phase 4 wire ,10-60 Amp, accuracy class-I 50 Hz , conforming to IS: 13779, IP-54 with parameters to show data, time, current reading,load,PF,voltage and kWH, complete all as specified and directed. MAKE: HPL, L&T, Elmeasure.
S & F in repairs, installation, commissioning and testing IP 65 Thermoplastic PC Polycarbonate weatherproof Meter Box for Provision of 3 Nos Meter with multi level knockouts for cable glands in different sizes. The Meter Box Mini. Size 300 x 600 x 170. The Meter Box with Bakelite sheet at the bottom of Meters and The Meter Box pre-moulded knockouts shall be available on top and bottom of the Meter box to enable cable entries from both direction. Front Door totally Transparant for vision of Meter Reading. The Meter box shall have an grooved cable entry with breakable metal seals at the bottom of the box via pre-moulded knockout to enable Wall mounting Type . Lid fasteners will be tool operated it will be sealable with accessories. The Meter box shall have elongated holes inside them for wall mounting provision. In the event of formation of condensed water, the meter box shall have a minimum of two condensation knock-outs inside to ensure optimum safe performance. The Meter box shall fulfill the following standards Weatherproof : Rainwater proof, temperature resistant. IEC 60670-22 : Particular requirements for connecting boxes and enclosures. The Meter Box Should withstand glow wire test at 960C in accordance with IEC 60 695-2-11 UL subject 94, should be flame retardant and self-extinguishing in nature, so that fire should not be spread all over in the event of fire due to short circuit. . IEC 60529 : IP 65 degree of protection. UV Resistant in accordance with IEC 61 439-1, Clause no 8.4.4. Degree of protection against mechanical load IK 08 (5 Joule) ) in accordance with accordance with EN IEC 62262 Make- Hensel/Rittal/Emitter/Schneider/ABB.
S&F sheet metal enclosure double door type for DBs ( when MCB to be used) 8 way 240 volts with 200 Amps rated busbar and neutral link. Make- Legrand/ Havells/ L&T/ ABB
S&F sheet metal enclosure double door type for DBs ( when MCB to be used) 4 way TPN 415 volts with 200 Amps rated busbar and neutral link. Make- Legrand/ Havells/ L&T/ ABB
MCB SP, 5-32 Amps, 230 volts, 10 kA rupturing capacity, 'C' curve type, complete all as specified and directed.
MCB " C" series single pole & neutral, 240 V 16 to 32 Amps all as specified.
S & F MCB " C" series single pole & neutral, 240 V 40 Amps breaking capacity 10 kA Amps all as specified. Make- Legrand/ Havells/ L&T/ ABB
S & F MCB " C" series TPN 63 Amps, 415 V all as specified. Make- Legrand/ Havells/ L&T/ ABB
Submain wiring with PVC insulated unsheathed copper conductor cable, multi stranded, single core, FRLS type, 1100 volts grade 2 x 6sqmm complete drawn in and including casing caping ISI marked of suitable size and its accessories along with 1x 6sqmm PVC insulated unsheathed copper conductor cable, multi stranded for continuous earth wire including making good the disturbed surface, complete all as specified and directed. Note :- 2 +1 run of 6Sqmm cable including casing caping of suitable size shall be measured as one running metre.
Earthing complete with galvanized mild steel plate electrode 60 cm x 60 cm x 6 mm thick buried directly in ground vertically (in earth pit not less than 2.25 meter deep below ground level) with the top edge of earth plate at a depth not less than 1.5 meter below normal ground level, the earth electrode surrounded by adequate quantity of charcoal dust and salt to a packed thickness of 15 cm on all sides and including GI wire 4mm dia bolted (with GI nuts, bolts & check nuts) and riveted to earth (Plate) electrode at one end and connected to main switch board /panel/ test point at the other including watering GI pipe (medium grade) 20mm bore from bottom of earth pit to top of electrode and 20mm GI pipe light grade for earth wire protection complete with earth pit inplain cement concrete (1:2:4), type B0 using 12.5mm graded crushed stone aggregate with 40 mm thick cover of reinforced cement concrete (1:2:4) , type B-I , using 20 mm graded crushed stone aggregate, reinforced with XPM weight not less than 4 Kg /Sqm and 6mm dia bar handle ,excavation and earth work in any type of soil, returning filling in and removal of surplus soil including testing including testing on completion, complete all as specified and and shown in electrical plate No 3 of MES Schedule 2009 Part-I, and as directed . Note:- AFTER COMPLETION OF EARTHING, IF DESIRED RESISTANCE IS NOT OBTAINED, THE EARTHING WILL BE RE DONE BY CONTRACTOR AT HIS OWN RISK AND COST TO ENTIRE SATISFACTION OF ENGINEER-IN-CHARGE. Note: Satisfactory test report of earthing work shall be produced by the contractor duly signed by Engineer-in-charge and Garrison Engineer alongwith the RAR/ final bill. No payment of earthing work shall be realeased without satisfactory test report produced by the contractor.
Supply and install hi wall split type Air Conditioner inverter type units indoor/outdoor unit complete with heating and cooling function with cordless remote control unit and with in built air ioniser and Plasma filter for better air quality with 4 star rating of capacity 1.5 TR split unit air conditioner electric driven single phase copper condensor complete all as specified and directed. Make-Hitachi/Carrier/Bluestar
Supply and fix copper tubing 1/4 inches dia suitable for AC ducting complete with brazing and jointing complete all as specified and directed.
Supply and fix copper tubing 1/2 inches dia suitable for AC ducting complete with brazing and jointing complete all as specified and directed.
Supply and fix PVC rigid drain pipe 20 mm dia along with connecting accessories and fixing saddle at every 1 m complete all as specified and directed.
Supply and fix copper cable 4 sqmm 3 core with necessary bottle lugs and connecting complete all as specified and directed.
M&L sub main wiring with multistranded FRLS copper conductor cable PVC sheathed in and including PVC casing caping with two runs of 4.0 Sqmm and 4.0 Sqmm FRLS copper conductor as earth wire and connected to earth dolly all as specified and as directed. Make -cable- Finolex/Havells/Kallinga/Polycab.
Supply & fix Voltage Stabilizer 4 KVA capacity , copper wound suitable for input voltage 120 V to 280 V & output voltage stabilized 220 V , copper wound single phase 50 Hz along with time delay relay along with LCD display complete with all mounting accessories and as specified and as directed. Make- Volina/ V guard/Premium/Voltamp/sinetrac
M/S BASHIR AHMAD AND SONS
M/S ABDUL RASHID AND CO
M/s Gh Qadir and Sons
M/S SHABIR AHMAD SHAH AND CO
M/S LEO TRADERS
ORISON ENTERPRISES
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .