Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹19.4 LAccepted-AOC | L1 | Accepted-AOC THE LOWESST TENDERER | |
| 2 | L2₹19.9 L+₹47,422.80 (2.45%)Rejected-Finance | L2 | Rejected-Finance THE LOWEST TENDERER | |
| 3 | L3₹22.3 L+₹3.0 L (15.3%)Rejected-Finance SADASHIV PHUGE NAGAR OPP SANDVIK FACTORY RADHIKA RESIDENCY F WING FLAT NO 7 PHUGEWADI PUNE 411 012 | PUNE | MAHARASHTRA | 411012 | L3 | Rejected-Finance THE LOWEST TENDERER | |
| 4 | L4₹23.1 L+₹3.7 L (19.2%)Rejected-Finance 24 25 MANGAL ARCADE TELCO ROAD OPP HOTEL DOUBLE TREE MOHAN NAGAR CHINCHWAD PUNE 411019 | PUNE | MAHARASHTRA | 411019 | L4 | Rejected-Finance THE LOWEST TENDERER | |
| 5 | L5₹23.3 L+₹4.0 L (20.4%)Rejected-Finance | L5 | Rejected-Finance THE LOWEST TENDERER |
Tender Value
Refer Docs
EMD Value
₹56,000
Closing Date
23 Jan 2023, 6:00 pmClosed
GE MH AND RH KIRKEE
Military Engineer Services Garrison Engineer MH and Range Hills Range Hills Road Kirkee Pune 411003
CERTAIN MAINT OF LT EXT ELECT SUPPLY INCL REP OF PANEL FEEDER PILLAR PANEL AND REPLACEMENT OF OLD UNSV OH LINE WITH UG CABLE AND CONNECTED ITEMS AT STN WKSP EME POL DEPOT RANGE HILLS BDTC ASHOK NAGAR MANDALAY LINE AND QMTI MAP UNDER GE MH RH KIRKEE
2022_MES_571589_1
8348/E8
Open Tender
Electrical and Maintenance Works
Item Rate
330 days
GE MH AND RH KIRKEE
AS PER TENDER DOCUMENTS
8 documents required · 8 mandatory
₹500
GE MH AND RH KIRKEE
₹56,000
22 Feb 2023
27 Dec 2022
25 Jan 2023
27 Dec 2022
23 Jan 2023
11 Jan 2023
27 Dec 2022 - 16 Jan 2023
Amount
Excavating in trenches not exc 1.5m wide and not exc 1.5m in depth for laying UG cable, pipe line etc and getting out in soft / loose soil complete all as specified and directed.
Excavating in trenches not exc 1.5m wide and not exc 1.5m in depth for laying UG cable, pipe line etc and getting out in hard / dense soil complete all as specified and directed.
Returning filling including spreading leveling watering and well ramming in layers not exceeding 25 cm thick each layer of soil complete and all as specified.
Removing excavated material to a distance not exceeding 50 mtr and depositing where directed at a level not exceeding 1.5 mtr above starting point. Complete and all as specified.
M&L for riddled earth cushioning to under ground cable in trenches / existing cable trenches/ducts in layers of 8 cm deep before laying the cable and 15 cm deep after laying and stretching the cable complete all as specified and directed by Engineer-in-Charge Note:- Measurement shall be taken after gentling punning.
Supply and laying un-reinforced precast concrete cable cover LV, Type I, flat, size 250mm x 150mm x 40mm for under ground cable all as specified and directed.
Re-laying only brick or cable cover all as specified & directed by Engineer-in-Charge.
Taking down unserviceable cable of any size upto 300 Sqmm carefully from trenches/poles/ducts/LT panels, OH conductors all as specified and directed by Engineer-in-Charge
Re-laying only the serviceable cable of any size and description obtained from Item No-07 above after joining etc all as directed. Note: (i) While re-laying retrived sand will be re-used without any extra cost. (ii) Re-trived Bricks and PCC cover shall be paid as laying only under relevant item of this BOQ. (iii) Earth works shall be meaured and paid under relevant item.
Material and labour for fixing or passing through pipe, laid in trenches or fixed to pole/wall or fixed to LT panel board, insulated, armoured heavy duty electric cable with aluminium conductor, XLPE, 1100 volts grade, cross-sectional area of following size complete all as specified and directed by Engr-in-charge:-
16 sqmm 2 core.
25 sqmm 3.5 core.
35 sqmm 3.5 core.
50 sqmm 3.5 core.
70 sqmm 3.5 core.
95 sqmm 3.5 core.
120 sqmm 3.5 core.
185 sqmm 3.5 core.
240 sqmm 3.5 core.
300sqmm 3.5 core.
Dimantling and taking down old/unsv cross arms, bracing, supports etc complete carrying to store for credit all as specified and directed.
Supply and fixing cross arms bracings supports clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding bending cold or hot, drilling holes for bolts in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of aluminium paints complete all as specified and directed.
Dismatling and taking down old/unsv ACSR conductor any size complete to carrying to store for credit all as specified and directed
S&F ACSR conductor incl jointing with existing conductor and stringing on LT pole and proper fastening to pin/shackle insulators with aluminium binding wires and required jumpering connection all as directed.
Dimantling and taking down old/unsv LT insulator of any type any size from pole/stay or carrying to store for credit complete all as specified and directed.
S&F pin type, porcelain, vitreous, brown, including one galvanised mild steel spindle, two galvanised iron washer and one galvanised iron nut, 100mm height and 65 mm dia for 1100 volts grade all as specified and directed.
Material and labour for earthing complete with GI earth plate 600mm x 600mm x 6.3 mm thick electrode buried directly in ground (earth pit not less then 2.25 metres deep below ground level ) with top edge of the plate not less then 1.5 metres below normal ground level connected to GI earth strip 32 x 6 mm by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No. 3 of MES schedule Part-I and incl 40 mm bore light grade GI protection pipe (upto 7.5 metres beyond outer edge of earth pit) PCC M-10 grade (Nominal Mix) using 40mm graded stone aggregate in pit with 40mm thick RCC cover in reinforced cement concrete M-15 grade (Nominal Mix) using 20mm graded stone aggregate, reinforced with 8mm dia bar both way @ 150mm c/c, watering arrangement with funnel and wire mesh and 20 mm bore light grade GI watering pipe, common salt and charcoal filling, necessary excavation and earth work complete. Note : Rate of item is deemed to be included for excavation in hard rock, by compressor machine to achieve required depth.
Labour only for restringing of overhead ACSR conductor of any size of 4 wire on pole after disconnecting all jumper connection & binding of insulators and including rejointing all connections and insulators, jumper binding with aluminium conductor complete all as specified and directed . Note : Pole to pole distance will be measured as one job
M & L for jointing the LT cable with heat shrinkable straight through joint, by disconnecting the cable ends, removing the damaged portions of cable, by suitable means, joining by ferrules etc and testing for LT 1100 V cable of following size complete all as directed and specified:-
3.5/4 core 6-16 Sqmm.
3.5/4 core 25-50 Sqmm.
3.5/4 core 70-120 Sqmm.
3.5/4 core 150-185 Sqmm.
3.5/4 core 240-300 Sqmm.
Supply, replace, testing & commissioning of LT capacitor upto 5 to 15 KVAR, 440Volt of Heavy duty for non-linear loads up to 440 V cylinderical type on existing APFC panel and necessary panel wiring, all as directed and satisfied by Engineer-in-Charge. Make : L & T/ Legrand/Schneider
Supply, replace, testing & commissioning of LT capacitor upto 20 to 25 KVAR, 440Volt of Heavy duty for non-linear loads up to 440 V cylinderical type on existing APFC panel and necessary panel wiring , all as directed and satisfied by Engineer-in-Charge. Make : L & T / Legrand/ Scheider.
Supply, replace, testing & commissioning of duty contactor of capacity of 5 to 15 KVAR on existing APFC panel and necessary panel wiring all as directed and satisfied by Engineer-in-Charge Make :L & T / Legrand/ Scheider.
Supply, replace, testing & commissioning of duty contactor of capacity of 20 to 25 KVAR on existing APFC panel and necessary panel wiring all as directed and satisfied by Engineer-in-Charge Make : L & T / Legrand /Schneider.
S & F in repairs CT coil up to ±5 A capacity all as directed by Engineer-in-Charge
Supply and fixing MCCB, 63 amps, 3 pole, 415 V, 16 KA breaking capacity, with Thermal magnetic release, optium 2.0, incl dismentling taking down unsv one, making cutting of existing panel for fixing MCCB on suitable fitting and making good the panel all as directed by Engineer-in-Charge
Supply and fixing MCCB, 100 amps, 3 pole, 415 V, 16 KA breaking capacity, with Thermal magnetic release, optium 2.0, incl dismentling taking down unsv one, making cutting of existing panel for fixing MCCB on suitable fitting and making good the panel all as directed by Engineer-in-Charge
Supply and fixing MCCB, 125 amps, 3 pole, 415 V, 25 KA breaking capacity, with Thermal magnetic release, optium 2.0, incl dismentling taking down unsv one, making cutting of existing panel for fixing MCCB on suitable fitting and make panel good and all as directed by Engineer-in-Charge
Supply and fixing MCCB, 160 amps, 3 pole, 415 V, 25 KA breaking capacity, with Thermal magnetic release, optium 2.0, incl dismentling taking down unsv one, making cutting of existing panel for fixing MCCB on suitable fitting and making good the panel all as directed by Engineer-in-Charge
Supply and fixing MCCB, 200 amps, 3 pole, 415 V, 25 KA breaking capacity, with Thermal magnetic release, optium 2.0, incl dismentling taking down unsv one, making cutting of existing panel for fixing MCCB on suitable fitting and making good the panel all as directed by Engineer-in-Charge
Supply and fixing MCCB, 250 amps, 3 pole, 415 V, 36 KA breaking capacity, with Thermal magnetic release, optium 2.0, incl dismentling taking down unsv one, making cutting of existing panel for fixing MCCB on suitable fitting and making good the panel all as directed by Engineer-in-Charge
Supply and fixing MCCB 63 Amps, 4 pole, 415V with Adjustable type, optium 2.0 incl dismentling taking down unsv one, making cutting of existing panel for fixing MCCB on suitable fitting , Iincluding use required sheet metal and making good the panel all as directed by Engineer-in-Charge
Supply and fixing MCCB 100 Amps, 4 pole, 415 V, 16 KA breaking capacity, with Thermal magnetic release, optium 2.0 incl dismentling taking down unsv one, making cutting of existing panel for fixing MCCB on suitable fitting and making good the panel all as directed by Engineer-in-Charge
Supply and fixing MCCB 125 Amps, 4 pole, 415 V, 16 KA breaking capacity, with Thermal magnetic release, optium 2.0 incl dismentling taking down unsv one, making cutting of existing panel for fixing MCCB on suitable fitting and making good the panel all as directed by Engineer-in-Charge
Supply and fixing MCCB, 4 pole, 415 V, 16 KA breaking capacity, with Thermal magnetic release, optium 2.0, 125 amps, incl dismentling taking down unsv one, making cutting of existing panel for fixing MCCB on suitable fitting and making good the panel all as directed by Engineer-in-Charge
Supplying & laying in treanches or fixing on wall / pole 40 mm nominal bore, light grade, galvanised coated steel tube conforming to IS 1239 (Part-1): 2004 including all fittings conforming to IS 1239 (Part-2): 2011 complete all as specified and as directed.
Supplying & laying in treanches or fixing on wall / pole 50 mm nominal bore, light grade, galvanised coated steel tube conforming to IS 1239 (Part-1): 2004 including all fittings conforming to IS 1239 (Part-2): 2011 complete all as specified and as directed.
Supplying & laying in treanches or fixing on wall / pole 80 mm nominal bore, light grade, galvanised coated steel tube conforming to IS 1239 (Part-1): 2004 including all fittings conforming to IS 1239 (Part-2): 2011 complete all as specified and as directed.
M & L for trimming of branches of trees with in 3 mtr on either side of the electric lines/poles with suitable T & P and disposing the waste as directed and as specified. Note : Measurement for triming of tree branches shall be measured once only for entire period of completion.
Taking down old unserviceable line separator and S&F rigid PVC line separator suitable for 2 wire, made from high grade PVC material, distance between phase 300mm, suitable for use with 1100 volts grade. Make : Shree Balaji Power Plast/Goyal Power Plast or equivalent.
All as per item No 39 above but of 4 wire
M&L for road cutting and making good with PCC M-10 grade (nominal mix) using 40mm graded stone aggregate of 150mm X 100mm in respect of width and thickness complete all as specified and directed by Engineer-in-Charge
Decarbonizing of LT indoor/outdoor Panel/feeder pillar box any type removing unserviceable MCCBs, burnt busbars, unserviceable indicator lamps, unserviceable Ammeter, unserviceable Volt meter , replacing burnt, damaged bus bar of any size and fixing proper hanging front and rear openings, welding of hinges including welding of brokieng MS sheet using extra sheets replace burnt thimbles with new existing size thimbles replacing with new MCCB, incluidng dismantling the existing connected cables with cable gland and re-connecting the same cables complete all as specified and directed by Engineer-in-Charge Note : (i) MCCBs,Bus bars,indicator lamps, Ammeter, Volt meter, will be measured & paid separately as supply only .
Servicing of APFC panel cleaning, tightning of connections, setting programme, testing of CT including caliberation of APFC panel replace unserviceable capacitors, capacitor contactor, breakers, power factor controller after servicing testing panel and achive power factor of 1.000 all as directed by Engineer-in-Charge. Note: Capacitors, capacitor contactor, power factor controller measered and paid separately.
Note For item No 42 & 43 : (i) Quoted rate includes replacement of damaged panel look as per existing as per site required. (ii) Painting of panels with mounting stand by applying two coat of synthetic enamel paint including preparation of steel surface shall be deemed to included in unit rate quoted. (iii) suitable size of lugs and cable gland for panel shall be deemed to be included in unit rate quoted. (iv) Necessary MS sheet, Hinges and welding shall be deemed to be included in unit rate quoted. (v) Rate includes cleaning of panel by using high speed air blower to remove dust.
Supply and fix power factor controllers 5 steps, with timer, 415 volt, AC, 50 HZ power supply and replacing old unserviceable controllers including suitable wiring complete all as directed by Engineer-in-Charge Make : L &T Cat No ETACONM005R or equivalent make of Scheider, EPCOS
Supply and fix aluminium Bus Bar with suitable holes and bus bar insulating sleeve cover as per Existing size at site as per requirement all as directed by Engineer-in-Charge including removing unserviceable aluminium bus bar .
Supply, fix of RYB indicator lamp LED type( set of three lamp) for incoming and outgoing supply by making suitable hole of sizes all as directed by Engineer-in-Charge.
Hardcore of gauge n.exc 63mm ,deposited, spread, and levelled in layers n.exc 15 cm thickness (below or above ground level), water and well rammed to a true shape except material broken stone or boulders available at site shall be reused and making good all as specified and directed by Engineer-in-Charge
M&L for cleaning of MES electric supply installations/campus by surface dressing or trimming of natural ground to remove small unequalities not exc 15 cm deep (including removing vegetation/ shrubs/brush wood/ under growth) and carrying away the rubbish to a distance of not exc 50 mtr away complete at an interval of every 30 days for the various sub stations. Note: (1) Spray of herbsite deemed included in quoted rate. (2) Measurement for removing vegetation/ shrubs/brush shall be measured once only for entire period of completion.
M&L for preparing old painted steel surfaces and applying two coats of aluminium paint to steel tubular/rail pole complete with connected fittings such as brackets ,channels complete all as directed by Engineer-in-Charge
S&F in replacement of old steel tubular swaged pole complete with cast iron base plate , finial taper plug bolts nuts and screws as specified type 410 SP-31 (9m long) confirming to IS : 2713 and made out of structural steel tube confirming to IS: 1161 and painted internally with a coat of bituminous paint and externally one primer coat, one under coat and one finishing coat of aluminium paint as specified. Note : Excavation and earth work and PCC will be measured and paid separately.
M & L for PCC M-7.5 grade (nominal mix) using 40mm graded stone aggregrate as in foundation for filling in, mass concrete for foundation of pole, transformer, panel board, stay, post top lantern, repairs to road cutting, drain path etc complete all as specified and as directed.
M & L for PCC M-15 grade (nominal mix) using 20mm graded stone aggregrate as in coping of new pole including necessary form work complete all as specified and as directed.
Taking down unserviceable LT panel and Supply, install, commissioning and testing of LT outdoor type feedar pillar box 415 V/440 Volts outer size of 1.2 x 0.9 x 0.45 m , IP-65 protection of suitable size made out of 3 mm thick CRCA sheet with both side openable door with locking arrangement and complete panel should be powder coated with having neoprene rubber gasket for sealing door, doors of the panel should be removable type, including 300 A current capacity Aluminium bus bar for 3 Nos phase, 1 No of neutral of suitable size horizontal and vertical mouniting on suitable capacity of insulators, Ammeter & voltmeter of 0.5 A accuracy with suitable size of Current Transformers copper wounded, resin cast, RYB indicators lamp in each in and outgoing etc with provision for 01 No Incoming 250 Amp 4 Pole 36 KA & 4 Nos of 63 Amp,16 KA 4 Pole MCCBs outgoing with Analog street light timer , control panel wiring with PVC insulated multi standard copper conductor IS mark, internal compartment for mounting MCCBs/MCBs and bus bars using 2 mm thick CRCA sheet, the panel shall be mounting on 50 x 50 x 6 mm MS angle iron and 60 cm above the normal ground level & embedded 20 cm below ground level in PCC foundation M-15 grade (Nominal Mix) using 20 mm graded stone aggregate, connect new UG cable for Incoming from panel and out going four nos thorugh MCCB cable shall enter through cable glands for safety of cable where enter through panel complete all as specified and directed by Engineer-in-Charge
Taking down unserviceable Bus bar panel and Supply, install, commissioning and testing of Bus bar panel box 415 V/440 Volts outer size of, 0.90 x 0.90 x 0.45m confirming to IEC 61439 with IP-65 protection of suitable size made out of 3 mm thick CRCA sheet with locking arrangement and complete panel should be powder coated with having neoprene rubber gasket for sealing door, doors of the panel should be removable type, including 300 A current capacity Aluminium bus bar for 3 Nos phase, 1 No of neutral of suitable size horizontal and vertical mouniting on suitable capacity of insulators, RYB indicators lamp in each in and outgoing with provision for 01 No Incoming 125 Amps, 16 KA, 04 pole, outgoing MCCB's 63 Amps 3 Pole, 10KA-4 Nos outgoing, control pannel wiring with PVC insulated multi standard copper conducted cable IS mark, internal compartment for mounting MCCBs/MCBs and bus bars using 2 mm thick CRCA sheet, the panel shall be mounting on 50 x 50 x 6 mm MS angle iron and 60 cm above the normal ground level & embedded 20 cm below ground level in PCC foundation M-15 grade (Nominal Mix) using 20 mm graded stone aggregate, connect new UG cable for Incoming from panel and out going ten nos thorugh MCCB cable shall enter through cable glands for safety of cable where enter through panel complete all as specified and directed by Engineer-in-Charge
Note for item No 53 & 54:- (i) Cable termination with double crimp gland (ii) Current Transformer should be caliberated and tested on MSEDL certificate should produce by contractor. (iii) Panel should be CPRI certified.
Supply and fixing in existing panel Digital LED voltmeter Flush mounting 96 x 96 mm L&T cat no WL131020OOOO Cl 0.5 accuracy all as specified and directed by Engineer-in-Charge
Supply and fixing in existing panel Digital LED amp meter Flush mounting 96 x 96 mm L&T cat no WL132020OOOO Cl 0.5 accuracy all as specified and directed by Engineer-in-Charge
Excavating in trenches n exc 1.5m wide and not exc 1.5m in depth; for foundation etc or for shafts wells, cesspits, manholes ier holes etc 10 Sq m on plan and exc 1.5m in depth and getting out in hard rockcomplete all as directed.
M & L for preparing old painted steel surfaces and applying two coats of aluminium paint to chain link fancing and supporting angles (Iron/ concrete) complete complete all as directed by Engineer-in-Charge
N D ELECTRICAL
M/S kirpan Enterprises
metro electrical services
ASHWINI ELECTROMECH ENGINEERING SERVICES
Adinath Technical Services
M/S. Niksun Electro-Infra Private Limited
Mahindra Electric Stores
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .