Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹5.3 LAccepted-AOC SURVEY NO 93 392 PACHMARHI NEAR MILITARY HOSPITAL PAHMARHI HOSHANGABAD M P 461 881 | PACHMARHI | HOSHANGABAD | MADHYA PRADESH | 461881 | L1 | Accepted-AOC L1 | |
| 2 | L2₹5.5 L+₹11,606.50 (2.14%)Rejected-Finance 53 SHANTI S SANIK COLONY BAIRAGARH BHOPAL MP 462 030 | BHOPAL | BHOPAL | MADHYA PRADESH | 462030 | L2 | Rejected-Finance Not Admitted | |
| 3 | L3₹5.7 L+₹25,294.60 (4.67%)Rejected-Finance | L3 | Rejected-Finance Not Admitted | |
| 4 | L4₹5.9 L+₹52,164 (9.64%)Rejected-Finance | L4 | Rejected-Finance Not Admitted | |
| 5 | L5₹6.0 L+₹54,320.50 (10.0%)Rejected-Finance | L5 | Rejected-Finance Not Admitted |
Tender Value
Refer Docs
EMD Value
₹13,400
Closing Date
7 Dec 2021, 6:00 pmClosed
AGE Indpt Pachmarhi
AGE Indpt Pachmarhi Dist- Hoshangabad (MP)-461881
REPAIR/MAINT OF KIRAN COLONY PUMP HOUSE AND PANDAV CAVE PUMP HOUSE WITH ALLIED WATER SUPPLY PIPE LINE IN CONNECTED AREAS AT AEC TRG COLLEGE AND CENTRE PACHMARHI.
2021_MES_487526_1
CA No. AGE(I)/PACH/ of 2021-22(8440/E8)
Open Tender
Civil Works - Water Works
Item Rate
180 days
Pachmarhi MP
Class E Category a(ii)
8 documents required · 8 mandatory
₹500
AGE Indpt Pachmarhi
₹13,400
Yes
22 Apr 2022
10 Nov 2021
9 Dec 2021
10 Nov 2021
7 Dec 2021
24 Nov 2021
Amount
M&L for taking out old unserviciable burnt winding of centrifugal motor, 3 phase, 415 volts, 50 Hz, AC supply after disconnecting all electrical connections and rewinding by using super enamelled copper conductor of existing gauge and size by maintaining existing turn ratio, applying insulation varnish and drying up to specified period to achieve desired insulation value including reassembling of motor after rewinding and testing before reinstalation and including all electrical connection using suitable size of lugs complete complete all as specified and as directed of following capacity :-
10 HP capacity.
15 HP capacity.
M&L for transporting Submersible/ Centrifugal Pump Set any capacity from Pump House/ E&M store yard at Pachmarhi to Pipariya and back (nearest workshop) for repairing including carefully loading/ unloading etc complete all as specified and as directed.
M&L for lifting out/ taking up carefully submersible Pump Set and motor by deploying skilled labour from bore well after disconnecting electrical and pipe line conections, with the help of chain pully block with tripod including column pipe and submersible cable from 220-260 feet approx depth, disconnecting pump and motor from coupling and keeping aside for testing / checking submersible pump set and other connected acessories for servicibility complete all as specified and as directed.
M&L for dismantling of motor, checking rotar, stator, thrust bearing and other parts for its serviceability complete all as specified and as directed.
M&L for taking out old unserviciable burnt winding of submersble motor 7.5/10 / 12 / 12.50 HP, 3 phase 415 volts, 2900 RPM, 50 Hz AC supply and rewinding by using copper super enamelled conductor PVC insulated of existing gauge and size by maintaining existing turn ratio and reassembling of submersible motor after rewinding by replacing following burn out parts complete all as specified and as directed. Note : Spares required shall be measured and paid separately under appropriate item of BOQ/ Sch 'A'.
Supply only following submersible motor spares/ parts (As per existing make / type and size) complete all as specified and as directed :-
Thrust bearing.
Sand guard.
Coupling assy made out of stainless steel with key.
M&L for dismantling of pump, checking impeller, distance sleeves, bush and other parts for its serviceability complete all as specified and as directed.
M&L for reassembling of submersible pump after repairing and by replacing burnt out parts complete all as specified and as directed. Note : Spares required shall be measured and paid separately under appropriate item of BOQ/ Sch 'A'.
Supply only following submersible pump spares/ parts (As per existing make / type and size) complete all as specified and as directed :-
Housing bush brass.
Stage bush.
Distances sleaves.
Impeller.
M&L for assembling pump and motor after repairing and testing at workshop by technician complete all as specified and directed.
M&L for lowering down, submersible Pump Set and motor by deploying skilled labour inside bore well, with the help of chain pully block with tripod including column pipe and submersible cable up to approx depth 220', after connecting pump and motor with coupling, and making electrcal and pipe line connections etc complete all as specified and directed. Note : Materials required shall be measured and paid separately under appropriate item of BOQ/ Sch 'A'.
Submersible cable, PVC insulated, multistranded copper conductor, 1100 volts grade, 3 core flate of size 6 Sqmm. Make: Havells,RR kabel,Polycab
S&F in repair foot valve, ISI Marked, GI/ CI body, heavy duty having one eng flanged or internal screwed suitable to fix in suction pipe and other side strainer with leather flape and counter weight including all fixing arrengements as new nuts, bolts, washers and gasket including testing complete all as specified and directed for following size :-
100mm bore
150mm bore
S&F in repair Automatic star delta starter in sheet metal enclosure, suitable for submersible/ centrifugal pump set with relay, contactor, auxilary contactor suitable to run on 440 volts, 50 Hz, AC supply complete all as specified and directed. Make : L&T (ML 1.5) or equivalent make as specified.
Taking down base frame of centrifugal pump set from pump house after dismantling of pump and motor after disconnecting electrical and water supply connection and M&L for fabrication of base frame from structural steel as per existing shape and size including cutting, drilling, welding, replacement of foundation nut and bolts etc including refixing of pump and motor on new base frame making proper aligngnment and further fixing on PCC foundation and making electrical and water supply connection complete all as specified and directed. Note: Cost of PCC foundation is deemed to be included in the quoted rate.
Excavating in post holes (or similar holes) each n exc 0.5 cu. m, getting out, returning,filling in and ramming earth or broken rubble mixed with earth around, in layers not exceeding 25 cm and getting out in soft/loose Soil
M &L for cement concrete type C2 1:3:6 (using 40 mm graded granite stone aggregate ) in foundation,filling and mass concrete.
S&F Rolled sections as in main and cross beams, hip and jack rafters; purlins where connected to common rafters and running rails and guides for sliding doors; fixed with angle cleats or other connecting plates
Pre- painted galvatume aluminum zinc coating GI based corrugated steel sheet 0.50mm thick of an colour having tensile strength of 550 Mpa as in roof covering/cladding to wall, fixed with self tapping screws as specified
Painting of steel surface of any description, over 10cm in width or girth apply two coat of synthetic enamel paint over a coat of red oxide primar.
Demolition of brickwork or stone boulder masonry, built in cement mortar or cement lime mortar including all quoins,arches, pillars,etc. but excluding ashlar facings, dressed stonework and precast concrete articles complete all as specified and directed.
M&L for brick work with modular size full brick subclass ‘B’ bricks, straight or curved on plan exc 6m mean radius, built in CM (1:6) complete all as specified and directed.
Taking down cement/ lime plaster of any description on brick work or stone walls etc including racking out joints hacking for key scrubbing down with water etc complete all as spfd directed.
M&L for 15mm thick rendering on surfaces of brick work or stone walling in CM 1:6 finishing the surface fair & even complete all as spfd and directed.
Framed work as in doors or gates of angle or other section with gusset plates, rails, braces, etc., complete, drilled for fixing of steel sheeting or other covering, Doo0rs etc. to be prepared for hanging or sliding with and including either hooks and hinges or steel hanging door fittings (exclusive or steel sheeting or other covering, running rails and guides) and hanging; also fastening and fixing complete all as specified and directed.
M & L for demolition of concrete in ground floors and pavings n exc 15 cm thickness (below or above ground level) complete all as specified and directed
M&L for PCC 1:4:8 type D-2 using 40mm graded stone aggregate as in flooring on existing sub base surfaces of OH tank,pump houses finished cement concrete surface even and smooth without using extra cement including necessary form work and concrete (PCC) to be cast in alternate bays complete all as specified and directed. complete all as specified and directed.
M&L for machine pressed precast concrete interlocking paver block any shape and size confirming to IS 15658-2006 of 60 mm thickness, M-35 Grade complete all as specified and directed.
M&L for moorum filling floors or pavings laid in layers n exc 15 cm thick , spread, levelled, and blind earth and rammed in cluding watering all as spesified and directed by Engr -In- Charge.
M&L for PCC 1:3:6 type C-1 using 20mm graded stone aggregate as in thrust block to support the pipe at corner and junctions, copings, benching, bed plates, bond stones, kerbs or mud stops etc and the like including weathering slightly rounded/ chamfered angles with & including necessary use and waste of form work for fair faces of concrete, complete all as specified and directed.
S&F 3.15 mm dia galvanised steel wire chain link fencing(wire mess size100x100mm)incl line wire (stiffness 10mm MS round bar/tor bar) 4 Nos horrizontly all as specified and directed
S&F joist, chanel, MS pipe, angle or tee sections as in post and structs in fencing incl cutting of to shape as directed drilling holes knotching for wire etc, flat iron fillete (for securing wire mesh/chain-link fencing etc) incl all necessary drilling, riveting,nut bolt etc and similar work confirming to Gde-Fe-410-0 or Fe-310-0.
M&L two coats of synthetic enamel paint over one coat of red oxide primer on steel surfaces exc 10cm width or girth including preparation of steel surfaces, complete all as spfd and directed.
S&F in repairs galvanised 2 strand, steel barbed wire 2.24 mm dia barbed with 2 mm dia barbs at 75 mm spacings and straining and fixing to any type of standard rails straining bolts, including securing or tying at crossing with and provision of galvanised mild steel wire, staples or steel pins etc as directed. (Each line wire to be measured separetaly)
Supply, fixing / laying, jointing and testing of GI pipes, medium grade, ISI marked with all fittings fixed on wall/ roof or laid in trenches/ floors complete all as specified including taking out the old pipe as directed for the following size :-
50mm bore
25mm bore
20mm bore
S&F in repair sluice valve 100 mm dia ISI Marked (IS 14846-2000), Class PN-1.6, both ends flanged with CI body, stainless steel spindle, chucknut and iron wheel etc including provision of new nuts, bolts, washers and gasket including testing complete all as specified and directed.
S&F in repair sluice valve 150 mm dia ISI Marked (IS 14846-2000), Class PN-1.6, both ends flanged with CI body, stainless steel spindle, chucknut and iron wheel etc including provision of new nuts, bolts, washers and gasket including testing complete all as specified and directed.
S&F in repair Gun metal globe or gate valve with iron wheel head, ISI marked screwed both ends for iron pipes and fixed including taking down the old one complete all as specified and directed for the following size:-
50mm bore
25mm bore
20mm bore
M & L for Excavation for taking out/laying cable in trenches in soft/loose soil not exc 1.5 m wide and not exceding 1.5 m deep for LT 1100 V under ground cable /GI pipe complete all as specified and directed by Engineer-in-Charge
Returning filling in including spreading, watering and well ramming in layers not exc 25 cm complete all as specified and directed.
Removing surplus soil to distance not exceeding 50 M and depositing where directed at a level not exceeding 1.5m above the starting point complete all as specified and directed.
S & F sub main wiring using approved colour coding (Phase-red,Neutral-black,Earth-green) complete with two single core FRLS PVC insulated and unshealthed stranded copper conductor cable 4 sqmm as current carrying conductor and one run of 4.0 sqmm as earth contunity conductor ,voltage rating 1100 volt ,ISI marked drawn in and including concealed PVC conduit ISI marked of dia not less than 25 mm and thickness 1.8 mm with stranded accessories along with one run of FRLS PVC green colour insulated,unshealthed,stranded copper conductor of size 4 sqmm all as specified and directed .Note: Two run of single core FRLS PVC cable with one run of earth contunity conductor and conduit shall be measured as one unit. Make of wire:HAVELLS/PLAZA/FINOLEX
Supply and fixing in replacement Ceiling rose surface bakelite three terminal ,complete all as specified and directed. Make:HAVELLS/ANCHOR/PLAZA
M&L for earthing complete with galvanized steel earth plate 600x600x6 mm thick, buried directly in ground (earth pit not less than 2.25 mtr deep below ground level ) with top edge of the plate not less than 1.5 meters below normal ground level, connected to galvanised iron strip 25X4 mm dia as earthing lead by means of bolts, nuts, check-nuts, and washers of galvanised iron or steel besides welding at all joints as shown in drawings and including excavation and earth work, GI pipe light grade 40 mm bore for protection of GI strip from earth electrode to and including the earth test point of galvanised Iron/steel . supplying and laying charcoal stone aggregate) chamber and RCC cover of size 54x54x50 mm (1:2:4) type B1 using 20 mm graded crushed stone aggregate reinforced with 8 mm dia TMT bars @ 75mm C/C both ways with mild steel handle 12 mm dia, PGI funnel with wire mesh, 20 mm dia GI pipe medium grade for watering all as shown in drawing including taking out the old one. Note - Cost of GI strip and GI protection pipe up to a distance 7.5 M shall be included in quated rate of above Items.
Material and labour for GI earthing strip of size 25X4 mm including nesassary brazing and connecting existing earthing system including taking out the old one complete all as specified and directed by Engineer-In-Charge.
M/S Shanti Enterprises
GHASI RAM SAHU
M/S RAKESH TRADERS
ROYAL CONSTRUCTION
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .