220 KV S/S Campus Majhola Moradabad
For Increasing Capacity of 33 11 KV S S UmaerpurMeera District Bijnor from 2x5 MVA to 10 plus 5 MVA under the business plan scheme 2021-22 IN THE JURISDICTION OF EC WD, MBD UNDER EC WC-II MEERUT (PVVNL).
2021_PVVNL_661830_1
11/ECWD(M)/2021-22
Open Tender
Electrical Works
Fixed-rate
30 days
BIJNOR
Please refer Tender documents.
2 documents required · 2 mandatory
₹1,180
EE ECWD MBD
₹5,000
1 Jan 2022
22 Dec 2021
31 Dec 2021
22 Dec 2021
30 Dec 2021
22 Dec 2021
90 days
Safe carriage of following stock material, from Store Center of PPVNL to site of 33/11KV S/S Umarpur Meera (Bijnor). (Distance approx.- 150Kms.):for Item No. 1.01 to 1.03 1.01 – Switchyard items and other materials, such as Isolator Structure, Jointing Kit, control cable, M.S round, 11KV TPMO, 11KV Disc Insulator, 11KV Disc Fitting, 11KV Pin insulator, 11KV fuse set, Stay complete, M.S earthing rod, M.S angle, M.S channel, G.I, wire , M.S angle 65x65x6mm, M.S channel 100x50, Control cable, Post insulator etc.
S.T.Poles-11M.long
11KV Alumn. Cable XLPE- 3x300/3x185Sq.mm
2. Safe carriage of following stock material, from Store Center of PPVNL to site of 33/11KV S/S Umarpur Meera (Bijnor). (Distance approx.- 150Kms.): for Item No.2.01 to 2.05 2.01 – 11KV O/G Switchgear
33KV Control pannel for Single feeder
33KV Control pannel for double T/F
33KV CT outdoor 200/100/1Amp.
33KV Line Isolator
Providing &laying of G.I.Strip of size 50x6mm for connecting the earthmat with each equipment (Post Insulators, T/F Body & its neutral and M.S.Frame of Cabe Supporting Structure), various steel structures. The work also includes cutting, bending, straightening, over laping and welding the earth strip with earth mat and by using high quality arc welding in already digged trenches, as per PVVNL guidline. as per site requirement.
Making earthing of all 11KV Switchgears, other equipments on both earth terminal inside the control room by providing G.I.Strip in size 50x6mm. with 32mm. dia M.S.Round laid in trench with proper electric welding, as per PVVNL guidline.
Boring and lowering by providing of G.I.Pipe size 40mm dia, into the ground upto water level or minimum 20Mtr, which ever is more, with the lower end of solid copper cone Approx 224mm long and 750gm in weight shall be provided and screwed in pipe as well as bringing out a continuous copper wire 6 SWG, from the cone upto the ground surface where it will be bolted to the G.I. Strip for Transformer neutral connection, the G.I.Strip will be connected to star point through providing Copper Bond Strip of size-35x6mm, as per PVVNL guidline.
Nutral Link Structure for Power T/F, As per RESSPO, as follows: Fabrication of structure, including cutting, straightening, drilling of holes and electric welding, as per Drawing., Excavation of earth, Grouting with C.C. in ratio 1:4:8
Mounting & fixing of following outdoor equipments, on single Bay, by providing Bolt, Nuts &Washers. As per Respo norms & PVVNL guidline.for Item No.7.01 to 7.03 7.01– 33KV C.T 200/100/1A
Fixing & installation 33KV Post insulator for fuse set. As per PVVNL guidline & site requirement
Fixing & installation 33KV line Isolator. As per PVVNL guidline & site requirement.
Erection of 1No. 1No. O/G Switchgears, in alignment, in Control Room, including safe shifting, from Dump Place. Making 4No. Pockets for each and providing/fixing of Reg Bolt by CC in ratio 1:2:4, with tightening also.
Commissioning & fixing of Bus bar (Copper), between each Switchgear, by bolt, nut & washers and HT compound and providing & tapping HT Tape, Empire Tape & PVC Tape, on each joint & Bus Coupler connect which existing Bus-bar (it extra fitting requirement than provided by the contractor)
Safety/Dragging/lifting of 33/11KV, 10MVA T/F on Plinth from the unloaded place.
Erection of 33/11KV, 10MVA Power T/F on Plinth, by fixing all accessories, like Radiators, Conservator Tank, Filling the T/F Oil to desired level and ensuring that there is no leakage, complete job in all respect. As per PVVNL guidline.
Erection of Double Pole Structure on STP 11M.long, with fabrication of all accessories, such as Channel/Angle. Fixing of all accessories on Double Pole, by providing &fixing M.S.Clamp with Bolt,Nut&Washers. Earthing to be provided on each supports by driving M.S.Earthing Rod and connecting between Rod &Supports, by providing, G.I wire of 6 SWG as per RESPO Norms. as per RESPO Norms.
Grouting of STP 11M. long, with CC in ratio 1:4:8, complete in all respect, as per RESPO Norms.
Erection of Stay Set-16x1800mm. on Double Pole, including digging of pits of size-0.75x0.75x1.5M. Grouting in CC ratio 1:4:8 Cement, Sand & Stone Shingle. Binding and nozelling of Stay Wire, complete in all respect, by providing & fixing of Stay Clamp, as per RESPO Norms.
Digging of Trench of size 0.45x0.6M., for laying of 11KV Cable for incoming/outgoing feeder and T/F. As per respo norms & site requirement.
Laying of 11KV XLPE 3x300/3x185Sq.mm. Alumn.Cable in the Trench, for T/F and Feeders, from Control Room. As per PVVNL guidline & actual site conditions. As per respo norms & site requirement.
providing & laying of Ist Class Bricks on both sides and on Top of the Cable. Filling the Sand, inside the Bricks and refilling of loose earth in the Trench. As per PVVNL guidline & actual site conditions.
Making of joints by 11KV (3x300Sq.mm) Heat Shrink type Jointing Kits, Indoor/Outdoor type, providing & fixing of Alumn. Lugs of proper size, by crimping on each phase of the Cable at both ends. As per PVVNL guidelines.
Making of joints by 11KV (3x185Sq.mm) Heat Shrink type Jointing Kits, Indoor/Outdoor type, providing & fixing of Alumn. Lugs of proper size, by crimping on each phase of the Cable at both ends.
Fixing of Cable Box on 10MVA T/F, 11KV Switchgears, by Bolt & Nuts and tapping the joints by providing HT/Empire/PVC Tape and Copper Strip of size 50x6mm., 75mm.long, including proper tapping.
Mounting of 11KV Cable boxes on Double Pole, by providing & fixing of M.S.Clamp, made of 65x6mm. M.S.Flat, with Bolts,Nuts & Washers, including providing & fixing 3mm. thick 100mm. dia G.I.Pipe-3M.long, with pipe supporting Clamp-2No. on each, made of 65x6mm M.S.Flat.
Repairing of VCB, CT, Lightening arrerstor, plints & foundation as per PVVNL guidelines.
Laying of Control Cable in Packka Trench, from all VCB/CTs/T/F to 33KV Control Panel and making connection for operation & protection of equipments, by using ferrules including commissioning battery charger with battery by providing copper lead with lugs & dressing of Control Cable and making arrangement for testing in the equipments.
Erection of 01 No. 33KV T/F control pannel & 33KV feeder control pannel in alignment in control room, including sage shifting from dump place, making 04 No. pockets for each and providing/fixing of Reg. bolt byee in ratio 1:2:4 with tightining also.
Assembling and installation of the cabinet of 24 volt battery and battery charger including grouting of foundation bolt as per manufacturer drawing in control room including safe shifting. The electric connection between battery and battery charger with flexible copper lead of size 7/20SWG shall be done properly. The work including wireing upto control pannels, testing & commisnoning in al respect as per pvvnl guidline.
Providing & fixing 1 No. MCB Box 63amp. TPN and 03 No. 32 Amp. SPN box and power plug on wall and it is proper grouting including it is connection with A/C supply by providing proper size of connection wire.
Shifting of removal of protecton board in control room and same will be erected on appropriate location of control room for create space for erection of 11KV VCB outgoing as per PVVNL guidline
Safe dixmantalling of 03 No. CTs defective and line isolator of Bus bar No. 01 and kept on sage place of control rooms as per PVVNL guidline.
Painting of the following structure with one coat of ready mixed primer and two coats of ISI Mark Alumn. Paint after rubbing with sand paper to the surface of the structure includidng labour and T&P complete in all respect.:for Item No.29.01 tp 29.06 29.01 – Line Isolator Structure
Fuse Set Structure
Post Insulator, L.A.Structure
V.C.B.Structure, C.T.Structure
M.S.Frame for Cable
11KV Double Pole Structure on SP-55 STP
Draining of oil from conservator, radiators of existing 5MVA T/F, at 33/11KV S/S Tisotra (Bijnor), into the dry & clean drums and staking at the safe place at 33/11KV S/S Tisotra (Bijnor),
Dismantling of conservator, radiators and other accessories from existing 5MVA Transformer.
Shifting of 5MVA Transformer main body and other accessories from the substation switchyard to outside the switchyard.
Hiring of D/G Set, including carriage, loading, unloading & operating charges (with fuel) at 33/11KV Substation, :for Item No.33.01 to 33.02 33.01 – 20 KVA, 3 Phase D/G Set for testing of equipments installed at Sub-station.
5 KVA, Single Phase D/G Set for testing of equipments installed at Sub-station.
Providing required No. of Technicians to work on power T/F, HT/LT Panels, during testing as assisting technical hands of test team during commissioning & energisation.
M/S TRACKERS CONSTRUCTION
M/S SARLOK SERVICES
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .