Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
| 2 | Admitted-Finance H NO 2 460 SHIVKRUPA MANGAL OFFICE NEAR UPHALIVANCHEN TA HAVELI DISTRICT PUNE PIN NO 412202 | PUNE | PUNE | MAHARASHTRA | 412202 | Admitted-Finance |
| 3 | Admitted-Finance | Admitted-Finance |
Tender Value
₹11 L
EMD Value
₹22,000
Closing Date
29 Jan 2024, 3:00 pmClosed
DIRECTOR IISER PUNE
IISER Pune Dr Homi Bhabha raod Pashan pune 411008
Providing Electrical Distribution for Chemistry Lab no CF 302, C122 at Main Building, IISER Pune.
2024_IISRP_790140_1
05/ IISER/PUNE/2023 24
Open Tender
Electrical Works
Works
90 days
IISER PUNE
As per NIt
3 documents required · 3 mandatory
₹1,180
DIRECTOR IISER PUNE
₹22,000
9 Feb 2024
12 Jan 2024
30 Jan 2024
12 Jan 2024
29 Jan 2024
12 Jan 2024
Amount
Please note that Quoted rates are inclusive of taxes,labor, transportation, royaltie etc. Nothing Extra shall be paid separtely.
Supplying and fixing following Modular socket on the existing raceways & PVC DLP truncking with required accessories to complete jobs. including connections, as required. . 6 Pin 15/16 amp universal amp socket outlet ( Approved Make : Legrand / MK Honeywell EVO )
Supplying and fixing following Modular switch / socket on the existing raceways & PVC DLP truncking with required accessories to complete jobs. including connections, as required including connections, as required. . 4 Module Box with faceplate & cover ( Approved Make : Legrand / MK Honeywell EVO )
25 mm X 5 mm copper earth strip on surface: Providing and fixing 25 mm X 5 mm copper stripfrom earth electrode as required.
END TERMINATION: Supply and installation of End termination of cables with compression brass cable glands, Al crimping type lugs should be used for Al cables and Cu lugs with soldering and ferrules for the following 1.1kv class Al./Cu. XLPE/PVC insulated using necessary crimping tool and all other accessories as required and Including the cost of all materials, lobour, Handling of Materials of equipment and machineries all lead lift, loading and unloading, transportation, if any other incidental charges at all level complete all as per specification and as directed by Engineer-in charge. 4 Core x 4 Sqmm Armoured Copper Cable. ( Approved Make : Dowells / CI / Electrowerke )
END TERMINATION: Supply and installation of End termination of cables with compression brass cable glands, Al crimping type lugs should be used for Al cables and Cu lugs with soldering and ferrules for the following 1.1kv class Al./Cu. XLPE/PVC insulated using necessary crimping tool and all other accessories as required and Including the cost of all materials, lobour, Handling of Materials of equipment and machineries all lead lift, loading and unloading, transportation, if any other incidental charges at all level complete all as per specification and as directed by Engineer-in charge. 4 Core x 10 Sqmm Armoured Copper Cable. ( Approved Make : Dowells / CI / Electrowerke )
ERECTION for Recessed/Surface Mounted 2'X2' , 36 / 40 W LED Luminaire incluilding ceiling hook, drop wires 3 R x 1.5 sqmm copper flex wire from ceiling point to fitting with full covered flex pipe, stray wire / cable for handing fitting on false ceiling or mouting on ceiling with surface box assembly etc as required and complete. Cutting in metal / false ceiling for required cut out is in scope of agency.
FINAL DISTRIBUTION BOARDS. PART - C - DB's & MCB's : Supply, Installation, Testing and Commissioning of all MCB Distribution Boards (10KA) 415V, made out of 16SWG MS sheet steel enclosure hinged MS cover/over flanged cover (double door) with cutouts for operating the MCB knobs and comprising of phase bus bars, neutrals and earth bus with tapped holes, bakelite phase barriers, pvc insulator shoes for incoming wire, etc complete. DB's shall be mounted by grouting in to the wall/angle to brick wall as required. DB's shall be suitable for Three Phase / single phase loads. Or DB's shall be mounted on suitable M.S. angle and supporting flat. DB's shall include termination lugs etc., all complete. (Note: Local fabrication not permitted. Only factory made boxes shall be installed and all MCB's shall be with 10 KA rating)Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer ) as required. 4 way (4 + 18), Double door for UPS DB ( Approved Make : Legrand / Schneider / L&T / MK )
INDUSTRIAL POWER SOCKETS on wall : 32Amp, single phase : Supply and fixing 32A, 3 pin, Single phase, Industrial Socket with safety shutters controlled by One no. of 32A, double Pole MCB to be mounted on wall, ( The job includes cutting & chasing on exisiting wall, fixing the box in position as required including rough plastering.) As per IEC 61439-3. suitable for flush mounting and surface mounting. 3P+ P+E Five pole, IP 44, material of plug & socket polyamide 6. Including the cost of all materials, lobour , HOM of equipment and machinerys all lead lift, loading and unloading,transportation, if any other incidental charges at all level complete all as per specification and as directed by Engineer-incharge. MCB/PLUG/BOX -32A . ( Approved Make : Legrand / Schneider / L&T / MK )
INDUSTRIAL POWER SOCKETS on wall : 32Amp, three phase : Supply and fixing 32A, 5 pin, three phase, Industrial Socket with safety shutters controlled by One no. of 32A, three Pole MCB to be mounted on wall, ( As per IEC 61439-3. suitable for flush mounting and surface mounting. 3P+ P+E Five pole, IP 44, material of plug & socket polyamide 6. The job includes cutting & chasing on exisiting wall, fixing the box in position as required including rough plastering.) Including the cost of all materials, lobour , HOM of equipment and machinerys all lead lift, loading and unloading,transportation, if any other incidental charges at all level complete all as per specification and as directed by Engineer-incharge. MCB/PLUG/BOX - 32A ( Approved Make : Legrand / Schneider / L&T / MK )
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required. Upto 35 sq. mm (clamped with 1mm thick saddle)
LIGHT CIRCUIT WIRING : Wiring for circuit / submain wiring in concealed pipe below false ceiling (by chieseling the wall and covering with chicken mesh with rough plastering) / surface mounted. Including ISI mark PVC Conduit with 25mm DIa of 2mm thick with PVC insulated FRLS single core wires with colour code of following: 2 x 2.5 sqmm + 1 x2.5 sqmm earth wire. ( Approved Make : Polycab / Finolex / RR kabel )
Light Point Wiring : Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required.Group C
POWER SWITCHES / SOCKETS on walls - G.I. BOX. : Supplying and fixing following size / modules, GI box along with modular base and cover plate for modular switches in recess etc, as required. ( The job includes cutting & chasing existing wall, fixing the box in position as required including rough plastering.) (In all the rooms, vertical drops of conduits and switch boxes shall be concealed in the wall). Boxes should be of same make as that of modular accessories. :6 Module ( Approved Make : Legrand / MK Honeywell EVO )
PVC RACEWAYS ( Along the wall) DLP U- PVC adaptable trunking : Supply & installation of surface mounted DLP U- PVC adaptable trunking raceways, fabricated out of U-PVC to Off-White or approved shade as per IS 733 of thickness 2.0mm for the base and sides with removable covers, complete with necessary bends, suitable sized junction boxes, internal angle, external angle, flat 90 degree angle , end caps and tees,minor civil works if any etc, Complete. (For every 1mtr distance cable tag has to be provided for each circuit in the raceways - as more that 1C FRLS copper wire is required for 1 Circuit) PVC RACEWAYS ( Along the wall), DLP U- PVC adaptable trunking . Size: 105x 50mm PVC Raceways for Power & Data with above specifications 105x 50mm PVC Raceways ( Approved Make : Legrand / MK Honeywell EVO )
Supply and installation of 48 port fully loaded patch panel with IO modules suitable for UTP CAT 6 cable and required mounting accessories for existing network rack.Quoted rate shall be including material, labour, taxes, duties, lead, lift, loading, transportation, unloading, storing , scaffolding etc, making holes in walls , filling holes with mortar etc complete as per direction of Engineer In‐ charge. Nothing extra shall be paid separately. ( Approved Make : Dlink / RR Kabel / Netgear )
Supply and making end termination for UTP 4 pair CAT 6 LAN cable with required IO modules which is suitable for modular type base , cover plates and accessories ( At field side ) as required.Quoted rate shall be including material, labour, taxes, duties, lead, lift, loading, transportation, unloading, storing , scaffolding etc, making holes in walls , filling holes with mortar etc complete as per direction of Engineer In‐charge. Nothing extra shall be paid separately. ( Approved Make : Legrand / MK EVO )
Supply and making end termination for UTP 4 pair CAT 6 LAN cable with required IO modules which is suitable for modular type base , cover plates and accessories ( At Rackside side ) as required.Quoted rate shall be including material, labour, taxes, duties, lead, lift, loading, transportation, unloading, storing , scaffolding etc, making holes in walls , filling holes with mortar etc complete as per direction of Engineer In‐charge. Nothing extra shall be paid separately. ( Approved Make : Legrand / MK Honeywell EVO )
Supply of 2meter length cat 6 patch cord with Rj 45 terminations on both ends as complete. ( Approved Make : Dlink / Legrand / Polycab )
Supply of Recessed/Surface Mounted 2'X2' , 36 / 40 W LED Luminaire Light with Single piece molded Polycarbonate diffuser, Lighting and electrical parameters are inline with 2'X2' Luminaire. Luminaire should give more volumetric light & higher vertical illumination.Luminaire should be available in different Lumen Packs of 4000 lm with different CCT.. LED Used shall be SMD type and fixture should have minimum efficacy at System level (Not Chip Level) >=100 lumens/watt, Life of fixture 50000hrs@L70% Lumen maintenance, CCT up to 6500, CRI >80, PF >0.95 and SDCM 4 for good light quality, an operating Voltage Range of 140 - 270 V.Minimum Internal Surge Protection 2.5KV The fixture should comply with the parameters as per IS10322. The LED driver should comply to IEC61000-3-2 ed.3.2, 2009 for Harmonics, IEC61347 -2 -13, 2006 in Conjunction with IEC61347-1 ed.2.0, 2007 for Electrical Safety, IEC62384 ed.1.1, 2011 for performance and IEC61547 ed.2.0, 2009, CISPR-15 for EMI. Manufacturer shall have inhouse lab approved by NABL or ministry of science of govt of India. LM 79 and LM80 reports need to be submitted from a NABL/UL accredited lab to verify above parameters. ( Approved Make : Wipro / Crompton / Philips / Bajaj )
Supplying and drawing of UTP 4 pair CAT 6 LAN Cable in the existing surface/ recessed Steel/ PVC conduit as required. 1 run of cable ( Approved Make : Dlink / Legrand / Polycab )
Supplying and drawing of UTP 4 pair CAT 6 LAN Cable in the existing surface/ recessed Steel/ PVC conduit as required. 3 run of cable ( Approved Make : Dlink / Legrand / Polycab )
Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioninq etc. as required. Triple pole and neutral. ( Approved Make : Legrand / Schneider / L&T / MK )
Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioninq etc. as required. Single pole. ( Approved Make : Legrand / Schneider / L&T / MK )
Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioninq etc. as required. Triple pole. ( Approved Make : Legrand / Schneider / L&T / MK )
Supplying and fixing following Modular switch / socket on the existing raceways & PVC DLP truncking with required accessories to complete jobs. including connections, as required including connections, as required. . 3 Pin 5/6 amp socket outlet ( Approved Make : Legrand / MK Honeywell EVO )
Supplying and fixing following Modular switch / socket on the existing raceways & PVC DLP truncking with required accessories to complete jobs. including connections, as required including connections, as required. . 6 Module Box with faceplate & cover ( Approved Make : Legrand / MK Honeywell EVO )
Supplying and fixing following Modular switch / socket on the existing raceways & PVC DLP truncking with required accessories to complete jobs. including connections, as requiredincluding connections, as required. . 15/16 amp switch ( Approved Make : Legrand / MK Honeywell EVO )
Supplying and fixing following Modular switch / socket on the existing raceways & PVC DLP truncking with required accessories to complete jobs. including connections, as requiredincluding connections, as required. . 5/6 amp switch ( Approved Make : Legrand / MK Honeywell EVO )
Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required. ( Approved Make : Legrand / MK Honeywell EVO )
Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required ( for Data cable ) 25 MM ( Approved Make : Precision / Diamond / Modi )
Supplying and fixing TPN sheet steel enclosure on surface/ recess without MCB complete with connections, testing and commissioning etc. as required. ( Approved Make : Legrand / Schneider / L&T / MK )
Supplying fixing and wiring Current Operated RCBOs,240V/415V 50Hz with 10KA short circuit with standing capacity 25amps. double pole, 30/100mA, and Including the cost of all materials, lobour, HANDLING OF MATERIALS of equipment and machinery all lead lift, loading etc, complete.RCBO 63 A, 4P, 100 mA . ( Approved Make : Legrand / Schneider / L&T / MK )
Supplying fixing and wiring Current Operated RCBOs,240V/415V 50Hz with 10KA short circuit with standing capacity 25amps. double pole, 30/100mA, and Including the cost of all materials, lobour, HANDLING OF MATERIALS of equipment and machinery all lead lift, loading etc, complete. ( RCBO 32/40 A 4P, 30mA including metal enclouser box with installation of surface, as complete. ). ( Approved Make : Legrand / Schneider / L&T / MK )
Supplying fixing and wiring Current Operated RCBOs,240V/415V 50Hz with 10KA short circuit with standing capacity 25amps. double pole, 30/100mA, and Including the cost of all materials, lobour, HANDLING OF MATERIALS of equipment and machinery all lead lift, loading etc, complete.RCBO 32/40A, DP, 30mA. ( Approved Make : Legrand / Schneider / L&T / MK )
Supplying LT cable having copper conductor XLPE insulated sheathed,galvanised steel tape armoured cable with pvc outer sheathing 1.1 KV ( Confirming to IS 7098 Part-II amended upto date as per the following sizes). Including the cost of all materials, lobour, Handling of materials of equipment and machineries all lead lift, loading and unloading, transportation, if any other incidental charges at all level complete all as per specification and as directed by Engineer-in charge. 4 Core x 10 Sqmm Armoured Copper Cable. ( Approved Make : Polycab / Finolex / RR kabel )
Supplying LT cable having copper conductor XLPE insulated sheathed,galvanised steel tape armoured cable with pvc outer sheathing 1.1 KV ( Confirming to IS 7098 Part-II amended upto date as per the following sizes). Including the cost of all materials, lobour, Handling of materials of equipment and machineries all lead lift, loading and unloading, transportation, if any other incidental charges at all level complete all as per specification and as directed by Engineer-in charge. 4 Core X 4 sqmm copper armoured cable ( Approved Make : Polycab / Finolex / RR kabel )
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required.2 X 4 sq. mm + 1 X 4 sq. mm earth wire ( Approved Make : Polycab / Finolex / RR kabel )
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes ofFRLS PVC insulated copper conductor, single core cable in surface/ recessedmedium class PVC conduit as required 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire ( Approved Make : Polycab / Finolex / RR kabel )
Providing boreing / drilling bore well of 150mm dia for casing / strainer pipe , by suitable method, including drilling in all strata, including hiring & running charges of all equipments, tools, plants and machinenaries required for the job, all complete as per direction of Engineer in charge.
Supply, installation, testing and commissioning of Chemical earthing using electrode of size 76 mm minimum diameter, minimum 03 meter long and connected with 50x5 mm copper internal strip, material of conustruction COPPER, complete with existing excavation / bore, civil work for chamber, cast iron cover size 450 x 450 mm, with backfill compound as requred to fill earth pit up to mark. the earth resistance shall be as per IS 3043
Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) * 8 way double door
Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required ( for Data cable ) 40 MM
Supplying and fixing TPN sheet steel enclosure on surface/ recess without MCB complete with connections, testing and commissioning etc. as required.
BBP Electricals
SONHIRA ELECTRIC COMPANY
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .