This NIT is for ELECTRICAL WORKS FOR PANAGARH LPG PLANT. Detailed scope, terms and
2400016460-HD-09050
5100016460
Open Tender
Saraikela Kharsawan, Jharkhand
₹0
₹7.5 L
25 Oct 2024
4 Oct 2024
25 Oct 2024
25 Oct 2024
4 Oct 2024 - 15 Oct 2024
| Item No | Item Title | Description | Qty | Unit |
|---|---|---|---|---|
| 1 | SUP LT PANELS | SUP LT PANELS — PPLY OF LV SWITCHGEAR, PMCC (PMCC PANEL FOR PUMPS INCLUDING VFD WITH SOFT STARTER BYBASS SUITABLE FOR 1 LPG PUMP- 1 SET, VFD WITH SO STARTER BYPASS WITH CHANGEOVER MECHANISM SUITABLE FOR 2 LPG PUMPS - 1 SET, EMERGENCY DISTRIBUTION BUS & FEEDER & OTHER POWER SUPPL : DESIGN; MANUFACTURE; TESTING AT MANUFACTURER'S WORKS;INSPECTION;PACKING & SUPPLY OF PMCC PANEL ( OF FOLLOWING CURRENT RATINGS) FRE STANDING, DOUBLE FRONT, VERMIN AND DUST PROOF; FRONT & BACK OPERATING HAVING 415 VOLTS; 50KA(1 SEC); 50Hz; 3 PHASE AND NEUTRAL ALUMI UM BUS BAR AT THE TOP WITH A HEAT SHRUNK PVC SLEEVE MADE OF 14 GUAGE(2 MM MIN.) COLD ROLLED SHEET STEEL DULY 7 TANKS PROCESS FOR S FACE PREPARATION & SPRAY PAINTED POWDER COATED IN SHADE 631 OF IS - 5 LIGHT ADMIRALTY GREY COLOUR, ENAMEL PAINT; 2 COATS OF EPOXY PR ER, 2 COATS OF EPOXY BASE FINISH PAINT; MINIMUM THICKNESS OF PAINT SHALL BE 80 MICRONS; C.R SHEET STEEL THICKNESS MUST BE 2.03 MM (1 SWG) FOR LOAD BEARING AND 1.6 MM FOR NON LOAD BEARING MEMBERS.ALL AROUND (TOLERANCE +/- 0.14 MM AS PER IS:513).BUSBAR SHALL BE MADE F ELECTROLYTIC GRADE WROUGHT ALUMINIUM ALLOY OR ALUMINIUM; ALLOY; OR ELECTROLYTIC ELECTRIC GRADE COPPER; CONFORMING TO RELEVANT INDI STANDARD COMPLETE AS PER TENDER SPECIFICATION & DRAWINGS.THE PMCC FOR PUMPS & OTHER POWER SUPPLY COMPRISES WITH 630A ACB AS MAIN COMERS, COMMUNICABLE DIGITAL MULTIFUCTION METER (COMPRISES WITH VOLTMETER, ENERGY METER, AMMETER, FREQUENCY METER, POWER FACTOR MEAS ING SYSTEM) WITH UNDER VOLTAGE, EARTH FAULT OVER RS 485, OVERCURRENT RELAY & PHASE INDICATING LAMPS WITH MENTIONED OUTGOING FEEDERS SPECIFIED RATINGS IN SINGLE LINE DIAGRAM. THE PANEL WILL BE INDOOR TYPE, FREE STANDING, FLOOR MOUNTING, DUST & VERMIN PROOF, SHEET TAL ENCLOSED, DOUNLE FRONT, CUBICAL TYPE, DRAW OUT CONSTRUCTION OF 3PH, (4)W, (415) V, (50) HZ, TPN, (50) KA / (1) SEC, AS PER SPECI CATION AND DIRECTION OF HPCL ENGINEER CONFIRMING TO IS- 8623 AND IS- 13947. COMPLETE AS PER SLD AND TENDER SPECIFICATIONS/DATA SHEET & AS INSTRUCTED BY HPCL.APPROXIMATE DIMENSION - 4500MM(L) X 900MM(D) X 2175MM(H)(THIS IS A MINIMUM PANEL DIMENSION SPECIFIED.VENDO TO SPECIFY DURING DETAILED ENGINEERING AS PER JOB REQUIREMENT & SLD).MODULE HEIGHT 300MM MINIMUM. CODES and STANDARDS. MINIMUM DEGRE OF ENCLOSURE PROTECTION SHALL BE IP 4X. TYPE OF INDICATING LAMPS SHALL BE CLUSTER LED.THE PANEL WILL BE MANUFACTURED CONFIRMING TO A PER IEC-61439 AND IS-13947.THE PANEL WILL BE COMPRISING OF FOLLOWING BASIC FEEDERS:A) 630A ACB WITH O/C, E/F, S/C & U/V RELEASE CROPROSSOR BASED, EDO TYPE AS INCOMMER WITH METERING UNIT.B) 1 NOS. 90 KW ACTIVE FRONT END (IGBT based rectifier) Regenerative Ty Variable Frequency Drive (VFD) system WITH SOFT STARTER BYPASS & Sinus filter Suitable for 800-1000 motor cable length FEEDER WITH ERMISTOR CONTROL UNITC) 1 NOS. 90 KW ACTIVE FRONT END (IGBT based rectifier) Regenerative Type Variable Frequency Drive (VFD) sys m VFD WITH SOFT STARTER BYPASS FEEDER WITH CHANGE OVER MECHANISM FOR OPERATING 2 LPG PUMPS & Sinus filter Suitable for 800-1000 moto cable length FEEDER WITH THERMISTOR CONTROL UNIT FOR INDIVIDUAL MOTORS.D) 1-NO. 250A CHANGE OVER SWITCH FOR OPERATION OF TWO NOS.9 W MOTORE) 2-NOS. 5.5 KW DOL STARTER FEEDER FOR COOLING PUMPS.F) 1 NO.1.5 KW FEEDER DOL SPARE FEEDER.G) 15-NOS. 63 A TPN MCCB UTGOING FEEDER with Thermal Magnetic release.H) 7-NOS 63A TPN MCCB OUTGOING FEEDER WITH ELRI) 5-NOS. 32A TPN MCCB OUTGOING FE ER WITH ELRJ) 1-NO. 2.5-4 A TP MPCB OUTGOING FEEDER FOR CONTROL TRANSFORMER (415/110V, 1.5KVA)K) 1-NO 250A TP MCCB FEEDER.L) -NO. 100A TP MCCB FEEDER.M) 2-NOS. 200A 4P MCCB WITH O/C, E/F & SHUNT TRIP RELEASE FEEDER WITH ELECTRICAL AND MECHANICAL INTERLOC NOTE: ALL THE FEEDER SHALL HAVE ROTARY HANDLE EXTENDED UPTO PANEL EXTERIOR WITH PROVISION FOR LOTO FACILITY.REF. TENDER. DRG. .- C533-04-DRG-401 (REV -3) | - | LOT |
| 2 | SUP DV INDIC PANEL | SUP DV INDIC PANEL — PPLY OF PLC BASED DV INDICATION CUM ACTUATION PANEL WITH 12" HMI FOR INDICATION AND LED TOGGLE SWITCH FOR ACTUATION FOR 20 ZONES HAV G THIRD PARTY INTEGRATION WITH EXISTING PLC BASED FIRE FIGHTING PANEL ON OPEN PROTOCOL HAVING FOLLOWING BOM:1. MCB SP, C CURVE, 6A ATING - 02 NOS2.MCB DP, C CURVE, 6A RATING - 03 NOS3. CONTROL TERMINALS FOR 2.5MM SQ: 100 NOS4. INDICATION LAMP 22.5MM DIA (RE / 24 V DC: 05 NOS5. ELECTRONIC HOOTER_ 24V DC- 01 NO.6. RED LIGHTED TOGGLE SWITCH - 20 NOS.7.AUX RELAY WITH 2 NO/ NC CHANGEOVE CONTACTS-26 NOS.8. ACKNOWLEDGE PUSH BUTTON (GREEN) - 01 NO.9.RESET PUSH BUTTON (BLACK) - 01 NO.10. CONTROL ON/OFF SELECTOR SWI H - 01 NO.11.PARALLEL REDUNDANT POWER SUPPLY 240V AC TO 24V DC 6A WITH DIODE ORING MODULE - 01 SET12. PLC HAVING 01 NO. 32 CHANN DI CARD, 1 NO. 16 CHANNEL DO CARD & DUAL RS 485 COMMUNICATION PORT.PLC SHALL BE EXPANDABLE UPTO FOR 250 I/Os13. 12" HMI- 01 NOS. ANEL SHALL SINGLE FRONT, FREE STANDING, WALL/STAND MOUNTING, FIXED TYPE CUBICAL AND NON COMPARTMENTLISED SUITABLE FOR INDOOR INSTALL IONS.DEGREE OF PROTECTION SHALL BE IP42.PANEL SHALL BE PAINTED BY ELECTROSTATIC POWDER COATING PAINT AFTER NECESSARY TREATMENT HAVIN FOLLOWING SHADES:a) PANEL - RAL-7035FABRICATION DETAIL:-PANEL SHALL BE FABRICATED BY CRCA SHEET WITH BELOW MENTIONED SIZES:a FRAME - 2.0mm/14SWGb) FRONT DOORS - 1.6mm/16SWGc) BACK DOORS/ - N/ASIDE COVERSd) GLAND PLATE - 2mm/1.4SWG (UNDRILLED)e) BASE RAME - N/Af) MOUNTING PLATE - 2.0mm/14SWG | - | Each |
| 3 | SUP - 63A FLP LDB | SUP - 63A FLP LDB — ENDOR TO SUPPLY NORMAL SUB-LIGHTING PANEL INDOOR FLAMEPROOF, GENERAL PURPOSE, WALL/STRUCTURE MOUNTED TYPE (LP) IP-55 WITH INTREGAL RE RETADENT, UV STABILIZED FRP CANOPIES FOR OUTDOOR AREA, SUITABLE FOR SAFE AREA,EW-D TYPE SUITABLE FOR ZONE-2 GAS GROUP IIA / IIB A PER IS- 12063/1987 (IEC- 60529/1989)a) INCOMER - 3PH,(4)W,(415)V,(50)HZ,TPN,(25)KA/(1)SEC, 1 NO 63A TPN MCB WITH ELCB of 30mAb) OU OING - 415V / 240V, 10NOS , 6A SPN MCBFOR NORMAL LIGHTING SUPPLY TO MSV TOP & MANIFOLD & AROUND MSV ROAD AREA.NOTE: The Scope o Supply also includes supply of PESO Approved Plugs for 20% Outgoing Cable entries. Bidder to quote accordingly" | - | Each |
| 4 | SUP - 63A FLP LDB | SUP - 63A FLP LDB — ENDOR TO SUPPLY NORMAL SUB-LIGHTING PANEL INDOOR FLAMEPROOF, GENERAL PURPOSE, WALL/STRUCTURE MOUNTED TYPE (LP) IP-55 WITH INTREGAL IRE RETADENT, UV STABILIZED FRP CANOPIES FOR OUTDOOR AREA, SUITABLE FOR SAFE AREA,EW-D TYPE SUITABLE FOR ZONE-2 GAS GROUP IIA / IIB PER IS- 12063/1987 (IEC- 60529/1989) a) INCOMER - 3PH,(4)W,(415)V,(50)HZ,TPN,(25)KA/(1)SEC, 1 NO 63A TPN MCB WITH ELCB of 30mAb) TGOING - 415V / 240V, 6 NOS , 6A SPN MCB FOR NORMAL LIGHTING SUPPLY TO TT GANTRYNOTE: The Scope of Supply also includes supply PESO Approved Plugs for 20% Outgoing Cable entries. Bidder to quote accordingly" | - | Each |
| 5 | SUP - 32A FLP ELDB | SUP - 32A FLP ELDB — ENDOR TO SUPPLY SUB-LIGHTING PANEL INDOOR FLAMEPROOF, GENERAL PURPOSE, WALL/STRUCTURE MOUNTED TYPE (LP) IP-55 WITH INTREGAL FIRE R ARDENT, UV STABILIZED FRP CANOPIES FOR OUTDOOR AREA, SUITABLE FOR SAFE AREA,EW-D TYPE SUITABLE FOR ZONE-2 GAS GROUP IIA / IIB AS PER S- 12063/1987 (IEC- 60529/1989) a) INCOMER - 1PH WITH NEUTRAL(2)W,(230)V,(50)HZ,SPN,(10)KA/(1)SEC, 1 NO 32A SPN MCB WITH ELCB of mAb) OUTGOING - 8NOS , 6A SPN MCBFOR EMERGENCY / CRITICAL LIGHTING SUPPLY TO MSV TOP & MANIFOLD AREA & TT GANTRYNOTE: The Scop of Supply also includes supply of PESO Approved Plugs for 20% Outgoing Cable entries. Bidder to quote accordingly" | - | Each |
| 6 | SUP WP UPS DB | SUP WP UPS DB — UPPLY INSTALL, TESTING & COMMISIONING OF WP IP 55 RATING ENCLOSURE OR BETTER 230 V, 63A, 50KA FOR 1SEC, SPN, SINGLE FRONT, WALL MO T, INDUSTRIAL TYPE OF 240V, 1PH, MCB DB FOR MSV INSTRUMENTATION & CRITICAL LIGHTING SUPPLY ALONGWITH SPD Type 1+2(1 Phase) at inc ing Supply of UPS DB. CABLE SIZES TO BE AS PER REQ. LOAD (MINIMUM 2.5 SQ.MM).The panel shall be complete in all respects with necess y indication lamps for powering, necessary control wiring voltmeter, ammeter etc. ALL THE METERS SHALL BE COMMUNICABLE OVER RS 485a INCOMER - 1PH WITH NEUTRAL (2) W ,(230)V,(50)HZ,DP,(50)KA/(1)SEC, 1 NO 63 MCCB WITH ELCB of 30mA with Thermal Magnetic release & xtended Rotary Handle (extended upto outside the Panel) b) OUTGOING - i) 30NOS, 6A SPN MCBii) 6 NOS.,16A SPN MCBiii) 5 NOS. 2A SPN MCBiv) 2 NOS. 25 A TP Changeover Power Contactor" | - | LOT |
| 7 | SUP - 63A FLP WELDING | SUP - 63A FLP WELDING — PPLY OF 63A, 415 VOLT AC,3-PH&N (5-PIN) FLAMEPROOF & WEATHERPROOF WITH MCB, SWITCH SOCKET WITH PLUG TOP, 4 NOS AND LOOPING FACILITY, LAMEPROOF DOUBLE COMPRESSION NIPLATED BRASS CABLE GLAND FOR INCOMING AND OUTGOING CABLES, PVC SHROUD,2MM THICK FRP CANOPY WITH SIDE VER AND OTHER ACCESSORIES.SUPPLY IS INCLUSIVE OF WP & FLP DOUBLE COMPRESSION CABLE GLANDS, MOUNTING BRACKET, PVC SHROUD, EQUAL NO OF P PLUGS AS NO OF CABLE ENTRIES AS PER CABLE ENTRY SIZE AND ALL OTHER ACCESSORIES. | - | Each |
| 8 | SUP - 6 WAY FLP JB | SUP - 6 WAY FLP JB — UPPLY OF FLAMEPROOF & WEATHER PROOF JUNCTION BOX GENERAL PURPOSE WITH FRP CANOPY; CLASSIFICATION, HAZARD AREAS:EX-D-ZONE I AND II,GA GROUP:IIC; INGRESS PROTECTION:IP66; MATERIAL:CAST ALUMINIUM ALLOY LM-6; DIMENSION:N/A; CROSS SECTION,TERMINAL:2.5 MM2 (M20 X 1.5P ( ; NO OF CABLE ENTRIES:6; GASKET : ENDLESS NEOPRENE RUBBER; FINISH : INSIDE & OUTSIDE LIGHT GREY EPOXY POWDER COATING SHADE NO.-631 A PER IS : 5; EARTHING : 1 NO INSIDE AND 2 NOS OUTSIDE; TERMINALS: CLIP-ON TERMINALS OF SUITABLE FOR TERMINATION UPTO 4 SQ.MM COPPER/A MINUM CONDUCTOR CABLE; MOUNTING ARRANGEMENT : WALL / COLUMN/ STRUCTURAL INCOMING CABLE: 7C- 24C X 2.5SQMM (1 NO). BIDDER TO CHECK AT ITE DURING DETAILED ENGINEERING BEFORE PLACING ORDER. OUTGOING CABLE: 3C X 1.5 SQMM (5 NOS)SUPPLY INCLUSIVE OF FLP DOUBLE COMPRESSI NI PLATED BRASS CABLE GLANDS, MOUNTING BRACKET,PVC SHROUD, EQUAL NO OF SS FLP PLUGS AS NO OF CABLE ENTRIES AS PER CABLE ENTRY SIZE D ALL OTHER ACCESSORIES. CABLE OPENINGS ARE TENTATIVE, MAY VARY AT TIME OF PLACEMENT OF PO.Make: Baliga /FCG/Flameproof control gea /Flexpro." | - | Each |
| 9 | SUP - 4 WAY FLP JB | SUP - 4 WAY FLP JB — UPPLY OF FLAMEPROOF & WEATHER PROOF JUNCTION BOX GENERAL PURPOSE WITH FRP CANOPY; CLASSIFICATION, HAZARD AREAS:EX-D-ZONE I AND II,GA GROUP:IIC; INGRESS PROTECTION:IP66; MATERIAL:CAST ALUMINIUM ALLOY LM-6; DIMENSION:N/A; CROSS SECTION,TERMINAL:2.5 MM2 (M20 X 1.5P ( ; NO OF CABLE ENTRIES:4; GASKET : ENDLESS NEOPRENE RUBBER; FINISH : INSIDE & OUTSIDE LIGHT GREY EPOXY POWDER COATING SHADE NO.-631 A PER IS : 5; EARTHING : 1 NO INSIDE AND 2 NOS OUTSIDE; TERMINALS: CLIP-ON TERMINALS OF SUITABLE FOR TERMINATION UPTO 4 SQ.MM COPPER/A MINUM CONDUCTOR CABLE; MOUNTING ARRANGEMENT : WALL / COLUMN/ STRUCTURAL SUPPLY INCLUSIVE OF FLP DOUBLE COMPRESSION NI PLATED BRASS BLE GLANDS, MOUNTING BRACKET,PVC SHROUD, EQUAL NO OF SS FLP PLUGS AS NO OF CABLE ENTRIES AS PER CABLE ENTRY SIZE AND ALL OTHER ACCES RIES. CABLE OPENINGS ARE TENTATIVE, MAY VARY AT TIME OF PLACEMENT OF PO.Make: Baliga /FCG/Flameproof control gears/Flexpro." | - | Each |
| 10 | SUP OF FLP PW SKT | SUP OF FLP PW SKT — PPLY AND INSTALLATION OF FLAMEPROOF & WEATHER PROOF (WP-FLP) POWER SOCKET FOR POWER SUPPLY TO COMPOSITE CRITICAL LIGHTING UNIT, GENE L PURPOSE WITH FRP CANOPY IN DIE CAST ALUMINIUM LM-6 ENCLOSURE SUITABLE FOR ZONE-1&2 GAS GROUP IIA & IIB. INDOOR TYPE, CONSIST OF 15 240V AC SPN PLUG SOCKET WITH MCB ISOLATOR AND CLIP ON TYPE TERMINALS SUITABLE FOR WALL/STRUCTURAL MOUNTING, COLOUR SHED -LIGHT GREY OXY SHED 631 AS PER IS-5 WITH CABLE ENTRY 3/4' ET X 2NOS. | - | Each |