Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹14.3 LAccepted-AOC | L1 | Accepted-AOC Lowest bidder | |
| 2 | L2₹15.6 L+₹1.3 L (9.44%)Rejected-Finance | L2 | Rejected-Finance Not lowest bidder | |
| 3 | L3₹15.7 L+₹1.4 L (9.85%)Rejected-Finance LIG 10 VIVEK NAGAR NAVIBAGH BHOPAL MADHYA PRADESH 462038 | BHOPAL | MADHYA PRADESH | 462038 | L3 | Rejected-Finance Not lowest bidder | |
| 4 | L4₹16.3 L+₹2.0 L (14.1%)Rejected-Finance | L4 | Rejected-Finance Not lowest bidder | |
| 5 | L5₹19.8 L+₹5.5 L (38.5%)Rejected-Finance | L5 | Rejected-Finance Not lowest bidder |
Tender Value
₹20 L
Closing Date
2 Mar 2023, 6:00 pmClosed
Garrison Engineer Dronachal
GE Dronachal, Dronachal Top, Neori Hills, Bhopal 462038
REPLACEMENT OF LT PANELS AND ALLIED WORKS AT DRONACHAL BASE BHOPAL
2022_MES_570077_2
8739/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
Bhopal
Class-E, Category b (i) and as per NIT documents
6 documents required · 6 mandatory
₹500
Garrison Engineer Dronachal
Yes
27 Apr 2023
10 Feb 2023
4 Mar 2023
10 Feb 2023
2 Mar 2023
17 Feb 2023
10 Feb 2023 - 16 Feb 2023
Amount
Excavation in trenches in soft/hard of any type soil not exceeding 1.5m deep and not exceeding 1.5 m wide and getting out complete all as specified and directed.
Returning, filling in including spreading, levelling, watering and well ramming excavated soil in layers not exceeding 25 cm thick each, back in trenches after cables have been laid and tested,poles, stays , struts have been erected and tested , all complete all as specified and directed at site.
Removing excavated surplus soil (Soft/hard soil) obtained from excavation to a distance not exceeding 50 mtr and deposting where directed at a level not exceeding 1.5m above the starting point complete all as specified and directed.
Supply and spread dry river sand for UG cable cushioning including punning on top and bottom of the cable complete all as specified and directed.
Supply and lay standard size common burnt clay building bricks sub class 'B' for cable protection, laid dry complete all as specified and directed.
M&L for earthing complete with galvanised steel earth plate electrode size 600x600x6.3mm thick burried directly in ground vertically in a pit of depth not less than 2.25 mtr below ground levels with top edge of the earth plate not less than 1.5 mtr below normal ground level surrounded from all sides by mixture of charcoal and common salt and electrode connected to and including galvanised iron strip 32X6 mm earth lead by means of bolts, nuts, check nuts and washers of galvanised steel and GI pipe light grade 20mm dia bore for watering funnel with wire mesh. CI cover with frame, PCC chamber pit with PCC 1:3:6 type C-2 excavation and earth work all as shown in electrical plate No 5 connected to earthing test point all as specified or indicated including testing on completion.NOTES 1. The unit rate includes for protection pipe and GI strip dia from top of earth plate upto 5.00 meter above groung level.
M&L cutting PCC/floor/road and taking out cable and making good, including material as per existing after laying of pipe for cable protection complete all as specified and directed size of trench not more than 0.30 x 0.30 cm.
S&F in replacement of GI Pipe medium grade on wall/floor for cable protection with fixing arrangement size 80mm dia complete all as specified and directed.
Taking down the existing unserviceble U/G cable of any size , any type from the trench including tracing out the fault with the help of megger complete all as specified and directed.
Supply and Laying XLPE heavy duty armoured electric under ground cable aluminum conductor 1100 volts grade in trenches/on pole through sleeves etc. complete all as specified and directed.
Cross sectional area 185 Sqm 31/2 Core.
Cross sectional area 240 Sqm 3.5 Core.
Cross sectional area 120 Sqm 3.5 Core.
Supply and fixing earth continuity conductor or main earthing lead 32 x 6 mm GI strip laid in pipe/ fixed to poles or any other indicated situation including jointing by using GI nuts, bolts, washer and saddle in addition to welding complete all as specified and directed.
M&L for outdoor/indoor LT panel board/Capacitor Panels/feeder pillar boxes with welding of front/Back side covers with suitable size hinges, locking system with 300mm long MS sliding door bolt 16mm dia, rubber gasket of appropriate size including proper fixing with nut bolts etc with minor spare parts like aluminium bus bars, PVC/porcelin cable connector, insulators, cable lugs etc and including spray painting with one coat of synethetic enamel paint outer & innner side with two coat of lime wash on plinth of panel board including connected accessories in any size complete all as specified and directed by Engineer-in-charge .
Supply installation, testing and commissioning LT Feeder piller board out door type cubicle panel boardsuitable for 3 phase,4 wire 415 volt 50 hz factory febricated approved CPRI powder coated made out of 3.15 mm thick CRCA sheet and MS angle iron sectiom 40X40X6mm frame with front and back openable double door system with locking arragement louver and air vent gaket for natural flow of air with canopy, inner compartment made out of 2 mm the CRCA sheet duly compartmentalized for each MCCB of incoming and outgoing with lockable arragement with alluminium bus bar three phase and neutral of capacity of 800 amp marked red, yelllow, black and blue inslulators, made of high strength insulated material suitable 1100 voltage all controll PVC wires shall be with 2.5 sq mm multistrand copper conductor and shall be properly bunched, tied, frerruled for proper indication , Panel shall be grouted on PCC foundation complete all as specified and directed with following accessories:-
Supply installation, testing and commissioning LT Feeder piller board out door type cubicle panel boardsuitable for 3 phase,4 wire 415 volt 50 hz factory febricated approved CPRI powder coated made out of 3.0 mm thick CRCA sheet and MS angle iron sectiom 40X40X6mm frame with front and back openable double door system with locking arragement louver and air vent gaket for netural flow of air with conopy, inner compartment made out of 2 mm the CRCA sheet duly compartmentalized for each MCCB of incoming and outgoing with lockable arragement with alluminium bus bar three phase and neutral of capacity of 800 amp marked red, yelllow, black and blue inslulators, made of high strength insulated material suitable 1100 voltage all controll PVC wires shall be with 2.5 sq mm multistrand copper conductor and shall be properly bunched, tied, frerruled for proper indication , Panel shall be grouted in PCC foundation complete all as specified and directed with following accessories:-
Supply, installed, test and commissioning of automatic power factor control panel 150 KVAR, having 12 Banks, panel fabricated with 3.15mm thick CRCA sheet with angle iron frame of 40 x 40 x 6mm, duly painted with two coats of synthetic enamel paint over a coat of red oxide with following
(i) Aluminium bus- bar 400 Amps,supported with suitable size Porcelain insulators , suitable size brass nut, bolts and washers with heat shrinkable colour coded PVC sleeving for 3 phase & neutral . - 01 Set (ii) MCCB, TPN, 36 KA, 320A adjustable type suitable for capacitor bank-1No iii)APFC Relay with Auto mode -1No. iv) Capacitor MPP-H , 3 Phase, 415Volts, 50HZ 150KVAR ie ( 25x5+10x1+5x2 +3x1+2x1=150KVAR) V) MCB with contactor for Capacitor switching vi) Bank ON/OFF indication lamps vii) Cooling fan ,SP, 230 Volts.-1Nos / As required.
Supply, installed, test and commissioning of automatic power factor control panel 80 KVAR, having 12 Banks, panel fabricated with 3.15mm thick CRCA sheet with angle iron frame of 40 x 40 x 6mm, duly painted with two coats of synthetic enamel paint over a coat of red oxide with following
(i) Aluminium bus- bar 400 Amps,supported with suitable size Porcelain insulators , suitable size brass nut, bolts and washers with heat shrinkable colour coded PVC sleeving for 3 phase & neutral . - 01 Set (ii) MCCB, TPN, 36 KA, 250A adjustable type suitable for capacitor bank-1No iii)APFC Relay with Auto mode -1No. iv) Capacitor MPP-H , 3 Phase, 415Volts, 50HZ 80KVAR ie ( 10x7+5x1 +3x1+2x1=80KVAR) V) MCB with contactor for Capacitor switching vi) Bank ON/OFF indication lamps vii) Cooling fan ,SP, 230 Volts.-1Nos / As required.
Supply and installation , testing & commissioning self supporting totally enclosed factory fabricated LT bus bar panel box made out of 3.15mm thick MS sheet with projected globe roof for rain water protection, dust and vermin proof hinged double shutter doors with neorprene rubber gasket , epoxy powder coated including danger plate, earth strip, ventilation louvers , bottam detachable gland plate complete with suitable size zinc chromium plated nuts, bolts, and washers etc outdoor type cubicle panel board suitable for 3 phase 4 wire ,415 volt ,50 HZ and 40 mm x 40 mm x 6 mm angle iron frame, weather proof ventilated with locking arrangement incl of PCC pedestal , comprising the following & including taking down the existing Feeder pillar panel board:-
(i) Aluminium bus- bar 400Amps,supported with suitable size Porcelain standlock with suitable size brass nut, bolts and washers with heat shrinkable colour coded PVC sleeving for 3 phase & neutral . - 01 Set
M&L for fixing the name board fabricated with MS Sheet 2mm thick of size 1.5x3 feet and fixed with suitable GI Clamp on 2/4 pole structure including writing the detail of Sub Stn and feeder etc with blue background & white colour Letter as directed by Engr -in Charge.
MODI CORPORATION
PRAGATI ELECTRICALS AND ELECTRONICS
CREATIVE CONSTRUCTION
BHARADWAJ BROTHERS
M/s AKG Engineers & Contractors
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .