| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹21.3 LAccepted-AOC | ₹21.3 L | L1 | Accepted-AOC Tender accepted due to lowest and quoted reasonable rates |
| 2 | L2₹23.5 LRejected-Finance 99 MODEL TOWN PATHANKOT 145001 | PATHANKOT | PATHANKOT | PUNJAB | 145001 | ₹23.5 L | L2 | Rejected-Finance Higher side quoted amount |
| 3 | L3₹24.0 LRejected-Finance | ₹24.0 L | L3 | Rejected-Finance Higher side quoted amount |
| 4 | L4₹24.1 LRejected-Finance | ₹24.1 L | L4 | Rejected-Finance Higher side quoted amount |
| 5 | L5₹51.1 LRejected-Finance | ₹51.1 L | L5 | Rejected-Finance Higher side quoted amount |
| Sl No | Description | Qty | Unit | Vishav Karma Refrigeration and Electric Work L5 | satpal and brothers L2 | M/S SINGHAL ENGINEERS L4 | JK ENTERPRISES L3 | M/S HIMANSHU BUILDERS L1 |
|---|---|---|---|---|---|---|---|---|
| 1.00 | Taking down old unserviceable copper/aluminium point wiring (light, fan, socket , power socket and bulk head fittings) on surface/concealed wiring, wooden batten/casings & caping complete, including fixture and fittings such as switches, ceiling roses,pendents holder, regulators and sockets by unscrewing carefully from boards etc and making good disturbed surfaces of walls, as per existing finishes complete all as spd and directed. | 2,805 | Per point | 23 ₹64,515 | 1 ₹2,805 | 18 ₹50,490 | 2 ₹5,610 | 1 ₹2,805 |
| 2.00 | M&L for Modular point wiring for one light/one fan controlled by one switch with 1.5 sqmm PVC insulated unsheathed multistrand copper conductor FRLS-H cable with and including PVC concealed conduit ISI marked heavy duty for one light fan/bell point controlled by one switch including Modular cover plate and modular metallic flush boxes of suitable way modular boxes and cover plates including PVC green insulated unsheathed 1.5 sqmm multistrand copper conductor FRLS-H cable as continous earthwire and connecting to earth duly, complete all as specified and directed.
Note: (a) Insulation test of point wiring (b) colour coding is to be maintained .(Ph-Red, N-Black, Half -Yellow, Earth- Green) (c) Metallic flush box should of same make of modular switch socket. | 350 | Per Point | 699 ₹2.4 L | 350 ₹1.2 L | 290 ₹1.0 L | 300 ₹1.1 L | 380 ₹1.3 L |
| 3.00 | All as per srl item No 2 here-in-before but MODULAR call Bell point complete all as specified and directed. | 15 | Per Point | 399 ₹5,985 | 350 ₹5,250 | 399 ₹5,985 | 320 ₹4,800 | 400 ₹6,000 |
| 4.00 | All as per srl item No 2 here-in-before but MODULAR 3 pin 5 amps socket outlet on the same board with other switch complete all as specified and directed. | 60 | Per Point | 299 ₹17,940 | 100 ₹6,000 | 90 ₹5,400 | 100 ₹6,000 | 100 ₹6,000 |
| 5.00 | All as per srl item No 2 here-in-before but MODULAR 3 pin 5 amps socket outlet on independent Board complete all as specified and directed. | 60 | Per Point | 699 ₹41,940 | 350 ₹21,000 | 299 ₹17,940 | 280 ₹16,800 | 400 ₹24,000 |
| 6.00 | All as per srl item No 2 here-in-before but MODULAR 15/16 Amps socket outlet on inependent board with 2.5 sqmm copper conducter FRLS-H cable and 2.5 sqmm PVC insulated unsheathed copper onductor cable FRLS-H (Green Colour) as earth lead complete all as specified and directed. | 40 | Per Point | 1,999 ₹79,960 | 450 ₹18,000 | 399 ₹15,960 | 350 ₹14,000 | 450 ₹18,000 |
| 7.00 | M&L for point wiring with 4 sqmm PVC insulated unsheathed multistrand copper conductor FRLS-H cable in PVC concealed conduit terminated in new anodised pressed steel sunken box with ISI marked bakelite laminated sheet fixed with cadmium plated screws and washers for switches and sockets, including 4 sqmm PVC insulated unsheathed multistrand copper conductor FRLS-H as earth continuity conductor connected to common earth dolly including, cutting chiseling for concealed piping ,including insulation test of point wiring and making good disturbed surface area and white wash/colour wash to matching with the existing colour and all as specified .Note: colour coding is to be maintained .
Note: (a) Insulation test of point wiring (b) colour coding is to be maintained .(Ph-Red, N-Black, Half -Yellow, Earth- Green) | 40 | Per Point | 2,499 ₹99,960 | 650 ₹26,000 | 599 ₹23,960 | 400 ₹16,000 | 550 ₹22,000 |
| 8.00 | M&L for point wiring for light / fan controlled by one switch with 1.50 sqmm PVC insulated unsheathed multistrand copper conductor FRLS-H cable in existing PVC concealed conduit terminated in new anodise pressed steel sunken box with ISI marked bakelite laminated sheet fixed with cadmium plated screws and washers for switches and sockets, including 1.5 sqmm PVC insulated unsheathed multistrand copper conductor FRLS-H as earth continuity conductor connected to common earth dolly including, cutting chiseling for concealed boxes, including insulation test of point wiring and making good disturbed surface area and white wash/colour wash to matching with the existing colour and all as specified .Note: colour coding is to be maintained . (Ph-Red, N-Black, Half -Yellow, Earth- Green). | 1,100 | Per Point | 599 ₹6.6 L | 310 ₹3.4 L | 269 ₹3.0 L | 280 ₹3.1 L | 340 ₹3.7 L |
| 9.00 | All as per Srl No 8 here-in-before but for call Bell point complete all as specified and directed . | 10 | Per Point | 349 ₹3,490 | 310 ₹3,100 | 289 ₹2,890 | 300 ₹3,000 | 360 ₹3,600 |
| 10.00 | All as per Srl item No 8 here-in-before but for 5 pin 5 amps socket outlet or independent board complete all as specified and directed. | 100 | Per Point | 599 ₹59,900 | 330 ₹33,000 | 299 ₹29,900 | 250 ₹25,000 | 360 ₹36,000 |
Updated dates
Tender Value
Refer Docs
EMD Value
₹80,000
Closing Date
27 Oct 2025, 6:00 pmClosed
GE(W) PATHANKOT
GE(W) PATHANKOT
REPAIR/MAINTENANCE AND REWIRING TO INTERNAL ELECTRIFICATION WITH COMPLETE FITTING FIXTURES AND CONNECTED ALLIED WORKS IN OTM ACCN OF ZONE A AND B UNDER GE(W) PATHANKOT
2025_MES_732966_1
GE/PKT-66/2025-26
Open Tender
Miscellaneous Works
180 days
GE (W) PATHANKOT
As per NIT and Tender Documents
9 documents required · 9 mandatory
₹500
GE (West) Pathankot
₹80,000
8 Jan 2026
27 Sept 2025
29 Oct 2025
27 Sept 2025
27 Oct 2025
12 Oct 2025
Amount
Taking down old unserviceable copper/aluminium point wiring (light, fan, socket , power socket and bulk head fittings) on surface/concealed wiring, wooden batten/casings & caping complete, including fixture and fittings such as switches, ceiling roses,pendents holder, regulators and sockets by unscrewing carefully from boards etc and making good disturbed surfaces of walls, as per existing finishes complete all as spd and directed.
M&L for Modular point wiring for one light/one fan controlled by one switch with 1.5 sqmm PVC insulated unsheathed multistrand copper conductor FRLS-H cable with and including PVC concealed conduit ISI marked heavy duty for one light fan/bell point controlled by one switch including Modular cover plate and modular metallic flush boxes of suitable way modular boxes and cover plates including PVC green insulated unsheathed 1.5 sqmm multistrand copper conductor FRLS-H cable as continous earthwire and connecting to earth duly, complete all as specified and directed. Note: (a) Insulation test of point wiring (b) colour coding is to be maintained .(Ph-Red, N-Black, Half -Yellow, Earth- Green) (c) Metallic flush box should of same make of modular switch socket.
All as per srl item No 2 here-in-before but MODULAR call Bell point complete all as specified and directed.
All as per srl item No 2 here-in-before but MODULAR 3 pin 5 amps socket outlet on the same board with other switch complete all as specified and directed.
All as per srl item No 2 here-in-before but MODULAR 3 pin 5 amps socket outlet on independent Board complete all as specified and directed.
All as per srl item No 2 here-in-before but MODULAR 15/16 Amps socket outlet on inependent board with 2.5 sqmm copper conducter FRLS-H cable and 2.5 sqmm PVC insulated unsheathed copper onductor cable FRLS-H (Green Colour) as earth lead complete all as specified and directed.
M&L for point wiring with 4 sqmm PVC insulated unsheathed multistrand copper conductor FRLS-H cable in PVC concealed conduit terminated in new anodised pressed steel sunken box with ISI marked bakelite laminated sheet fixed with cadmium plated screws and washers for switches and sockets, including 4 sqmm PVC insulated unsheathed multistrand copper conductor FRLS-H as earth continuity conductor connected to common earth dolly including, cutting chiseling for concealed piping ,including insulation test of point wiring and making good disturbed surface area and white wash/colour wash to matching with the existing colour and all as specified .Note: colour coding is to be maintained . Note: (a) Insulation test of point wiring (b) colour coding is to be maintained .(Ph-Red, N-Black, Half -Yellow, Earth- Green)
M&L for point wiring for light / fan controlled by one switch with 1.50 sqmm PVC insulated unsheathed multistrand copper conductor FRLS-H cable in existing PVC concealed conduit terminated in new anodise pressed steel sunken box with ISI marked bakelite laminated sheet fixed with cadmium plated screws and washers for switches and sockets, including 1.5 sqmm PVC insulated unsheathed multistrand copper conductor FRLS-H as earth continuity conductor connected to common earth dolly including, cutting chiseling for concealed boxes, including insulation test of point wiring and making good disturbed surface area and white wash/colour wash to matching with the existing colour and all as specified .Note: colour coding is to be maintained . (Ph-Red, N-Black, Half -Yellow, Earth- Green).
All as per Srl No 8 here-in-before but for call Bell point complete all as specified and directed .
All as per Srl item No 8 here-in-before but for 5 pin 5 amps socket outlet or independent board complete all as specified and directed.
All as per Srl item No 8 here-in-before but for 3 pin 5 amps socket outlet on the same board with other switch complete all as specified and directed.
M&L for point wiring with 2.5 sqmm PVC insulated unsheathed multistrand copper conductor FRLS-H cable in existing PVC concealed conduit terminated in new anodised pressed steel sunken box with ISI marked bakelite laminated sheet fixed with cadmium plated screws and washers for switches and sockets, including 2.5 sqmm PVC insulated unsheathed multistrand copper conductor FRLS-H as earth continuity conductor connected to common earth dolly including, cutting chiseling for concealed piping ,including insulation test of point wiring and making good disturbed surface area and white wash/colour wash to matching with the existing colour and all as specified. Note: colour coding is to be maintained .(Ph-Red, N-Black, Half -Yellow, Earth- Green).
M&L for Modular point wiring for one light/one fan controlled by one switch with 1.5 sqmm PVC insulated unsheathed multistrand copper conductor FRLS-H cable in exisitng PVC concealed conduit ISI marked heavy duty for one light fan/bell point controlled by one switch including New Modular cover plate and new modular metallic flush boxes of suitable way including PVC green insulated unsheathed 1.5 sqmm multistrand copper conductor FRLS-H cable as continous earthwire and connecting to earth duly, complete all as specified and directed Note: (a) Insulation test of point wiring (b) colour coding is to be maintained .(Ph-Red, N-Black, Half -Yellow, Earth- Green) (c) Metallic flush box should of same make of modular switch socket.
All as per Srl No 13 here-in-before but for call Bell point complete all as specified and directed .
All as per Srl item No 13 here-in-before but for 5 pin 5 amps socket outlet or independent board complete all as specified and directed.
All as per Srl item No 13 here-in-before but for 3 pin 5 amps socket outlet on the same board with other switch complete all as specified and directed.
All as per srl item No 13 here-in-before but MODULAR 15/16 Amps socket outlet on independent board with 2.5 sqmm copper conducter FRLS-H cable and 2.5 sqmm PVC insulated unsheathed copper conductor cable FRLS-H (Green Colour) as earth lead complete all as specified and directed.
S&F switch piano flush type one way 5 amps SP 240 volts complete all as specified and directed.
S&F switch piano flush type one way 15 amps SP 240 volts complete all as specified and directed.
S&F socket outlet 2 in 1, 3 pin 5 amps flush type 240 volts complete all as specified and directed.
S&F socket outlet 2 in 1, 5 pin, 5 and 15 amps flush type 230 volts complete all as specified and directed.
S&F lamp holder/batton holder/angle holder insulated body with bakelite back plate suitable for fittings complete all as specified and directed.
S&F switch Bell push, flush type, 5 amp one way complete all as specified and directed by Engr-in-charge.
S&F Bell Ding Dong, AC 230 Volts single Phase complete all as specified and directed by Engr-in-charge.
S&F ceiling rose 65 x 50mm three terminals complete all as specified and directed.
S&F ceiling fan regulator electronic socket type 5 stage speed variation ISI marked complete all as specified and directed.
S&F Modular switch 1 way 6 A, 1 module complete all as specified and directed.
S&F Modular switch 1 way 16A, 1 module complete all as specified and directed.
S&F Modular Socket 6A/ 2/3 pin combined 2 module complete all as specified and directed.
S&F Modular Socket, 16A - 2/3 pin combined 2 module complete all as specified and directed.
S&F Modular Fan regulator 6A 1 module , complete all as specified and directed.
S&F Modular Bell push 6A 1 module , complete all as specified and directed.
S&F in replacement sleek LED mirror light fitting 2 feet long 1x10 W including inbuilt ind driver complete with all accessories prewired and connecting electrically to ceiling rose using PVC insulated and overall sheathed flexible copper conductor cable of suitable size complete all as required at site or directed.
S&F in replacement of CFLs with LED Lamp, B22 type ,12 watt,complete all as specified and directed.
S&F in replacement energy saving decorative LED box type 20 W, 6500K, cool white, Lumen efficiency 110 lumen/watt, light fitting PVC housing provided for efficient heat dissipation with polycarbonate diffuser & integrated electronic driver complete with all accessories prewired and making connections with twisted flexible copper cable of suitable size from ceilling rose/PVC connector to light fittings complete all as spd and directed by Engr -in -charge.
S&F in replacement energy saving decorative LED box type 20 W, 3000K, Warm white, Lumen efficiency 110 lumen/Watt, light fitting light fitting extruded aluminium housing provided for efficient heat dissipation with polycarbonate diffuser & integrated electronic driver complete with all accessories prewired without tube and making connections with twisted flexible copper cable of suitable size from ceilling rose/PVC connector to light fittings complete all as spd and directed by Engr -in -charge.
S&F in replacement LED Bulkhead fitting 10 watt all as specified and directed by Engr-in-charge.
S&F in repair surface light with motion sensor with WW/NW/CW, round/square in shape, with dimlight surface, of 15 Watt with 360 degree motion sensing within a radius of 4.5 meter with advance motion sensing technology of the accessing the movement for activating the light when needed complete with hassel free operations with 100 lumens per watt round in shape, 145mm in diameter, Height 40mm, wattage -15W, with nominal flux of 1500 lumen, 100 lumen/watt NW-4000K & CW with 6500K, warm white with 3000K including to mount synthetic diffuses complete making connections with twisted flexible copper cable of suitable size from ceilling rose/PVC connector to light fittings complete all as spd and directed by Engr -in -charge.
M&L for providing/ cutting the round/ square hole of required size in wall finishing the distrubed surfaces as per existing finishes complete all as spd and S&F propeller PVC type AC ventilating fans, Single phase, 230 volts 250 mm sweep complete and supply and grouting the ragged bolts in wall, fixing the frame on the exhaust side (outer surface of the wall) and connecting with suitable size copper cable from ceiling rose to exhaust fan motor and writting MES No. with black synthetic enamel paint 2.0 cm high complete all as spd and directed by Engr-in-charge.
M&L for providing/ cutting the round/ square hole of required size in wall finishing the distrubed surfaces as per existing finishes complete all as spd and S&F MS ventilating fans Single phase, 230 volts 300 mm or 12” H.D EX Fan (900 RPM) complete and supply and grouting the ragged bolts in wall, fixing the frame on the exhaust side (outer surface of the wall) and connecting with suitable size copper cable from ceiling rose to exhaust fan motor and writting MES No. with black synthetic enamel paint 2.0 cm high complete all as spd and directed by Engr-in-charge.
S&F in replacement of Decorative Gate Light Moon Opal made up of high Grade unbreakable polycarbonate material suitable for and including 12/20 Watt LED Bulb complete all as specified and directed.
S&F in replacement of existing unsv sheet metal enclosure with sheet metal enclosure MCB distribution board single pole and neutral with a two pin and earth plug and socket 20 amps 240 volts, complete with one single pole MCB of 20 amps 'C' curve complete all as specified and directed.
S&F in replacement of sheet metal enclosure MCB distribution board, double door with IP-43 protection single phase 240 volts 12 way, including suitable size copper bus bar and neutral link fixed flush in wall including chases in wall for fixing DB and making good distributed wall surfaces to match with existing specification complete all as specified and directed.
S&F in replacement of sheet metal enclosure MCB distribution board, double door with IP-43 protection single phase 240 volts 6 way, including suitable size copper bus bar and neutral link fixed flush in wall including chases in wall for fixing DB and making good the distributed wall surfaces to match with existing specification complete all as specified and directed.
S&F in replacement of sheet metal enclosure MCB distribution board, double door with IP-43 protection single phase 240 volts 8 way, including suitable size copper bus bar and neutral link fixed flush in wall including chases in wall for fixing DB and making good the distributed wall surfaces to match with existing specification complete all as specified and directed.
S&F in replacement for MCB SP 240 volts any rating from 6 to 40 amps, 'C' curve with rupturing capacity 10 KA, including providing thimble for out going cables complete all as specified and directed.
S&F in replacement for MCB SPN 240 volts any rating from 6 to 40 amps, 'C' curve with rupturing capacity 10 KA, including providing thimble for out going cables complete all as specified and directed.
S&F in replacement for MCB SPN 240 volts any rating from 63 amps, 'C' curve with rupturing capacity 10 KA, including providing thimble for out going cables complete all as specified and directed.
S&F in replacement sub Main Wiring with two PVC insulated unsheathed multistrand FRLS-H flexible copper conductor cable of size 2x6 sqmm and one PVC insulated multistrand unsheathed FRLS-H flexible copper conductor cable of size 6 sqmm (green colour) as earthing lead connecting to main earthing dolly drawn in and including non metallic PVC concealed conduit 20mm dia complete and making good to disturbed surface complete of wall/floor with cement mortar and finishes to match the existing surface complete all as specified and directed.
All as per srl item No 49 here-in-before but submain wiring with 2 single core 4 sqmm and one 4 sqmm as eathing lead complete all as above but 4.00 Sqmm.
S&F in replacement of old unsv sheet metal enclosures distribution boards, double door three phase 415 volts 4 ways vertical TPN DB for comprising three phase four wire copper strip bus bar of appropriate capacity complete all as specified and directed and comprising of the following (a)MCCB FOUR POLE 63 AMPS AC 415 VOLTS 16 KA=01 NO as incoming and 12 nos. MCB SP 40 Amps, C series as outgoing. ( (i) MCCB, MCB and DB should be of same make. (ii) The DB shall be flush fixed ,and making good the disturbed surface matching with existing specifications shall be part of job at no extra cost.(iii)connection of theMCCBs/ MCBs with cable shall be made through appropriate size pin /bottle type thimble -properly crimped.(iv) all the vacant holes of the DB shall be provided with blank plates of appropriate size. (v) double continuous earth wire shall be provided for each three phase DB from earthing mains dolly.
S&F in replacement bldg secuirty light fitting energy saving high efficiency LED street light fitting 25 Watts, 5700 K, IP 66, having pressure die cast housing with toughened glass and individual high power LEDs with secondary optics, prismatic polycarbonate cover complete including GI bracket of size 25 mm dia bent to shape having length on less than 0.9 mtr fixing with clamp etc and making connections using cord flexible copper cable of suitable size from ceilling rose/ PVC connector to light fittings or as directed by Engr-in-chrage.
M&L for earthing complete with galvanised steel earth plate electrode , 600 x600 x 6mm thick burried directly in the ground (earth pit not less than 2.25 mtr deep below ground level)with top edge of the plate not less than 1.5mtr below ground level connected to galvanised iron wire 4mm dia as earth lead by means of bolts, nuts and washers of GI up to test point , GI tubing 15 mm bore light grade protection pipe , GI watering pipe 20mm bore light grade with funnel and wire mesh , charcoal ,salt packed around the earth plate and precast PCC 1:2:4 (Nominal mix ) reinforced with XPM having weight not less than 4 kg /sqm including suitable handle of 6mm dia MS bar and angle iron 40x40x3mm frame for cover including earth work in any type of soil , removal of surplus soil to a distance n.exc 50m and connecting , testing on completion complete all as shown on electric plate No 03 of SSR -2009 Part I complete all as specified and directed.(Note: Excavation and earth work is deemed to be included in the rates quoted).
S&F in repair Aluminium strip 25x3 mm with saddles and fixing screws etc. for roof conductors and down conductors above ground.
S&F in repair Test point terminal block made of gun metal or phosphorus bronze size 75X75X25mm drilled and screwwed including 3 Nos 8mm dia 25mm long Hex. Head screw.
S&F in repair Air termination, single pointed aluminium rod 12 mm dia and 300 mm long.
M&L for Galvanized iron tubing, 50mm bore medium grade, ISI marked, including fittings and laid in trenches/under road/drains, fixed to poles/walls with required size of flat iron (25mmx3mm) clamps, bolts, nuts and washers for protection of LT electric cable including taking out old existing pipe complete.
S&F in repair cast Iron/ pressed steel terminal boxes 100mm X 100mm X 60 mm deep for accommodate the test point terminal block with 3mm thick plastic laminated sheet cover.
S&F in replacement MCCB 4 Pole 100 Amps, thermal magnetic release having, breaking capacity 16 KA, 415 Volt in the existing TPN DB including any addition / alteration to the DB to accommodate the new MCCB and connections complete all as specified and as directed by Engineer-in-Charge.
S&F in replacement MCCB 4 Pole 63 Amps, thermal magnetic release having, breaking capacity 16 KA, 415 Volt in the existing TPN DB including any addition / alteration to the DB to accommodate the new MCCB and connections complete all as specified and as directed by Engineer-in-Charge.
S&F in replacement 20mm Rigid non-metallic PVC conduit heavy duty exclusive of boxes (junction/terminal) but inclusive of all tees, bends, elbows, reducers, bell mouth tube ends and fixing accessories such as couplers, lock nuts, saddles, pipe hooks etc complete all as specified and directed.
S&F in replacement 25mm Rigid non-metallic PVC conduit heavy duty exclusive of boxes (junction/terminal) but inclusive of all tees, bends, elbows, reducers, bell mouth tube ends and fixing accessories such as couplers, lock nuts, saddles, pipe hooks etc complete all as specified and directed.
S&F in repair 1100 volts grade heavy duty cable PVC insulated aluminium conductor, served with inner sheathing of PVC tape and overall PVC sheathed in service connection one twin core flat cable or circular 10 Sqmm including PVC conduit of suitable size complete all as specified and directed by Engr-in-charge.
S&F in replacement Decorative & cylindrical shape 8 Watt LED Bollard garden light with integrated LED driver offers comfortable soft light high durability & IP 65 complete all as specified and directed by Engr-in-Charge.
S&F in replacement LED slim panel 12W LED ceiling round/square 6" light fitting 220 V AC recessed type with high efficiency PMMA diffuser soft glare free light complete with driver holder & driver & LED lamp suitable for roof ceiling including connecting up with driver flexible copper conductor cases of suitable size complete all as specified and directed by Engr-in-Charge.
S&F in replacement LED slim panel 7W LED ceiling round/Square 4" light fitting 220 V AC recessed type with high efficiency PMMA diffuser soft glare free light complete with driver holder & driver & LED lamp suitable for roof ceiling including connecting up with driver flexible copper conductor cases of suitable size complete all as specified and directed by Engr-in-Charge.
S&F in replacement LED luminaire 600 mm X 600 mm , 35/36 watt 220 V AC (Cool white/Warm white) recessed type with high efficiency PMMA diffuser soft glare free light complete with driver holder & driver & LED lamp suitable for roof ceiling including connecting up with driver flexible copper conductor cases of suitable size complete all as specified and directed by Engr-in-Charge.
S&F in repair LED Driver suitable for LED luminaire 600 mm X 600 mm , 35/36 watt 220 V AC with universal connector complete including connecting up with driver flexible copper conductor cases of suitable size complete all as specified and directed by Engr-in-Charge.
S&F in repair decorative LED spotlight 12W with surface mounted aluminium structure warm white 3000K, available with adjustable light engine to achieve the desired illumination angle including inbuilt driver complete connecting up with flexible copper conductor of suitable size complete all as specified and directed by Engr-in-Charge.
S&F in replacement single phase electric meter 10-60Amp, class-1 having polycarbonate strong body with LCD display including meter box and electric connection with 4 sqmm copper wire complete all as specified and as directed by Engineer in charge. Note : Unserviceable meter has to be deposited in AGE E/M Store yard.
S&F in repair decorative Wall mounted LED light in brass finish fixture with cognace hammered glass diffuser suitable for 9W LED lamp B22 base complete including 9 W LED Warm white lamp, connecting up with suitable size flexible copper cable complete all as specified and directed by Engr-in charge.
Supplying, laying, jointing, commissioning and testing in replacement XLPE insulated screened PVC bedded, armoured, heavy duty underground electric cable with stranded aluminium conductor 1100 volts grade of cross sectional area 35 sq mm 3.5 core confirming to IS-7098 (Part-I-1988) laid in trenches, along poles through pipes etc complete all as specified and directed by Engineer-in-charge.
All as per item No 72 above but cable of cross sectional area 25 sq mm 3.5 core.
All as per item No 72 above but cable of cross sectional area 25 sq mm 3.5 core.
All as per item No 72 above but cable of cross sectional area 16 sq mm 2 core.
Excavation in trenches not exceeding 1.5 m wide and not exceeding 1.5 m in depth and getting out in soft/loose soil for laying of cable ,pole foundation,stay,laying of pipe etc complete all as specified and directed.
M&L for sand cushioning to under ground cables with a layer of sand 8 cm before laying the cable and 15 cm after laying the cable complete all as specified
M&L for old size Brick covering with equal to length of brick as mechanical protection to cable with well burnt sub class 'B' bricks laid as directed.
Returning filling in, including spreading ,leveling ,watering and well ramming in layers not exc 25 cm complete all as specified.
Removing excavated soil to a distance not exceeding 50 mtr and deposting where directed at a level not exceeding 1.5 mtr above the starting point complete all as specified.
Supplying, jointing and testing in replacement heat shrinkable type out door end terminatin jointing kit, suitable for cable of size upto 25 Sqmm to 50 Sqmm, 3.5/4 core aluminium conductor 1100 Volts including making connections complete all as specified and directed by Engineer-in-Charge.
Supplying, jointing and testing in replacement heat shrinkable type straight through jointing kit, suitable for cable of size 25 to 50 Sqmm, 3.5/4 core aluminium conductor 1100 Volts including making connections complete all as specified and directed by Engineer-in-Charge.
Note:-The accepted amount will be arrived after deducting the Sch of credit i.e. Rs 1,57,883.00 and any other reduction if any from quoted amount.
satpal and brothers (BID ID -3459912)
JK ENTERPRISES (BID ID -3460580)
M/S SINGHAL ENGINEERS (BID ID -3455502)
Vishav Karma Refrigeration and Electric Work (BID ID -3455596)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.30 MB
tender66.pdf
Tender Documents • 1.65 MB
BOQ_820683.xls
BOQ • 1.10 MB
Download all tender documents and submit your bid