Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹69.0 LAccepted-AOC 205 2ND FLOOR AKANSHA COMPLEX ZONE I M P NAGAR BHOPAL | BHOPAL | BHOPAL | MADHYA PRADESH | ₹69.0 L | L1 | Accepted-AOC Accepted due to being lowest rate. |
| 2 | L2₹71.7 LRejected-Finance | ₹71.7 L | L2 | Rejected-Finance Rate quoted more than L1. |
| 3 | L3₹77.5 LRejected-Finance | ₹77.5 L | L3 | Rejected-Finance Rate quoted more than L1. |
| 4 | L4₹79.1 LRejected-Finance BETUL M P | BETUL | MADHYA PRADESH | ₹79.1 L | L4 | Rejected-Finance Rate quoted more than L1. |
| 5 | L5₹82.5 LRejected-Finance 29 V M TOWER S 1 OPP BATRA HOSPITAL ZONE 1 M P NAGAR BHOPAL 462011 | BHOPAL | BHOPAL | MADHYA PRADESH | 462011 | ₹82.5 L | L5 | Rejected-Finance Rate quoted more than L1. |
Tender Value
₹96.8 L
EMD Value
₹96,838
Closing Date
9 Mar 2026, 5:30 pmClosed
EXECUTIVE ENGINEER
E. E. PWD E/M, Division No. 1, Shed No. 11A Bara Dafater Jawahar Chowk Bhopal
Providing New AMF Panel and Controller Panel and Shifting of DG Set and New Controller Panels for A-Block, B- Block, C- Block and O2 Plant from main Panel with Seperate Supply Cables and Cable for Oxygen Plants and Street Lights at JP Hospital-1250,
2026_PWDRB_485016_1
156/TS/2025-2026 E/M/Bpl/e-tendering (1st Call)
Open Tender
Electrical Works
90 days
Bhopal
As Per Tender Documents
10 documents required · 10 mandatory
₹10,000
₹96,838
16 Jun 2026
25 Feb 2026
11 Mar 2026
25 Feb 2026
9 Mar 2026
25 Feb 2026
For Providing New AMF Panel & Controller Panel & Shifting of DG Set & New Controller Panels for A-Block, B- Block, C- Block & O2 Plant from main Panel with Seperate Supply Cables & Cable for Oxygen Plants and Street Lights at JP Hospital-1250, Bhopal. (Detail Schedule Attached)
SECTION 4
BILL OF QUANTITIES (BOQ)
General Description of work : For Providing New AMF Panel & Controller Panel & Shifting of DG Set & New Controller Panels for A-Block, B- Block, C- Block & O2 Plant from main Panel with Seperate Supply Cables & Cable for Oxygen Plants and Street Lights at JP Hospital-1250, Bhopal. 1st Call. P. A. C. 9683835.00 on Electrical SOR 01-01-2024, Completion period 90 Days (i/c rainy season)
Probable Amount of Contract :
(Rs. In Figure) :-
(Rs. In Words) :-
Item No.
PART 1: for Providing New AMF Panel & Capacitor Panel with Shifting of DG Set at JP Hospital-1250, Bhopal.
Supply of ISI Marked On-Load Change over switches panel mouniting type confirming to IS : 13947 (part I & III ) with front operated 4 pole, 415 V with two earthing terminals if required.
800 Amps. .(open - execution )
Supplying of ISI marked and approved make of moulded case circuit breaker (MCCB) suitable for 3 phase,3 pole, 50 Hz, 415 Volts, (Ics=100%Icu) AC supply with thermal - magnetic release having respective breaking capacity (KA) at 415 Volts cited against their range standard conforming to IS/IEC 60947-2
MCCB 25kA current rating - 63 to 100 Amp & adjustable overload setting 80% 100% of In, adjustable short circuit setting 6-10 In 3 Pole
MCCB 36kA current rating - 400Amp & adjustable overload setting 80% -100% of In, adjustable short circuit setting 6-10 In 3 Pole
Supplying of ISI marked and approved make of moulded case circuit breaker (MCCB) suitable for 3 phase,3 pole, 50 Hz, 415 Volts, (Ics=100%Icu) AC supply with Micro-Processor release having respective breaking capacity (KA) at 415 Volts cited against their range standard conforming to IS/IEC 60947-2
MCCB 36kA current rating - 400Amp 3 Pole µ-processor release, over load 40% -100% x In. & short circuit 1.5 - 8 x Ir. adjustable
Supply of ISI marked and accepted standard of miniature circuit breaker (MCB) of 'C' series with short circuit indication, suitable for 240/415 Volts,50 Cycle, 10 kA/15 kA Value AC supply conforming to IS : 8828 : 1996, IEC : 60898 :2002 & 60947-2 but without enclosures :-
Single Pole
MCB SP 6Amp to 32Amp 10kA rating
For Four pole
MCB FP 50Amp to 63 Amp 10kA rating
Fixing of MCB/MCCB/Isolator in sheet steel enclosure as required as per accepted practice, including mounting on busbar and cable connection etc. complete (labour only)
MCB/MCCB Isolator TP/TPN/FP
Supply and fixing of mixed die-electric ultra-heavy duty APP capacitor 440Volt, 3 Ph., peak inrush current upto 500 x In, over current upto 3 x In(normal current), operating losses total not more than 0.35 W/kVAR, operating life not less than 300000 hrs, switching 20000 operation/year, as per IS:13340- 1993, IS:13341-1992, IS:13585-1994, of approved make as required as per specification
5 to 25 kVAR bank
Supply and fixing of LT panel accessories of approved make in existing LT panel including connections etc. as required as per specification.
Multifunction Meter
Aluminium bus bar strips with PVC sleeves
LED lamp indicator
Supplying and fixing of capacitor duty contactor of approved make in existing power factor/LT panel including connections etc.as required as per specification.
For 5 kVAR 440V,3Ph,50Hz, Aux contact-1NO
For 10 kVAR 440V,3Ph,50Hz, Aux contact-1NO
For 15 kVAR 440V,3Ph,50Hz, Aux contact-1NO
For 25 KVAR 440V,3Ph,50Hz, Aux contact-1NO
Automatic power factor relay 12 Steps 230V 144 x 144mm
Supplying and fixing of cooler/A.C. M.S. angle iron stand including flat iron supports, grouting in wall if required, welding, painting with primer and two coat of superior quality paint complete.
Dismantling of existing underground cable safely with its accessories and refilling the trench to ground level including recoiling of dismantled cable
Dismantling of D.F. board, D.P. switch, T.P. & T.P.N. switch or D.B. of any size complete with board or angle/flat iron frame and making site clear including the refilling hole & repainting to match colour of wall.
Supply and laying 4.0mm (8 SWG) dia. G.I. wire at 0.5 metre below ground level as conductor earth electrode including jointing etc. as required.
Supply and laying 25mm X 5mm G.I. strip at 0.5 metre below ground level as strip earth electrode including jointing etc. as required.
Supply of XLPE insulated power cable (conforming IS-7098 Part-I) 1100 Volt grade, 1 core/2 core/3½ core/4 core ISI marked with alu. stranded /solid conductor
3½ core armoured
supplying and fixing heavy duty cable gland for P.V.C. insulated armoured cable with brass washer, rubber ring complete erected with cable and lead connection etc. as per specification complete
Gland size 70 mm, 3 x 240 sq. mm, 3½ x 300 sq. mm
Gland size 82 mm 3½ x 400 sq. mm
Supplying and fixing crimping type alum. lugs as per I.S.S. specification suitable for following size of cable with alu./copper solid/stranded conductor evenly crimped with high/pressure tool and connected to switch gear/bus/M.C.C.B. /M.C.B. etc. as required complete.
Supplying & installing G.I. pipe for protection of underground cable fixed on wall/support/in trench/fixed between two rigid existing support of wall/beam for erection of ceiling Fan/down rod for stiff pendent for light luminaries /fan /protective for earthing, lightening conductor down strip/overhead service line/for submersible cable or centrifugal pump for water supply with necessary iron clamp coupler, bend, tee, elbow, nuts and bolts etc. complete in an approved manner as required to complete excluding cost of excavation/ dismantling & other finished masonry Item complete.
For 'B' class pipe ISI marked (IS-1161- 68)
Laying of one number armoured / unarmoured power cable 1.1 KV grade of size exceeding 120 sq. mm but not exceeding 400 sq. mm. in the existing RCC Hume /Stone ware/G.I. Pipe/ DWC Pipe/ surface in existing trench as required.
Supply and erection of hot dip G.I. cable tray perforation not more than 17.5% for specific dimensions along with tees, bends. The cable tray shall be hang from ceiling/ fixed to wall with necessary angle/flat iron/hanging rod, for ceiling suspensions, clamp, anchor fastener, nuts, bolts, washers, not more than 1.0 mtr. apart complete as per specification to complete the job. The tray shall be as follows :-
300 x 50 x 1.6mm thick
Supply, fabrication and erection of angle/channel/flat iron fitting for overhead line & sub-station etc such as 'D' bracket, cross arms, top clamp, 'V' cross arms, back/support clamp or other similar work etc. including nut bolts of required size, making holes, fabrication, welding, cutting, etc. and painting with one coat of red oxide paint & two coat of aluminium paint as required as per specification.
Total Part 1
(with 18% GST) Total Part 1
PART 2: for Providing New Controller Panel for A Block from main Panel with Supply cable at JP Hospital-1250, Bhopal.
Supply of ISI Marked On-Load Change over switches panel mouniting type confirming to IS : 13947 (part I & III ) with front operated 4 pole, 415 V with two earthing terminals if required.
800 Amps. .(open - execution )
Supplying of ISI marked and approved make of moulded case circuit breaker (MCCB) suitable for 3 phase,3 pole, 50 Hz, 415 Volts, (Ics=100%Icu) AC supply with thermal - magnetic release having respective breaking capacity (KA) at 415 Volts cited against their range standard conforming to IS/IEC 60947-2
MCCB 25kA current rating - 63 to 100 Amp & adjustable overload setting 80% 100% of In, adjustable short circuit setting 6-10 In 3 Pole
MCCB 25kA current rating - 125Amp & adjustable overload setting 80% 100% of In, adjustable short circuit setting 6-10 In 3 Pole
MCCB 36kA current rating - 250Amp & adjustable overload setting 80% -100% of In, adjustable short circuit setting 6-10 In 4 Pole
MCCB 36kA current rating - 400Amp & adjustable overload setting 80% -100% of In, adjustable short circuit setting 6-10 In 3 Pole
Supply of ISI marked and accepted standard of miniature circuit breaker (MCB) of 'C' series with short circuit indication, suitable for 240/415 Volts,50 Cycle, 10 kA/15 kA Value AC supply conforming to IS : 8828 : 1996, IEC : 60898 :2002 & 60947-2 but without enclosures :-
Single Pole
MCB SP 6Amp to 32Amp 10kA rating
Double pole
MCB DP 6Amp to 32Amp 10kA rating
For Four pole
MCB FP 50Amp to 63 Amp 10kA rating
Fixing of MCB/MCCB/Isolator in sheet steel enclosure as required as per accepted practice, including mounting on busbar and cable connection etc. complete (labour only)
MCB/MCCB Isolator TP/TPN/FP
Supply and fixing of LT panel accessories of approved make in existing LT panel including connections etc. as required as per specification.
Multifunction Meter
Aluminium bus bar strips with PVC sleeves
LED lamp indicator
Supplying and fixing of cooler/A.C. M.S. angle iron stand including flat iron supports, grouting in wall if required, welding, painting with primer and two coat of superior quality paint complete.
Dismantling of existing underground cable safely with its accessories and refilling the trench to ground level including recoiling of dismantled cable
Dismantling of D.F. board, D.P. switch, T.P. & T.P.N. switch or D.B. of any size complete with board or angle/flat iron frame and making site clear including the refilling hole & repainting to match colour of wall.
Supply and laying 4.0mm (8 SWG) dia. G.I. wire at 0.5 metre below ground level as conductor earth electrode including jointing etc. as required.
Supply and erection of approved make safe earthing electrode consisting pipe-in-pipe technology as per IS 3043-1987 made of corrosion free G.I. pipes with constant ohmic value surrounded by highly conductive compound with high charge dissipation suitable for effective and maintenance free earthing in earth pit of minimum bore dia. 150mm size, as mentioned below :
With 3 metre pipe of 80mm outer dia., 40mm inner dia and 14mm terminal dia. In soft/hard rock/marshy soil with 50 kgs. (two bag) back filling bentonite compound UL listed and confirm to relevant International/Indian standards around electrode upto ground level.
Supply of XLPE insulated power cable (conforming IS-7098 Part-I) 1100 Volt grade, 1 core/2 core/3½ core/4 core ISI marked with alu. stranded /solid conductor
3½ core armoured
supplying and fixing heavy duty cable gland for P.V.C. insulated armoured cable with brass washer, rubber ring complete erected with cable and lead connection etc. as per specification complete
Gland size 70 mm, 3 x 240 sq. mm, 3½ x 300 sq. mm
Gland size 82 mm 3½ x 400 sq. mm
Supplying and fixing ferrules as per IS - specification suitable for following size of cable for circuit identification including connection as required complete
Supplying and fixing crimping type alum. lugs as per I.S.S. specification suitable for following size of cable with alu./copper solid/stranded conductor evenly crimped with high/pressure tool and connected to switch gear/bus/M.C.C.B. /M.C.B. etc. as required complete.
Supplying & installing G.I. pipe for protection of underground cable fixed on wall/support/in trench/fixed between two rigid existing support of wall/beam for erection of ceiling Fan/down rod for stiff pendent for light luminaries /fan /protective for earthing, lightening conductor down strip/overhead service line/for submersible cable or centrifugal pump for water supply with necessary iron clamp coupler, bend, tee, elbow, nuts and bolts etc. complete in an approved manner as required to complete excluding cost of excavation/ dismantling & other finished masonry Item complete.
For 'B' class pipe ISI marked (IS-1161- 68)
Laying of one number armoured / unarmoured cable 1.1.KV grade of size exceeding 120 sq. mm. but not exceeding 400 sq. mm direct in ground including excavation in all soil/ murrum /soft rock, and sand cushioning protective covering and refilling the pit etc. as required
Laying of one number additional armoured / unarmoured power cable 1.1KV grade of size exceeding 120 sq. mm. but not exceeding 400 sq. mm. direct in ground in the same trench in one tier horizontal formation including excavation, sand cushioning, protective covering and refilling the pit etc. as required.
Laying of one number armoured / unarmoured power cable 1.1 KV grade of size exceeding 120 sq. mm but not exceeding 400 sq. mm. in the existing RCC Hume /Stone ware/G.I. Pipe/ DWC Pipe/ surface in existing trench as required.
Supply of approved type cable cover flag stone 200mm width & 32mm to 50mm thick of required length inclusive of transport as required.
Supply &fixing cable route marker round/square size 100mm, 5mm. thick, G.I. Plate duly bolted/welded on 35mm x 35mm x 5mm angle iron 60cm long including excavation, grouting in cement concrete 1:2:4 (1cement and 2 coarse sand: 4 graded stone aggregate 20mm nominal size) foundation of size 20cm x 20cm x 30cm duly embedded in ground 30cm depth or as required.
Supply and erection of hot dip G.I. cable tray perforation not more than 17.5% for specific dimensions along with tees, bends. The cable tray shall be hang from ceiling/ fixed to wall with necessary angle/flat iron/hanging rod, for ceiling suspensions, clamp, anchor fastener, nuts, bolts, washers, not more than 1.0 mtr. apart complete as per specification to complete the job. The tray shall be as follows :-
150 x 50 x 1.6mm thick
300 x 50 x 1.6mm thick
Total Part 2
(with 18% GST) Total Part 2
PART 3: for Providing New Controller Panel for B Block from main Panel with Supply cable at JP Hospital-1250, Bhopal.
Supplying of ISI marked and approved make of moulded case circuit breaker (MCCB) suitable for 3 phase,3 pole, 50 Hz, 415 Volts, (Ics=100%Icu) AC supply with thermal - magnetic release having respective breaking capacity (KA) at 415 Volts cited against their range standard conforming to IS/IEC 60947-2
MCCB 36kA current rating - 250Amp & adjustable overload setting 80% -100% of In, adjustable short circuit setting 6-10 In 4 Pole
MCCB 36kA current rating - 400Amp & adjustable overload setting 80% -100% of In, adjustable short circuit setting 6-10 In 3 Pole
Supplying of ISI marked and approved make of moulded case circuit breaker (MCCB) suitable for 3 phase,3 pole, 50 Hz, 415 Volts, (Ics=100%Icu) AC supply with Micro-Processor release having respective breaking capacity (KA) at 415 Volts cited against their range standard conforming to IS/IEC 60947-2
MCCB 36kA current rating - 400Amp 3 Pole µ-processor release, over load 40% -100% x In. & short circuit 1.5 - 8 x Ir. adjustable
MCCB 36kA current rating - 630Amp 3 Pole µ-processor release, over load 40% -100% x In. & short circuit 1.5 - 8 x Ir. adjustable
1000 Amp. Manual drawout 50 kA
Supply of ISI marked and accepted standard of miniature circuit breaker (MCB) of 'C' series with short circuit indication, suitable for 240/415 Volts,50 Cycle, 10 kA/15 kA Value AC supply conforming to IS : 8828 : 1996, IEC : 60898 :2002 & 60947-2 but without enclosures :-
Single Pole
MCB SP 6Amp to 32Amp 10kA rating
For Four pole
MCB FP 50Amp to 63 Amp 10kA rating
Fixing of MCB/MCCB/Isolator in sheet steel enclosure as required as per accepted practice, including mounting on busbar and cable connection etc. complete (labour only)
MCB/MCCB Isolator TP/TPN/FP
Supply and fixing of LT panel accessories of approved make in existing LT panel including connections etc. as required as per specification.
Multifunction Meter
Aluminium bus bar strips with PVC sleeves
LED lamp indicator
Supplying and fixing of cooler/A.C. M.S. angle iron stand including flat iron supports, grouting in wall if required, welding, painting with primer and two coat of superior quality paint complete.
Dismantling of existing underground cable safely with its accessories and refilling the trench to ground level including recoiling of dismantled cable
Dismantling of D.F. board, D.P. switch, T.P. & T.P.N. switch or D.B. of any size complete with board or angle/flat iron frame and making site clear including the refilling hole & repainting to match colour of wall.
Supply and laying 4.0mm (8 SWG) dia. G.I. wire at 0.5 metre below ground level as conductor earth electrode including jointing etc. as required.
Supply and laying 25mm X 5mm G.I. strip at 0.5 metre below ground level as strip earth electrode including jointing etc. as required.
Supply and erection of approved make safe earthing electrode consisting pipe-in-pipe technology as per IS 3043-1987 made of corrosion free G.I. pipes with constant ohmic value surrounded by highly conductive compound with high charge dissipation suitable for effective and maintenance free earthing in earth pit of minimum bore dia. 150mm size, as mentioned below :
With 3 metre pipe of 80mm outer dia., 40mm inner dia and 14mm terminal dia. In soft/hard rock/marshy soil with 50 kgs. (two bag) back filling bentonite compound UL listed and confirm to relevant International/Indian standards around electrode upto ground level.
Supply and installation of polycarbonate heavy duty pit cover tested for 5000Kg SWL for earth electrode at ground level size 300x300x155 mm with lockable lid.
Supply of XLPE insulated power cable (conforming IS-7098 Part-I) 1100 Volt grade, 1 core/2 core/3½ core/4 core ISI marked with alu. stranded /solid conductor
3½ core armoured
supplying and fixing heavy duty cable gland for P.V.C. insulated armoured cable with brass washer, rubber ring complete erected with cable and lead connection etc. as per specification complete
Gland size 50 mm ,3½ x 150 sq. mm,3 x 185 sq. mm
Gland size 70 mm, 3 x 240 sq. mm, 3½ x 300 sq. mm
Gland size 82 mm 3½ x 400 sq. mm
Supplying and fixing crimping type alum. lugs as per I.S.S. specification suitable for following size of cable with alu./copper solid/stranded conductor evenly crimped with high/pressure tool and connected to switch gear/bus/M.C.C.B. /M.C.B. etc. as required complete.
Laying of one number armoured / unarmoured power cable 1.1 KV grade of size exceeding 120 sq. mm but not exceeding 400 sq. mm. in the existing RCC Hume /Stone ware/G.I. Pipe/ DWC Pipe/ surface in existing trench as required.
Supply and erection of hot dip G.I. cable tray perforation not more than 17.5% for specific dimensions along with tees, bends. The cable tray shall be hang from ceiling/ fixed to wall with necessary angle/flat iron/hanging rod, for ceiling suspensions, clamp, anchor fastener, nuts, bolts, washers, not more than 1.0 mtr. apart complete as per specification to complete the job. The tray shall be as follows :-
300 x 50 x 1.6mm thick
450 x 50 x 2 mm thick
Total Part 3
(with 18% GST) Total Part 3
PART 4: for Providing Cable for Electrical Supply to Oxygen Plantsat JP Hospital-1250, Bhopal.
Supply of XLPE insulated power cable (conforming IS-7098 Part-I) 1100 Volt grade, 1 core/2 core/3½ core/4 core ISI marked with alu. stranded /solid conductor
3 1/2 core armoured
Supplying and fixing heavy duty cable gland for P.V.C. insulated armoured cable with brass washer, rubber ring complete erected with cable and lead connection etc. as per specification complete.
Gland size 70 mm, 3 x 240 sq. mm, 3½ x 300 sq. mm
Supplying and fixing crimping type alum. lugs as per I.S.S. specification suitable for following size of cable with alu./copper solid/stranded conductor evenly crimped with high/pressure tool and connected to switch gear/bus/M.C.C.B./M.C.B. etc. as required complete.
Cable Laying
Laying of one number armoured / unarmoured cable 1.1.KV grade of size exceeding 120 sq. mm. but not exceeding 400 sq. mm direct in ground including excavation in all soil/ murrum /soft rock, and sand cushioning protective covering and refilling the pit etc. as required.
Supplying and erection of 100mmx110mm shackle insulator with G.I. bolts, nuts and straps etc. as required.
Supplying and fixing of cooler/A.C. M.S. angle iron stand including flat iron supports, grouting in wall if required, welding, painting with primer and two coat of superior quality paint complete.
Total Part 4
(with 18% GST) Total Part 4
PART 5: for Providing New Controller Panel for C Block from main Panel at JP Hospital-1250, Bhopal.
Supplying of ISI marked and approved make of moulded case circuit breaker (MCCB) suitable for 3 phase,3 pole, 50 Hz, 415 Volts, (Ics=100%Icu) AC supply with thermal - magnetic release having respective breaking capacity (KA) at 415 Volts cited against their range standard conforming to IS/IEC 60947-2
MCCB 25kA current rating - 63 to 100 Amp & adjustable overload setting 80% 100% of In, adjustable short circuit setting 6-10 In 3 Pole
MCCB 25kA current rating - 125Amp & adjustable overload setting 80% 100% of In, adjustable short circuit setting 6-10 In 3 Pole
MCCB 36kA current rating - 250Amp & adjustable overload setting 80% -100% of In, adjustable short circuit setting 6-10 In 4 Pole
MCCB 36kA current rating - 400Amp & adjustable overload setting 80% -100% of In, adjustable short circuit setting 6-10 In 3 Pole
Supply of ISI marked and accepted standard of miniature circuit breaker (MCB) of 'C' series with short circuit indication, suitable for 240/415 Volts,50 Cycle, 10 kA/15 kA Value AC supply conforming to IS : 8828 : 1996, IEC : 60898 :2002 & 60947-2 but without enclosures :-
Single Pole
MCB SP 6Amp to 32Amp 10kA rating
For Four pole
MCB FP 50Amp to 63 Amp 10kA rating
Supply of approved make, powder coated metal double door vertical TPN MCCB sub-main DB IP 43 protection with provision for MCCB upto 630A, 36kA/50kA, TP as incomer and space for TP MCCBs as outgoing inclusive of tin-plated electrolytic copper busbar 250A/400A/630A as per incoming MCCB rating, neutral bar 100% of phase, earth bar 50% of phase & two earth terminals etc. complete as per IEC:61439-2(without MCCBs)
12 Way without MCCB I/C 250Amp, O/G 100Amp
16 Way without MCCB I/C 250Amp, O/G 100Amp
Fixing of MCB/MCCB/Isolator in sheet steel enclosure as required as per accepted practice, including mounting on busbar and cable connection etc. complete (labour only)
MCB/MCCB Isolator TP/TPN/FP
Labour charges for fixing sheet steel enclosures, MCCB DB surface mounting type, as per accepted practice on 35x35x 5 mm angle iron clamp, including supplying and fixing of clamp duly embedded in wall, cable connection etc. complete :-
Supply and fixing of LT panel accessories of approved make in existing LT panel including connections etc. as required as per specification.
Multifunction Meter
Aluminium bus bar strips with PVC sleeves
LED lamp indicator
Supplying and fixing of cooler/A.C. M.S. angle iron stand including flat iron supports, grouting in wall if required, welding, painting with primer and two coat of superior quality paint complete.
Dismantling of existing underground cable safely with its accessories and refilling the trench to ground level including recoiling of dismantled cable
Dismantling of D.F. board, D.P. switch, T.P. & T.P.N. switch or D.B. of any size complete with board or angle/flat iron frame and making site clear including the refilling hole & repainting to match colour of wall.
Supply and laying 4.0mm (8 SWG) dia. G.I. wire at 0.5 metre below ground level as conductor earth electrode including jointing etc. as required.
Supply and laying 25mm X 5mm G.I. strip at 0.5 metre below ground level as strip earth electrode including jointing etc. as required.
Supply of XLPE insulated power cable (conforming IS-7098 Part-I) 1100 Volt grade, 1 core/2 core/3½ core/4 core ISI marked with alu. stranded /solid conductor
3½ core armoured
supplying and fixing heavy duty cable gland for P.V.C. insulated armoured cable with brass washer, rubber ring complete erected with cable and lead connection etc. as per specification complete
Gland size 50 mm ,3½ x 150 sq. mm,3 x 185 sq. mm
Supplying and fixing crimping type alum. lugs as per I.S.S. specification suitable for following size of cable with alu./copper solid/stranded conductor evenly crimped with high/pressure tool and connected to switch gear/bus/M.C.C.B. /M.C.B. etc. as required complete.
Laying of one number armoured / unarmoured cable 1.1.KV grade of size exceeding 120 sq. mm. but not exceeding 400 sq. mm direct in ground including excavation in all soil/ murrum /soft rock, and sand cushioning protective covering and refilling the pit etc. as required
Laying of one number armoured / unarmoured power cable 1.1 KV grade of size exceeding 120 sq. mm but not exceeding 400 sq. mm. in the existing RCC Hume /Stone ware/G.I. Pipe/ DWC Pipe/ surface in existing trench as required.
Total Part 5
(with 18% GST) Total Part 5
PART 6: for Providing Illumination, S/F of Street & Flood Lights with Cables in JP Hospital campus-1250, Bhopal (MP)
Supply of ISI marked and accepted standard of miniature circuit breaker (MCB) of 'C' series with short circuit indication, suitable for 240/415 Volts,50 Cycle, 10 kA/15 kA Value AC supply conforming to IS : 8828 : 1996, IEC : 60898 :2002 & 60947-2 but without enclosures :-
Single pole
MCB SP 6Amp to 32Amp 10kA rating
Four pole
MCB FP 50Amp to 63 Amp 10kA rating
Supplying of approved make TPN MCB DB metal double door IP 43 protection with provision for FP MCB/ Isolator/ RCCB/ RCBO as incomer and SP MCBs as outgoing inclusive of busbar, neutral bar, earth bar, connection copper wire not less than 16 sq.mm & two earth terminals etc. complete as per IS:13032(exclusive of MCB & isolator):
Fixing of MCB/MCCB/Isolator in sheet steel enclosure as required as per accepted practice, including mounting on busbar and cable connection etc. complete (labour only)
MCB/Isolator SP/DP
MCB/MCCB Isolator TP/TPN/FP
Labour charges for fixing sheet steel enclosure, MCB DB surface mounting type, as per accepted practice on 25x5mm flat iron clamp duly embedded in wall, cable connection etc. complete.
Supply and fixing street light with high power LED of 3 to 6 Watt each on existing bracket assembled on single MCPCB and additional unique peanut lens on each LED, system lumens output with efficacy>120 lm/Watt. luminiare having color temp upto 6500K & 50000 hrs. burning life with minimum @ L 70, The colour rendering index of LED light should be more than 70. Luminiare comprises of driver, PF> 0.95 & surge protection 10KV. Housing made of pressure die cast aluminium with heat resistant flat glass, IP65 protection. Submission LM 79-08/IS16106 (2012), IEC60598, IEC61347 i/c connection wire, testing etc. to complete the job.
90Watt, color temp 3000-6500k as required.
Supplying and fixing flood light with high power LED of 3 to 6 Watt each assembled on single MCPCB and additional unique peanut lens on each LED, system lumens output with efficacy>120 lm/Watt. luminiare having color temp upto 6500K & 50000 hrs. burning life with minimum @ L 70, The colour rendering index of LED light should be more than 70. Luminiare comprises of driver, PF > 0.95 & surge protection 10KV. Housing made of pressure die cast aluminium with heat resistant flat glass, IP65 protection. Submission LM 79-08/IS16106 (2012), IEC60598, IEC61347i/c connection wire, testing etc. to complete the job.
120Watt, color temp 3000-6500k as required.
Supply of XLPE insulated power cable (conforming IS-7098 Part-I) 1100 Volt grade, 1 core/2 core/3½ core/4 core ISI marked with alu. stranded /solid conductor
Armoured 2 core
Supply, fabrication and erection of angle/channel/flat iron fitting for overhead line & sub-station etc such as 'D' bracket, cross arms, top clamp, 'V' cross arms, back/support clamp or other similar work etc. including nut bolts of required size, making holes, fabrication, welding, cutting, etc. and painting with one coat of red oxide paint & two coat of aluminium paint as required as per specification.
Total Part 6
(with 18% GST) Total Part 6
(Part 1 + Part 2+ Part 3+ Part 4+ Part 5+ Part 6) Total PAC Rs
Executive Engineer PWD E/M Division No. 1, Bhopal
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.04 MB
TenderDocument.pdf
Tender Documents • 10.99 MB
Schedule.pdf
Tender Documents • 0.07 MB
BOQ_570229.xls
BOQ • 0.36 MB
Download all tender documents and submit your bid