| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹16.5 LAccepted-AOC | L1 | Accepted-AOC Awarded |
| Sl No | Description | Qty | Unit | SHUBH TRADERS L1 |
|---|---|---|---|---|
| 1.00Current Transformer (Resin Cast) | ||||
| 1.01 | Current Transformer (Resin Cast) for 16.5 kV Generator Bus duct of 250 MW Unit No. 10 & 11
(CT Ref. No. CT-2,7,8), Existing CT Sr. No. 1184
Ratio-12500/5 A
Make- Prayog
Class – 0.2s
Burden – 75 VA
ISF - <= 5
Drawing enclosed | 6 | NOS. | 68,200 ₹84,499.8 Lowest |
| 1.02 | Current Transformer (Resin Cast) for 16.5 kV Generator Bus duct of 250 MW Unit No. 10 & 11
(CT Ref. No. CT-10), Existing CT Sr. No. 1191
Ratio-12500/5 A
Make- Prayog
Class – PS
Vkp>= - 250Rct+1000V
RCT (75⁰C) - <= 5ohms
Iex@Vk/2 – 150mA
Drawing enclosed | 3 | NOS. | 1,54,300 ₹1,91,177.7 Lowest |
| 1.03 | Current Transformer (Resin Cast) for 16.5 KV UAT Bus duct of 250 MW Unit No. 10 & 11
(CT Ref. No. CT-13A/13B), Existing CT Sr. No. 1196
Ratio-800/1 A
Make- Prayog
Class – 5P20
Vkp>= - 50Rct+200V
Iex@Vk/2 <= – 30mA
RCT (75⁰C) - <= 5ohms
Drawing enclosed | 3 | NOS. | 49,804 ₹61,707.14 Lowest |
| 1.04 | Current Transformer (Resin Cast) for 16.5 KV UAT Bus duct of 250 MW Unit No. 10 & 11
(CT Ref. No. CT-15A/15B), Existing CT Sr. No. 1208
Ratio-800/1 A
Make- Prayog
Class – 0.2s
Burden – 10 VA
ISF - <= 5
Drawing enclosed | 3 | NOS. | 1,04,602 ₹1,29,601.88 Lowest |
Tender Value
Refer Docs
Closing Date
1 Dec 2022, 3:00 pmClosed
SE PNW, SARNI
STPS, MPPGCL, SARNI
Procurement of various Current Transformers Resin Cast for 16.5kV Generator and UATs Bus Duct of 250 MW Unit for T and C-4, STPS, MPPGCL, Sarni.
2022_MPPGC_232044_1
PE-1400
Single
Electrical Goods/Equipments
Item Rate
60 days
STPS, MPPGCL, SARNI
Please refer Tender documents.
4 documents required · 4 mandatory
₹0
Exempted
11 Oct 2025
11 Nov 2022
5 Dec 2022
11 Nov 2022
1 Dec 2022
11 Nov 2022
Current Transformer (Resin Cast)
Current Transformer (Resin Cast) for 16.5 kV Generator Bus duct of 250 MW Unit No. 10 & 11 (CT Ref. No. CT-2,7,8), Existing CT Sr. No. 1184 Ratio-12500/5 A Make- Prayog Class – 0.2s Burden – 75 VA ISF - <= 5 Drawing enclosed
Current Transformer (Resin Cast) for 16.5 kV Generator Bus duct of 250 MW Unit No. 10 & 11 (CT Ref. No. CT-10), Existing CT Sr. No. 1191 Ratio-12500/5 A Make- Prayog Class – PS Vkp>= - 250Rct+1000V RCT (75⁰C) - <= 5ohms Iex@Vk/2 – 150mA Drawing enclosed
Current Transformer (Resin Cast) for 16.5 KV UAT Bus duct of 250 MW Unit No. 10 & 11 (CT Ref. No. CT-13A/13B), Existing CT Sr. No. 1196 Ratio-800/1 A Make- Prayog Class – 5P20 Vkp>= - 50Rct+200V Iex@Vk/2 <= – 30mA RCT (75⁰C) - <= 5ohms Drawing enclosed
Current Transformer (Resin Cast) for 16.5 KV UAT Bus duct of 250 MW Unit No. 10 & 11 (CT Ref. No. CT-15A/15B), Existing CT Sr. No. 1208 Ratio-800/1 A Make- Prayog Class – 0.2s Burden – 10 VA ISF - <= 5 Drawing enclosed
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .