Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
| 3 | Rejected-Technical | Rejected-Technical NON RESPONSIVE |
Tender Value
₹15.5 L
EMD Value
₹31,000
Closing Date
24 Feb 2020, 6:00 pmClosed
ER.MUJIB A TAK
O/o DEPUTY DIRECTOR TOURISM, M AND W JAMMU
Illumination facility from National Highway to Club Building at Jammu Tawi Golf Course, Sidhra
2020_Tourm_92841_1
e-NIT No. 101 of 2019-20 Dated-14-02-2020
Open Tender
Electrical Works
Item Rate
30 days
GOLF COURSE SIDHRA
Please refer Tender documents.
3 documents required · 3 mandatory
₹500
Yes
DEPUTY DIRECTOR TOURISM M AND W JAMMJU
₹31,000
28 Feb 2020
15 Feb 2020
25 Feb 2020
15 Feb 2020
24 Feb 2020
15 Feb 2020
Amount
Supply, installtion of Hot dip Galvanised 16m High Mast for LED flood lights with motorised carriage of approved makes with its accessoreis, Mast shall be in two section hot dip galvanised and suitable for wind velocity as per IS:875 (i.e. 55 m/sec). It should also include accessories of the high mast including head frame, steel wire rope 6mm (dia 7/19 construction), Trailing cable, double drum winch, galvanised luminaire Carriage sutiable for required luminaries symmetrically as shown in the lighting design and its control gear boxes, lighting final. The mast shall have integral power tool installaled in the base compartment for its operation including one set (6 No.) of foundation bolts manufactured from special steel along with nuts,washers, anchor plates and templates. Make:SYSKA/Bajaj/Surya.Complete as per the instructions of Engineer Incharge.
Providing reinforced cement concrete foundation of size and design as per drawing approved by OEM original Equipment manufacturer which should be strickly followed.
Supply,installtion,testing and commissioning of 250W LED flood lights with min 120 lumens/watt with LM 79 and LM 80report with min IP 65 protection. Make:Syska/Panasonic/Philips/Bajaj/IB Complete as per the instructions of Engineer Incharge.
Sypply,installtion, testing and commissioning of floor Mounted Outdoor Type Double Door Low voltage outdoor panel IP54 Suitable for operation on 433V 4 Phase, 50Hz Supply, Made for 2.0mm CRCA Sheet enclosure with luminium bus bar four wire with following switchgears and metering. Necessary arrangement be made for termination of incoming cable and outgoiing cables. LT Panel shall be manufactured as per IS8623. Complete as per the instructions of Engineer Incharge.
Incomer
63 A 4 Pole MCCB 25-KA-1 No.
60A 4 Pole contractor-1 No.
Digital Astronomical based time switch equivalent to 1 Channel Alpharex Astro-1 No. Make : L&T, Legrand, Siemens
Surge protection Device Class B+C 3P+N Legrand/OBO/JMV
Bushar shall be Almunium TPN 200A duly supported on DMC insulators and covered with heat shrinkable color coded PVC sleeves
Outgoings
32A 2 Pole MCB 10 KA-10 Nos
32 A 4 Pole MCB 10-KA-1 No
Make of MCCB/Contractor/TimeSwitch/SPD: Schneider (Acti-9), Legrand (DPX3), Siemens (Betagard)/L&T/C&S
One No industrial socket of min 20 A cap.
Supply and laying of 3 core 2.5 sqmm cable form panel to LED Lights including connection at both ends.
Supply and laying of main cable from existing transformers station pannel up to proposed site of panel for high mast lighting with 4 X 35 Sq mm Aluminium Armoured cable (Make Polycab/KEI/Gloster) laid in HDPE Pipe (ISI mark PN 8) of 4" by digging trench of 0.75 mtx x 1mt through the main panel with MCCB 4P, 63A. Complete as per the instructions of Engineer Incharge.
Chemical type Maintainance free earthing with 3 MTR 50 MM GI electrode with connection of panel/high mast with 25 x 3 mm GI Strip make JMVGMAX/OBO with CPRI approved and NABL certified test report. Complete as per the instructions of Engineer Incharge.
Construction of platform of Size 10' X 8'X4' including brickwork and P.C.C of M-10 P.C.C Grade (1:3:6) 1 Cement, 3 Sand, 6 crushed course stone agg. Including earthwork as directed by the engineer-in-charge and laying of 40 mm thick cement concrete flooring 1:2:4 finished with a floating coat of neat cement slurry on top and plastering the exposed sides with cement mortar 1:4 complete in all respects alongwith steps.
Supply and laying of 240 sq.mm 3.5 core aluminium armoured cable with thimbling and tapping as required at site and laying it in PVC Pipe (Astro/Supreme/Prince/Filonex with pressure capacity 110cm.sq) of 160 mm by digging trench of 1 mtr deep and 0.75 mtr wide and covering it back as it was earlier. Make : Polycab/KEI/Gloster
Supply, Testing, Fixing and commission of 350 watt LED Flood light with average lux not less than 110 lumens/watt. The light must be outdoor type vibration, surge and weather proof with high energy efficient capable of illumination open field for playing at night with IP 66 level of protection. Make philips, cromption, IBled, Havells, Syska
Supply, Testing, Fixing and comissiong of 240 X 3.5 Core outdoor type termination kit MAKE 3m, Raychem, Yamuna Densons.
LT Panel
Panel 1:
Incomer : 200 A 4 Pole MCCB 50 KA
Outgoing :
1) 6A/16/32A SP 10 KA C Curve MCB : 4 No
2) 32 A 4 Pole 18 KA MCCB : 1 No
3) Motor Starter of 1 HP DOL
4) Motor Starter of 10 HP FASD Type
SPD with B+C protection (make : JMW/OBO/Teracel)
The panel should have provision for incomer cable of 3.5 c 35mm sq for the outgoing cable as per the outgoing No. of MCB AND MCB
One No industrial socket of min 20 A cap.
Panel should be made of CRCA 1.6 mm thick sheet and duly painted with two coats of powder coating, outdoor type, with stand made of 50 mm x 6 mm thick angle to be grouted at height of 2 feet from ground level. The panel should be outdoor type with double door arrangement, dust and vermin proof with ammeter and voltmeter for each phase (CPRI APPROVED)
Make: Power control system/Jaima/Gupta and Friends. JK Power Control. Make for switch Gear/MOTOR STARTER : BCH/ABB/ L&T
GLOBAL ENGINEERS
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .