Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹33.7 LAccepted-AOC | ₹33.7 L | L1 | Accepted-AOC BEING LOWEST BIDDER |
| 2 | L2₹35.0 LRejected-AOC SHIV BARI ROAD NEAR KASUMAL HOTEL BIKANER 334003 RAJASTHAN | BIKANER | BIKANER | RAJASTHAN | 334003 | ₹35.0 L | L2 | Rejected-AOC OTHER THAN LOWEST BIDDER |
| 3 | L3₹37.3 LRejected-AOC | ₹37.3 L | L3 | Rejected-AOC OTHER THAN LOWEST BIDDER |
| 4 | L4₹38.0 LRejected-AOC | ₹38.0 L | L4 | Rejected-AOC OTHER THAN LOWEST BIDDER |
| 5 | L5₹40.4 LRejected-AOC | ₹40.4 L | L5 | Rejected-AOC OTHER THAN LOWEST BIDDER |
| Sl No | Description | Qty | Unit | MAJOR REFREGERATION AND ELECTRICALS L1 | M/s Rohit Construction Co. L2 | BANSAL BROTHERS L5 | GURDEEP SINGH AND COMPANY L4 | SRI SAI CONSTRUCTION COMPANY L6 | BHADU BUILDERS L3 |
|---|---|---|---|---|---|---|---|---|---|
| .10Notes:- (i) 100 percent nonperishable items of the work shall be deposited by the L1 bidder within 30 days after placing of work order. (ii) The critical path network shall be submitted by L1 bidder immediately after the acceptance of tender and approved by GE. (iii) The bidders must ensure to visit the site, check relevant documents and makes of materials required to be incorporated under the subject from concern Engineer-in-Charge. (iv) Material obtained from demolition/dismantled and the serviceable material (other than reused in the work) shall be the property of the Govt and shall be removed and deposited in the MES Store Yard without any extra cost to Govt. (v) In case of non-availability of any make mentioned under list of Makes, the L1 Bidder shall obtain non-availability / non-manufacturing certificate from the concern OEM / authorised dealers and submitted to Accepting Officer, the L1 bidder may be incorporated Group-I category makes as approved by HQ CE SWC Jaipur / HQ CE BTZ in the works after prior approval of Accepting Officer. (vi) L1 Bidder shall produce E-way bill alongwith test certificate from OEM / manufacturer for costly items / major items of amount above Rs 50,000/- along with RAR’s and Final Bill. (vii) L1 Bidder shall be maintained an album containing Photos of all the material brought at site and each stage wise work progress and kept at site. Same shall be deposited in Engineer-in-Charge office after completion of work. (viii)It shall be ensured by the bidder that main item and fixtures/base material shall be from the same manufacturer. (ix) Sufficient tradesman,Labours needed for subject work shall be deployed by the bidder on daily basis ans as required by Engineer-in-charge. (x)The cost of all the above provisions shall be deemed to be included in the quoted rate of bidder,nothing extra shall be paid to the bidder on this account. (viii) The cost of all the above provisions shall be deemed to be included in the quoted rate of bidder, nothing extra shall be paid to the bidder. | |||||||||
| 1.00 | Dismantling existing unserviceable Aluminium conductors, steel reinforced (ACSR conductor) from overhead lines on LT poles, of any type and any size complete all as specified and as directed by Engineer-in-charge | 3 | Quintal | 3,500 ₹10,500 | 1,000 ₹3,000 | 1,000 ₹3,000 | 250 ₹750 | 2,000 ₹6,000 | 1,000 ₹3,000 |
| 2.00 | M&L for Aluminium conductor, steel reinforced (ACSR) any type of ACSR conductor as per site requirement of size /make as ordered including stringing for overhead line on LT poles including aluminum binding wire 14 SWG, jumpers, line tapes, conducting jelly etc complete all as specified and as directed by Engineer-in-Charge.
(Notes : (i) The ACSR conductors shall be conforming to IS-398 and as specified in SSR Part-I.(ii) The unit rate quoted shall also be deemed to include for supply & fixing of aluminium binding wire, aluminium tapes etc which shall not be included in the weight of conductors.(iii) Weight of conductors shall be determined by measuring true horizontal distance between centers of two adjacent poles and compounding the weight of conductors of that size and length and 3% extra added for sag, jointing, jumpers etc
(iv) Weight of the conductors shall be calculated from the nominal weights given in tables in the relevant IS.) | 3 | Quintal | 11,000 ₹33,000 | 20,000 ₹60,000 | 25,000 ₹75,000 | 17,000 ₹51,000 | 19,000 ₹57,000 | 21,000 ₹63,000 |
| 3.00 | S&F in replacement shackle type insulators, vitreous porcelain white, brown or green for working pressure 1100 volts grade of 100 mm height and 115 mm dia including galvanized mild steel straps of 31mm x 5mm size,14mm dia insulator bolts, washers and nuts complete all as specified and directed by Engineer-in-Charge. | 50 | Each | 2,300 ₹1.1 L | 150 ₹7,500 | 150 ₹7,500 | 30 ₹1,500 | 70 ₹3,500 | 50 ₹2,500 |
| 4.00 | S&F in replacement pin type insulator of size 100mm height, 65 mm dia porcelain, vitreous white, brown or green insulator suitable for 1100 volts grade including one galvanized mild steel spindle, two GI washer and one GI nut complete all as specified and directed by Engineer-in-Charge. | 50 | Each | 1,550 ₹77,500 | 150 ₹7,500 | 150 ₹7,500 | 80 ₹4,000 | 200 ₹10,000 | 30 ₹1,500 |
| 5.00 | M&L for fixing in replacement of Cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections conforming to Fe-410-0 or Fe-310-0 grade including necessary nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape and size as directed and including applying two coats of aluminium paint (under & finishing coats) over a coat of red oxide zinc chromate primer on exposed steel surfaces after preparation of surfaces, supplied and fixed in repair complete all as specified and as directed by Engineer-in-Charge.
(Note: - (i) Sizes & types of members and shape of the cross arms etc shall be as required at site all as directed by the Engineer-in-Charge.(ii) Un-exposed steel surfaces shall be given one coat of red-oxide zinc chromate primer only. Cost of the same is included in unit rate of the item and nothing extra shall be paid on this account.) | 2 | Quintal | 9,000 ₹18,000 | 8,500 ₹17,000 | 11,000 ₹22,000 | 8,000 ₹16,000 | 7,700 ₹15,400 | 50 ₹100 |
| 6.00 | S&F in replacement stay assembly complete with accessories as shown in electrical plate No 1 using stay rod 20 mm dia x 1800mm long, stay bow 14mm dia and stay plate 30 cm x 30 cm x 6 mm including stay wire 8 SWG x 7 strands, loop type insulator with over all dimensions 90x140mm and clearence of hole 25.5mm, stay clamps and painting to exposed surfaces of mild steel work with two coats of aluminum paint over a coat of red oxide primer, complete all as specified and directed by Engineer-in-Charge.
Note : Excavation, earthwork and PCC in foundation shall be measured and paid seperately under respective items of BOQ. | 6 | Each set | 1,000 ₹6,000 | 2,000 ₹12,000 | 2,000 ₹12,000 | 800 ₹4,800 | 1,800 ₹10,800 | 1,200 ₹7,200 |
| 7.00 | M & L preparing old painted surfaces by scraping and removing old paints, rust, etc. from Steel Tubular Poles (above the Planting Depth and PCC Copings) and Mild Steel Cross Arms, Cable Protection Pipe, Brackets, etc. and applying one Coat of Red Oxide Zinc Chrome Primer, alternate Yellow & Black Strips Painting (5 No. Each Strip 300 mm wide) and remaining portion of Pole also including numbering to poles with synthetic enamel paint on black base of size 15 cm x 10 cm and numbering in 8 cm height of number with white paint and Cross Arms, Cable Protection Pipe, Brackets, etc. treated with Two Coats of Aluminium Paint complete all as specified and directed by Engineer-in-Charge | 200 | Each Job | 320 ₹64,000 | 220 ₹44,000 | 300 ₹60,000 | 180 ₹36,000 | 350 ₹70,000 | 350 ₹70,000 |
| 8.00 | M & L preparing old painted surfaces by scraping and removing old paints, rust, etc. from Pre-stressed Concrete cement Pole (above the Planting Depth and PCC Copings) and Mild Steel Cross Arms, Cable Protection Pipe, Brackets, etc. and applying Two Coats of Synthetic Enamel Painting in alternate Yellow & Black Strips Painting (5 No. Each Strip 300 mm wide) and remaining portion of Pole treated with Two Coats of Exterior Weather Proof Paint also including numbering to poles with synthetic enamel paint on black base of size 15 cm x 10 cm and numbering in 8 cm height of number with white paint and Mild Steel Cross Arms, Cable Protection Pipe, Brackets, etc. treated with Two Coats of Aluminium Paint complete all as specified and directed by Engineer-in-Charge. | 250 | Each Job | 160 ₹40,000 | 220 ₹55,000 | 250 ₹62,500 | 85 ₹21,250 | 180 ₹45,000 | 100 ₹25,000 |
| 9.00 | Disconnecting over head conductors and insulators any Nos on existing damaged Pre -stressed Concrete Cement LT poles, dismantling MS work such as cross arms /clamps/hooks etc, stay and street light (where exists), excavating and taking out damaged pole making good hole to receive new pole and M&L for Ereting Pre-stressed concrete poles 9 meter long, 102mm x 172mm at top and 102 mm x 279 mm at bottom, class 10, complying with requirements of IS-1678, including painting with two coats of synthetic enamel paint (in alternate black & white/yellow strips of 30 cm height) upto 1.5 meter height from top of PCC coping and also including numbering to poles with synthetic enamel paint on black base of size 15 cm x 10 cm and numbering in 8 cm height of number with white paint, including dismantling of old unserviceable one complete all as specified and as directed by the Engineer-in-Charge.
Note : Earthwork, Cement Concrete, etc. shall be measured and paid under respective Items. | 10 | Each Job | 6,500 ₹65,000 | 7,500 ₹75,000 | 7,000 ₹70,000 | 6,000 ₹60,000 | 6,500 ₹65,000 | 7,000 ₹70,000 |
Updated dates
Tender Value
₹40 L
EMD Value
₹80,000
Closing Date
17 Jan 2026, 6:00 pmClosed
GE (A) SURATGARH
GE (A) SURATGARH MILITARY STATION
REPAIR/RENEWAL/REPLACEMENT UNDER MAINT OF LT OHT LINES, UG CABLES, STREET LIGHTS AND ALL TYPE OF PANELS AND CONNECTED SERVICES OF BIRADHWAL, CETC, ASCON NODES AND ALL OUT STATION AREAS UNDER GE (ARMY) SURATGARH AT SURATGARH MIL STATION
2025_MES_744207_1
GE(A)/SOG-TOKEN-70/2025-26
Open Tender
Electrical and Maintenance Works
120 days
IN THE AOR OF GE (A) SURATGARH
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
GE(A) SURATGARH
₹80,000
Yes
6 Feb 2026
12 Dec 2025
19 Jan 2026
12 Dec 2025
17 Jan 2026
3 Jan 2026
12 Dec 2025 - 18 Dec 2025
Notes:- (i) 100 percent nonperishable items of the work shall be deposited by the L1 bidder within 30 days after placing of work order. (ii) The critical path network shall be submitted by L1 bidder immediately after the acceptance of tender and approved by GE. (iii) The bidders must ensure to visit the site, check relevant documents and makes of materials required to be incorporated under the subject from concern Engineer-in-Charge. (iv) Material obtained from demolition/dismantled and the serviceable material (other than reused in the work) shall be the property of the Govt and shall be removed and deposited in the MES Store Yard without any extra cost
Dismantling existing unserviceable Aluminium conductors, steel reinforced (ACSR conductor) from overhead lines on LT poles, of any type and any size complete all as specified and as directed by Engineer-in-charge
M&L for Aluminium conductor, steel reinforced (ACSR) any type of ACSR conductor as per site requirement of size /make as ordered including stringing for overhead line on LT poles including aluminum binding wire 14 SWG, jumpers, line tapes, conducting jelly etc complete all as specified and as directed by Engineer-in-Charge. (Notes : (i) The ACSR conductors shall be conforming to IS-398 and as specified in SSR Part-I.(ii) The unit rate quoted shall also be deemed to include for supply & fixing of aluminium binding wire, aluminium tapes etc which shall not be included in the weight of conductors.(iii) Weight of conductors shall be determined by measuring true horizontal distance between centers of two adjacent poles and compounding the weight of conductors of that size and length and 3% extra added for sag, jointing, jumpers etc (iv) Weight of the conductors shall be calculated from the nominal weights given in tables in the relevant IS.)
S&F in replacement shackle type insulators, vitreous porcelain white, brown or green for working pressure 1100 volts grade of 100 mm height and 115 mm dia including galvanized mild steel straps of 31mm x 5mm size,14mm dia insulator bolts, washers and nuts complete all as specified and directed by Engineer-in-Charge.
S&F in replacement pin type insulator of size 100mm height, 65 mm dia porcelain, vitreous white, brown or green insulator suitable for 1100 volts grade including one galvanized mild steel spindle, two GI washer and one GI nut complete all as specified and directed by Engineer-in-Charge.
M&L for fixing in replacement of Cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections conforming to Fe-410-0 or Fe-310-0 grade including necessary nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape and size as directed and including applying two coats of aluminium paint (under & finishing coats) over a coat of red oxide zinc chromate primer on exposed steel surfaces after preparation of surfaces, supplied and fixed in repair complete all as specified and as directed by Engineer-in-Charge. (Note: - (i) Sizes & types of members and shape of the cross arms etc shall be as required at site all as directed by the Engineer-in-Charge.(ii) Un-exposed steel surfaces shall be given one coat of red-oxide zinc chromate primer only. Cost of the same is included in unit rate of the item and nothing extra shall be paid on this account.)
S&F in replacement stay assembly complete with accessories as shown in electrical plate No 1 using stay rod 20 mm dia x 1800mm long, stay bow 14mm dia and stay plate 30 cm x 30 cm x 6 mm including stay wire 8 SWG x 7 strands, loop type insulator with over all dimensions 90x140mm and clearence of hole 25.5mm, stay clamps and painting to exposed surfaces of mild steel work with two coats of aluminum paint over a coat of red oxide primer, complete all as specified and directed by Engineer-in-Charge. Note : Excavation, earthwork and PCC in foundation shall be measured and paid seperately under respective items of BOQ.
M & L preparing old painted surfaces by scraping and removing old paints, rust, etc. from Steel Tubular Poles (above the Planting Depth and PCC Copings) and Mild Steel Cross Arms, Cable Protection Pipe, Brackets, etc. and applying one Coat of Red Oxide Zinc Chrome Primer, alternate Yellow & Black Strips Painting (5 No. Each Strip 300 mm wide) and remaining portion of Pole also including numbering to poles with synthetic enamel paint on black base of size 15 cm x 10 cm and numbering in 8 cm height of number with white paint and Cross Arms, Cable Protection Pipe, Brackets, etc. treated with Two Coats of Aluminium Paint complete all as specified and directed by Engineer-in-Charge
M & L preparing old painted surfaces by scraping and removing old paints, rust, etc. from Pre-stressed Concrete cement Pole (above the Planting Depth and PCC Copings) and Mild Steel Cross Arms, Cable Protection Pipe, Brackets, etc. and applying Two Coats of Synthetic Enamel Painting in alternate Yellow & Black Strips Painting (5 No. Each Strip 300 mm wide) and remaining portion of Pole treated with Two Coats of Exterior Weather Proof Paint also including numbering to poles with synthetic enamel paint on black base of size 15 cm x 10 cm and numbering in 8 cm height of number with white paint and Mild Steel Cross Arms, Cable Protection Pipe, Brackets, etc. treated with Two Coats of Aluminium Paint complete all as specified and directed by Engineer-in-Charge.
Disconnecting over head conductors and insulators any Nos on existing damaged steel tubular swaged LT poles, dismantling MS work such as cross arms /clamps/hooks etc, stay and street light (where exists), excavating and taking out damaged pole making good hole to receive new pole and M&L for Ereting Steel Tubular Swaged Pole Type 410-SP-31 (9.0 Metre long) including Cast Iron Base Plate, Finial Taper Plug, Cap, Mild Steel Bolts, Nuts, Screws including applying two coats of Black Bituminous Paint Internally and Externally from bottom End of Pole upto PCC Coping and applying with two coats of Aluminium Painting over a coat of red oxide Primer (Externally from Top of Coping)and applying Two Coats of Synthetic Enamel Painting in alternate Yellow & Black Strips Painting (4 No. Each Strip 300 mm wide) and also including numbering to poles with synthetic enamel paint on black base of size 15 cm x 10 cm and numbering in 8 cm height of number with white paint, including dismantling of old unserviceable one complete all as specified and as directed. Note : Earthwork, Cement Concrete, etc. will be measured and paid under approprite Items.
Disconnect the electric supply from Main GO/DO and taking down old existing Loose ACSR conductor mounted on Steel/PCC pole 3 to 5 Conductor and Re-stringing of existing over head line ACSR conductor/GI wire of any size/type including repair of conductor broken due to wind storm/expansion, contraction etc, on existing LT steel and/or PCC pole including replacement of aluminium binding wire of suitable size and refixing of all old accessories carefully without damaging of insulator etc complete all as specified and directed by Engineer-in-Charge. Note:- Length of each conductor shall be measured as one length.
M & L for PCC (1:2:4) type B-1 using 20 mm graded stone aggregate as in new / old coping of poles etc including weathering, slightly rounded or chamfered angle and throating, necessary form work and fair finishing all exposed faces of concrete without using extra cement complete all as specified and directed by Engineer-in-charge
M & L for PCC (1:3:6) typeC-2 using 40mm graded stone aggregate as in foundation for stays & mass concrete including necessary form work and fair finishing complete all as specified and directed by Engineer-in-charge
M & L for PCC (1:4:8) type D-2 using 40mm graded stone aggregate as in foundation for poles, struts & mass concrete including necessary form work and fair finishing to exposed surfaces complete all as specified and directed by Engineer-in-charge
S&F in replacement LED flood light of 160 watt with high pressure die cast housing with lens with lument output 6000K complete (including LED, drive and internally prewired) with on board 5 KV surge protection with 10 KV external SPD. The luminaries shall be monolithic construction totally enclosed dust and water proof with minimum IP 66 protection as per IS 10322-1982 (part-I) with latest amanedments and input voltage range 140-300V AC, frequency 50-60 Hz, P.F should be more than 0.9. The efficiency of LED luminaries system shall be more than 100 lumens per watt and FRLSH cable PVC insulated stranded copper conductor, 1100 volts grade, 2.5 sqmm x 3 core of ISI marked for light to ceiling rose complete including arrangement of mounting for street light as required at site complete all as specified and directed by Engineer-in-charge.
Excavation in trenches, not exc 1.5 m wide and n. exc 1.5 m depth; or n exc 10 Sqm on plan and n exc 1.5 m in depth for foundations of poles, struts, stays, joints or laying underground cable etc. in soft/loose soil, & getting out including taking out old brick or precast cable cover complete all as specified and directed by Engineer-in-Charge.
Returning, filling in, including spreading, levelling, watering and well ramming in layers n.exc 25cm thick complete all as specified and directed by Engineer-in-Charge
Removal of excavated soil/ material to a distance not exc 50 metre and depositing where directed at a level n. exc 1.50 metre above the starting point complete all as specified and directed by Engineer-in-Charge.
All as per item No 35 above but cable of cross sectional area 16 sq mm 2 core.
Supply and fixing HDPE DWC Pipe dia inner dia 75mm and outer dia 90mm for laying of cable laid in trenches complete all as specified and as directed by the Engineer-in-Charge. Note:- excavation and earth work shall be measured and paid for separately.
Supply and fixing HDPE DWC Pipe dia inner dia 50mm and outer dia 63mm for laying of cable laid in trenches complete all as specified and as directed by the Engineer-in-Charge. Note:- excavation and earth work shall be measured and paid for separately.
Taking out old underground LT Cable of size 10 sqmm to 240 Sqmm of 3.5 core from LT Panels trenches/floors /road/wall/ pipe/pole/including taking out loop from trenches upto 1.5 mtrs depth, cutting the faulty end of cable and refixing the cable in original position by using flat aluminium sockets/ thimble/ and insulating the all nacked wires of any size including making connection with MCCB's/ Switches complete all as directed by Engineer-in-Charge. Note : Exacavation for taking out LT cable from will measured and paid separatly.
Supply and fixing HDPE DWC Pipe dia inner dia 32mm and outer dia 40mm for laying of cable laid in trenches complete all as specified and as directed by the Engineer-in-Charge. Note:- excavation and earth work shall be measured and paid for separately.
Supplying, jointing and testing in replacement heat shrinkable type indoor / outdoor end termination jointing kit, suitable for different size of cable 35 sq mm to 120 sq mm aluminium conductor 1100 Volts including making connections complete all as per following.
Supplying, jointing and testing in replacement heat shrinkable type straight through jointing kit, suitable for different size of cable aluminium conductor 1100 Volts including making connections complete all as per following and directed by Engineer-in-Charge.
All as per item No 24 above but suitable for cable of size 185 sqmm to 300 sqmm.
All as per item No 26 above but sui
All as per item No 26 above but suitable for cable of size 16 sq mm to 25 sqmm.
All as per item No 26 above but suitable for cable of size 95 sqmm to 120 sqmm.
Trimming/pruning of the tree branches comming cross electric power head line LT feeder cleaning the span and making it free from touching the tree branches complete all as specified and as diredted by Engineer-In-Charge. (Note :-(i) All item of LT overhead lines taken together shall be measured as one unit for the payment purpose under this item. (ii) Only such length shall be measured where trees are required to be cut/trimmed as directed by Engineer-In-Charge. (iii) Removing branches from road and diposition at a distance of more than 500 meter) (iv) Ladder wheel shall be arranged by the contractor at his own cost, nothing extra shall be paid on this account.
Supply and fixing 32 mm dia 1.2 metre long GI pipe light grade bracket for fixing street light made to shape at including MS clamps (FI Plate 25X4mm as per site requirement) 02 Nos and nut and bolts duly painted with two coats of synthetic enamel paint over a coat of red oxide primer complete as required at site complete all as specified.
S&F in replacement following MCCB , thermal magnetic release in the existing feeder pillar box including any addition / alteration to the panel to accommodate the new MCCB & making connections with 25x3 mm copper strip as required from main bus bars, making necessary welding work, metal work for fixing base plate etc and connections complete all as specified and as directed by Engineer-in-Charge. Make:- Legrand / L&T / Schneider / Indoasian
table for cable of size 185 sqmm to 300 sqmm.
All as per item No 26 above but suitable for cable of size 35 sq mm to 70 sqmm.
Disconnecting over head conductors and insulators any Nos on existing damaged Pre -stressed Concrete Cement LT poles, dismantling MS work such as cross arms /clamps/hooks etc, stay and street light (where exists), excavating and taking out damaged pole making good hole to receive new pole and M&L for Ereting Pre-stressed concrete poles 9 meter long, 102mm x 172mm at top and 102 mm x 279 mm at bottom, class 10, complying with requirements of IS-1678, including painting with two coats of synthetic enamel paint (in alternate black & white/yellow strips of 30 cm height) upto 1.5 meter height from top of PCC coping and also including numbering to poles with synthetic enamel paint on black base of size 15 cm x 10 cm and numbering in 8 cm height of number with white paint, including dismantling of old unserviceable one complete all as specified and as directed by the Engineer-in-Charge. Note : Earthwork, Cement Concrete, etc. shall be measured and paid under respective Items.
All as per item No. 30 here-in-before but MCCB 4 Pole, 160 Amps rating, breaking capacity 36 KA, 415 Volt complete all as specified and directed.
All as per item No. 30 here-in-before but MCCB 4 Pole, 250 Amps rating, breaking capacity 36 KA, 415 Volt complete all as specified and directed.
All as per item No. 30 here-in-before but MCCB 4 Pole, 400 Amps rating, breaking capacity 36 KA, 415 Volt complete all as specified and directed.
Supply and fixing in replacement weather proof PVC insulated, sheathed three core stranded aluminium conductor cable of size 2.5 Sqmm, 1100 Volts grade conforming to IS:9968 (Part-I) 1988 or IS:694-1990 complete all as specified and directed by Engineer-in-Charge.
Locating the fault in LT cable of any size for any type of fault like open cable short between phases/Neutral ,grounded cable with help of cable fault locator and pin pointing location with the help of audio signal ,excavation at the fault and openning cable to suitable distence and depth for making a cable joint and including complete Earth work all as specified and as directed .(note:-1. The joint kit will be paid separately. 2:-contractor will have to arranged the cable fault locator or other testing Eqpt /tools as required &same shall be deemed to be includede in the item rate Quoted)
All as per item No. 30 here-in-before but MCCB 4 Pole, 630 Amps rating, breaking capacity 50 kA, 415 Volt complete all as specified and directed.
All as per item No 35 above but cable of cross secitonal area 240 sq mm 3.5 core.
All as per item No 35 above but cable of cross sectional area 185 sq mm 3.5 core.
All as per item No 35 above but cable of cross sectional area 120 sq mm 3.5 core.
All as per item No 35 above but cable of cross sectional area 95 sq mm 3.5 core.
All as per item No 35 above but cable of cross sectional area 70 sq mm 3.5 core.
All as per item No 35 above but cable of cross sectional area 35 sq mm 3.5 core.
All as per item No 35 above but cable of cross sectional area 25 sq mm 4 core.
All as per item No 35 above but cable of cross sectional area 16 sq mm 4 core.
All as per item No. 30 here-in-before but MCCB 4 Pole, 63 Amps rating, breaking capacity 16 KA, 415 Volt complete all as specified and directed.
Suppyling, installing, testing and commissioning factory made outdoor type bus bar chamber having MCCB 4 Pole, 415 Volts, 160 Amps of suitable size for operation on 415 volts, 3 phase, 4 wire, 50 Hz, outer shell made out of 3.15mm thick CRCA sheet duly powder coated coated siemens gray shade and completely weather, vermin & dust proof, adequate air ventilation at sides & back, door shall be provided with double door fix with hinges and locking arrangements etc suitables to accomodate the 250 Amps aluminium bus bar fixed Horizontally in staggred manner minimum length 450mm, 3 phases and neutral duly insulated with heat shrinkable PVC sleeves and colour coded mounted on heavy duty DMC insulators duly connected with 160Amps MCCB including provision for taking out incoming and outgoing cables detachable plate at bottom for cable entry and making six Nos hole in each bus bar including with bottom frame made out of angle iron 50mm x 50mm x 5mm and 600mm long 4 legs duly painted with 2 coats of synthetic enamel paint over a coat of red oxide primer on exposed surfaces grouted in PCC 1:2:4 type B1 using 20mm graded stone aggregate blocks of size 30cm x 30cm x 60cm complete all as specified and as directed by Engineer-in-charge.
S&F as in replacement three phase automatic street light switch suitable for 5 KW load complete with Infrared sensor based NATURE SWITCH for automatic switching of street / security lights compitable with exisitng timer box. Lighting switch operation should be based on natural light lux level. Required illuminance level for switching ON is < 30 Lux and for switching OFF > 10 Lux. The sensor should also have part night operation facility for 4,5,6,........11 & 12 hours. complete all as specified and directed by Engineer in charge. Make :- Nature switch shall be same make of exisitng timer box i.e. KAKATIYA ENERGY SYSTEM PVT LTD cat aprt No. Swadeep 02EC5KW3P or Equivalent make as specified in Appx 'A'.
Supply and fixing in replacement electronic MPPCB for street light (Make as per site requirement) 220/240 V suitable for existing LED light fitting , 45 Watts ,60WATT /complete all as specified and directed by Engineer-in-Charge.
Taking down LED security/street light fitting such as 30/45/60/72/90 watt etc for find out faults including cleaning of glass with castic soda solution and refixing the same in existing position after carrying out necessary repair / replacement of unserviceable parts complete all as specified and directed by Engineer-in-Charge. Notes :- (i) The accessories / spare parts which are required to be replaced shall be measured and paid in respective item. (ii) Ladder wheel shall be arranged by the Contractor. (iii) Detection and rectification of fault in over head/under ground line shall be done by the contractor.
M&L for preparation of existing painted surfaces of Panel Board / Feeder Pillar box (indoor / outdoor type), area not exceeding 10 square metre each and applying one coat of synthetic enamel paint after preparation of surfaces on external and internal surfaces of approved tint by using spray machine inclusive of writing SM / MES No / name of feeders etc. (not exceeding of height 5 cm each) including welding of broken panel door, tightening electric connection of switch gears and cleaning of vegetation all around the panels up to one meter from all sides complete all as specified and as directed by Engineer-in-charge.
Taking down 150-200 watt flood light fitting for finding out faults and refixing the same in existing position after carrying out necessary repair and wiring with 4 sqmm 3 core copper PVC cable, tightning of loose connection and cleaning of glass complete all as specified and directed by Engineer-in-Charge. Notes :- (i) Ladder wheel shall be arranged by the Contractor. (ii) Detection and rectification of fault in over head/under ground line shall be done by the contractor.
Supply only and testing LED Street light fitting of 45 Watt including LED lamps complete with body robust,corrosion resistant,superior finish and without any cracks or through holes,made in a single piece by high pressure die cast aluminium alloy.The luminaries shall be monolithic construction totally enclosed dust and water proof with minimum IP -65 / 66 protection as per IS - 10322-1982(Part -I) with latest amendments and input voltage range 140 - 300 V, AC, frequency 50 - 60 Hz ,P.F should be more than 0.9 with Total Harmonic Distoration THD(I) less than 15% ,cool white colour and lamp starting time should not be more than 10 second fitting should be provided with 10 KV surge protection.Driver should be constant current constant voltage driver .Driver should have high voltage withstanding capacity upto 300 V, AC. Driver should also have double phase protection,no load , open circuit and short circuit protection .LED light fitting should be suitable for ambient temperature from -10 degreeCentrigrade to 60 degree Centrigrade and humidity level 10% to 90 % RH. Covers should be polycarbonate/toughened glass to ensure minimum IP 65 degree protection.Cover should not degrade due to heating and ageing.The efficiency of LED luminaries system shall be more than 100 lumens per watt and must be certified by the LM-79 test report and including provision of connection for street light from pole box with 2.5 Sqmm PVC insulated stranded copper conductor FRLSH cable, 1100 Volts grade ISI marked complete all as specified and directed by Engineer-in- charge.
All as per item No. 30 here-in-before but MCCB 4 Pole,125 Amps rating, breaking capacity 16 KA, 415 Volt complete all as specified and directed.
Description as per Item No. 16 but not exc 3 mtr in depth complete all as specified and directed by Engineer-in-Charge.
Supply only 10 KV surge protector suitable for any type of LED fitting & make complete all as specified and directed by Engineer-in-Charge.
All as per Item No 35 above but Cable of Cross Sectional Area 10 sq mm 2 Core
Inspection/checking/tightening of connections for LED Security/Street light fitting such as 30/45/60/72/90 watts etc for tighting the connection with replacement of twin core multi strand 2.5 Sqmm aluminium wire complete all as specified and directed by Engineer-in-Charge.
Supplying, laying, jointing, commissioning and testing in replacement XLPE insulated screened PVC bedded, armoured, heavy duty underground electric cable with stranded aluminium conductor 1100 volts grade confirming to IS-7098 (Part-I-1988) laid in trenches, along poles through pipes etc complete all as specified and directed by Engineer-in-charge. Make :- Havells / Gloster / Finolex / Polycab/RR cables or equivalent make as specified in Appendix 'A'
Supply only electronic driver (Make as per site requirement) 220/240 V suitable for existing LED light any type fitting Watts complete all as specified and directed by Engineer-in-Charge. Make Wipro/Philips/Crompton or equivalent Technocommercial makes as mentioned in Appx 'A'
S&F in replacement three phase automatic street light switch suitable for 5 KW load complete with Infrared sensor based NATURE SWITCH for automatic switching of street / security lights with three number two pole power contractors 40 Amps (Type - MU40-2P, Cs90119) with coil voltage 220 / 240 V and incoming MCBs single pole - 03 Nos, outgoing MCBs single pole - 03 Nos of rating 32 Amps & circuit wiring with single core multi stranded of size 10 Sqmm. Lighting switch operation should be based on natural light lux level. Required illuminance level for switching ON is < 30 Lux and for switching OFF > 10 Lux. The sensor should also have part night operation facility for 4,5,6,........11 & 12 hours. The sensor along with suitable power contactor (S), Incoming -outgoing MCB's should be enclosed in a Rust proof, electric shock proof, termite proof and FR grade thermoplastic polycarbonate enclosure with hinged lid confirming to IP66 protection class 2. The circuit should also have provision for manual operation (i.e. sensor By-pass option). The enclosure sould be mounted on 40mm x 40mm x 5mm angle iron structure and the structure height minimum 600mm and must be grouted in PCC (1:2:4) type B-1 using 20mm graded stone aggregate blocks of size 30cm x 30cm x 60cm complete all as specified and directed by Engineer in charge. KAKATIYA ENERGY SYSTEM PVT LTD cat aprt No. Swadeep 02EC5KW3P or Equivalent make as specified in Appx 'A'.
S&F as in repair LED Bollard 08 Watt IP65 cone series acts as imposing street furniture . The elegant yet minimailistic design acts a silent observer and giving light, diffuser at the upper portion adds fucctional Value into landscape environmental with all accessories complete all as specified and as direcetd. Make :- Havells Cat Part No. CONEBLS8W
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.35 MB
T70.pdf
Tender Documents • 0.97 MB
BOQ_833324.xls
BOQ • 0.37 MB
Download all tender documents and submit your bid