| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹37.7 LAccepted-AOC | L1 | Accepted-AOC L1 | |
| 2 | L2₹41.6 L+₹3.9 L (10.4%)Rejected-AOC | L2 | Rejected-AOC L2 |
Tender Value
₹35.9 L
EMD Value
₹71,763
Closing Date
21 Jun 2022, 4:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Executive Engineer, Elect. Div.V, Bicholim
O/o Executive Engineer, Elect. Div.V, Bicholim
Work of erection of new 200KVA DTC near Village Panchayat Pilgao, new 100KVA DTC at Hindlewada, Mayem and enhancement of DTC capacity from 100KVA to 200KVA at Gaonkarwada, Mayem
2022_ED_3806_1
Tender-03/Div-V (2022-23)
Open Tender
Electrical Works
Item Rate
90 days
MAYEM CONSTITUENCY
As per NIT
4 documents required · 4 mandatory
₹500
₹71,763
22 Sept 2023
28 Apr 2022
25 Jun 2022
29 Apr 2022
21 Jun 2022
9 May 2022
180 days
Amount
COST OF MATERIAL
A) Work of erection of 200 KVA Distribution Transformer Centre near V.P PILIGAO
Supply of HDGI DP structure material
Supply of 11kv disc insulator 70KN with metal parts
Supply of 11 KV , 200 A Horn gap fuse unit (Set of three)
Supply of Distribution Transformer 200 KVA 11/0.44 KVA Aluminium wound, Energy efficiency Level II as per IS 1180(part-I); 2014
Supply of MS Distribution box with MCCB 400 A & kit-kat fuses
Supply of ACSR 'WEASEL' Conductor. 6/1/2.59 (nominal aluminium area 30 Sq.mm.) (139 amp max at 45 °C) for earth wires and guard loops
Supply of XLPE Single Core unarmoured XLPE 240 sq mm 1.1KV grade (4-run)
Supply of XLPE Single Core unarmoured XLPE 120 sq mm 1.1KV grade (12-run)
Supply of Al. Crimping lug 240 sq.mm
Supply of Al. Crimping lug 120 sq.mm
Supply of Anti climbing device alongwith suitable two stay clamps & two pairs of H.D.G.I nuts bolts as per drg No. CEE/E-478
Supply of Enamelled danger boards 11000 Volts as per drg no. CEE/E-490
Supply of G.I. Earthing pipe 8' long 40 mm. Dia class B, Fabricated & perforated including alternate layers 30 Cm. Thick of charcoal, salt, & earth (charcoal & salt 10 Kgs. each for per pit) inclusive of excavation, backfilling and spreading of excavated earth evenly.
Supply of Distribution Transformer Metering unit with DLMS/COSEM protocol energy meter with modem
Supply of 11KV /LT HDG stay set complete with HDG stay rod & HDG plate , break insulator 8 KV, HDG stay clamps , HDG nut bolts & HDG stay wire 7/10 SWG etc for 11mtr long RCC pole
Supply of H.S.11KV Termination kit outdoor 120 to 185sqmm XLPE 3 core
Supply of HDGI stay clamps for RCC pole11m L.A
Supply of cut point channel forRCCpole 11m
Supply of JT KIT O/D HT ABC of 70,95&120 sqmm
Supply of top fitting X arm channel for 11m RCC pole with clamps and nutbolts
Supply of HDGI 11KV V-shape X-arm with clamp & nutbolt 11m pole
Supply of 11KV pin insulator with G.I pin
Supply of LT shackle insulator with HDG metal parts
B) Work of erection of 100 KVA Distribution Transformer Centre Hindlewada
Supply of HDGI DP structure material
Supply of 11kv disc insulator 70KN with metal parts
Supply of 11 KV , 200 A Horn gap fuse unit (Set of three)
Supply of Distribution Transformer 100 KVA 11/0.44 KVA Aluminium wound, Energy efficiency Level II as per IS 1180(part-I); 2014
Supply of MS Distribution box with MCCB 200 A & kit-kat fuses
Supply of ACSR 'WEASEL' Conductor. 6/1/2.59 (nominal aluminium area 30 Sq.mm.) (139 amp max at 45 °C) for earth wires and guard loops
Supply of XLPE Single Core unarmoured XLPE 240 sq mm 1.1KV grade (4-run)
Supply of XLPE Single Core unarmoured XLPE 120 sq mm 1.1KV grade (12-run)
Supply of Al. Crimping lug 240 sq.mm
Supply of Al. Crimping lug 120 sq.mm
Supply of Anti climbing device alongwith suitable two stay clamps & two pairs of H.D.G.I nuts bolts as per drg No. CEE/E-478
Supply of Enamelled danger boards 11000 Volts as per drg no. CEE/E-490
Supply of G.I. Earthing pipe 8' long 40 mm. Dia class B, Fabricated & perforated including alternate layers 30 Cm. Thick of charcoal, salt, & earth (charcoal & salt 10 Kgs. each for per pit) inclusive of excavation, backfilling and spreading of excavated earth evenly.
Supply of Distribution Transformer Metering unit with DLMS/COSEM protocol energy meter with modem
Supply of 11KV /LT HDG stay set complete with HDG stay rod & HDG plate , break insulator 8 KV, HDG stay clamps , HDG nut bolts & HDG stay wire 7/10 SWG etc for 11mtr long RCC pole
Supply of LT shackle insulator with HDG metal parts
Supply of HDGI stay clamps for RCC pole9m L.A
Supply of H.S.11KV Termination kit outdoor 120to 185XLPE 3 core
Supply of H.S.11KV Straight through joint 3 core 120to 185sqmm
Supply of XLPE cable 11kv armoured 3 c X185sq.mm
Supply of cut point channel forRCCpole 9m
Supply of Sand for cushioning of HT underground cables.0.1*0.45*850
Supply of Kaddapa of size 600mm length x 250mm width x 50mm thick as a protective cover for underground cables.
Supply of Cable Route marker
Supply of Warning tape.
C) Work of enhancement of transformer capacity from 100 KVA to 200 KVA at Gaonkarwada, Mayem.
Supply of Distribution Transformer 200 KVA 11/0.44 KVA Aluminium wound, Energy efficiency Level II as per IS 1180(part-I); 2014
Supply of Distribution box (M.S) with 400 Amps MCCB & Kit kat fuses
Supply of Al. Crimping lug 300 sq.mm
Supply of Al. Crimping lug 120 sq.mm
Supply of XLPE Single Core unarmoured XLPE 300sq mm 1.1KV grade (3-run)
Supply of XLPE Single Core unarmoured XLPE 150sq mm 1.1KV grade (3-run)
Supply of XLPE Single Core unarmoured XLPE 95sq mm 1.1KV grade (3-run)
Supply of XLPE Single Core unarmoured XLPE 120 sq mm 1.1KV grade (9-run)
COST OF ERECTION
A) Work of erection of 200 KVA Distribution Transformer Centre near V.P PILIGAO
Erection of HDGI DP structure material
Erection of 11 KV rated voltange GOAB switch 200 A with operating pipe support of class B, 25 mm dia.
Erection of 11kv disc insulator 70KN with metal parts
Erection of 11 KV , 200 A Horn gap fuse unit (Set of three)
Erection of 9 KV, 5 KA Lightning arrestor pole mounted
Erection of Distribution Transformer 200 KVA 11/0.44 KVA Aluminium wound, Energy efficiency Level II as per IS 1180(part-I); 2014
Erection of MS Distribution box with MCCB 400 A & kit-kat fuses
Erection of ACSR 'WEASEL' Conductor. 6/1/2.59 (nominal aluminium area 30 Sq.mm.) (139 amp max at 45 °C) for earth wires and guard loops
Erection of XLPE Single Core unarmoured XLPE 240 sq mm 1.1KV grade (4-run)
Erection of XLPE Single Core unarmoured XLPE 120 sq mm 1.1KV grade (12-run)
Erection of Anti climbing device alongwith suitable two stay clamps & two pairs of H.D.G.I nuts bolts as per drg No. CEE/E-478
Erection of Enamelled danger boards 11000 Volts as per drg no. CEE/E-490
Erection of G.I. Earthing pipe 8' long 40 mm. Dia class B, Fabricated & perforated including alternate layers 30 Cm. Thick of charcoal, salt, & earth (charcoal & salt 10 Kgs. each for per pit) inclusive of excavation, backfilling and spreading of excavated earth evenly.
Erection of RCC pole 11m long
Erection of Distribution Transformer Metering unit with DLMS/COSEM protocol energy meter with modem
Erection of 11KV /LT HDG stay set complete with HDG stay rod & HDG plate , break insulator 8 KV, HDG stay clamps , HDG nut bolts & HDG stay wire 7/10 SWG etc for 11mtr long RCC pole
Erection of H.S.11KV Termination kit outdoor 120 to 185sqmm XLPE 3 core
Erection of HDGI stay clamps for RCC pole11m L.A
Erection of cut point channel forRCCpole 11m
Erection of JT KIT O/D HT ABC of 70,95&120 sqmm
Erection of top fitting X arm channel for 11m RCC pole with clamps and nutbolts
Erection of HDGI 11KV V-shape X-arm with clamp & nutbolt 11m pole
Erection of 11KV pin insulator with G.I pin
Erection of LT shackle insulator with HDG metal parts
Erection of HDG LT 2 pin X-arm channel type with HDG clamps nut- bolts for 11mtr long RCC pole
Erection of HDG LT 4 pin X-arm channel type with HDG clamps nut- bolts for 11mtr long RCC pole
B) Work of erection of 100 KVA Distribution Transformer Centre Hindlewada
Erection of HDGI DP structure material
Erection of 11 KV rated voltange GOAB switch 200 A with operating pipe support of class B, 25 mm dia.
Erection of 11kv disc insulator 70KN with metal parts
Erection of 11 KV , 200 A Horn gap fuse unit (Set of three)
Erection of 9 KV, 5 KA Lightning arrestor pole mounted
Erection of Distribution Transformer 100 KVA 11/0.44 KVA Aluminium wound, Energy efficiency Level II as per IS 1180(part-I); 2014
Erection of MS Distribution box with MCCB 200 A & kit-kat fuses
Erection of ACSR 'WEASEL' Conductor. 6/1/2.59 (nominal aluminium area 30 Sq.mm.) (139 amp max at 45 °C) for earth wires and guard loops
Erection of XLPE Single Core unarmoured XLPE 240 sq mm 1.1KV grade (4-run)
Erection of XLPE Single Core unarmoured XLPE 120 sq mm 1.1KV grade (12-run)
Erection of Anti climbing device alongwith suitable two stay clamps & two pairs of H.D.G.I nuts bolts as per drg No. CEE/E-478
Erection of Enamelled danger boards 11000 Volts as per drg no. CEE/E-490
Erection of G.I. Earthing pipe 8' long 40 mm. Dia class B, Fabricated & perforated including alternate layers 30 Cm. Thick of charcoal, salt, & earth (charcoal & salt 10 Kgs. each for per pit) inclusive of excavation, backfilling and spreading of excavated earth evenly.
Erection of RCC pole 9m long
Erection of RCC pole 11m long
Erection of Distribution Transformer Metering unit with DLMS/COSEM protocol energy meter with modem
Erection of 11KV /LT HDG stay set complete with HDG stay rod & HDG plate , break insulator 8 KV, HDG stay clamps , HDG nut bolts & HDG stay wire 7/10 SWG etc for 11mtr long RCC pole
Erection of LT shackle insulator with HDG metal parts
Erection of HDGI stay clamps for RCC pole9m L.A
Erection of H.S.11KV Termination kit outdoor 120to 185XLPE 3 core
Erection of H.S.11KV Straight through joint 3 core 120to 185sqmm
Erection of XLPE cable 11kv armoured 3 c X185sq.mm
Erection of cut point channel forRCCpole 9m
Erection of HDG LT 2 pin X-arm channel type with HDG clamps nut- bolts for 11mtr long RCC pole
Erection of HDG LT 4 pin X-arm channel type with HDG clamps nut- bolts for 11mtr long RCC pole
Erection of Excavation in any type of soil including hard laterite soil. (Dimensions : 1.0*0.45*850)
Erection of Refilling of excavated soil (Dimensions : 0.9*0.45*850)
Erection of Cable Route marker
C) Work of enhancement of transformer capacity from 100 KVA to 200 KVA at Gaonkarwada, Mayem.
Erection of Distribution Transformer 200 KVA 11/0.44 KVA Aluminium wound, Energy efficiency Level II as per IS 1180(part-I); 2014
Erection of Distribution box (M.S) with 400 Amps MCCB & Kit kat fuses
Erection of Removing of MS distribution box
Erection of Removal Distribution Transformer 100 KVA 11/0.44 KVA Aluminium wound, Energy efficiency Level II as per IS 1180(part-I); 2014
Erection of XLPE Single Core unarmoured XLPE 300sq mm 1.1KV grade (3-run)
Erection of XLPE Single Core unarmoured XLPE 150sq mm 1.1KV grade (3-run)
Erection of XLPE Single Core unarmoured XLPE 95sq mm 1.1KV grade (3-run)
Erection of XLPE Single Core unarmoured XLPE 120 sq mm 1.1KV grade (9-run)
Shri Mahalaxmi Enterprises
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .