Chief Engineer Pune Zone
Chief Engineer Pune Zone Dakshin Kaman Marg Camp Pune 411001
PROVN OF SEWAGE TREATMENT PLANT FOR OTM ACCN AT AUNDH MILITARY CAMP
2022_MES_504321_2
CEPZ/KKE/TOKEN-01 OF 2020-21
Open Tender
Civil Works
Lump-sum
365 days
Kirkee Pune
Class A category c(vii)
8 documents required · 8 mandatory
₹2,000
GE (MH AND RH) Kirkee
₹4.0 L
Yes
17 May 2022
28 Feb 2022
23 Mar 2022
28 Feb 2022
21 Mar 2022
5 Mar 2022
1 Mar 2022 - 3 Mar 2022
Amount
SCH 'A PART-I (BUILDING/STRUCTURAL WORKS FOR STP) Note: This schedule is not pre-priced by MES and the rate indicated as "Rs 0.00" under Col 6 signifies this fact only
Construction of civil structures for Sewage Treatment Plant (STP based on MBBR technology : for electro mechanical equipments refer Item No 4.00 to 4.61 here-in-after) of capacity 0.3 MLD comprising of items/ structures all as shown on drawing No ADG/2020/AR/01 Sheet No. 1R/5,2R/5,3/5 to 5/5 & related structural drawing No. ADG/2020/STR/001(R) sheet No 1/8 to 8/8 & PHE drawing No. ADG/2020/PHE/001(R) Sheet No. 1/1 complete all as shown on drawing and all as specified and directed.:-
(a) Receiving inlet chamber
(b) Primary units ie Stilling chamber, Fine screen, OGT and Grit chamber, Mechanical scraper assembly
(c) Equalisation tank
(d) Covered Anoaxic Tank
(e) MBBR (Aeration) Tanks (Two Nos)
(f) Clarifier zone
(g) Chlorine contact cum filter feed tank
(h) Chlorination room
(j) Platform for filter tanks (including Activated charcoal filter and Multi grade sand filter)
(k) Treated water tank 5600mm X 3000mm
(l) Sludge Holding tank
(m) Plateform for Pumps
(n) RCC stair case, Brick masonry steps, Ramps, Platforms, MS railing, Steel ladders, MS rungs, Inlet and outlet pipes of pumps
(o) Panel room, Rest room and Office including ramps, steps, plateform
(p) Filter press machine room
(q) Air blower unit
NOTE: Schedule ‘A’ Part II to XI are Prepriced by MES. Bidders shall insert their lumpsum amount in the Green coloured field under Col-13 only.
Total amount of Sch 'A' Part-II (Internal Electric Supply)
Total amount of Sch ‘A’ Part III (Internal Water Supply)
Total amount of Sch ‘A’ Part IV (External Electrification)
Total amount of Sch ‘A’ Part V (Treated Water Supply )
Total amount of Sch ‘A’ Part VI (Roads/Paths and culverts)
Total amount of Sch 'A' Part-VII (Area drainage)
Total amount of Sch 'A' Part-VIII (Fencing and Gate)
Total amount of Sch ‘A’ Part IX (Sewage Line)
Total amount of Sch ‘A’ Part X (Pumping Machinery)
Total amount of Sch ‘A’ Part XI (Excavation, Earthwork & Site development)
SCH 'A PART XII (Miscellaneous B/R and E/M works including electro mechancal equipments of STP) Note: This schedule is not pre-priced by MES and the rate indicated as "Rs 0.00" under Col 6 signifies this fact only
Electro Mechanical Equipments of Sewage Treatment Plant:-
Supply install, testing & commissioning Air blowers with motors, accoustic enclosures with all accessories, Each Capacity 350 Cum/hr with 0.65Kg/Sqcm, Single stage, air cooled, twin lobe type to supply air for aeration tank, Continuous duty, design code BS 1571, End connection flanged as per ANSI B 16.5 150lb, Noise level shall be less than 85 db at 1.86 m distance from blower, Motor shall be TEFC sq cage induction motor Class F, IP 55 protection, Material of Construction(MOC) - Casing CI IS 210 Gr FG 260, Shaft EN 24, Foundation bolts SS304, Accessories to be provided with each blower - Base frame, suction filter, silencer, safety relief valve, V-belt, drive & driven pulleys, belt guard, foundation bolts, Non return valve,butter fly valve of size as per OEM recommendation as pressure gauge with built-in snubber & glycerine filled, accoustic hood etc., complete all as specified and directed. MAKE: Atlas Capco/ Ingersol/ KPT/ Everest
Supply install, testing and commissioning electrically operated M S chain pulley block suitable for capacity 2 tonne with 6m lift complete with load chain, longitudinal span 5m tested to 50% over load as per IS:3832 carrying IS mark complete all as specified and directed. (For sewage collection sump)
Supply install, testing and commissioning process reactor for aerobic attached growth biological moving bed bio reactor (MBBR) process with 02 Nos (in series) process reactor & virgin media suitable for MBBR process cylindrical shaped media wagon wheel design having external fins, non toxic, surface area 400 sqm per cum having specific gravity 0.90gm/sqcm and voidage >95% complete . Size of reactor tank 2.8mx 3mx 3m = 25.2cum ) complete all as specified by OEM & in Drg No ADG/2020/PHE/001(R) and as directed. Note : Provn of tanks shall be measured and paid seperately under apropriate item.
Supply, install, testing & commissioning Polyelctrolyte dosing tank agitators, 0.37KW, slow speed SS304, with motors, continuous duty operation to mix DWPE solution 0.1% from HDPE tank of size 100 liters solution viscosity 200 cp, sp. Gravity 1.05, impeller turbine type of 100 rpm speed, gear box shall have service factor of 2, sq cage induction motor IP 55 protection class F insulation, Material of Construction(MOC) shall be - impeller, shaft & coupling - SS304, complete including suitable dia of delivery hose not less than 5 mtr length, clamping etc. all as specified and directed.
Supply, install, testing & commissioning Polyelectrolyte dosing system with 800 lit capacity HDPE dosing tank and pump set, mechanically actuated diaphragm type metering pump, Capacity 30 LPH, continuous duty, manual stroke adjustment, tolerance on capacity +/- 5%, flooded suction, discharge pressure 1.50 kg/cm2, fluid consistency 0.1 to 0.5%, viscosity 200 cp, Material of Construction(MOC) - Housing CI IS 210 GR. FG 260, Head PP, Antisyphon valve, hardwares, strainer, PRV - SS 304, Motor TEFC sq cage induction type, IP 55, Class F insulation complete including suitable dia of delivery hose not less than 5 mtr length, clamping etc all as specified and directed.
Supply and fix brass Non return Valve for GI pipe of 20mm bore with required GI fittings for connection complete all as specified and directed .
Supply and fix brass Non return Valve for GI pipe of 25mm bore with required GI fittings for connection complete all as specified and directed .
Supply and fix brass Non return Valve for GI pipe of 40mm bore with required GI fittings for connection complete all as specified and directed .
Supply, install, testing and commissioning of PVC ring fit pipes 110mm dia conforming to IS 4985:2000, perfect linking at joints, and cuts of pipes wherever necessary including jointing of PVC pipes and including specials with jointing of approved type and giving hydraulic testing to the required pressure as per ISS (based on resin rate of Rs. 78296 per MT) 100 NB - 10 kg/sqcm complete all as specified and directed.
Supply, install, testing & commissioning screw pumps with motors, Cap = 6.0 Cum/hr @ 60 m head, to transfer biological sludge, continuous duty, single stage, helical screw rotor, with coupling guard, mechanical seal, foundation bolts, sp gr 1.05, viscosity 10 cp, sludge consistency 0.8-1.2%, max size of particle 60mm, Motor type TEFC, Class F insulation, IP 55 protection, Material of Construction(MOC) - Casing, rotor, pump shaft - alloy steel, casing ring - nitrile bonded, foundation bolts - SS304, base plate - MSEP, suitable RPM mounting frame, PCC foundation as required, complete including Non return valve, butter fly valve, pressure release valve of sizes as per OEM recommendation all as specified and directed.
Supply,install, testing & commisioning of centrifugal , horizontal, non clog pump with motor, CI cap 13.6 Cum/Hr, 30m head for filteration system, with necessary GI piping, foot valve of suitable size as per OEM recommendation and gun metal NRV and gate valve at dilivery, provision for level switches coupled for high and low levels including necessary foundation on suitable size base frame complete all as specified and directed by Engr-in-charge.
Supply & Fixing Hypochloride dosing system with 100 Lit HDPE dosing tank and dosing set disinfection system with disinfectent 6% c12 with chlorine dose 5mg/Ltr in CCT through dosing, electric metering pump, 0.08KW capacity=6-10LPH, continuous duty, manual stroke adjustment, tolerance on capacity +/-5%, flooded suction, discharge pressure 2.00kg/Sqcm, fluid consistency 0.1 to 0.5%, viscocity 200cp, MOC housing CI IS 210 Gr. FG 260, Head PP, Antisyphon valve, hardwares, strainer, PRV - SS 304, Motor TEFC sq cage induction type, IP 55, Class F insulation complete all as specified and directed.
Supply,install, testing and commissioning of filtration system comprising of dual media filter for removal of fine suspended solids from treated sewage and activated carbon filter for removal of colour & odour from treated sewage, with following specifications including back wash arrangement and manhole cover for replacement of filter media
(a) Dual Media filter=01 No
(i) Flow rate 6.8Cum/Hr
(ii) Dia of adequate size as per OEM suitable for flow rate
(iii) HOS of adequate size as per OEM suitable for flow rate
(iv) MOC = 8mm shell/10mm dish, MS bitumenous paint inside
(v) Filter Media = minimum 300mm Anthracite and 500mm sand under bed supporting media .
(b) Activated carbon filter=01 No
(i) Flow rate 6.8Cum/Hr
(ii) Dia of adequate size as per OEM suitable for flow rate
(iii) HOS of adequate size as per OEM suitable for flow rate
(iv) MOC = 8mm shell/10mm dish, MS bitumenous paint inside
(v) Filter Media = Minimum Activated carbon , 900mm carbon depth and 600mm under bed supporting media. NOTE:- Any minor item required as per sound Engineering practice is deemed to be included in the quoted rate.
Supply & Fixing PP ball valves 15NB screwed conforming to relevant ISS with latest amendments complete with all led, lift and fixing including cost of nuts and bolts etc all as specified and directed.
Supply & Fixing CI wafer type butterfly/gate valves PN 1.6 BS 5155, manual 50NB conforming to relevant ISS with latest amendments complete with all led, lift and fixing including cost of nuts and bolts etc. all as specified and directed.
Supply & Fixing CI wafer type butterfly valves PN 1.6 BS5155, manual 150NB conforming to relevant ISS with latest amendments complete with all led, lift and fixing including cost of nuts and bolts etc. all as specified and directed.
Supply & Fixing cast steel double flanged CI dual plate type check valves class 150 API 594, 150NB conforming to relevant ISS with latest amendments complete with all led, lift and fixing including cost of nuts and bolts etc. all as specified and directed.
Supply & Fixing CI dual plate type check valves PN 1.6 BS 5155, manual 50NB conforming to relevant ISS with latest amendments complete with all led, lift and fixing including cost of nuts and bolts etc. all as specified and directed.
Supply & Fixing CI sluice valve PN 1.6 BS 5155, manual 80NB Tube settler conforming to relevant ISS with latest amendments complete with all led, lift and fixing including cost of nuts and bolts etc.all as specified and directed.
Supply and Fixing glycerene filled Stainless steel pressure gauge of 150mm dia of range 0-14kg/Sqcm suitable for the pumpsets with and including nipple, stop cock & two way cock and chemical seal for cleaning & necessary length of copper tubing complete all as specified and directed.
Supply, install, testing & commissioning of electrically operated Filter press of capacity 6.0 Cum /Hr of size 24"x 24" x18 Nos plates bottom discharge with scraper unit (bath type) 3 or 4 points anti vibration mounts with heavy duty/ brakes and heavy duty clutch driven MOC for structure/plates: MS /PP and trolleys-02 Nos with TEFC 415 Volts 3 phase electric motor complete all as specified and directed.
Supply ,install , test & commission, claritubesettler of following specifications :- (a) Type - Circular claritube settler with mechanical scrapper (b) Hydraulic loading - 300 cum/day (c) Tube Modules - Square tube PVC (d) Tube Modules Qty - 1.5 cum (e) Mechanism Type - Central pheripheral drive (f) MOC of tube settler - virgin PVC (g) Shape of media - Hyxagonal shape (h) Over flow wires - type V notch, MOC - Epoxy painted, walkway - 6 mm thick chequerd plates (i) Clarifier RPM = 0.15 RPM (j) Electric moter rating = 1.5 KW TEFC, squirrel cage induction, 415 V AC 3 phase, class F insulation, IP-55. Note : Provn of RCC tank allied B/R items shall be measured & paid seperately.
Supply, install , testing & commissioning and giving test and trial Submersible non clog sewage pump set to handle unscreened crude sewage specific gravity 1.05 and solids and organic waste upto 100 mm size. Generally the pump shall conform to IS 9137,IS 5600 with Squirrel cage, induction electric motor A.C. 3 phase, 415 V, 50 Hz, Voltage/frequency variation +/-6% and 3% respectively and 2900 RPM speed motor rating to have a margin of 15% over the maximum power absorbed by any of the pumps during the entire working range of pump. Electric motor shall generally conform to IS : 325 complete all as specified and directed. The pump should be capable of delivering a discharge (stated below) against head (stated below) at 2900 RPM speed and suitable for single as well as parallel operation with other pumps incl suitable rating/ length of submersible cable from pump to starter for 1 DWF pump with discharge capacity 12.5Cum/Hr head 12m complete including Non return valve, butter fly valve of size as per OEM recommendation all as specified and directed.
Supply, install , testing & commissioning and giving test and trial Submersible non clog sewage pump set to handle unscreened crude sewage specific gravity 1.05 and solids and organic waste upto 100 mm size. Generally the pump shall conform to IS 9137,IS 5600 with Squirrel cage, induction electric motor A.C. 3 phase, 415 V, 50 Hz, Voltage/frequency variation +/-6% and 3% respectively and 2900 RPM speed motor rating to have a margin of 15% over the maximum power absorbed by any of the pumps during the entire working range of pump. Electric motor shall generally conform to IS : 325 complete all as specified and directed. The pump should be capable of delivering a discharge (stated below) against head (stated below) at 2900 RPM speed and suitable for single as well as parallel operation with other pumps incl suitable rating/ length of submersible cable from pump to starter for 2 DWF pump with discharge capacity 25Cum/Hr head 12m complete including Non return valve, butter fly valve of size as per OEM recommendation all as specified and directed.
Supply, installation and testing complete electronic digital type water level indicator device suitable for operating at 230v +/- 10%, 50Hz system having 150mm size digital display and alarm at low/high level of sump. The complete unit fitted in MS sheet base in two boxes,one box to be installed at sump and second at pump house both unit to be connected with flexible copper cable of 0.5sqmm 8 pair and length from sensor to pump house building. All enclosed in sheet metal encloser of 02 mm thick with hinged door and locking arrangeement and support GI wire/PVC pipe etc properly laid or fixed on wall / surface complete all as specified and directed.
Supply & Fixing PVC insulated sheathed copper conductor 3 core, 10 Sqmm, flat cable, suitable for submersible Pumps complete all as specified and directed by the Engineer in Charge.
Supply and laying XLPE insulated, screened, PVC innersheathed galvanised unarmoured electric power cables (heavy duty) with stranded copper conductor electric cable 1100 volts grade suitable for earth system of size 1.5 Sqmm 10 core complete all as specified and as directed.
Supply and laying XLPE insulated, screened, PVC innersheathed galvanised unarmoured electric power cables (heavy duty) with stranded aluminium conductor electric cable 1100 volts grade suitable for earth system of size 50 Sqmm 3.5 core complete all as specified and as directed.
Supply and laying XLPE insulated, screened, PVC innersheathed galvanised unarmoured electric power cables (heavy duty) with stranded copper conductor electric cable 1100 volts grade suitable for of size 2.5 Sqmm 4.0 core complete all as specified and as directed.
Supply and laying XLPE insulated, screened, PVC innersheathed galvanised unarmoured electric power cables (heavy duty) with stranded copper conductor electric cable 1100 volts grade suitable of size 4.0 Sqmm 4.0 core complete all as specified and as directed.
Supply and laying XLPE insulated, screened, PVC innersheathed galvanised unarmoured electric power cables (heavy duty) with stranded copper conductor electric cable 1100 volts grade suitable of size 6.0 Sqmm 4.0 core complete all as specified and as directed.
Supply and laying XLPE insulated, screened, PVC innersheathed galvanised unarmoured electric power cables (heavy duty) with stranded copper conductor electric cable 1100 volts grade suitable of size 10.0 Sqmm 4.0 core complete all as specified and as directed.
Supply,fixing and installation of ABC type Fire Extinguisher of capacity 6.0 Kg as per IS 2878 complete all as per manufacturer instructions.
Supply and Lay MS fire bucket of 13 ltrs capacity of fire approved quality, painted Red filled with sand complete all as specified and as directed.
Supply and lay MS pedestal stand duly painted, hooks for suspending fire buckets including necessary fixing arrangement for pedestal stand complete all as specified and design as directed by the Engineer in charge.
Supply, install, test & commisioning of sewage feed pump (Raw sewage pump from equilisation tank to anoxic tank) non clog submersible pump set with discharge 12.5cum/hr @10m head, 2900 RPM, CI body pump shall confirm IS 9137, IS5600 with squirrel cage induction eletric motor conforming to IS-325 complte with all accessories Non return valve, butter fly valve of size as per OEM recommendation all as specified and as directed.
Supply, install , Testing & commissioning of Electro Magnetic Flow meter (EMF) as per ISO 4064 with accuracy +/- 0.5% of measured valve and protection as per given specification. Flow meter shall be suitable for 25 Cum/Hour 65 NB dia PTFE lined with 4-20 mA out put without communication port remote cable length upto 20m, electrode material SS 316 L make including the pipe line cutting, levelling and installation of flow meter with necessary fixing arrangements complete all as specified and directed.
Supply, install, testing and commissioning of motor ( flash mixer) of suitable capacity to operate the peak flow condition with reduction gear motor shall be TEFC sq cage induction type, class F insulation, MOC casing CI, IS 210 GR, FG-260, shaft EN-20 foundation bolts SS-304 ,as per OEM complete as specified and as directed
Supply and fix level control switch, liquid bouyancy type all as directed
Supply and fix air rotameter, differential area, bypass type with orifice plate all as directed
Supply and fix auto desludge valve, electric actuator, timer based type ( 01 No at clari tube settler and 01 No at MBBR) of dia 100 mm all as directed
Supply and fixing all socketed specials or socketed branch flanged specials of 80mm to 150mm dia ISI standarad MS specials of required thickness with and including 3 coats of approved make Epoxy paint from inside and outside complete all as directed
Supply and assenbling including jointing and fixiing in position MS ERW pipe fine cut of internal dia 100 mm bore if thickness 5.4 mm conforming to IsS 4270-2001 ( ISI marked ) both ends flanged and covered awith suitable dummy cover including with electric arc welding both side all as specified for header to make branch connection including painting , the pipes with single coat of epoxy primer and two coats of red enamealed paint and complete all as specified and directed .
Supply and install perforated MS cable trays of size 450mm width X 50 mm depth X 1.6 mm thickness including horizontal and vertical bends, reducers, tees, cross members duly painted with two coats of epoxy paint over a coat of zinc chrome primer and other accessories as required, duly suspended from the ceiling with and including MS suspendors ( 10mm dia threaded rod, anchor fasteners and angle of size 40X40X5mm thick). Complete all as directed.
Supply and install perforated MS cable trays of size 300mm width X 50 mm depth X 1.6 mm thickness including horizontal and vertical bends, reducers, tees, cross members duly painted with two coats of epoxy paint over a coat of zinc chrome primer and other accessories as required, duly suspended from the ceiling with and including MS suspendors ( 10mm dia threaded rod, anchor fasteners and angle of size 40X40X5mm thick). Complete all as directed.
Supply and install perforated MS cable trays of size 150mm width X 50 mm depth X 1.6 mm thickness including horizontal and vertical bends, reducers, tees, cross members duly painted with two coats of epoxy paint over a coat of zinc chrome primer and other accessories as required, duly suspended from the ceiling with and including MS suspendors ( 10mm dia threaded rod, anchor fasteners and angle of size 40X40X5mm thick). Complete all as directed.
Supply , install, test and commissioning weatherproof, dust and vermin proof LT distribution panel, factory made, indoor type of suitable size so as to accommodate the following accessories, depth not less than 500 mm, IP-54 and all as per IE rules, prewired and fabricated with 2mm thick CRCA sheet, powder coated double door aprons, mounted on MS angle iron frames 50X50X6 mm welded in shape with two coats of synthetic enamal paint over a coat of red oxide primer including necessary grouting in PCC 1:3:6, type-C1 using 20mm graded coarse stone aggregates, complete with PCC 40 cm above ground level incuding cable terminations with glands, lugs etc and consisting of following :
(a) Copper strip bus bar 200 Amp ( 4 Nos) - 03 Nos for Phase and 01 No of neutral duly coloured sleeved mounted on epoxy insulators- 01 Set
(b) In coming - MCCB for 125 A, FP, 415 Volts, 50 Hz, ICU 25 KA, thermally adjustable betwwen 75-100%-01 No
(c) Outgoing: (i) MCCB 40 Amp, FP, 415 Volt, 50 Hz, 16 KA, thermally adjustable between 70-100% - 05 (02 Nos Air Blowers + 03 Nos sewage pump ) (ii) power contactors with thermal overload relay up to 15 HP for main, Star & delta -05 Nos (iii) single phase preventer- 05Nos, (iv) MCB TPN 30 Amp 10KA - 08 Nos(02 Nos EQT/Anoxic Pumps + 02 Nos filteration system + 02 Nos screw pump + 02 Nos Electric press), (v) Power contactors with thermal over load relay up to 7.5HP for DOL starter-08 Nos, (vi) Single phase preventor -15 Nos, (vii) MCB SP 6 A -18 Nos, (viii) Push button with NO/NC for start/stop- 32 Nos, (ix) Indication lamp for start/stop (green/red)-32 Nos., (x) Hooter,Trip ,Reset/Accept Push button with NO/NC-01 Set, (xi) Relay logic for level based ON/OFF controls for pumps-01 Set, (xii) Multi function meter with suitable CTs -01 No
Misc E/M and B/R items
Supply and fix Energy efficient ceiling fan of 1200 mm (48") sweep BEE 5 star rated high speed low power consumption superior aluminium blades and provn of 3 core flexible copper conductor cable of size 23/0.19 from ceiling rose to ceiling fan complete all as specified and directed . confirming to Cat Part No- KASSELS STAR of make- Bajaj of equivalent Make as given as given in Appx 'C'.
S & F LED tube light fitting 1x20 watt, energy saver indoor domestic plastic extruded luminaire with decorative, prewiredand including connecting up with twin core twisted flexible copper conductor cable with suitable size from ceiling rose to connector all as specified and as directed. Make as given in Appx 'C'.
S & F LED Energy Efficient security light fitting 30 watts LED pressure die cast aluminium housing in heat resistant glass cover with IP 65 protection and including GI pipe as require length and size with fixing accessories complete all as specified & directed complete with M & L for fixing / mounting bracket, clamps, nuts, bolts, washers etc. Make as given in Appx 'C'.
S & F MCB SP 240 volts 6 to 32 Amps 10 KA complete all as specified and directed.Make as given in Appx 'C'.
S & F MCB SPN 240 Volts 32 Amp 10 KA complete all as specified and directed.Make as given in Appx 'C'.
S & F MCB TPN 40A, 415, 10 KA complete all as specified and directed.Make as given in Appx 'C'.
S & F exhaust fan, with louvers, single phase, heavy duty, PVC, 230 mm sweep, 1400 RPM including fixing of mounting frame in the round hole cutting in the wall, by means of rugged bolts, nuts and washers etc, including three core copper conductor flexible cord of 0.5 Sqmm cross sectional area of required length from ceiling rose to the porcelain connector block of the exhaust fan complete all as specified and directed.Make as given in Appx 'C'.
S & F LED 70/72W light fittings, aesthetically designed luminaire with excillent thermal management delight luminaire with IP 65 protection input voltage range 120-270 Volts AC, 50Hz, power factor rating not less than 0.95 heat sink, complete and connecting flexible copper conductor wire PVC insulated of 2x2.5Sqmm and 1x2.5Sqmm as in earth conductor of Make as given in Appx 'C', complete all as specified and as directed.
Supply and fix LT junction box for street light, sheet moulding compound (SMC) type with hinged type door and locking arrangement, off white colour, of size 200x160x98 mm (internal) comprising 6Amps MCB ,01 No. bakelite base neutral link and 01 No. earthing terminal bolt and nut and connecting up cables with aluminium terminal lugs including fixing arrangements including wiring from junction box to street light fitting alongwith 2x2.5sqmm+1x1.5sqmm earth wire of FR PVC insulated copper conductor, single core cable in surface /recessed as required in steel conduit complete all as specified and directed. Make:- Hansel or equivalent of make listed in Appendix 'C'.
Supply and fix automatic street light switching panel based on lux level on natural light and sensor alongwith suitable power contactor as per IEC-60947-4-4, 40 Amps MCB TP and support terminal and enclosed in pole/wall mounted factory made PVC enclosure made out of rust, shock,termite proof FR grade confirming to IP 54 of maximum capacity 6kw 3 phase 415 Volt complete all as specified and directed.
Supply, install, testing & commissioning of open well submersible monoblock pump set 7 stage, of capacity 15HP with electric driven, 3 phase, 415V, discharge-840LPM, head 50metre complete all as specified and directed. Make: Kirloskar Model No. KS6G-1507R or equivalent make as given in Appx 'C".
M & L for submersible cable round or flat of 4 core 6Sqmm with multistranded copper conductor complete all as specified and as directed.
M & L for fully automatic star delta starter 415 volts relay range 13-32 Amps suitable for submersible pump set of 15HP complete all as specified and as directed. . Make: L & T Cat No. CS94091 or equivalent or equivalent make as given in Appx 'C".
M & L for cutting through existing bitumenous road /PCC/floorof approximate size width 500mm to 600mm and depth 600mm along cross section of road for laying GI pipe for encasing of cable or laying of CI/GI pipe line after laying, repairing the road to match with the original finishing with PCC 1:3:6 type C-1 using 20mm graded coarse stone aggregates complete all as specified and as directed.
M&L for 80mm thick machine pressed pre-cast cement concrete interlocking paver blocks with grey cement and pigment, rubber moulded any shape and size confirming to IS 15658-2006, M-35 grade as in floor/pavement laid over and including 30mm thick crushed stone sand complete all as specified and as directed.
S & F RCC precast man hole covers heavy duty including outer frame and set in cement mortar 1:6 all as specified and directed.
Material and labour for fly ash brick masonry valve chamber size 600mmx600mmx600mm of internal dimension, fly ash brick masonry chamber 230mm thick(valve chamber) built in CM 1:6, PCC 1:2:4 type B-1, 100mm thick in floor, 15mm thick plaster in CM 1:4 on internal/external surface, PCC 1:3:6 type C-1, 75mm thick as in coping, MS sheet cover 6mm thick with angle iron 40x40x6mm, flat iron hold fast of 15mmx4mm including locking arrangement with lock and key 65mm pad lock ( Pad lock brass 6 levers with keys in duplicate), handle 6mm dia 30cm long, applying with 2 coats of synthetic enamel paint over one coat of red oxide primer on all metal works complete all as specified and directed including necessory excavation and earthwork complete.
Supply, laying, testing and commissionnig of UG LT cables 1100 volts grade, XLPE insulated, screened and PVC sheathed, galvanised steel strip or wire armoured with multi stranded aluminum conductor, conforming to IS 7098 Part-I heavy duty including cable glands, cable lugs in LT panel/MDB in building etc to suit the cable including material and labour for all jointing/connecting material as required size, cables laid in trenches/ducts/under plinth floors passing through pipes etc, fixed on wall complete of following sizes :-
(a) 95 sqmm x 3.5 core
(b) 6 sqmm x 4core
M & L for earthing with 600x600x6.00 mm Galvanised steel earth plate electrode buried vertically in ground (earth pit not less than 2.25 metre deep below normal ground level) with top edge of the plate at a depth of not less than 1.5 m below ground level, connected to and including Galvanised steel Strip of size 32x 6 mm by means of bolts, nuts and check nuts and washers of galvanised steel with and including 40 mm dia GI medium grade pipe for protection of GI strip to the extent of 7.5 metres as earthing lead including charcoal dust and salt packed all around the earth plate in the earth pit all as per Electrical Plate No. 3 of SSR Part I (2009) including PCC foundation / chamber in mix 1:2:4 type B1 with M.S. angle iron frame, C.I. Cover with provision of locking arrangement and 20 mm dia medium grade G.I. Pipe from top edge of the earth plate upto M.S. funnel with wire mesh provided inside the concrete earth pit for watering arrangement, complete including excavation and earthwork in any type of strata and testing complete including fill up the earth pit with soil for best result and removal of excavated material from the site complete all as specified and directed. Note :- Earth protection pipe & earthing lead upto and including 7.5 m length is deemed included in unit rate quoted by the contractor.
M&L for earthing with GI plate 600mm x 600mm x 6mm thick, burried directly in ground (earth pit not less than 2.25 meter deep below ground level) with top edge of plate not less than 1.5 Mtr below normal ground level, connecting to galvanized iron or steel earth wire 4.0mm dia (No.8 SWG) upto 7.5 Mtr long from earth point to test point by means of bolts, nuts, check nuts, washers and provision of charcoal, salt etc including watering arrangement with 20mm dia GI pipe, 15mm dia light grade pipe for protection of GI wire upto 7.5 mtr, MS funnel, PCC chamber in cement concrete 1:3:6 type C1 and finished even and smooth without using extra cement, 50 mm thick precast RCC cover 1:2:4 type B1 including 10 mm dia deformed bars @100 mm c/c on both ways for full size of chamber complete all as per electrical plate No 3 including necessary excavation and earth work in any type of strata and testing complete including fill up earth pit with soil for best results and removal of excavated material from the site complete all as directed. Note :-Earth protection pipe and earthing lead up to and including 7.5m lenghth is deemed to be included in unit rate quoated by contractor.
S & F GI strip of size 32x6mm burried in ground or fixed to wall/pole including fixing clamp made out of 40x5mm MSFI nuts, bolts and washers ( For additional provision beyond 7.5m)
Supplying Installing testing & commissioning Diesel Engine driven Generating set 415 V, 3 Phase, 4 Wire as per BS 5514/IS-10002 complete with Automatic on mains failure (AMF) panel, of capacity continuous rating 50 KVA at NTP conditions with acoustic enclosure considering all derating factors and comprising of the following :-
(a) ALTERNATOR : Closed type regulated with brushless self excitation 415 V, 3 Phase, 4 Wire, 50 HZ, 0.8 PF 1500 RPM with voltage variation plus or minus 2.5% of rated voltage from no-load to full-load Anti vibration mounted drip proof type with class 'F' insulation, steel ball/roller bearings at both ends of the alternator shaft, with necessary controls as recommended by the manufacturer confirming to BS-5000/IS-4772 capable of supplying unbalanced load, alternator make : Stamfort/Crompton/Jyoti Electric Co/Cummins
(b) Engine : Multi/cylinder compression ignited, heavy duty, turbocharged, compact diesel engine water cooled through radiator with water pump hydraulic governing mechanism, all as per BS-5514/IS-3046, 1500 RPM class A1 governing/ control gauges. RPM /Hours meters etc suitable for generating application and capable of giving an output of 50 KVA for coupled altemator under NTP conditions, complete with following :-
(i) Flywheel with housing ad mesh protection.
(ii) Flexible coupling set directly mounted to engine and alternator with coupling guard
(iii) Air-cleaner dry type with vacuum indicator.
(iv) Fuel pump FIP/CRDI and fuel piping 15mm MS Pipe with bends, flanges etc
(v) Fuel filter with water separator and filter element.
(vi) Lub-oil filter with filter element
(vii) DC heavy duty starter as per OEM recommendation.
(viii) Maintenance free DC batteries as per OEM recommendation.
(ix) Engine overspeed stop/trip switch
(x) Radiator with fan, thermostat
(xi) Dynamo/Alternator for battery charging
(xii) Corrosion inhibitor coolant.
(xiii) Engine control panel electronic digital display type consisting of battery voltage indicator lub oil temp and pressure gauges, coolant water temp gauge RPM indicator cum hour meter etc
(xiv) Safety controls for alram due to high water temp (HWT) and low luib oil pressure (LLOP)
(xv) Any other devices/ accessorsdies recommended/ supplied by the manufacturers as standard eqpt. Engine Make : Cummins/Greaves/Perking
(c) The engine and alternator will be coupled, aligned and mounted on a specially designed common base frame fabricated from MS channels of suitable cross sectional area and length with bottom drilled holes suitable for and including supplying and fixing anti vibration pads, Make Dunlop/ Polybond of reqd size and numbers as recommended by the manufactureres for mounting of 50 KVA DG Set
(d) Indoor Automated mains failure panel fabricated from CRCA Sheet, self supporting of size suitable for unmanned operation of DG set including necessary contactors and Bi- passing arrangements, manually operated on load change over 100Amps with all type of indicators and remote controlled operation of DG set and including necessary wiring between DG set and AMF panel inside GI pipe 40 mm dia as specified and directed.
(e) Diesel tank of adequate capacity for 12 hrs continous run on full load, with caliberated scale (fuel level indicator ) dip stick, fuel inlet/outlet, Air vent drain plug and intlet arragement for direct filling, including suitabsle size gate valve in outlet, tank to be fitted at suitable height.
(f) Acoustic enclosure with canopy cover to be provided as per CPCB norms
(g) PCC/RCC foundation complete as per OEM design.
(h) Documents : Three sets of following documents :- Maintenance and operation manuals for engine and alternator, spare parts catelogue, warranty/test certificates, schematic diagrams of control panels.
(j) Misc items : List of tools and two years normal maintenance spares as per manufactures recommended lists, duly priced, item wise
Note:- (i) Contractor shall satisfactorily conduct load test of DG Set for 12 hrs including run on 10% overload for 1 hr
(ii) Testing equipments and man power shalll be arranged by the contractor at his own risk and cost.
(iii) Fuel/ Lubricants required for 1st load test shall be arranged by the contractor at his risk and cost.
PHASE-II :Schedule 'A' Part-XIII: Manning and Operation of Sewage Treatment Plant. During 1st year of Defect Liability period from next day of completion of phase - I
Out sourcing for Manning and operation of Sewage Treatment Plant of 0.3 MLD capacity round the clock, by deploying total 3 FGM (Skilled) per day ( One FGM for one shift of 08 Hrs) including Saturday, Sunday and Holidays complete all as specified and as directed. The outsourcing of services including running of sewage treatment plant by logging of runing records, upkeep of installation consisting of STP, Pumping sets, DG set, Air compressor, Chlorination plant, Sluice valves and reporting the occurance at the installation on all working days including Sunday and Holidays complete all as directed.
Out sourcing for Manning and operation of Sewage Treatment Plant of 0.3 MLD capacity, in one shift per day, by deploying 01 Helper (Un-Skilled) per shift of 08 Hrs each including Saturday, Sunday and Holidays complete all as specified and as directed. The outsourcing of services including running of sewage treatment plant by assisting the FGM in operation of chlorine dosing , application of culture for development of bacteria in fab reactor and controlling the delivery of treated water output at water points of STP installation area including operating treated water installation from STP for gardening of nearby locations and cleaning installation premises with in a radius of 3m from the installation area on all working days including Sunday and Holidays complete all as directed.
PHASE-II (Contd) :Schedule 'A' Part-XIII: Manning and Operation of Sewage Treatment Plant During 2nd year of Defect Liability period
Out sourcing for Manning and operation of Sewage Treatment Plant of 0.3 MLD capacity round the clock, by deploying total 3 FGM (Skilled) per day ( One FGM for one shift of 08 Hrs) including Saturday, Sunday and Holidays complete all as specified and as directed. The outsourcing of services including running of sewage treatment plant by logging of runing records, upkeep of installation consisting of STP, Pumping sets, DG set, Air compressor, Chlorination plant, Sluice valves and reporting the occurance at the installation on all working days including Sunday and Holidays complete all as directed.
Out sourcing for Manning and operation of Sewage Treatment Plant of 0.3 MLD capacity, in one shift per day, by deploying 01 Helper (Un-Skilled) per shift of 08 Hrs each including Saturday, Sunday and Holidays complete all as specified and as directed. The outsourcing of services including running of sewage treatment plant by assisting the FGM in operation of chlorine dosing , application of culture for development of bacteria in fab reactor and controlling the delivery of treated water output at water points of STP installation area including operating treated water installation from STP for gardening of nearby locations and cleaning installation premises with in a radius of 3m from the installation area on all working days including Sunday and Holidays complete all as directed.
Note for BOQ item No - 6.01 to 7.02 : a) The contractor shall quote the rate for Manning and Operation only. Replacing of defective electromechanical parts, providing spares and maintenance of Sewage Treatment Plants and allied equipments during the period of 2 years (Defect Liability Period) from satisfactory completion of Phase -I shall be covered under Defect Liability Period.
b) As per Govt policy, adequate amount of insurance of all the workers shall be made against any accident before commencement of the work without extra cost to the department.
c) The work order for M & O shall be placed by GE at appropriate times & no price adjustment during whole period due to change in minimum fair wages shall be admissible.
d) The STP will be operated for 24 hours per day, unless otherwise specified by the Engineer-in-Charge / GE. Necessery recovery will be made for non operation of plants per shift at the proportional rate and the same shall be final and binding.
e)The operator being deployed in the work shall have minimum qualification of ITI with 02 years experience in the relevent field for FGM and Helper should be 10th pass with minimum 02 years experiance in relevent field. Necessary qualification certificate and experiance certificate shall be produced for verification of Engineer-in-Charge & get the approval before deploying for works.
f) Proper and effeicient functioning of the plant must be ensured through regular inspection by qualified Engineer bi-monthly preferably by OEM or by his authorised agency.
g) The contractor shall carry out routine maintenance as per procedure mentioned in the PS.
h) Staff deployed by the contractor shall carry out daily careful cleaning of the inside installation, greasing of pump, motors, panel boards, DG sets and internal portion of pump house building , 3m external portion , 3m in radius for outdoor panel boards and maintain installations in presentable condition all time all as specified and as directed.
j) The contractor shall carryout routine check and maintain check sheet daily, weekly, monthly and upkeep the installation , rectify normal trouble shooting, replacement of gland packing of pumps and sluice valves in installations and minor parts like nuts, bolts, washers, coupling rubber, star packing etc. without extra cost to the deparment.
k) Contractor will maintain log sheet daily and submit to department duly completed along with attendance sheet and payment register.
l) No T & P will be issued by the department for doing the above work, it shall be arranged and provided by the contractor like PH testing kit, chlorine test kit, turbidity test kit, pipe wrench, screw drivers, sluice valve opening /closing kit, cutting plier, digging tools etc.
m) The contractor shall check and implement all the labour laws/precautions for health and safety of labour /OEM operator working in hygenic conditions.
n) The contractor shall be get the testing of treated sewage from approved test laboratory ( NABL certified or state PCB approved) and keep records duly signed by Engineer-in-Charge as per interval of 3 months to ascertain result of treated sewage all as per requirement given in particular specification here-in-after. Expenditure for the same shall be borne by the contractors and is deemed to be included in quoted rates.
o) During Manning & Operation, if the person is absent from the duty, recovery shall be effected at the double the rates worked out from quoted rates at the proportional basis. For that purpose, proper duty roster and attendance register shall be maintained and signed by the Engineer-in-Charge. These item will be operated only when the plant is running satisfactorily & No payment will be made in case the plant is unserviceable due to any cause.
p) The rates quoted by the contractor shall be inclusive of proper uniform of technician/operator as directed by GE.
q) Salvage materials/sludge obtained after treatment shall be disposed off outside defence land as per local civil authorities laid down rules.
r) The contractor shall also be responsible for periodical cleaning of screens removal and disposal of screens material to a place outside defence land.
s) All consumables/chemicals like Sodium Hypo Chlorite, Dewatering Poly Electrolyte and Aerobic type bioculture powder for development of bacteria shall be paid separately as ‘Supply only items’ as mentioned in BOQ here-in-after on required/consumption basis as certified by Engineer-in-charge/GE.
t) The contractor shall not employ same tradesmen continuously for more than 11 months.
u) The contractor shall pay the wages to the operators through e payment i.e Aadhar linked bank accounts(Credit to their bank account). Engr-in-Charge shall ensure that e-payment made to operators and their wages shall not be less than minimum wages fixed by state Govt or central Govt whichever is more. Monthly e-banking statement shall be furnished by the contractor to the Engineer-in-Charge and the same shall be kept in record duly verified.
v) It is the responsibility of contractor to deposit the employees provident fund (EPF) to the concerned authority as per the prevailing scales as laid down by the Ministry of labour for all Electrician/ operator/ helper (as applicable) and necessay proof to this regard shall be submitted to Engr-in-charge for verification and records. The quoted rate shall be deemed to be included of above provisions. In case contractor fails to produce the proof of EPF, shall be liable for action as deemed fit. Decision of GE in this regard shall be final and binding.
Supply only Sodium Hypo Chlorite @ 6% concentration complete all as specified and as diretced.
Supply only Dewatering Poly Electrolyte @ 100% concentration complete all as specified and as diretced.
Supply only Aerobic type Bioculture powder for development of bacteria and reduces BOD and COD, suppresses foul odour from STP complete all as specified and as diretced.
Note for Item No 8 to 10:- The above qualtities of consumable to be incorporated during outsourciing for M & O of STPs for two years period. The rates for these items are aplicable for all the years of M & O and no claims for any change in rates shall be admissible for these items duriing this period. The procurement schedules of these items shall be as decided by the Engineer-in-Charge/GE.The contractor shall supply these chemicals for one month at a time and 15 days reserve stock shall be kept at site keeping in mind the expiry date of materials.
M/s JAIMAA ASSOCIATES
SANKALP INFRACON
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .