Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹22.8 LAccepted-AOC | L1 | Accepted-AOC L1 Accepted | |
| 2 | L2₹23.1 L+₹29,594.40 (1.30%)Rejected-AOC | L2 | Rejected-AOC L2 Rejected | |
| 3 | Rejected-Technical CHENNAI | CHENNAI | TAMIL NADU | 600001 | - | Rejected-Technical Technically Not Qualified |
| Sl No | Description | Qty | Unit | MULTI TECH CORPORATION L1 | S.ANBU L2 |
|---|---|---|---|---|---|
| 1.00Providing Electrification Works at 4th Floor, Panagal Building, Saidapet Estimate Amount Rs.23.10 Lakh | |||||
| 2.00Supply, Installation, Testing & Commissioning of double door type IP 42 powder coated Distribution Boards complete with MCBs/RCCB/ELCB/Isolators/ Bus bars Including all interconnections and other associated fixing accessories etc as reqd as per the site conditions. For fixing the DB on the wall / partition / coloumn, etc needs to be considered. The Ferrules identification to be done in both end. The Bus bars shall be tinned copper with seperate earth / neutral bus for each phase. Each circuit shall have yellow ferrules on all wires (Phase, Neutral & Earth) with circuit numbers, laminated A3 or A4 size SLD copy and distribution chart shall be stick inside of the DB doors, safe shroud to be provided for neutral links.('B' curve MCB for Lighting, C curve MCB for Raw power DB's and 'D' Curve MCB for UPS DB's to be used) | |||||
| 3.00 | a) LDB(7Segment) - 8Way as follows :
Incommer 40A TPN MCB- 1 No.
Sub-Incommer 40A, 30mA, 2P RCCB- 3 Nos.
Outgoing 6A SP MCBs - 24 Nos.
Separate Neutral Bus for Each Phase to be given | 1 | Nos | 31,100 ₹31,100 Lowest | 31,110 ₹31,110 |
| 4.00 | b)PDB & ACDB (VERTICAL DB) - 12Way as follows :
Incommer 125A TPN MCCB- 1 No.
Outgoing 16A/32A SP MCBs - 36 Nos.
Separate Neutral Bus for Each Phase to be given | 1 | Nos | 31,100 ₹31,100 Lowest | 31,110 ₹31,110 |
| 5.00 | c)UDB(7Segment) - 8Way as follows :
Incommer 63A TPN MCB- 1 No.
Sub-Incommer 63A, DP MCB- 3 Nos.
Outgoing 16A/20A SP MCBs - 24 Nos.
Separate Neutral Bus for Each Phase to be given | 1 | Nos | 31,100 ₹31,100 Lowest | 31,110 ₹31,110 |
| 6.00 | d)Single phase ELDB - 12Way as follows :
Incommer 3A 2P MCB- 1 No.
Incommer 6A SP MCB- 10 No.
Separate Neutral Bus for Each Phase to be given | 1 | Nos | 12,270 ₹12,270 Lowest | 12,280 ₹12,280 |
| 7.00 | e)MAIN DB 4 WAY VERTICAL as Follows:
Incomer : 125A Isolator
Out going : 3P 63A Isolator. | 1 | Nos | 19,300 ₹19,300 Lowest | 19,310 ₹19,310 |
| 8.00LT CABLES | |||||
| 9.00Supply and laying of Aluminium/Copper/Armoured/UnArmoured/Flexible (XLPE insulated for above 25sqmm cable) 1.1kv grade cable laid in tray / hume pipe / in ready made trenches, with nylon cable ties / MS Clamps @ 600mm interval etc., as required. | |||||
| 10.00 | 3.5 Core 70 sq. mm. Aluminium Armoured cable.(MAIN DB) | 70 | Mtrs | 750 ₹52,500 Lowest | 760 ₹53,200 |
Tender Value
₹23.1 L
EMD Value
₹24,000
Closing Date
31 Dec 2025, 3:00 pmClosed
The Project Director, DRDA, Kancheepuram
O/o The Project Director, DRDA, Kancheepuram
Providing Electrification Works at 4th Floor, Panagal Building, Saidapet
2025_RDTN_633850_1
DIPR/6649/Tender/2025 Dt.16.12.2025
Open Tender
Civil Works - Buildings
Item Wise
120 days
DRDA, Kancheepuram
Please refer Tender documents.
7 documents required · 7 mandatory
₹0
₹24,000
Yes
30 Jan 2026
18 Dec 2025
31 Dec 2025
18 Dec 2025
31 Dec 2025
18 Dec 2025
Amount
Providing Electrification Works at 4th Floor, Panagal Building, Saidapet Estimate Amount Rs.23.10 Lakh
Supply, Installation, Testing & Commissioning of double door type IP 42 powder coated Distribution Boards complete with MCBs/RCCB/ELCB/Isolators/ Bus bars Including all interconnections and other associated fixing accessories etc as reqd as per the site conditions. For fixing the DB on the wall / partition / coloumn, etc needs to be considered. The Ferrules identification to be done in both end. The Bus bars shall be tinned copper with seperate earth / neutral bus for each phase. Each circuit shall have yellow ferrules on all wires (Phase, Neutral & Earth) with circuit numbers, laminated A3 or A4 size SLD copy and distribution chart shall be stick inside of the DB doors, safe shroud to be provided for neutral links.('B' curve MCB for Lighting, C curve MCB for Raw power DB's and 'D' Curve MCB for UPS DB's to be used)
a) LDB(7Segment) - 8Way as follows : Incommer 40A TPN MCB- 1 No. Sub-Incommer 40A, 30mA, 2P RCCB- 3 Nos. Outgoing 6A SP MCBs - 24 Nos. Separate Neutral Bus for Each Phase to be given
b)PDB & ACDB (VERTICAL DB) - 12Way as follows : Incommer 125A TPN MCCB- 1 No. Outgoing 16A/32A SP MCBs - 36 Nos. Separate Neutral Bus for Each Phase to be given
c)UDB(7Segment) - 8Way as follows : Incommer 63A TPN MCB- 1 No. Sub-Incommer 63A, DP MCB- 3 Nos. Outgoing 16A/20A SP MCBs - 24 Nos. Separate Neutral Bus for Each Phase to be given
d)Single phase ELDB - 12Way as follows : Incommer 3A 2P MCB- 1 No. Incommer 6A SP MCB- 10 No. Separate Neutral Bus for Each Phase to be given
e)MAIN DB 4 WAY VERTICAL as Follows: Incomer : 125A Isolator Out going : 3P 63A Isolator.
LT CABLES
Supply and laying of Aluminium/Copper/Armoured/UnArmoured/Flexible (XLPE insulated for above 25sqmm cable) 1.1kv grade cable laid in tray / hume pipe / in ready made trenches, with nylon cable ties / MS Clamps @ 600mm interval etc., as required.
3.5 Core 70 sq. mm. Aluminium Armoured cable.(MAIN DB)
3.5 Core 50 sq. mm. Aluminium Armoured cable.(PDB &ACDB)
b)4 Core 16 sq. mm. Armoured Aluminium cable
c)4Core 16sqmm Armoured Copper cable.
d)1Core 16sqmm copper flexible cable
CABLE TERMINATION
Supply & Termination of the abovecables with compression type Brass cable glands, aluminum sockets for aluminum cables / copper sockets for copper cables, insulation tape, anti corrosive paste, brass clamps for gland earthing with 14 SWG copper wire to connect to nearest earth flat.
3.5 Core 70 sq. mm. Aluminium Armoured cable.(MAIN DB)
3.5 Core 50 sq. mm. Aluminium Armoured cable.(PDB &ACDB)
b)4 Core 16 sq. mm. Armoured Aluminium cable
c)4Core 16sqmm copper flexible cable
d)1Core 16sqmm copper flexible cable
CABLE TRAYS
Supply & installations of GI 2mm Thick, 50mm height Ladder Type cable trays complete with couplers, bends etc. The rate to include supports of 25x25mmx3mm thk of angle fixed to ceiling/Walls etc with Anchore bolt fasteners. The cable tray support shall be spaced at interval of not more than 2.0 Metrs interval & at all bends.
a)150mm wide
b)300mm wide
LIGHT FITTINGS
a)Supply, Installtion, Testing & Commissioning of 4feet suspended 40W LED linear channel Light Fitting. The rate shall including all required fixing accessories as per the site condition.
a)Supply, Installtion, Testing & Commissioning of 2*2 suspended 40W LED linear channel Light Fitting. The rate shall including all required fixing accessories as per the site condition.
b)Supply, Installtion, Testing & Commissioning of 20W LED Suspended down Light Fitting. The rate shall including all required fixing accessories as per the site condition.
b)Supply, Installtion, Testing & Commissioning of 20W LED Concealed Light Fitting. The rate shall including all required fixing accessories as per the site condition.
c)Supply, Installation, Testing & Commisioining of CIRCULAR LIGHT 1200mm dia round type light fitting with all required fixing accessories as per the site condition.
d)Supply, Installation, Testing & Commisioining of Track light with 4 Nos of 20W LED Light Fitting type light fitting with all required fixing accessories as per the site condition.
f)Supply, Installtion, Testing & Commissioning of Mirror Light Fitting. The rate shall including all required fixing accessories as per the site condition.
h)Supply, Installtion, Testing & Commissioning of LED Strip Light
Supply of Euroceil Translucent PVC Membrane with Aluminium Channels and High Quality PVC Harpoon strengthening the periphery. PVC Membrane adhering to EN 14716 standards, Made in Germany customized at state of the art ISO 9001:2015 certified manufacturing facility in India, with following test certificates: * Fire: b-s1-d0 * No Heavy Metals * A+ Emission Supply of OSRAM Chip Euroceil Bar LED with Compatible Drivers (Non-Dimmable) HSN 9405.10.90 CCT: Not Yet Confirmed Operating Volt: 12V/24V CRI: >80 Warranty: 5 years
WIRING FOR LIGHT FITTINGS
a)Primary light point wiring
Supply, Laying, Testing and Commissioning of primary light point with 6A modular type switch with front plate in factory made GI box and wiring using (3 x 1.5) Sqmm 1100V grade stranded FRLS copper wires drawn in 25 mm dia 2mm thick pvc conduit including all conduit accessories such as bends, junction boxes etc., complete.(Primary light point means wiring from first switch control to the first light fitting). Greay colour wire to be used for Emergency lights points.
b)Secondary light point wiring
Supply, Laying, Testing and Commissioning of Secondary light point wiring using (3 x 1.0) Sqmm 1100V grade stranded FRLS copper wires drawn in 25 mm dia pvc conduit including all conduit accessories such as bends, junction boxes etc., complete.(Secondary light point means looped from primary point).
Lighting & EL Circuit wiring
a)Supply, laying, Testing &Commissioning of circuit wiring using1.1grade (3R x 1.5) sqmm pvc insulated FRLS copper wire drawn in 25mm dia pvc conduit from the distribution board to Switch board/ first light and all accessories as required. All circuit terminations shall be provided with crimping type sockets / lugs, ferrules. There shall not be any joints in the circuits, only looping is allowed in terminal blocks & in switch boxs.
POWER OUTLETS
Supply and fixing of computer power outlets, Modular type (shuttered) switch sockets. Industrial type sockets shall be of Polycarbonate body with plug top. All switch / sockets shall be provided with printed labels / stickers indicating source code. Colour code for UPS socket plates : White/ as per Client or architect. Colour code for RP socket plates : Black/Grey/ as per the Client/architect requiment. All switch / sockets including front plate & frame which will be mounted on the metal boxes shall have removable film coat to protect from scraches & paint during installation.
Supply and Fixing of Set of 3 nos of 5A 5Pin (Round cum Flat) modular type Socket controlled by 1no of 16A modular Switch with front plate, without Metal back box fixing in the modular Workstation and all fixing accessories.
Supply and Fixing of Set of 2 nos of 5A 5Pin (Round cum Flat) modular type Socket controlled by 1no of 16A modular Switch with front plate, without Metal back box fixing in the modular Workstation and all fixing accessories.
Supply and Fixing of 1 no of 5/15A modular type Socket controlled by 1no of 15A modular Switch with front plate,Metal back box fixing in the wall/Partition and all fixing accessories.
Supply and Fixing of 20A DP+E industrial interlocking type socket with Polycarbonate enclosure box with plug top controlled by 20A DP D curve MCB with all accessories. (For Hub rack)
Supply, installation, testing & comissioning of MCB's in Metal box fixing in surface/concealed , as follows:
a)40/63A 4P ' C' curve MCB in Metal box in IP44 enclosure
b)16/20/25/32/63A DP ' C' curve MCB in Metal box in IP44 enclosure
EARTHING
a)Supply & Installation of Maintanance free chemical Earth with 40mm dia hot dipped Copper 2.6 mm thk, 3.0 mtrs deep, complete with all accessories such as chemical compound, earthing link, chamber etc. The earth resistance shall be not more than 2.0 Ohms.
b)Supply & Laying of 8SWG copper wire
Supply & Laying of 10SWG copper wire
c)Supply, Laying & Termination of PVC insulated 2Runs of Single core 10sqmm Green colour copper cable with suitable size PVC conduit for dedicated earthing with all fixing accessories.
d)Supply, Installation, Testing, Commissioning of Earth Bus of following sizes inside powder coated MS fabricated box to be mounted on insulator as follows:
1)25mmx3mm x 250 mm Long Copper Bus
2)25mmx6mm x 250 mm Long Copper Bus
MISCELLENOUS
a)Supply & Installation of 1.0 KVA Invertor, 1Phase input & 1 Phase output with overload, short circuit protection and 30.0 Minutes SMF Battery back up with MS battery rack and all accessories as required.
b)TEMPORARY POWER - FOR CONSTRUCTION
c)Arranging temporary Lighting & Power for all agencies to work including suitable protection through MCBs/ELCBs/MCCBs & wiring /cabling. power shall be provided to all agencies during execution with required no. of light fixtures as per the site condition & required Industrial Socket outlets as per the site condition till commissioning stage.
d)REMOVING OF EXISTING WORK
e)Existing of all electricals pipe & switch socket , wiring and existing DB'S Metal box and others
GST Amount for providing Service to Government Contract Works for the above Construction Work. { GST Amount is the Total GST Amount for overall quoted amount Construction above this row in column "BB" for all works in this package} (Refer Clause 13.2 & 13.3 of Section 2 of Instruction to Bidders (ITB) of SBD)
S.ANBU (BID ID -1547182)
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 0.16 MB
Technicalbid02.pdf
Tender Documents • 0.76 MB
Pricebid02.pdf
Additional Documents • 0.54 MB
BOQ_758405.xls
BOQ • 0.40 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .