| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹50.4 LAdmitted-Finance 894 NEAR 132 KV POWER HOUSE SINDHARI ROAD BALDEV NAGAR BARMER RAJ 344001 | BARMER | RAJASTHAN | 344001 | ₹50.4 L | L1 | Admitted-Finance |
| 2 | L2₹56.1 LAdmitted-Finance NO 28 KUMHARON KI BASTI DHOONDHA BARMER RAJASTHAN 344035 | BARMER | RAJASTHAN | 344035 | ₹56.1 L | L2 | Admitted-Finance |
| Sl No | Description | Qty | Unit | DEVARAM CONSTRUCTION COMPANY L2 | GITANSH ENGINEERS AND COMPANY L1 |
|---|---|---|---|---|---|
| 1.00 | Supply, install, testing & commissioning of LT control panel board "out-door type" of size 1800 mm (height) x 1500 mm (breadth) x 500 mm (depth) (minimum dimensions), factory fabricated CPRI approved (type-tested) with suitable neoprene rubber gasket to make it completely dust & vermin proof & degree of protection not less than IP-55 & general construction confirming to IS-13947, double door, front & back openable. The panel shall be provided with ventilation facility in the form of louvers for better heat dissipation & high grade Copper bus-bar wrapped with coloured PVC tape /sleeves of rating in conformity to the Incoming ACB/MCCB rating. The panel board shall be fabricated out of 3.15 mm thick (for outer portions) & 2.00 mm thick (for inner portions) CRCA sheet duly pre-treated & powder coated, supporting angle iron frame of size 50X50X6mm fixed at 75 cm height from groud level & MC channel base suitable for 3 Phase, 4 wire system 415 /440 volts grade including complete internal wiring with not less than 2.5 Sqmm copper wire including cable glands and lugs of suitable sizes with suitable PCC (1:3:6) type C-2 foundation , necessary earthwork (if any) complete all as specified & as directed with & including the following accessories : | 1 | Each Job | 2,66,000 ₹2.7 L | 2,07,777 ₹2.1 L |
| 1.01(X-MER Panel) (i) BUS-BAR & INTERNAL CONNECTIONS : The bus-bars shall be made up of 04 Nos high grade Copper with rating should be suitable as per incoming Breaker, duly insulated with 1100 Volts grade standard colour coded PVC sleeves & rigidly mounted on suitable sized "F" class insulators of non-hygroscopic, non-combustible, all internal connections from main bus-bars to switch gears etc. PROVISION FOR CABLE ENTRY : The provision for cable entry /exit shall be provided in the bottom for both incoming & out-going cables with the help of glands matching the existing/New LT cable sizes. INCOMING : (a) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 36 KA & of rating 250 to 320 A - 01 Nos. Make : L & T, Cat No : CM98403OOQOOG or techno-commercially equivalent of Legrand /Siemens/Havells. | |||||
| 1.02OUTGOINGS : (a) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 25 KA & of rating 200 to 250 Amps - 02 (01W+1S) Nos. Make : L & T, Cat No : CM90642OOPO or techno-commercially equivalent of Legrand /Siemens/Havells. (b) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 25 KA & of rating 80 to 100 A - 02 No. Make : L & T, Cat No : CM91712OOKOOG or techno-commercially equivalent of Legrand /Siemens/Havells. (c) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 25 KA & of rating 63 to 80 A - 02 Nos. Make : L & T, Cat No : CM91712OOJOOG or techno-commercially equivalent of Legrand /Siemens/Havells. (d) Time switch 415 Volts, 3 Phase of 20 Amps rating with Contactor complete . Make : L&T, Cat No (AUTS02DIG00- timer, CS94190-contactor) or techno-commercially eqvt of Legrand /Siemens/Havells. (e) MCB SPN "C" series having breaking capacity 10 KA of rating 06 to 32 Amps - 01 No. Make : L&T/Legrand /Siemens/Havells. (f) MCB TPN "C" series having breaking capacity 10 KA of rating 06 to 32 Amps - 01 No. Make : L&T /Legrand /Siemens/Havells. | |||||
| 1.03INSTRUMENTATION SYSTEM : (a) Digital type Multi-Function meter with built in selector Switch & 03 Nos CTs matching with the I/C breaker, Accuracy Class - 1.0, 3 phase, Size 96 x 96 mm. Make : L & T, Cat No: WL411010OOOO or techno-commercially equivalent of Elmeasure /Secure. (b) Indicator lamp with integral circuit (230/240 Volts) & cluster LED (Red, Orange, Blue) - 01 Set. (c) Danger notice plate of size 20 x 15 cm of 1.6mm thick mild-steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal-red colour and fixed with MS clamps, bolts and nuts of approved size, for LT conforming to IS-2551 - 02 Nos (Front & Back). (d) Door opening key - 02 Nos | |||||
| 2.00 | All as per item 1 here in before but of size 1800 mm (height) x 1500 mm (breadth) x 500 mm (depth) (minimum dimensions) with & including the following accessories:
(Stn HQ Panel, RHQ Panel & ORs Mess and Line Panel)
(i) BUS-BAR & INTERNAL CONNECTIONS :
The bus-bars shall be made up of 04 Nos high grade Copper with rating should be suitable as per incoming Breaker, duly insulated with 1100 Volts grade standard colour coded PVC sleeves & rigidly mounted on suitable sized "F" class insulators of non-hygroscopic, non-combustible, all internal connections from main bus-bars to switch gears etc.
PROVISION FOR CABLE ENTRY :
The provision for cable entry /exit shall be provided in the bottom for both incoming & out-going cables with the help of glands matching the existing LT cable sizes.
INCOMING :
(a) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 25 KA & of rating 160-200 A - 01 Nos.
Make : L & T, Cat No : CM90642OONO or techno-commercially equivalent of Legrand /Siemens/Havells
(b) Onload changeover switch, open-execution modular construction type, confirming to IS/IEC 60947-3, rated current 200 Amps, 415 Volts, 4 Pole, AC - 01 No. Make : L & T, Cat No : CO22000OOOO or techno-commercially equivalent in ABB/ Siemens. | 3 | Each Job | 2,39,000 ₹7.2 L | 2,07,777 ₹6.2 L |
| 2.01OUTGOINGS : (a) MMCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 25 KA & of rating 80 to 100 A - 03 No. Make : L & T, Cat No : CM91712OOKOOG or techno-commercially equivalent of Legrand /Siemens/Havells (b) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 25 KA & of rating 63 to 80 A - 03 Nos. Make : L & T, Cat No : CM91712OOJOOG or techno-commercially equivalent of Legrand /Siemens/Havells. (c) MCB TPN "C" series having breaking capacity 10 KA of rating 40 to 63 Amps - 02 No. Make : L&T/Legrand /Siemens/Havells. (d) MCB TPN "C" series having breaking capacity 10 KA of rating 06 to 32 Amps - 01 No. Make : L&T /Legrand /Siemens/Havells. | |||||
| 2.02INSTRUMENTATION SYSTEM : (a) Digital type Multi-Function meter with built in selector Switch & 03 Nos CTs matching with the I/C breaker, Accuracy Class - 1.0, 3 phase, Size 96 x 96 mm. Make : L & T, Cat No: WL411010OOOO or techno-commercially equivalent of Elmeasure /Secure. (b) Indicator lamp with integral circuit (230/240 Volts) & cluster LED (Red, Orange, Blue) - 01 Set. (c) Danger notice plate of size 20 x 15 cm of 1.6mm thick mild-steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal-red colour and fixed with MS clamps, bolts and nuts of approved size, for LT conforming to IS-2551 - 02 Nos (Front & Back). (d) Door opening key - 02 Nos | |||||
| 3.00 | All as per item 1 here in before but of size 1500 mm (height) x 1200 mm (breadth) x 500 mm (depth) (minimum dimensions) with & including the following accessories:
( MI Room Panel)
(i) BUS-BAR & INTERNAL CONNECTIONS :
The bus-bars shall be made up of 04 Nos high grade Copper with rating should be suitable as per incoming Breaker, duly insulated with 1100 Volts grade standard colour coded PVC sleeves & rigidly mounted on suitable sized "F" class insulators of non-hygroscopic, non-combustible, all internal connections from main bus-bars to switch gears etc.
PROVISION FOR CABLE ENTRY :
The provision for cable entry /exit shall be provided in the bottom for both incoming & out-going cables with the help of glands matching the existing LT cable sizes.
INCOMING :
(a)MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 25 KA & of rating 160-200 A - 01 Nos.
Make : L & T, Cat No : CM90642OONO or techno-commercially equivalent of Legrand /Siemens/Havells
(b) Onload changeover switch, open-execution modular construction type, confirming to IS/IEC 60947-3, rated current 160 Amps, 415 Volts, 4 Pole, AC - 01 No. Make : L & T, Cat No : CO21600OOOO or techno-commercially equivalent in ABB/ Siemens. | 1 | Each Job | 2,25,000 ₹2.3 L | 2,01,111 ₹2.0 L |
| 3.01OUTGOINGS : (a) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 25 KA & of rating 80 to 100 A - 02 Nos Make : L & T, Cat No : CM91712OOKOOG or techno-commercially equivalent of Legrand /Siemens/Havells. (b) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 25 KA & of rating 63 to 80 A - 05 Nos. Make : L & T, Cat No : CM91712OOJOOG or techno-commercially equivalent of Legrand /Siemens/Havells. (c) MCB TPN "C" series having breaking capacity 10 KA of rating 40 to 63 Amps - 02 No. Make : L&T/Legrand /Siemens/Havells. (d) MCB TPN "C" series having breaking capacity 10 KA of rating 06 to 32 Amps - 01 No. Make : L&T /Legrand /Siemens/Havells. (e) Time switch 415 Volts, 3 Phase of 20 Amps rating with Contactor complete . Make : L&T, Cat No (AUTS02DIG00- timer, CS94190-contactor) or techno-commercially eqvt of Legrand /Siemens/Havells. | |||||
| 3.02INSTRUMENTATION SYSTEM : (a) Digital type Multi-Function meter with built in selector Switch & 03 Nos CTs matching with the I/C breaker, Accuracy Class - 1.0, 3 phase, Size 96 x 96 mm. Make : L & T, Cat No: WL411010OOOO or techno-commercially equivalent of Elmeasure /Secure. (b) Indicator lamp with integral circuit (230/240 Volts) & cluster LED (Red, Orange, Blue) - 01 Set. (c) Danger notice plate of size 20 x 15 cm of 1.6mm thick mild-steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal-red colour and fixed with MS clamps, bolts and nuts of approved size, for LT conforming to IS-2551 - 02 Nos (Front & Back). (d) Door opening key - 02 Nos | |||||
Updated dates
Tender Value
₹45 L
EMD Value
₹90,000
Closing Date
4 Apr 2026, 6:00 pmClosed
GE (A) BARMER
GE (A) BARMER JALIPA CANTT
SPL REPAIR REPLACEMENT OF OVERHEAD LT LINE INTO LT UG CABLE INCL CONNECTED WORKS AT LANCERS GH AT JASAI MIL STN
2026_MES_748709_2
8878/E8
Open Tender
Electrical and Maintenance Works
180 days
BARMER
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
GE (A) BARMER
₹90,000
Yes
7 Apr 2026
10 Mar 2026
6 Apr 2026
10 Mar 2026
4 Apr 2026
17 Mar 2026
Supply, install, testing & commissioning of LT control panel board "out-door type" of size 1800 mm (height) x 1500 mm (breadth) x 500 mm (depth) (minimum dimensions), factory fabricated CPRI approved (type-tested) with suitable neoprene rubber gasket to make it completely dust & vermin proof & degree of protection not less than IP-55 & general construction confirming to IS-13947, double door, front & back openable. The panel shall be provided with ventilation facility in the form of louvers for better heat dissipation & high grade Copper bus-bar wrapped with coloured PVC tape /sleeves of rating in conformity to the Incoming ACB/MCCB rating. The panel board shall be fabricated out of 3.15 mm thick (for outer portions) & 2.00 mm thick (for inner portions) CRCA sheet duly pre-treated & powder coated, supporting angle iron frame of size 50X50X6mm fixed at 75 cm height from groud level & MC channel base suitable for 3 Phase, 4 wire system 415 /440 volts grade including complete internal wiring with not less than 2.5 Sqmm copper wire including cable glands and lugs of suitable sizes with suitable PCC (1:3:6) type C-2 foundation , necessary earthwork (if any) complete all as specified & as directed with & including the following accessories :
(X-MER Panel) (i) BUS-BAR & INTERNAL CONNECTIONS : The bus-bars shall be made up of 04 Nos high grade Copper with rating should be suitable as per incoming Breaker, duly insulated with 1100 Volts grade standard colour coded PVC sleeves & rigidly mounted on suitable sized "F" class insulators of non-hygroscopic, non-combustible, all internal connections from main bus-bars to switch gears etc. PROVISION FOR CABLE ENTRY : The provision for cable entry /exit shall be provided in the bottom for both incoming & out-going cables with the help of glands matching the existing/New LT cable sizes. INCOMING : (a) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 36 KA & of rating 250 to 320 A - 01 Nos. Make : L & T, Cat No : CM98403OOQOOG or techno-commercially equivalent of Legrand /Siemens/Havells.
OUTGOINGS : (a) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 25 KA & of rating 200 to 250 Amps - 02 (01W+1S) Nos. Make : L & T, Cat No : CM90642OOPO or techno-commercially equivalent of Legrand /Siemens/Havells. (b) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 25 KA & of rating 80 to 100 A - 02 No. Make : L & T, Cat No : CM91712OOKOOG or techno-commercially equivalent of Legrand /Siemens/Havells. (c) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 25 KA & of rating 63 to 80 A - 02 Nos. Make : L & T, Cat No : CM91712OOJOOG or techno-commercially equivalent of Legrand /Siemens/Havells. (d) Time switch 415 Volts, 3 Phase of 20 Amps rating with Contactor complete . Make : L&T, Cat No (AUTS02DIG00- timer, CS94190-contactor) or techno-commercially eqvt of Legrand /Siemens/Havells. (e) MCB SPN "C" series having breaking capacity 10 KA of rating 06 to 32 Amps - 01 No. Make : L&T/Legrand /Siemens/Havells. (f) MCB TPN "C" series having breaking capacity 10 KA of rating 06 to 32 Amps - 01 No. Make : L&T /Legrand /Siemens/Havells.
All as per item 1 here in before but of size 1800 mm (height) x 1500 mm (breadth) x 500 mm (depth) (minimum dimensions) with & including the following accessories: (Stn HQ Panel, RHQ Panel & ORs Mess and Line Panel) (i) BUS-BAR & INTERNAL CONNECTIONS : The bus-bars shall be made up of 04 Nos high grade Copper with rating should be suitable as per incoming Breaker, duly insulated with 1100 Volts grade standard colour coded PVC sleeves & rigidly mounted on suitable sized "F" class insulators of non-hygroscopic, non-combustible, all internal connections from main bus-bars to switch gears etc. PROVISION FOR CABLE ENTRY : The provision for cable entry /exit shall be provided in the bottom for both incoming & out-going cables with the help of glands matching the existing LT cable sizes. INCOMING : (a) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 25 KA & of rating 160-200 A - 01 Nos. Make : L & T, Cat No : CM90642OONO or techno-commercially equivalent of Legrand /Siemens/Havells (b) Onload changeover switch, open-execution modular construction type, confirming to IS/IEC 60947-3, rated current 200 Amps, 415 Volts, 4 Pole, AC - 01 No. Make : L & T, Cat No : CO22000OOOO or techno-commercially equivalent in ABB/ Siemens.
OUTGOINGS : (a) MMCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 25 KA & of rating 80 to 100 A - 03 No. Make : L & T, Cat No : CM91712OOKOOG or techno-commercially equivalent of Legrand /Siemens/Havells (b) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 25 KA & of rating 63 to 80 A - 03 Nos. Make : L & T, Cat No : CM91712OOJOOG or techno-commercially equivalent of Legrand /Siemens/Havells. (c) MCB TPN "C" series having breaking capacity 10 KA of rating 40 to 63 Amps - 02 No. Make : L&T/Legrand /Siemens/Havells. (d) MCB TPN "C" series having breaking capacity 10 KA of rating 06 to 32 Amps - 01 No. Make : L&T /Legrand /Siemens/Havells.
All as per item 1 here in before but of size 1500 mm (height) x 1200 mm (breadth) x 500 mm (depth) (minimum dimensions) with & including the following accessories: ( MI Room Panel) (i) BUS-BAR & INTERNAL CONNECTIONS : The bus-bars shall be made up of 04 Nos high grade Copper with rating should be suitable as per incoming Breaker, duly insulated with 1100 Volts grade standard colour coded PVC sleeves & rigidly mounted on suitable sized "F" class insulators of non-hygroscopic, non-combustible, all internal connections from main bus-bars to switch gears etc. PROVISION FOR CABLE ENTRY : The provision for cable entry /exit shall be provided in the bottom for both incoming & out-going cables with the help of glands matching the existing LT cable sizes. INCOMING : (a)MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 25 KA & of rating 160-200 A - 01 Nos. Make : L & T, Cat No : CM90642OONO or techno-commercially equivalent of Legrand /Siemens/Havells (b) Onload changeover switch, open-execution modular construction type, confirming to IS/IEC 60947-3, rated current 160 Amps, 415 Volts, 4 Pole, AC - 01 No. Make : L & T, Cat No : CO21600OOOO or techno-commercially equivalent in ABB/ Siemens.
OUTGOINGS : (a) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 25 KA & of rating 80 to 100 A - 02 Nos Make : L & T, Cat No : CM91712OOKOOG or techno-commercially equivalent of Legrand /Siemens/Havells. (b) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 25 KA & of rating 63 to 80 A - 05 Nos. Make : L & T, Cat No : CM91712OOJOOG or techno-commercially equivalent of Legrand /Siemens/Havells. (c) MCB TPN "C" series having breaking capacity 10 KA of rating 40 to 63 Amps - 02 No. Make : L&T/Legrand /Siemens/Havells. (d) MCB TPN "C" series having breaking capacity 10 KA of rating 06 to 32 Amps - 01 No. Make : L&T /Legrand /Siemens/Havells. (e) Time switch 415 Volts, 3 Phase of 20 Amps rating with Contactor complete . Make : L&T, Cat No (AUTS02DIG00- timer, CS94190-contactor) or techno-commercially eqvt of Legrand /Siemens/Havells.
All as per item 1 here in before but of size 1800 mm (height) x 1500 mm (breadth) x 500 mm (depth) (minimum dimensions) with & including the following accessories:- (Officer Mess Panel & 62.5 KVA DG Set EB Panel ) (i) BUS-BAR & INTERNAL CONNECTIONS : The bus-bars shall be made up of 04 Nos high grade Copper with rating should be suitable as per incoming Breaker, duly insulated with 1100 Volts grade standard colour coded PVC sleeves & rigidly mounted on suitable sized "F" class insulators of non-hygroscopic, non-combustible, all internal connections from main bus-bars to switch gears etc. PROVISION FOR CABLE ENTRY : The provision for cable entry/exit shall be provided in the bottom for both incoming & out-going cables with the help of glands matching the existing LT cable sizes. INCOMING : (a) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 25 KA & of rating 160-200 A - 01 Nos. Make : L & T, Cat No : CM90642OONO or techno-commercially equivalent of Legrand /Siemens/Havells.
OUTGOINGS : (a) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 25 KA & of rating 125 to 160 Amps - 02 . Make : L & T, Cat No : CM90642OOMO or techno-commercially equivalent of Legrand /Siemens/Havells. (b) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 25 KA & of rating 80 to 100 A - 02 No. Make : L & T, Cat No : CM91712OOKOOG or techno-commercially equivalent of Legrand /Siemens/Havells. (c) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 25 KA & of rating 63 to 80 A - 04 Nos. Make : L & T, Cat No : CM91712OOJOOG or techno-commercially equivalent of Legrand /Siemens/Havells. (d) Time switch 415 Volts, 3 Phase of 20 Amps rating with Contactor complete . Make : L&T, Cat No (AUTS02DIG00- timer, CS94190-contactor) or techno-commercially eqvt of Legrand /Siemens/Havells. (e) MCB TPN "C" series having breaking capacity 10 KA of rating 63 Amps - 03 No. Make : L&T /Legrand /Siemens/Havells.
All as per item 1 here in before but of size 1800 mm (height) x 1500 mm (breadth) x 500 mm (depth) (minimum dimensions) with & including the following accessories:- (125 KVA DG Set Panel) (i) BUS-BAR & INTERNAL CONNECTIONS : The bus-bars shall be made up of 04 Nos high grade Copper with rating should be suitable as per incoming Breaker, duly insulated with 1100 Volts grade standard colour coded PVC sleeves & rigidly mounted on suitable sized "F" class insulators of non-hygroscopic, non-combustible, all internal connections from main bus-bars to switch gears etc. PROVISION FOR CABLE ENTRY : The provision for cable entry /exit shall be provided in the bottom for both incoming & out-going cables with the help of glands matching the existing LT cable sizes. INCOMING : (a)MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 25 KA & of rating 200 to 250 A - 01 Nos. Make : L & T, Cat No : CM90642OOPO or techno-commercially equivalent of Legrand /Siemens/Havells. (b) Onload changeover switch, open-execution modular construction type, confirming to IS/IEC 60947-3, rated current 200 Amps, 415 Volts, 4 Pole, AC - 01 No. Make : L & T, Cat No : CO22000OOOO or techno-commercially equivalent in ABB/ Siemens.
OUTGOINGS : (a) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 25 KA & of rating 160-200 A - 02 Nos. Make : L & T, Cat No : CM90642OONO or techno-commercially equivalent of Legrand /Siemens/Havells. (b) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 25 KA & of rating 125 to 160 Amps - 02 . Make : L & T, Cat No : CM90642OOMO or techno-commercially equivalent of Legrand /Siemens/Havells. (c) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 25 KA & of rating 63 to 80 A - 02 Nos. Make : L & T, Cat No : CM91712OOJOOG or techno-commercially equivalent of Legrand /Siemens/Havells. (d) MCB TPN "C" series having breaking capacity 10 KA of rating 06 to 32 Amps - 02 No. Make : L&T/Legrand /Siemens/Havells. (e) MCB TPN "C" series having breaking capacity 10 KA of rating 40 to 63 Amps - 02 No. Make : L&T /Legrand /Siemens/Havells.
All as per item 1 here in before but of size 1500 mm (height) x 1200 mm (breadth) x 500 mm (depth) (minimum dimensions) with & including the following accessories:- (Mandir Panel & JCO Mess Panel) (i) BUS-BAR & INTERNAL CONNECTIONS : The bus-bars shall be made up of 04 Nos high grade Copper with rating should be suitable as per incoming Breaker, duly insulated with 1100 Volts grade standard colour coded PVC sleeves & rigidly mounted on suitable sized "F" class insulators of non-hygroscopic, non-combustible, all internal connections from main bus-bars to switch gears etc. PROVISION FOR CABLE ENTRY : The provision for cable entry /exit shall be provided in the bottom for both incoming & out-going cables with the help of glands matching the existing LT cable sizes. INCOMING : (a) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 25 KA & of rating 125 to 160 Amps - 01 . Make : L & T, Cat No : CM90642OOMO or techno-commercially equivalent of Legrand /Siemens/Havells.
OUTGOINGS : (a) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 25 KA & of rating 63 to 80 A - 04 Nos. Make : L & T, Cat No : CM91712OOJOOG or techno-commercially equivalent of Legrand /Siemens/Havells. (b) Time switch 415 Volts, 3 Phase of 20 Amps rating with Contactor complete . Make : L&T, Cat No (AUTS02DIG00- timer, CS94190-contactor) or techno-commercially eqvt of Legrand /Siemens/Havells. (d) MCB TPN "C" series having breaking capacity 10 KA of rating 06 to 32 Amps - 02 No. Make : L&T/Legrand /Siemens/Havells. (e) MCB TPN "C" series having breaking capacity 10 KA of rating 40 to 63 Amps - 02 No. Make : L&T /Legrand /Siemens/Havells.
Supply, install, testing & commissioning of LT busbar junction box "out-door type" of size 750 mm (height) x 600 mm (breadth) x 300 mm (depth) (minimum dimensions), factory fabricated CPRI approved (type-tested) with suitable neoprene rubber gasket to make it completely dust & vermin proof & degree of protection not less than IP-55 & general construction confirming to IS-13947, double door, front & back openable. The box shall be provided with ventilation facility in the form of louvers for better heat dissipation & high grade Copper bus-bar of Size 300mm x 70mm x 6mm , min spacing of 75mm between the busbars & wrapped with coloured PVC tape /sleeves of rating in conformity to the Incoming cable rating. The panel board shall be fabricated out of 3.15 mm thick (for outer portions) & 2.00 mm thick (for inner portions) CRCA sheet duly pre-treated & powder coated, supporting angle iron frame & MC channel base suitable for 3 Phase, 4 wire system 415 /440 volts grade including I/C & O/G cable opening on bottom & at both sides including cable glands of suitable sizes with suitable PCC (1:3:6) type C-2 foundation , necessary earthwork (if any) incl Incoming MCCB of 63 Amps in seprate portion complete all as specified & as directed.
M&L for shifting the existing panel/Changeover boxes alongwith MC Channel ang angle iron frame, to a place directed by Engr-in-Charge incl making suitable fixing arrangement and isolating the existing cables properly incl making connections of Cables at New Location with suitable Lugs and Glands complete all as specified and directed. The Rate Quoted by contractor is deemed to be inclusive of transportation cost of panel from existing location to New location including necessary PCC Work for fixing LT panel.
Excavation in trenches n.exc 1.5m wide and n.exc 1.5m in depth for taking out/laying of UG Cables, GI Pipe etc. and getting out in Soft/loose soil complete.
Returning, filling in including spreading, levelling, watering and well ramming in layers n.exc 25cm thick.
Removing of excavated material n.exc 50m and depositing where directed at a level n.exc 1.5m above the starting point.
Supply and spreading Tibba Sand including watering and consolidation in trenches for cushioning/cable protection all as specified and directed by Engr-in-Charge. Note : Punned thickness shall be measured and paid
Supply and laying un-reinforced precast concrete cable cover, class LV, type 1, flat size 250 mm x 150 mm x 40 mm and abutting each other with gap between adjacent precast concrete cable cover not exceeding 10 mm over underground cables in trenches for cable protection of U/G cables with width equal to length of bricks complete all as specified and directed
Description all as per Item Sl No 14 here in above but of bore 80 mm.
Description all as per Item Sl No 14 here in above but of bore 50 mm.
Description all as per Item Sl No 14 here in above but of bore 40 mm.
M&L for boring under road manually with labour suitable for inserting upto 100 mm bore pipe at a depth 0.75 to 1.0 mtr complete.
M&L for cutting the existing hardstanding/PCC/WBM road at a depth of not less than 60 cm & 30 cm in width for passing of LT cables through GI pipes, returning filling in, complete incl finishing the surfaces by providing cement concrete type B1 (1:2:4) with 20 mm graded aggregate upto 20 cm, finishing to a uniform smooth surface complete all as specified and as directed.
Supply, laying, jointing & testing XLPE insulated screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 16 sq mm 4.0 core in trenches / through GI pipe / fixed along with pole structure, Wall with suitable Clamps etc with all fixing & connecting accessories like Lugs, Gland etc complete all as specified & as directed.
Description all as per Item Sl No 20 here in above but of size 10 Sqmm 2.0 core.
Description all as per Item Sl No 20 here in above but of size 25 Sqmm 4.0 core.
Description all as per Item Sl No 20 here in above but of size 35 Sqmm 3.5 core.
Description all as per Item Sl No 20 here in above but of size 50 Sqmm 3.5 core.
Description all as per Item Sl No 20 here in above but of size 70 Sqmm 3.5 core.
Description all as per Item Sl No 20 here in above but of size 95 Sqmm 3.5 core.
Description all as per Item Sl No 20 here in above but of size 120 Sqmm 3.5 core.
Description all as per Item Sl No 20 here in above but of size 150 Sqmm 3.5 core.
Description all as per Item Sl No 20 here in above but of size 185 Sqmm 3.5 core.
Description all as per Item Sl No 20 here in above but of size 240 Sqmm 3.5 core.
M&L for earthing complete with Galvanised steel earth plate electrode 600 x 600 x 6 mm thick buried directly in ground (in vertical position) earth pit not less than 2.25 mtr below normal ground level with the top edge of the earth plate not less than 1.5 mtr (B.G.L.) and connected to GI earth strip 32 x 6 mm by means of bolts, nuts, check nuts, and washers of galvanized iron including PCC pit & cover with suitable handle, including necessary excavation and earth work in any type of soil, 20 mm dia med grade galvanized steel tube for watering with one end fixed with suitable funnel and wire mesh, 40 mm bore medium grade galvanized steel tubing for drawing earth lead GI strip protection & common salt, charcoal in alternate layers etc. complete all as shown in EP No 3 of SSR Part 1 all as specified and directed by Engr-in-charge
NOTE : 1) On completion of the complete work/job the Contr is to perform earth resistance tests for each earthing job in the presence of the Engr-In-Charge or his rep & submit test certificates duly signed & certified. If the test results are not satisfactory or not within the permissible limits of relevant Standards/IS then the job is to be redone without any extra cost to the Dept till the results are satisfactory.
Supply, installing, testing and commissioning factory made and tested AMF Panel 125 KVA with Byepass arrangement for Main & DG both Outdoor type, platform mounted, suitable for 415 Volts 3 Phase and neutral, 4 wire, 50Hz AC supply system having bus bar with insulated sleeves Copper bus bars of 250 Amps rating. The panel shall be dust and vermin proof, protection class ( IP-54 ) and made of 3.15 mm thick CRCA mild steel sheet, suitable supporting angle iron frame of size 50X50X6mm fixed at 75 cm height from groud level & MC channel base), front opening type with proper ferrule & cable gland, internal wiring with PVC insulated multistranded copper conductor PVC wire of adequate size but not less than 1.5 sqmm complete. All steel metal works including frame shall be with anticorrosive coating with seven tank process and finally epoxy polyester powder coating of Siemens grey shade 7035 embedded in ground with and including bocks of PCC 1:2:4 type B1 of block size 30x30x30 cm, The scope of work also comprising of the following:-
Under Voltage relay 415V AC for main -1 No.
Under voltage relay 415 V AC for DG - 1 No.
AC Timer 230 Volt , 2 No. +2 NC - 1 No.
DC Timer 12/24 V - 1No.
Engine Starting relay 12/ 24 V- 1 No
Control MCB SP 6 Amp. 230 V – 9 Nos.
Control MCB SP 16 Amp. 230 V – 2 Nos.
Battery Charger 12/24 DC - 1 No.
LED Indicating Light for Main & DG—6 Nos
LED Indicating Light for Main & Gen. ON – 2 Nos.
LED Indicating Light for battery Charger –1 No.
Digital Volt meter ( 0-500 V ) Flush Mounted 96 mm X 96 mm - 1 No.
Digital Amp meter ( 0-250 A ) Flush Mounted 96 mm X 96 mm - 1 No.
CT Coil 250/5 A CL-1 - 3 Nos.
DC Volt Meter 15/30 V analog type - 1 No.
DC Amp Meter 0-15 A analog type - 1 No.
Trickle / Boost switch –2 Nos.
Start & Stop Push Button - 2 Nos.
Analogue Frequency Meter –1 No.
Hooter 12/24 V DC - 1 No.
Power Contactor 255 Amps 4 Pole having coil voltage 415 V AC for DG Supply - 1 No.
Power Contactor 255 Amps 4 Pole having coil voltage 415 V AC for Main Supply - 1 No.
Incoming MCCB 250 Amps 415 V AC 25 KA 4 Pole Fixed Thermal Magnetic release for Main & DG Supply - 2 Nos.
Outgoing MCCB 250 Amps 415 V AC 25 KA 4 Pole Fixed Thermal Magnetic release for Load - 1 Nos.
Control Relay - 1 Set.
Over Load relay 3-5 A - 1 No.
On Load Change Over Switch 250 A 4 Pole Open execution For Bye Pass Main Supply - 1 No.
On Load Change Over Switch 250 A 4 Pole Open execution For Bye Pass DG Supply - 1 No.
Interconnecting Aluminium Link from MCCB to Contactors with Incoming & Outgoing- 1 Set.
The AMF Panel manufacturer should have following Govt. Approved Certificates: 1. Panel should be according to IEC-61439. CPRI Certification Degree of Protection IP-54 (IS/IEC : 61439 (Part-1), 2011 & IS/IEC : 61439 (Part-2) 2011) 2. Tempreature Rise (IS/IEC : 61439-1, 2011 & IS/IEC : 61439-2 2011) 3. CPRI Short Circuit IEC-61439-1 & 2 withstand strenght should be 70kArms for 1.0 Sec with intial peak of 154kApk 4. CPRI Certification IEC-61439-1 & 2 Rated current for short circuit not less than 4000 A with rated insulation voltage 660V 5. ISO 9001 CERTIFIED
Supply, installing, testing and commissioning factory made and tested AMF Panel 62.5 KVA with Byepass arrangement for Main & DG both Outdoor type, platform mounted, suitable for 415 Volts 3 Phase and neutral, 4 wire, 50Hz AC supply system having bus bar with insulated sleeves Copper bus bars of 150 Amps rating. The panel shall be dust and vermin proof, protection class ( IP-54 ) and made of 3.15 mm thick CRCA mild steel sheet, suitable supporting angle iron frame of size 50X50X6mm fixed at 75 cm height from groud level & MC channel base), front opening type with proper ferrule & cable gland, internal wiring with PVC insulated multistranded copper conductor PVC wire of adequate size but not less than 1.5 sqmm complete. All steel metal works including frame shall be with anticorrosive coating with seven tank process and finally epoxy polyester powder coating of Siemens grey shade 7035 embedded in ground with and including bocks of PCC 1:2:4 type B1 of block size 30x30x30 cm, The scope of work also comprising of the following:-
Under Voltage relay 415V AC for main -1 No.
Under voltage relay 415 V AC for DG - 1 No.
AC Timer 230 Volt , 2 No. +2 NC - 1 No.
DC Timer 12/24 V - 1No.
Engine Starting relay 12/ 24 V- 1 No
Control MCB SP 6 Amp. 230 V – 9 Nos.
Control MCB SP 16 Amp. 230 V – 2 Nos.
Battery Charger 12/24 DC - 1 No.
LED Indicating Light for Main & DG—6 Nos
LED Indicating Light for Main & Gen. ON – 2 Nos.
LED Indicating Light for battery Charger –1 No.
Digital Volt meter ( 0-500 V ) Flush Mounted 96 mm X 96 mm - 1 No.
Digital Amp meter ( 0-150 A ) Flush Mounted 96 mm X 96 mm - 1 No.
CT Coil 150/5 A CL-1 - 3 Nos.
DC Volt Meter 15/30 V analog type - 1 No.
DC Amp Meter 0-15 A analog type - 1 No.
Trickle / Boost switch –2 Nos.
Start & Stop Push Button - 2 Nos.
Analogue Frequency Meter –1 No.
Hooter 12/24 V DC - 1 No.
Power Contactor 130 A 4 Pole 415V AC for DG - 1 No.
Power Contactor 130 A 4 Pole 415V AC for Main - 1 No.
Incoming MCCB 125 A 25 KA 4 Pole Thermal Magnetic release for Main & DG Supply - 2 Nos.
Outgoing MCCB 125 A 25 KA 4 Pole Thermal Magnetic release for Load - 1 Nos.
ON Load Change Over Switch 125 A 4 Pole For Bye Pass Main Supply - 1 No.
On Load Change Over Switch 125 A 4 Pole For Bye Pass DG Supply - 1 No.
Over Load relay 3-5 A - 1 No.
Control Relay - 1 Set.
Interconnecting Aluminium Link from MCCB to Contactors with Incoming & Outgoing- 1 Set.
The AMF Panel manufacturer should have following Govt. Approved Certificates: 1. Panel should be according to IEC-61439. CPRI Certification Degree of Protection IP-54 (IS/IEC : 61439 (Part-1), 2011 & IS/IEC : 61439 (Part-2) 2011) 2. Tempreature Rise (IS/IEC : 61439-1, 2011 & IS/IEC : 61439-2 2011) 3. CPRI Short Circuit IEC-61439-1 & 2 withstand strenght should be 70kArms for 1.0 Sec with intial peak of 154kApk 4. CPRI Certification IEC-61439-1 & 2 Rated current for short circuit not less than 4000 A with rated insulation voltage 660V 5. ISO 9001 CERTIFIED
NOTE for Item Nos 32 & 33.33 : 1) Design / drawing / BOM of the AMF Panel Board duly showing the dimensions & accessories is to be obtained from the Manufacturer / Supplier & is to be got approved from the Engr-In-Charge & GE before placing final order to the manufacturer.
2) The electrical connection of digital Multi Functional Meter in the AMF panel is to be done from load side so that monitoring of various parameters viz. Voltage, Current, KW, KVA, power factor, frequency etc. can be done for both SEB mains & DG mains.
5) Existing DG for which the AMF Panels is required is of rating 120 KVA & 62.5,Subject AMF Panels shall be perfectly compatible for the existing DG Set & same must be suitable for Automatic Load Transfer from EB Supply to DG Supply & Vice-Versa.
Dismantling of ACSR conductor of any size/type from existing PCC/Steel poles all as directed by Engr - in - charge at site.
Dismantling of insulators of any size/type from existing PCC/Steel poles all as directed by Engr - in - charge at site.
Dismantling of Iron Cross Arms Angel/channel of any size/type from existing PCC/Steel poles along with clamps and Nut/bolts all as directed by Engr - in - charge at site.
Material and labour for taking down Old Unserviceable LT UG Cable/service cable of any size/type incl all Accessories
Make of LT Panel board:- BAFNA/UNIVERSAL/SHREEJI/OSIAN
Please Enable Macros to View BoQ information
stage.html
html • 0.03 MB
technical_846443.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.49 MB
BOQ_846443.xls
BOQ • 0.33 MB
TENDER8878.pdf
Tender Documents • 2.21 MB
NIT.pdf
Additional Documents • 0.46 MB
Download all tender documents and submit your bid