Loading…
India Infra Updates on WhatsApp
Join the Tenderkart WhatsApp channel for India Tender Updates
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹6.5 LAccepted-AOC | L1 | Accepted-AOC OK | |
| 2 | L2₹6.5 L+₹6,641 (1.03%)Rejected-Finance | L2 | Rejected-Finance Other than lowest | |
| 3 | L3₹8.4 L+₹2.0 L (30.6%)Rejected-Finance | L3 | Rejected-Finance Other than lowest |
Tender Value
₹10.8 L
EMD Value
₹21,600
Closing Date
11 Aug 2023, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
CWE Rajouri
HQ CWE RAJOURI PIN 900129 C/O 56 APO
PROVN OF TRANSFORMER FOR EMU (EXPLOSIVE MELTING UNIT) ALONGWITH ALLIED SERVICES AT NAUSHERA UNDER GE 862 EWS
2023_MES_609054_1
CWE/RAJ-24/2023-24
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
Rajouri
Please refer tender documents
9 documents required · 9 mandatory
₹500
GE 862 EWS
₹21,600
Yes
12 Dec 2023
14 Jul 2023
18 Aug 2023
14 Jul 2023
11 Aug 2023
28 Jul 2023
Amount
Excavation in trenches not exceeding 1.50m wide and not exceeding 1.50m in depth for foundation etc for shafts, wells,cesspits, man holes, pier holes etc not exceeding 10 sqm on plan and not exceeding 1.5m depth and getting out in hard / dense soil, complete all as specified.
All as per srl item No. 1 here in before but depth exceeding 1.5 m and not exc 3 m, complete all as specified and directed.
Returning, filling in, including spreading, leveling, watering and well ramming in layers not exceeding 25cm, in any type of soil, complete all as specified and as directed.
Removal of excavated material to a distance not exc.50 m and depositing where directed at a level not exceeding 1.5 mtr above starting point, complete all as specified.
M&L for dry sand cushioning to UG cable 8 cm thick before laying and 15cm thick after laying complete all as specified and directed. Note:- 1.Dry fine sand of best available quality shall be used. 2.Punned down thickness shall be made and paid.
Supply and laying sub class `B` bricks laid dry flat transversely along the length of cable with width equal to the length of bricks over sand cushioning as protection cover of cable laid, complete all as specified and directed.
M&L for Cement concrete 1:4:8 type D-2 using 40 mm graded crushed stone aggregate in foundation of poles / Struts and mass concrete incl necessary form work and fair finish to exposed surface without using extra cement complete all as specified directed.
M&L for Plain cement Concrete 1:2:4 type-B1 (using 20mm graded crushed stone aggregate) as in copings, bands etc incl slightly rounded or chamfered angles as directed including necessary form work,complete all as specified.
M&L for Plain cement concrete 1:3:6 type C-2 (using 40mm graded crushed stone aggregate) as in foundation of poles and stay assembly and coping of pole incl necessary formwork and fair finish to exposed surface without using extra cement complete all as specified and directed.
Supply , installed, commissioning and testing Transformer step down, Copper wounded, Outdoor type complete with standard fittings HT 11 KV/433 volts (at no load) 3 phase 4 wire, 50 Hz, 63 KVA capacity , vector group DYn-11 having primary (HT) voltage of 11 KV and secondary (LT) voltage of 433 V off load tap changing gear to provide volts with tapping on primary side having steps of +/- 2.5% from (+) 5 % to (-) 7.5% in equal steps ofv 2.5 % each, so as to vary voltage on secondary side, including first filling of transformer oil, the transformer shall be delta connected on 11 KV side & star connected on secondary side with neutral brought out incl provn of HT bushings on HV (delta connection) side & LT cable box on LV (star connection) side, conforming to IS 1180-2014 level II completed all as specified and directed.
Supply, laying, testing and commissioning HT cable 11 KV grade, XLPE insulated (earthed) screened, PVC bedded, galvanized iron strip armoured with stranded aluminium conductor cable of cross sectional area 95 sqmm, 3 core, ISI marked complete all as specified and directed.
S&F Cable jointing kit for 11 KV (earthed) grade cable for outdoor termination heat shrinkable type joint, complete with and including jointing material and accessories suitable for 3 core XLPE armoured aluminium cable of size 95 Sqmm, also with and including connecting single thimbles etc after disconnecting of electric supply, complete all as specified and directed.
Supply and fixing lightening arrester expulsion type complete with all fittings transmission class , discharge capacity 65 kilo Amps suitable for 11000 Volts HT line complete all as directed by Engr in Charge.
S&F Cross arms, bracing, support, clamps etc made out of mild steel channel or angle section of reqd size and shape including clamp, back plate with bolts, nuts & washers drilled for insulator bolts, welding, bending cold or hot in any shape or size including all fixing arrangement on HT/LT over head line and painted with two coats of aluminium paint over a coat of red oxide primer complete all as specified & as directed by Engr-in-Charge.
S&F Stay assembly comprising of GI stay rod 20 mm dia 1800mm long, stay plate 300mm x 500mm x 6mm, galvanised thimbles, MS plate made out of 40 x 6 mm flat iron, 40mm long stay bow of 14 mm dia and GI nuts, washers, 7/4 stay strand wire and all other accessories as shown in electrical plate No 1 on Ser Page No 495 of MES Schedule Part-I (2009) complete all as specified and directed. Note : Stay clamp, Stay wire, excavation and earth work and concrete for stay pit shall be measured and paid separately.
Supply and install HT 11 KV outdoor type gang operated air-break switch suitable for vertical mounting fixed type complete with required insulators of rating upto 200 Amp, triple pole, mechanically operated, mounted on insulator and steel frame with operating mechanism worked from ground level complete all as specified and directed.
Supply and erecting in truely vertical position steel tubular swaged pole, 11 metre long, complete with mild steel base plate 6mm thick of size 300mm x 300mm, B-118 finial taper plug, bolts, nuts, washers and screws, type 410 SP-55 including drilling of holes of required size and nuts for fixing of cross arms, painting with two coats of aluminium paint over a coat of red oxide primer and two coats of black bituminous paint for portion embedded in concrete, painting five black and white bands at lower portion of pole each of 300 mm height at 300mm spacing & marking pole Nos with black paint, complete all as specified and directed. (Note : Excavation, earth work and PCC in foundation of poles, coping etc shall be measured and paid separately under respective items of Sch 'A').
S&F Pin type insulator porcelain vitreous, white, brown or green including one galvanized mild steel spindle, two galvanized iron washer and one galvanized iron nut 150 mm height, 150 mm dia for 11000 volts grade, complete all as specified & as directed.
S&F Disc type insulator, porcelain, vitreous 145 mm height and 255 mm dia ball and socket type, white, brown or green single disc assembly for tension with tension clamps for conductors working pressure 11000 Volts, complete all as specified & as directed.
S&F loop type insulator, porcelain, vitreous white, brown or green insulator, large size with overall dimensions 140mm x 90mm, clearance of hole 25.5 mm, complete all as specified & as directed.
M&L for Danger notice board of 25 cm x 20 cm size, made out of 1.6 mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with MS clamps, bolts & nuts of approved size for HT pole, complete all as specified and directed.
S&F anti climbing device, spikes type fabricated out of M.S bars ( Round , Square and flat ) including nuts, bolts, washer and welding in two halves made to shape to suit the cross section of the pole, complete all as specified and directed.
Material and labour for earthing complete with galvanised steel earth plate electrode 600mmX 600mm thickness not less than 6 mm thick buried directly in ground vertically ( earth pit not less than 2.25 metres deep below ground level) with top edge of plate not less than 1.5 metres below ground level, connected to and including galvanised iron strip of size 32 X 6 mm by means of GI bolts, nuts, check nuts and washers of galvanised iron/steel all as per electrical plate no 3 of SSR Part-I connected to earth test point/MCB DBs/Equipment/Machinary all as specified and indicated complete with funnel, charcoal,dust,salt etc and GI Protection pipe 32 mm bore medium grade for protection of GI strip and GI watering pipe of 20 mm bore light grade,40 mm thick precast RCC M15 (nominal mix) cover reinforced with XPM weight not less than 4 Kg/Sqm with suitable handle of 6 mm dia MS bar and angle iron 40x40x4mm frame cover, PCC M-15 (Nominal Mix)pit, excavation and earth work in any type of soil and connected including test point, complete, all as specified and directed. Note: 1. Earth lead & protection pipe length upto and including 7.50 meter is deemed included in unit rate quoted by the contractor. 2. Earth filling shall be done by vegitable soil. 3. Soil should be free from stone, boulders, aggregate , gravels etc.
S&F GI pipe light grade 80 mm bore for cable protection fixed on poles or laid in trenches, under floor, ducts etc with fixing clamps of required size, nuts, bolts, washers etc. fixed, complete all as specified and directed.
Supply, laying, testing and commissioning cable 11 KV grade, XLPE insulated (earthed) screened, PVC bedded, galvanized iron strip armoured with stranded aluminium conductor cable of cross sectional area 70 sqmm, 3.5 core, ISI marked complete all as specified and directed.
Supply and straining of ACSR condutor of any size on LT poles without any kink and bends of various sizes complete including fixing to insulator with copper binding wire and coloured sleeved jumper connection with PG clamps complete all as specified and as directed.
Supplying, installing, testing and commissioning LT outdoor type panel board factory fabricated cubical kiosk type weather vermin proof with IP-54, for working on 3 phase, 4 wire, 415 volts AC, 50 Hz with locking arrangement and tested at CPRI for 35 MVA rupturing capacity, outer shell shall be made out of 3.15 mm thick CRCA sheet & MS angle iron frame duly powder coated of size 50x50x6mm frame with front and back open, double door system lockable, inner shell shall be made up of 2.00 mm thick CRCA sheet with entry holes for incomming & outgoing cables as approved by GE complete with & including 200 Amps rated aluminium bus bar chamber and cable alley chamber including cable gland of suitable size and adequate nos and cabinet for housing mounting switch disconnection fuse unit metering eqpt prewired with suitable size of copper conductor and duly factory powder coated mounted on PCC (1:4:8) platform commissioning washer chamber and comprising with the following:- Incomming MCCB a) Incomming MCCB 4 pole 35 KA 100 Amps - 1 Nos With ICS=ICU=100%. Outgoing MCCB a) Outgoing MCCB 4 pole 25 KA 63 Amps - 2 Nos With ICS=ICU=100%. b) Outgoing MCCB 4 pole 25 KA 40 Amps - 2 Nos With ICS=ICU=100%. (Spare) c) Digital combimeter (3 in 1) with 4 digit LED display-01 No. d) LED phase indication lamps RYB-01 Set e) Internal wiring with PVC insulated copper conductor multi stranded cable 1100 volts grade and copper bus bar 160 amps incl painting etc
M&L for Point wiring with two single core 1.5 Sqmm (nominal cross section area) FRLS PVC insulated sheathed copper conductor cable and one single core 1.5 Sqmm (nominal cross section area) FRLS PVC insulated unsheathed copper conductor cable as earth continuity to common earth and connecting to earth dolly running in and including medium grade rigid non metallic PVC concealed conduit in wall after cutting chases in wall including cast iron or pressed steel terminal box covered with and including 3mm thick bakelite sheet top cover fixed flush with wall using brass screws, washers and all requisite accessories such as PVC elbow, Tee, collars, bends etc. for mounting switches, sockets, fan regulators etc for one light / fan / exhaust fan point controlled by one way switch 6 Amp, complete all as specified. Note:-The colour coding of wiring to be followed as Red/Yellow/Blue for Phase/Neutral/Earth respectively.
S&F One 3 pin 6 Amp switch socket on the independent board, complete all as specified.
S&F One 3 pin 6 Amp switch socket on the same board with other switches with cables 1.5 sqmm, complete all as specified.
All as per srl item No 28 here in before but for one 6 pin socket outlet 15 Amp on independent with two single core 2.5 Sqmm size cable as phase & neutral and one single core 2.5 Sqmm as in continuous earth wire, complete all as specified.
S&F Switch piano, flush type, 6 Amp, single pole, one way (ISI marked) complete all as specified and as directed.
S&F Socket outlet 2 in 1 , 3 pin , 6 Amp flush type (ISI marked) complete all as specified and directed.
S&F Switch piano, flush type, 15 Amp, single pole, one way (ISI marked) complete all as specified and as directed.
S&F Socket outlet 2 in 1 , multipurpose 3 pin , 5/15 Amp flush type (ISI marked) complete all as specified and directed.
S&F Ceiling rose, surface bakelite 3 terminals PVC/ polycorbonate, isolated bady (ISI marked) complete all as specified and as directed. .
Supply and fix exhaust fan made of sturdy Engineering plastic complete with louvers shutter, voltage 230V, 50 Hz, RPM 1200, Copper winding of sweep 300m, complete all as specified.
Supply and fixing LED lights fitting 1x 20W, 220V, AC decorative box type with driver, holder including LED tube light connecting up with three core flexible copper conductor cable of suitable size from ceiling rose complete. all as specified and directed.
Supply and fixing 415V 10KA 'C' curve miniature circuit breaker (MCB) TPN of current carrying capacity 63 amps in the DB complete with connection testing and commissioning complete all as specified and directed.
Supply and fixing 415V 10KA 'C' curve miniature circuit breaker (MCB) TPN of current carrying capacity 6 to 32 amps in the DB complete with connection testing and commissioning complete all as specified and directed.
S&F sheet metal enclosure for distribution board 4 way TPN for 415 Volts double door for MCB, complete all as specified and directed.
Material and labour for earthing complete with galvanised steel earth plate electrode 600mmX 600mm thickness not less than 6 mm thick buried directly in ground vertically ( earth pit not less than 2.25 metres deep below ground level) with top edge of plate not less than 1.5 metres below ground level, connected to and including galvanised iron strip of size 25 X 4 mm by means of GI bolts, nuts, check nuts and washers of galvanised iron/steel all as per electrical plate no 3 of SSR Part-I connected to earth test point/MCB DBs/Equipment/Machinary all as specified and indicated complete with funnel, charcoal,dust,salt etc and GI Protection pipe 32 mm bore medium grade for protection of GI strip and GI watering pipe of 20 mm bore light grade,40 mm thick precast RCC M15 (nominal mix) cover reinforced with XPM weight not less than 4 Kg/Sqm with suitable handle of 6 mm dia MS bar and angle iron 40x40x4mm frame cover, PCC M-15 (Nominal Mix)pit, excavation and earth work in any type of soil and connected including test point, complete, all as specified and directed. Note: 1. Earth lead & protection pipe length upto and including 7.50 meter is deemed included in unit rate quoted by the contractor. 2. Earth filling shall be done by vegitable soil. 3. Soil should be free from stone, boulders, aggregate , gravels etc.
M/S PARSHOTAM KUMAR GUPTA
RAVI KUMAR
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.PDF
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .