Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹26.1 LAccepted-AOC | ₹26.1 L Quoted ₹27.5 L | L1 | Accepted-AOC Being L1 |
| 2 | L2₹29.7 L+₹2.2 L (8.09%)Rejected-Finance H NO 90 VILLAGE REWLA KHANPUR PO NAJAFGARH NEW DELHI 110043 | NEW DELHI | WEST DELHI | DELHI | 110043 | ₹29.7 L+₹2.2 L (8.09%) | L2 | Rejected-Finance Being not lowest |
Tender Value
₹41.9 L
EMD Value
₹83,800
Closing Date
2 Nov 2021, 6:00 pmClosed
CWE (AF) Gurgaon
HQ CWE (AF) Gurgaon, Old Palam Road, Delhi Cantt-110010
REPAIR REPLACEMENT SERVICING OF HT SWITCH GEAR, COMPACT SUB STATION, TRANSFORMERS, VOLTAGE STABILIZER, LT PANEL, FEEDER PILLAR BOX, LT HT CABLE FAULT DETECTION AND ALLIED WORKS AT 2003 STN UNDER GE (AF) GURGAON
2021_MES_479503_1
CA NO. CWE/GGN/GT-15/2021-22
Open Tender
Electrical and Maintenance Works
Item Rate
240 days
2003 Stn
As per NIT
9 documents required · 9 mandatory
₹500
GE (AF) Gurgaon
₹83,800
Yes
25 Jan 2022
4 Oct 2021
4 Nov 2021
4 Oct 2021
2 Nov 2021
19 Oct 2021
4 Oct 2021 - 18 Oct 2021
Amount
M&L for disconnecting electric outdoor/ indoor transformer of capacity up to 400 KVA , opening of top cover by unscrewing nut,bolts & washer etc and draining out complete transformer oil for servicing (any type of defect) of transformer with taking out core assy from tank by disconnecting from tap changer HT & LT side bushing studs to outside, removing the lamination in proper manner carefully which found major/ minor repair and storing the same in suitable container (container to be provided by the contractor) to keep aside for re-use (after repair) and lifting of core assembly by opening of top cover and other items for inspection/examination and lowering/ fixing of core assembly in its original position after inspection complete all as specified and directed. Note :- (i) Rate is deemed to be inclusive of T&P and manpower charges for lifting core and site visit charges of transformer specielist. (ii) Transportation charges of transformer to nearest workshop and return back for installation is deemed to be included in the quoted rate.
M&L for rewinding of HT coils with copper wire DPC/super enameled high quality matching with existing gauge and impedance including requisite insulating paper/material in each layer or winding complete all as spcified and as directed. Note - The rate quoted against the item is inclusive of cost of all types of insulating materials and heating/varnishing etc.
Complete all as per item No 2 above but LT coils with copper wire complete all as specified and as directed. Note - The rate quoted against the item is inclusive of cost of all types of insulating materials and heating/varnishing etc.
M&L for inserting of HT/ LT coils on limbs rewinded here in before/old after cleaning of lamination in proper way after insulating the limbs with requisite insulating materials on limbs in between limbs/ coils in workshop complete all as specified and as directed.
M&L for re-arranging the top lamination over coils in proper manner including fixing of top channel soldering in between coils as necessary and brazing of star delta connection with tap changer in workshop complete all as specified and as directed.
S&F in renewal of transformer bushing (any type) LT side including brass set stems conical bush/gasket for indoor/outdoor transformer for the following capacity :- Note : The rates quoted is deemed to be included the cost of necessary labour charges for draining out transforer oil, opening of top cover by unscrewing nut, bolts washers and and suitable size pad type almuminium bus bar, nut, bolts, packing washers etc.
Upto 250 KVA
S&F in replacement transformer porcelain bushing (any type) HT 11 KV including brass set stems conical bush/ gasket for indoor/outdoor transformer and CSS upto 400 KVA complete all as specified and as directed. Note : The rates quoted is deemed to be included the cost of necessary labour charges for draining out transforer oil, opening of top cover by unscrewing nut, bolts washers and and suitable size pad type almuminium bus bar, nut, bolts, packing washers etc.
S&F in renewal silica Jel breather assy with vent pipe for indoor/ outdoor transformer of the follolwing capacity :-
Up to 315 KVA
M&L for Dehydration including filteration and cleaning of transformer oil by dehydrating machine incl testing of sample before and after dehydration and filteration all as specified and directed . NOTE:- Contractor has to arrange the dehydration machine and testing kit without any extra cost and detailed test report of each transformer/voltage stabiliser submit to the department.
Supply & Filling /pouring of transformer oil of low viscosity having dielectric strength not less than 60 KV complete all as specified and as directed. NOTE:- Dielectric strength test shall be carried out at site before pouring/filling in transformers in the presence of Engr-in-Charge on the site.
M&L for painting of transformer and automatic servo voltage stabilizer with existing colour, by using spraying machine upto 400 KVA before cleaning/preparation of outer surface of transformer including writing of SM No, MES No. and capacity of transformer in red colour complete all as specified and directed by Engr in Charge.
M&L for Checking/ inspection on site of automatic servo Voltage satbilizer functionality and servicing it (i.e. Cleaning from inside & outside, greasing gears, Checking its automatic controls, PCB card, motor, checking for oil strength, Checking circuit connections, lamps, meters, output/ input current stabilization, thimbling/ renewing heated/ burntout cable connection etc.) complete all as directed and specified by Engineer in charge.
M&L for disconnecting the defective automatic servo Voltage satbilizer of Capacity upto 300 KVA from incoming and outgoing cables and opening of top cover by unscrewing nut,bolts & washers etc and taking out core assy from tank and removing the lamination in proper manner carefully for taking out serviceable/unserviceable primary and secondary coils stabilizers for checking the defects in winding coils by draining out transformer oil keeping the oil safe for re-use in containers provided by contractor and making ready for transportation to back to site and including making connections and testing complete including replacement of gasket set unserviceable nuts & bolts, washer, packings complete all as specified and directed by the Engr in Charge.
Transportation of unserviceable automatic servo Voltage stabilizer to nearest workshop and return back for installation in its original position/location after repairing from workshop upto 300 KVA capacity complete all as specified and directed. Note :- Rate is deemed to be inclusive of transportation & lifting, T&P and manpower charges.
M&L for inserting of LT coils on limbs rewinded here in before/old after cleaning of lamination in proper way after insulating the limbs with requisite insulating materials on limbs in between limbs/ coils in workshop complete all as specified and as directed.
M&L for rewinding of winding with copper wire DPC/ super enameled high quality matching with existing gauge and impedance including requisite insulating paper/material in each layer or winding complete all as spcified and as directed.
M&L for re-arranging the top cover by screwing nuts, bolts & washers lamination over coils in proper manner including fixing of top channel soldering in between coils as necessary and brazing connection in workshop complete all as specified and as directed.
Supply and fixing LT incomming and outgoing limbs/ studs with insulator for voltage stablizer upto 300 KVA of any size in workshop capacity and structure as per site, complete all as specified and directed.
M&L for disconnecting & reconnecting and shifting within sub stations and renewing old connection of Voltage stablizer with new LT panel, complete all as specified and directed. Note: Rate deemed to inclusive of any no of labour for lifting, T&P & material like aluminium thimble of any size for LT cable etc required for shifting of position with in sub-station and re-conneting.
Supply and fix in replacement of micro switch for upto 300 KVA voltage stabiliser make as per site , complete all as specified and as directed.
Supply and fix in replacement DPDT switches for upto 300 KVA voltage stabiliser make as per site complete all as specified and as directed.
Supply and fix in replacement Auto mannual switch for upto 300 KVA voltage stabiliser make as per site, complete all as specified and as directed.
Supply and fix in replacement high and low voltage indicator for upto 300 KVA voltage stabilizer make as per site, complete all as specified and as directed.
Supply and fix in replacement of servo circuit card suitable for voltage stabilizer for upto 300 KVA voltage stabiliser make as per site complete all as specified and as directed.
Supply and fix in replacement of dimmer coil suitable for for upto 300 KVA voltage stabilizer make as per site complete all as specified and as directed.
Supply and fix in replacement of gear suitable for for upto 300 KVA voltage stabilizer make as per site complete all as specified and as directed.
Supply and fix in replacement of PCB holders suitable for for upto 300 KVA voltage stabilizer make as per site, complete all as specified and as directed.
Supply and fix in replacement push button suitable for for upto 300 KVA voltage stabilizer as make per site, complete all as specified and as directed.
Supply and fix in replacement potentio meter suitable for for upto 300 KVA voltage stabilizer make as per site, complete all as specified and as directed.
Supply and fix in replacement electronics sensing card (PCB) suitable for voltage stabilizer of any capacity for upto 300 KVA voltage stabiliser and any make as per site complete all as specified and as directed.
Supply and fix in replacement electronic sensing transformer suitable for for upto 300 KVA voltage stabiliser of any capacity and any make as per site complete all as specified and as directed.
Supply and fix in replacement servo-motor of suitable torque rating for existing for upto 300 KVA voltage stabiliserof any capacity and any make as per site complete all as specified and as directed.
M&L for Servicing/ Decarbonsing/cleaning complete HT VCB indoor type and HT VCB in CSS, 11 KV cubicle type, consists of bus bar chamber, circuit chamber and metering chambers, by opening the spout/bus covers inspecting the bus bar joints, cleaning of bus bars, checking the bus bar spouts and circuit spouts for any flash overs/tracks, applying Becktol red solution to the bus bars and spouts having moderate tracking, replacement of bus bar/circuit spouts in case of spouts subjects to heavy tracking, applying HT insulated red compounds at the bus bar joints after tightening of joints, cleaning of bus bar insulators and bus bars with CTC and ensure proper decarbonisation and re-assembling complete all as directed by Engineer-in-Charge. Note: Rectification of mechanical complaint like spring charging, tripping of VCB, Locking of Gear assembly or any other minor defect is deemed to be included in quoted rate.
Disconnecting and taking out the Digital and manual IDMT relay any type and any make from 11 KV HT VCB indoor type and HT VCB in CSS,cleaning the contacts. Calibrating the relay by conducting primary injection and secondary injection tests,checking of current transformer, rectified of defects in control wiring for proper tripping of circuit brakers through CTs and relays and tripping coils.adjustment/setting to plug and time multiplier settings of the relay to achieve the discrimination in tripping time of upstream brakers,re-installation of the relay in circuit complete all as specified and as directed. NOTE:- The contractor shall provide necessary testing kits, testing equipments,tools etc and shall also prepare the detailed test reports panel wise duly bounded and submit to the department. Rate for the kits and equipment is deemed to be included in rate quoted. Testing and turning shall be carried out in the presence of Engineer-in-Charge to the satisfaction of department failing payment for the above item will not be made to the contractor. No claim from the contractor be entertained on this account.
S&F Maintenance free sealed lead acid battery of 12 V, 7Ah for HT VCB, as per site requirement, complete all as specified and directed. Note: Accessories like thimble of any type, wire, lead etc required for fixing battery is deemed to be included in quoted rate.
S&F Maintenance free sealed lead acid battery of 12 V, 26Ah for CSS, as per site requirement, complete all as specified and directed.
Taking down unserviceble CDG 61/31 relay and Supply, install, testing and commissioning of self powered microprocessor based numerical 3 Phase over current and earth fault relay with high set for both over current and earth fault with fault records suitable for panel mounting with auxialiary supply voltage range 24 V to 110 V AC/DC as per site requirement.complete all as specified and as directed Make: L&T/Areva/Micom/ABB/Alstom or equivalent make as approved by GE. Note:- 1. Replacement of existing relay and refixing of new relays and necessary control wiring , testing, calibration, setting to load requirements etc., are deemed to be included in the rates quoted. 2. Any modification/sheet metal work for relay fixing is deemed to be included in the quoted rates.
Taking down unserviceble VAJH13/23 master tripping relay and Supply, install, testing and commissioning of VAJH23,Two element high speed tripping relay with hand reset contacts. 1/2 N H , HR Contacts for panel mounting with auxialiary supply voltage range 24 V to 110 V AC/DC as per site requirement.complete all as specified and as directed. Make: L&T/Areva/Micom/ABB/Alstom or equivalent make as approved by GE. Note:- 1. Replacement of existing relay and refixing of new relays and necessary control wiring , testing, calibration, setting to load requirements etc., are deemed to be included in the rates quoted. 2. Any modification/sheet metal work for relay fixing is deemed to be included in the quoted rates.
Supply & replacement of HT Epoxy CT 50-25/5-5A, 15VA class 1.0 for metering and Class 5P10 for protection
Supply & replacement of 26A, 110 V power pack indoor type suitable for VCB having 26 A, 12 V, 10 Nos of SMF batteries and battery charger, complete all as specified and as directed.
S&F of switch air break, gang operated HT 11 KV triple pole, mechanically operated, mounted on insulators and steel frame, vertically or horizontally with operating mechanism worked from ground level, for current rating up to 200 amps complete including drop out fuse mechanism having 6 Nos insulatorsand taking down existing unserviceable switch complete all as specified and as directed. Note: (i) GOD must be having Nine (09) Insulators is deemed to be included in quoted rate. (ii) Any alteration required as per EIC is deemed to be included in quoted rate.
M&L for servicing of ACB with Microprocessor (Make: crompton greaves), Range (800 - 1250Amps) 415V, 50Hz,50 KA, after taking shut down and properly replacing flash out bus bars, settings relays and their mechanism, repairing charging mechanism & handle, removing wornout parts, repacing and testing and commissioning, complete all as specified and directed. Note: T&P and Parts required to make the ACB are deemed to be included in quoted rates.
Maintenance & repair of Compact substation from OEM at various location of following capacity (Note: rate quoted deemed to be inclusive of any type of T&P, testing kits, wiring of any type of existing size wire & tagging, CT's, metering and Metering Display device, manpower etc required at site for any type of maintenance). 1) IEC 62271.202, Type CSS - SN : 6.9, Transformer: 11/0.433kV, 250 kVA 2) IEC 62271.202, Type CSS - SN : 6.9, Transformer: 11/0.433kV, 150 kVA 3) IEC 62271.202, Type CSS - SN : 6.9, Transformer: 11/0.433kV, 150 kVA 4) IEC 62271.202, Type CSS - SN : 6.9, Transformer: 11/0.433kV, 200 kVA The scope of work is as follow:- A) RMU (HT Side) 1. Checking and making fuctionality of RMU mechanism in auto and manual mode. 2. Checking and toping up of SF6 gas of any quantity, rate quoted deemed to be inclusive of any type of T&P required at site and producing certifate of same from OEM. 3. Checking and making functional breakers ON/OFF operation, manually & electrically. 4. Functional checking of all electrical & mechanical interlock operation of RMU. 5. Testing of CTs & Relays with testing kit and producing certificate of same from OEM. 6. Caliberation of Relays and producing certifate of same from OEM.
B. Transformer (upto 250 KVA). 1. Checking and making Transformer functional. 2. Checking and toping up of oil level in T/F. 3. Checking and making Functional of cooling fan, if available. 4. Checking function of hooter/Buzzer. 5. Routine test of Transformer and producing test certificate of same. C. LT Side. 1. Checking and making all the ACB & MCCBs fuctional. 2. Checking and making all the ACB/MCCBs ON/OFF operation manually & electrically. 3. Checking and adjusting and servicing all the ACB and ACB relay setting as per load conditions, Metering devices, CT's and wiring of any type and producing certificate of the same. 4. Repair/replacement to APFC panel capacitor bank of 25KVAR x 4 (max) and APFC relay setting, repairing LCD display, repairing/replacing CT's, fans, contactors of any type, fuse is deemed to be included in quoted rate. 5. Repair replacement of battery charger upto 24 Volts is deemed to be included in quoted rate. 6. Repair/replacement of flash out Bus bar & insulators of any length, rating and any quantity is deemed to be included in quoted rate. 7. Repair/replacement of unserviceable handle assembly FNX/FN type, auxillary contact kit, LED indication of any colour, push button etc. is deemed to be included in quoted rate.
M&L stored energy T7 circuit breaker can be equipped with the spring charging motor to allow a complete remote control with T7 motorizable, the circuit breaker must be fitted with shunt trip, closing coil, spring charging motor and locking arrangement with front extended spread terminal of 500 Amps capacity 4 pole, 6KA complete all as specified and directed by EIC. Make: ABB cat No: 1SDA054602R1 or equivalent in approved makes. Note: Cost of Spreader, wiring & CT's are deemed to be included in quoted rates.
M&L for MCCB 400 Amps, 36 KA, 4 pole, 415V, 50Hz, adjustable type, with front extended spread terminal complete all as specified and directed. Make: ABB cat No: 1SDA054478R1or equivalent in approved makes.
M&L for MCCB 400 Amps, 36 KA, 3 pole, 415V, 50Hz, adjustable type, front extended spread terminal complete all as specified and directed. Make: ABB cat No: 1SDA054437R1 or equivalent in approved makes.
M&L for MCCB 320 Amps, 36 KA, 4 pole, 415V, 50Hz, adjustable type, front extended spread terminal complete all as specified and directed. Make: ABB cat No: 1SDA054477R1 or equivalent in approved makes.
M&L for MCCB 320 Amps, 36 KA, 3 pole, 415V, 50Hz, adjustable type, front extended spread terminal complete all as specified and directed. Make: ABB cat No: 1SDA054436R1 or equivalent in approved makes.
M&L for MCCB 250 Amps, 36 KA, 4 pole, 415V, 50Hz front extended spread terminal complete all as specified and directed. Make: ABB cat No: 1SDA051306R1 or equivalent in approved makes.
M&L for MCCB 250 Amps, 36 KA, 3 pole, 415V, 50Hz front extended spread terminal complete all as specified and directed. Make: ABB cat No: 1SDA051247R1 or equivalent in approved makes
M&L for MCCB 160 Amps, 36 KA, 4 pole, 415V, 50Hz front extended spread terminal complete all as specified and directed. Make: ABB cat No: 1SDA054272R1 or equivalent in approved makes
M&L for MCCB 160 Amps, 36 KA, 3 pole, 415V, 50Hz front extended spread terminal complete all as specified and directed. Make: ABB cat No: 1SDA054177R1 or equivalent in approved makes.
Supply only Thimble of aluminium LT Cable size 300 Sqmm
Supply only Thimble of aluminium LT Cable size 240 Sqmm
Supply only Thimble of aluminium LT Cable size 185 Sqmm
Supply only Thimble of aluminium LT Cable size 150 Sqmm
Supply only Thimble of aluminium LT Cable size 120 Sqmm
Supply only Thimble of aluminium LT Cable size 95 Sqmm
Supply only Thimble of aluminium LT Cable size 70 Sqmm
Supply only Thimble of aluminium LT Cable size 35 Sqmm
Supply only Thimble of aluminium LT Cable size 25 Sqmm
Suplly only HT tinned copper fuse wire of 20 amp
M&L for defect rectification HT 11 KV cable laid in trenches by locating fault with the help of electronic fault locating machine comprising of surge generator pulse, ECHO fault locator with high frequency distance calculator etc.including and additional excavation in normal alluvial strata required for exposing the cable fault ; removal of deteriorated portion of cable treating of cable and keeping the same ready for jointing work for cable of any size . The fault locating equipments will be brought to site within the hours complete all as specified and as directed. Note: Rates are inclusive of excavation, return refilling of cable at faulty pt in any type of soil by deploying any no of labours and T&P.
Complete all as item No 65 above but for LT 1100 volt grade cable of any size.
Supply & jointing heat shrinkable straight through joint suitable for HT 11KV (E) grade XLPE cable of size 120 Sq mm to 185 sqmm 3 core complete all as specified and as directed.
Complete all as item No 67 above but but 50 sqmm to 95 sqmm
M&L for Cable jointing kit for 11 KV (Earthed) grade cable for outdoor end termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 sqmm to 185 sqmm, complete all as specified and directed.
Complete all as item No 69 above but 50 sqmm to 95 sqmm.
Supply & jointing heat shrinkable straight through joint suitable for LT 1.1 KV Volt grade XLPE cable of size 240-300 Sq mm 3.5 core complete all as specified and as directed.
Complete all as item No 71 above but suitable for cable size 150-185 sq mm.
Complete all as item No 71 above but suitable for cable size 70-120 sq mm.
Supplying , laying, jointing and testing XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) with aluminium conductor, 11000 volts, grade cross sectional area 95 sq. mm 3 core complete all as specified and as directed.
Complete all as item No 74 above but suitable for cable size 120 sq. mm 3 core.
Complete all as item No 74 above but suitable for cable size 185 sq. mm 3 core .
Supply , fixing on wall with clamp, testing and commissioning in replacement and re-routing of XLPE insulated and PVC Sheathed , galvanized steel strip or wire armoured , heavy duty electric cable with aluminium conductor, 1100 volts grade of size 185 sqmm 3.5 core complete all as specified & directed.
Complete all as item No 77 above but suitable for cable size 25 sq. mm 4 core.
Returning filling in including spreading, leveling, watering and well ramming in layers n exc 25 cm complete all as specified and as directed.
Removal of excavated material/surplus soil to a distance n exc 50m and depositing where directed at a level n exc 50m above the starting point complete all as specified and as directed.
Supply and laying sand in trenches for protection of cable sand cushioning to cable 8 cm thick below cable and 15 cm thick above cable in layers all as specified and as directed.
M&L for brick protection with sub class 'B' old bricks laid dry flat 23cm in width over sand cushioning in trenches as perpendicular to the direction of underground cable complete all as specified and as directed.
M&L for boring/ auguring (upto 6mtr span) suitable hole and insertion of 50/80/100mm dia GI pipe not less than 600mm below existing PCC/Road/hard standing complete all as specified and as directed. Note: GI pipe will be paid in saperate item.
S&F in repair GI pipe light grade 50mm bore in trenches/ wall/ poles for protection of cable complete all as specified and as directed.
S&F in repair GI pipe light grade 80mm bore in trenches/wall/poles for protection of cable complete all as specified and as directed.
Surface excavation n.exc (not exceeding) 30 cm deep and averaging 15 cm deep and getting out in soft/ loose soil.
M&L for 75mm thick cement concrete type B-2, 1:2:4 (40mm graded aggregate) in sub floors concrete for interlocking tiles.
M&L for cement concrete 1:4:8 type D-2 (using 40mm gde agg) as in foundation or sub base and mass concrete etc complete all as specified and directed.
M&L for sand filling under floors for levelling and ramming including watering and consolidation.
M&L for Machine pressed precast conctete interlocking paver block any shape and size for floor tiling in MES Power House confirming to IS 15658-2006 of 80 mm thickness, M-35 Grade with grey cement and pigment.
M&L for excavating in post holes (or similar holes) each up to 1.50mtr depth as required directed by Engr-in-charge, getting out, returning, filling in and ramming earth or broken rubble mixed with earth around, in layer not exceeding 25 cm, in soft/ loose soil including n.exc 0.5 Cum, getting out, returning, filling in and ramming earth or broken rubble mixed with earth around, in layers not exceeding 25 cm, in soft and loose soil complete all as specified and directed.
M&L for cement concrete 1:2:4 type B-2 (using 40mm gde agg) as in foundation or sub base and mass concrete etc complete all as specified and directed.
S&F Rolled sections Fe 410-W (Gde- E- 250) quality- as in main and cross beams, hip and jack rafters; purlins where connected to common rafters and running rails and guides for sliding doors; fixed with angle cleats or other connecting plates.
S&F for Pre- painted galvatume aluminum zinc coating GI based corrugated steel sheet 0.50 mm thick of an colour having tensile strength of 550 Mpa as in roof covering/ cladding to wall, fixed with self tapping screws all as specified and as directed.
M&L Prepration new steel surface of any description not other wise described over 10 cm width or girth and applying two coat of synthetic enamel paint over one coat of red oxide complete all as specified and directed.
M&L for brick work with sub class 'B' Bricks, straight or curved on plain exc 6m mean radius built in CM 1:4 complete all as specified and as directed.
M&L for Rendering 15mm thick on fair faces of brick work or concrete surface with CM 1:4 complete all as specified and as directed.
Excavating in trenches, soft & loose soil n exc 1.5 m wide and n exc 1.5 m in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. n exc 10 sq m on plan and n exc 1.5 m in depth and getting out complete all as specified and as directed.
OUTGOINGS (i) MCCB, AC 415 volts, 3-Pole,400 Amp rating, 36 KA rupturing capacity, with adjustable thermal (70% to 100%) setting and fixed magnetic setting conforming to IS: 13947-II complete. - 01Nos .
M&L for Taking out the unserviceable LT Feeder Pillar including all connection and supply, installation, commissioning and testing of LT Feeder pillar outdoor type CPRI Approved base frame mounted dust proof with bus bar chamber to accommodate 3phase, 415Volt with suitable aluminium busbar designed as per relevant IS connected to busbar by aluminium strip of suitable Size, fabricated out of 2 mm thick CRCA sheet for outer chamber and 1.6 mm thick for partition and doors and painting with seven tank process with twin shutter closing & locking arrangements complete and fixed in PCC 1:2:4 type B-1 using 20 mm graded stone aggregate as in foundation 40 cm above ground level including provision for fixing of MCCB 200A 4Pole -1 Nos (Incomer), Ammeter,Voltmer,Indication Lamps and outgoing bus bar of suitable rating with provision of fixing 4 Nos outgoing cable of upto 95 Sqmm size with mean of nut bolt & washers complete with control wiring for the above accessories all as specified and as directed.
M&L for annual maintenance of solar LED street lights - 24 Nos (make: Aura). Replacement or repair to LED luminaire of 30 watts, including repair to its driver, PCB card, sensor, solar photo voltic panel/cell, inbuild Li-on batteries and any physical damage cause to panels, pole, hoding strip, GI supporter strips etc (fabrication of GI/MS frame on site and repairing tilted frames) by deploying authorised rep of Aura solar lightings, complete all as specified and directed Note: (i) Replacement of spare parts is included in quoted rates including battery, driver, PCB card, sensor, connecting terminals,photo voltic cell/panel, LED luminaire of 30 watt. (ii) contractor has to arrange T&P & labour for fabrication on site, repairing any physical damage to Solar street ights. (iii) Visiting charges by technicians is any nos of time included in quoted rates. (iv) Panelity of Rs. 1000 per light per day will recovered from contractor if light not found serviceable.
Supply and fix 3 Phase automatic timer switch with switches ON/OFF the street lights base on lux level of natural light current rating 40 Amps, 220 Volts, 50 Hz. The sensor based timer should also have over voltage and low voltage trip with auto reset facility the sensor alongwith suitable power contactor, MCB and support terminals should be enclosed in pole/wall mountable enclosure made of rust proof electric shock proof termite proof and FR grade special moulding compounds confirming to IP 65. The contactor MCB and circuit wiring shall have enough capacity to take load of 5/7 KW equally distrubuted over 3 phase complete all as specified and as directed. Make : Healer/Universal Swtich Gear/Kakatiya Note: Copper cable of 4 Sqmm x1core (12 Rm) and fixing timer on wall/pole with the help of faster & ms strip, nut bolt & washer is deemed to be included in quoted rates.
Dismantling steel poles/ struts, any size
M&L of Steel tubular swaged poles complete with cast iron base plate, finial taper plug, bolts, nuts & screws as specified type 410 SP-31 (9 metres long)
M&L of PCC 1:4:8 Concrete with 40mmm aggregrate 15 cm Depth in bottom of Pit for bed concrete steel tubular pole.
M&L PCC 1:3: 6 Concrete with 40mmm aggregrate 1.5 Mtr Depth of concrete for fixing of streel light steel tubular pole.
M&L for cement concrete 1:2:4 type, B1 using 20 mm graded stone aggregates as in copings including necessary use and waste formwork, weathering, slightly rounded or chamfered angles and throating etc complete all as specified and directed
Service/Repair for the automation water supply system installed at Master Monitoring panel via 1 No micro processor based Remote Terminal Unit Panel for 2 nos. of Level Sensor , 3 Nos Motor Actuated Butter fly Valve, installed at Mohammadpur OHT. The Scope of work includes carrying out complete repairs as required of all the sub systems viz. RTU(REMOTE TERMINAL UNIT) based Master Monitoring and audio generator (with all the accessories), motorised valves, Level sensors, Level SwitcheS, Remote communication panels, GSM Modem,personal computer, UPS, SCADA software for Automation system and generate backup of SCADA Database - 01 No replacement of unserviceable parts, refixing of old serviceable parts/new parts if any and preparing the records/register complete for the following places complete all as specified and directed. Note: Rates for the required spares are extra as specified below. OEM :- M/S CIMON SOFTWARE(INDIA) PVT LTD (1) Tools and Machinery for : (a) SCADA Automation of OHT level monitoring
Monthly Service Visit during fault/failure of any product or services for the automation water supply system installed at Master Monitoring & operating master panel via 1 No micro processor based Remote Terminal Unit Panel for 2 nos Nos level sensor , 3 Nos Motor actuated Motorise Valve panel installed at Mohammadpur OHT. The Scope of work includes carrying out complete monitoring as required of all the sub systems viz. RTU(REMOTE TERMINAL UNIT) based Master Monitoring and Audio Generator, motorised valves, Level sensors, personal computer, UPS, SCADA software for Automation system and generate backup of SCADA Database - 01 No replacement of unserviceable parts, refixing of old serviceable parts/new parts if any and preparing the records/register complete for the following places complete all as specified and directed. OEM :- M/S CIMON SOFTWARE(INDIA) PVT LTD (1) Tools and Machinery for : (a) SCADA Automation of OHT level monitoring
Note for Ser No 108 & 109: The shecdule item No 108 & 109 cosist of comprehensive, preventive and perodical maintenance of SCADA Automation of OHT level monitoring Make- CIMCON installed at 2003 Stn under GE(AF) Gurgaon. The comprehensive maintenance & preventive maintenance work under item No 108 & 109 shall be carried out only by through trained Engineer of M/s CIMOCON only as directed by Engr-in-Charge and GE. The contractor should have obtained MOU with M/s CIMCON and be submitted to office within 15 day of acceptance. Failing to which, contract shall be cancelled and MRO equal to earnest money shall be deposited by contractor.
Supply of Internet Security anti virus software with one user license for one year. Make :MacAfee / NPAV / QUICK HEAL or equivalent as approved by GE.
Supply of UPS of suitable capacity 600 VA, 230 V AC FOR MASTER CONTROL STATION. Make- APC /IBALL/ MICROTEK or equivalent as approved by GE.
Supply of Inverter Battery Backup 12 v, 42 ah panel.Make- Amar raja /Exide/ MICROTEK /Amron or equivalent as approved by GE.
supply and replace of maintanance free unserviceable battery 12 V, 150 AH with initial charging and testing compleete all as specified and as directed. Make: Amaron/Exide/Microtek or equivalent as approved by GE.
Supply of Ultra sonic Level Transmitter for level monitoring for Overhead Tank with Following specification: - 12 to 24 DC operatinted output 4-20 mA. Range 0-5 mtrs Make:- SIEMENS/Banner/Militronics/B&H/Punetectrol or equivalent as approved by GE.
Supply of Butterfly Valves of 150 mm line size along with Motorized actuator Make: Belimo/SD TORK/ MARSH or equivalent as approved by GE.
Supply of Actuator for 150 mm line size Butterfly valve and actuor can be direct mount/extended shaft mounting type with 2 nos. torque limit and 2 nos. open/close limit switches as per site Make: Belimo/SD TORK/ MARSH or equivalent as approved by GE.
Supply of Actuator for 250 mm line size Butterfly valve and actuor can be direct mount/extended shaft mounting type with 2 nos. torque limit and 2 nos. open/close limit switches as per site Make: Belimo/SD TORK/ MARSH or equivalent as approved by GE.
Supply of ARM7 based CPU Card with RS-485, USB, Ethernet, 2 Nos. RS-232 Port, SD card Socket, Real Time Clock of Model iRTU 6000 Make : Cimcon or equivalent as approved by GE.
Supply of Analog and digital Input Output interface Unit of Model iRTU 6000 Make : Cimcon or equivalent make as approved by GE.
Supply of 16 Digital Input, 8 Analog Input Module of Model iRTU 6000 Make : Cimcon or equivalent make as approved by GE.
Supply of 16 Digital Output Module of Model iRTU 6000 Make : Cimcon or equivalent make as approved by GE.
Supply of 24 V DC SMPS/ 5/12 VDC SMPS 2 AMP of Model iRTU 6000 Make : Cimcon / meanwell or equivalent make as approved by GE.
Supply of 5/12 VDC SMPS with battery Charging and cut-off Module of Model iRTU 6000 Make : Cimcon / meanwell or equivalent make as approved by GE.
suppply of Wireless modem suitable for GSM based communication system to be mounted in RTU OR at Master Control Station
S&F Nos. of GSM SIM card charges including Rental/ SMS charges for the period of 1 years.
Supply of External High Gain antenna Unit along with extension Patch cord complete all as specified and as directed.
Supply of Relay - 2 C/O, 240 V AC/ 24 VDC for Master and Slave Panel Make : IDEC/ PLA or equivalent make as approved by GE.
Supply of suitable rating MCB single pole 6-32 Amps 230 volts 'C' series 10 kA breaking capacity
Supply of Indication Lamp 230 VAC operated for panel Make: Esbee/ schenider or equivalent make as approved by GE.
Net Contract Sum will be after deducting Sch of Credit of Rs 1,36,355.00
Ish Engineers and Contractors
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .