Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Fee/PreQual/Technical FLAT NO F2 BLOCK A FIRST FLOOR THE LEGACY APARTMENT AIRPORT ROAD GOLA KA MANDIR GWALIOR MP 474005 | GWALIOR | GWALIOR | MADHYA PRADESH | 474005 | Admitted-Fee/PreQual/Technical |
| 2 | Admitted-Fee/PreQual/Technical | Admitted-Fee/PreQual/Technical |
Tender Value
₹22.9 L
EMD Value
₹45,900
Closing Date
20 Jun 2026, 6:05 pmClosed
CWE Jalandhar Cantt
HQ CWE Jalandhar Cantt, PIN 144005
Spl repair of fire fighting system and allied works at FF Installation No 1 and 2 at FAD under AGE I Suranussi
2026_MES_752086_2
8325/91/E8
Open Tender
Civil Works
Item Rate
180 days
HQ CWE Jalandhar Cantt
Class E Category c (vi) for contractors enlisted with MES
9 documents required · 9 mandatory
₹500
Yes
AGE (I) Suranussi
₹45,900
Yes
15 Jun 2026
30 May 2026
22 Jun 2026
30 May 2026
20 Jun 2026
8 Jun 2026
Supply,installation, testing and commissioning new LT panel box " CPRI type tested" cubicle type,with angle & frame, free standing, floor mounted, indoor, weather proof type, Double door, front and rear openable type working on 415 V 3-phase, 50 Hz, AC supply with copper bus bars-600 Amp Copper bus bar- 04 Nos, 600 amp rating considering current carrying cap 1.5 Amp/sqmm duly having colour coated heat shrinkable sleeves mounted on insulators weather proof, dust-proof and vermin proof with canopy on top, 3mm thick CRCA sheet steel enclosure,power coated CRCA-IP-55,Light grey painted as per the 7-tank process, weather proof IP-55 protection compartalized as per specification incl MS angle iron legs of height 900 mm made out of angle iron 50x50x6mm and including following component complete all as specified and as directed:- (1) Main Incomer section : MCCB with suitable rating for panel load 100 HP Pump e.g. 4 Pole, 400A, breaking cap 36kA.(I/C) Ics=100% Icu with phase separator & phase extender/copper links.
(C ) 20 HP Standby pump star delta starter (i) 3 Pole contactor e.g. 40 A AC-3 phase heavy duty-03 Nos (ii) thermal overload relay(22-35 A)-01 Nos (iii) over current protection relay (MCCB/MCB)-40 Amp-01 Nos (iv) Auto start start on main pump(25 HP jockey Pump) failure -01 Nos (v) Start/stop push button (Green and red) (vi) Indicating lamp (Running ,trip,auto,stand by active) (viii) single phase preventor (ix) star delta timer (0-30 sec) (xi) control MCCB 100 Amp 4 pole 25 KA 01 Nos with phase seperator & phase extender/copper links. (xii) Power & Control wiring with suitable size copper wire.
M&L for maintenance and servicing at site of existing diesel engine Set of capacity 113/153 BHP, installed at fire fighting No1 & 2 FAD complete including draining out & starting of diesel from tank, cleaning the tank thoroughly and refiling the drained out diesel, draining out engine oil from the chamber, cleaning the chamber thoroughly and replacing the engine oil with new to required level, replacing the fuel filter, check & clean air cleaner, check coolant level & make up to required level the same, drain the Fuel filter & water separator, filling the starting batteries with electrolyte/distilled water to maintain the required specific gravity, cleaning of battery terminals & applying petroleum jelly to battery terminal posts & brass connectors, replacement of V-belts, changing clips of air cleaner, checking of exhaust leakage, governor, breathers etc, adjust/set the same for proper functioning , checking of fuel, oil and water/coolant level etc, adjusting and keeping the fan belts to the desired tension, tightening all the bolts and nuts to the required torque etc, cleaning the diesel engine with accessories for satisfactory running and testing at connected load. complete all as directed. Note:- The quoted rate include the required engine oil distiled water as mentioned above.
Supply and fixing the following items for 113/153 BHP Diesel engine incl old removing UNSV parts.
(a) Control Safety for (Water) Temp,
(b) Control Safety for (Lub Oil) Pressure ,
(c) Water Temp Guage.
(d) Lub Oil Pressure Guage,
(e)Tachometer,
S& F Battery link lead made out with 6 sqmm min copper conductor PVC insulated with Bty terminal of +/- terminal 1.50mtr long
M & L Premixed Coolent for 113/153 BHP Diesel engine
S & F Lubricant Oil filter element primary and secondary with ring and washer for 113/153 BHP Diesel engine
S & F Air cleaner element with ring and washer for 113/153 BHP Diesel engine
S & F Rubber hose pipe set with clamps for 113/153 BHP Diesel engine
M & L for maintenance and servicing of existing pump set of capacity 20/25 HP pump having parts i.e impeller,shaft,wear ring,coupling,pump casing,shaft sleeves foundation Bolts and alignment etc as per site requirement Incl replacement of all UNSV parts as reqd to make the pump fully functional as directed by Engr-in charge
M & L for maintenance and servicing of pump set of capacity 100 HP pump having parts i.e impeller,shaft,wear ring,coupling,pump casing,shaft sleeves foundation Bolts and alignment etc as per site requirement Incl replacement of all UNSV parts as reqd to make the pump fully functional and directed by Engr-in charge
Supply laying testing and commissioning of the PVC insulated 50 Sqmm 3 core Copper cables for motor connection ,suitable for 3- phase 415 volt 50 Hz Ac including all neccessory accessories ,cable gland lugs laid in cable tray with proper protection complete all as specified and directed by Engg-in Charge
Supply laying testing and commissioning of the PVC insulated 10 Sqmm 3 core copper cables for motor connection ,suitable for 3- phase 415 volt 50 Hz Ac including all neccessory accessories ,cable gland lugs laid in cable tray with proper protection complete all as specified and directed by Engg-in-Charge
supply laying & testing PVC insulated, PVC sheathed cable galvanised steel strip or wire armoured electric control cable (heavyduty) with stranded copper conductor of size 1.5 sqmm ,2 core 1100 volt grade complete.
supply laying & testing PVC insulated, PVC sheathed cable galvanised steel strip or wire armoured electric control cable (heavyduty) with stranded copper conductor of size 2.5 sqmm ,3 core 1100 volt grade complete.
supply & install of Gylcerine filled pressue Guage (0-16Kg/sqcm) , with ball valve 10mm dia SS body gauge m
Supply & Installation of pressure Switch for automation of Fire fighting pumps having range (0-14Kg/sqcm)
M & L for hydrostatic testing of fire fighting pipeline system ,contractor shall perform hydrostatic pressure testing of all existing pipe line valves joint flanges and associated component approximately 4 KM pipe line length. The work include arrangement of all labour, equipment, water fitting, pressure guage(0-16kg/Sqcm), pumps, safety gear etc. Pipe ends must be properly capped or blank flanged . install pressure gauge (0-25 kg/sqcm) vent valve and drainage arrangement .fill the pipe line/system with clear water ,removing all air pocket (air release valve within quoted rates to be used). use hydrolic pump to pressurize the the system.apply test pressure of 1.5 of working pressure not less than 10 kg/sqmm & as decided by Engr-in-charge. hold the test pressure for minimum 24 hour.monitor the pressure gauge via callibrated pressue gauge.visual inspect all joint welds valves and fitting for minor leakage repaires and the section re- tested. All equipment & material to be provided by contractor High pressuere hydrostatic test pump, Callibrated pressure guage ,temporary end cap blank flanges and support ,pipe fitting and adopter ,safety PPE with in over all quoted rates. .
Supply and fixing in cast iron sluice valve PN 1.6 150 mm bore with flanged ends ISI mark with Gun metal spindle CI gate with brass ring and iron wheel handle with jointing material such as nuts /bolts washers and rubber insertion sheet etc including taking out old U/S sluice valve complete all as specified.
All as per item ser No 18 above here in before but 100 mm bore dia.
All as per item ser No 18 above here in before but 80 mm bore dia.
Supply and fixing hose box having transperent iron mount door of size 800 mm x 600 mm x 250mm min or suitable higher for keeping 2 Nos hose pipe of length 15 meter each ,branch pipe .nozzel coupling etc of MS sheet of thickness 2.0 mm with suitable MS Iron legs for fixing complete.
Supply & installation of Air Release valve 25 mm Dia with Control valve.
Supply and fix 63 mm dia 15 meter long CP hose conforming to IS 636 complete with male and female coupling complete.
Supply & fix of Branch Pipe ,gun metal 63 mm instantaneous inlet, made threaded outlet ,15mm bore nozzel short. As per IS 903 complete.
Excavation in trenches in soft/loose soil n exc 1.5 mtr wide and n exc 1.5 mtr in depth and getting out excavated soil complete all as specified and directed.
Returning filling in, trenches around pipe line including spreading , levelling, in layers n exc 25 cm after laying pipes and well ramming complete all as directed by Engineer-in-charge.
Removal of surplus excavated soil to a distance not exceeding 50 mtr away from site and depositing where directed at a level not exceeding 1.5 mtr above ground level complete all as specified and directed.
Taking up cast iron spigot and socketed pipe including cast iron fittings from trenches in existing position including burning old lead joint complete all as directed for following bores size:- (a) 80 mm bore dia
(b) 100 mm bore dia
(c) 150 mm bore dia
Relaying cast iron spigot and socketed pipe in trenches in new within 6 meters or old position after proper cleaning externally / internally complete all as directed by Engineer-in-charge of following :- (a) 80 mm bore
(b) 100 mm bore
(c) 150 mm bore
Supply, laying,testing and commissioning in trench Ductile iron pipe with flanged end ISI marked) Class K-9, in any length complete all as specified and directed for the following bores :- (a) 80 mm bore dia
(b) 100 mm bore dia
(c) 150 mm bore dia
Supply & Fixing cast iron/MS fitting/DI fitting such as bend any type radius and angle taper any type straight bends,D- Joint of Different sizes, increasing decreasing tee pieces single branch,Y junction coller ,cap and plug with spigot/socket end flange upto 150 mm bore including taking out old material all as directed
M&L for new run lead joint with spun yarn complete with all jointing material all as specified and directed for following bore :- (a) 80 mm bore dia
(b) 100 mm bore dia
(c) 150 mm bore dia
M & L for rectifying the leakage deploying sufficient labour (Skilled and helpers) for repair to leakage of pipes size 80 to 150 mm bore of any description such as CI/MS at any location including necessary excavation & earth work, cutting existing pipe lines, dewatering upto 6 mtr length etc complete all as specified. NOTE:- (i) Pipes, cost of jointing material(run lead) and cast iron fitting reqd shall be measured and paid separately under respective items. (ii) Quoted rate incl excavation cost (if JCB required for excavation arranged by contractor)
S&F 50mm dia. cast iron foot valve flanged type as per IS-4038 PN-2 having sheet Gunmetal disc face ring- Nitrile rubber, Hinge pin stainless steel AISI-410 with Cast iron bolted strainer with necessary nut, bolt, washers etc, complete including taking out old valves complete all as specified and directed
S&F in repairs 50 mm dia Non Return Valve of cast iron body , with both ends flanged, drilled at both the ends, conforming to IS-1538, having GM flap with nuts, bolts, washers, rubber gasket complete all as specified and directed.
S&F 150 mm dia. cast iron foot valve flanged type as per IS-4038 PN-2 having sheet Gunmetal disc face ring- Nitrile rubber, Hinge pin stainless steel AISI-410 with Cast iron bolted stainer with necessary nut, bolt, washers etc, complete including taking out old valves complete all as specified and directed
S&F in repairs 150 mm dia Non Return Valve of cast iron body , with both ends flanged, drilled at both the ends, conforming to IS-1538, having GM flap with nuts, bolts, washers, rubber gasket complete all as specified and directed.
M & L for maintenance free Eco safe corrosion resistant earthing comprising the followings:-- (a) High tensile low carbon steel earth 3 metre length and 17.2mm dia with 250 micron (average) molecularly bonded copper on the outer surface to conform with requirement of UL467 & IEC 62561-2 (Dia of the rod & UL Control Number alloted to the manufacturer should be embossed on the rod & UL certificate from the same manufacturer shall be submitted along with the material) (b) Back-fill earthing enhancing compound should strictly be a Eco Safe Carbon based conductive concrete type which has a resistivity of less than 0.12 Ohm Mtr as per Clause 14.5D of IEEE: 80 standard Back-fill compound should be electronically conductive (Like in metals) and should not depend on mositure for conduction. Jef Eco Safe Carbon based compound shall be supplied in 20 Pounds Bag. Back-fill compound should be enviorment friendly, should solidify when mixed with water and set like concrete and should not leach / diffuse into the ground. Back-fill compound shall not be mixed with any soil while pouring in the bore hole. Test Certificate as per as per IEC: 62561-7 for Back-fill compound shall be submitted along with material. (c) Earth termination clamp either of gun matel / tinned copper or tinned brass for termination both round and flat conductors of required size Note: Copper strip of size 32x6mm upto length 2mtr included in quoted rates.
Supply and fixing copper earth strip 32 x 6 mm buried in ground complete as specified and directed by Engr-in-Charge.
Supply and fixing Fire brigade inlet connection 2 way complete as specified and directed by Engr-in-Charge.
Supply and fixing Air cushion tank with relief valve 200 mm suitable for existing fire fighting hydrant system pressure complecte as specified and directed by Engr-in-Charge.
Supply and install fire hydrant stand post single out let type made out of 80mm dia. MS pipe, 1.50 mtr long, with 90 degree bend, both ends flanged complete all as specified & directed by Engineer-in-Charge.
M&L Joint with rubber or fibre board gasket for flanged pipe joint including complete all as specified and directed for following bores :- (a) 80 mm bore
(b) 100 mm bore
(c) 150 mm bore
Supply and lay GI tubing light grade with all fitting laid in trenches, or wall for strip protection pipe of size 40 mm bore complete all as specified and directed.
stage.html
html • 0.02 MB
tech_bid_open.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.25 MB
TENDERDOC91.pdf
Tender Documents • 1.49 MB
BOQ_860914.xls
BOQ • 0.36 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .