Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹42.5 LAccepted-AOC 39 40 DASHMESH MARKET CIVIL GURUDWARA LINE PORT BLAIR 744 101 | PORT BLAIR | SOUTH ANDAMANS | ANDAMAN AND NICOBAR ISLANDS | 744101 | L1 | Accepted-AOC Lowest | |
| 2 | L2₹49.6 L+₹6.2 L (14.2%)Rejected-AOC | L2 | Rejected-AOC Not Lowest | |
| 3 | L3₹51.3 L+₹7.9 L (18.2%)Rejected-AOC | L3 | Rejected-AOC Not Lowest |
Tender Value
₹35 L
EMD Value
₹70,000
Closing Date
7 Jul 2020, 6:00 pmClosed
GE UTILITY SECUNDERABAD
GE UTILITY, MUDFORT, SECUNDERABAD-500003
REPAIRS RENEWAL OF LT PANEL BOARD,LT FEEDER PILLAR BOX,EARTHINGS,LT UG CABLE AND OTHER MISC ALLIED WORKS OF ZONE-IIA AND IID AND ITS ADJOINING AREA UNDER AGE EM-II OF GE UTILITY SECUNDERABAD
2020_MES_351251_1
GE(U)/SEC/TOKEN/15 OF 2020-21
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
SECUNDERABAD
As per NIT
7 documents required · 7 mandatory
₹500
GE UTILITY SECUNDERABAD
₹70,000
Yes
5 Aug 2020
9 Jun 2020
9 Jul 2020
10 Jun 2020
7 Jul 2020
25 Jun 2020
Amount
Design, fabrication, supply and errecting connecting and testing totally enclosed LT Cubical panel board of suitable size(proper space shall be provided for working in each compartment), 3 Phase 4 wire system Outdoor type ,double door front and back openeing type sloped canopy(Hood) on top extended 100mm all-around, separate compartment for each control gear, cable alley, provision of knock out type plates for various sizes of cable up to 400 Sqmm 3.5 Core in and out(panel board shall have sufficent space to accommodate spare cables also if required) , incoming and outgoing feeders duly marked on revited plates etc,
CPRI approved factory made fabricated out of 3.15mm thik CRCA sheet duly treated through 7 tank pre treatment process and painted with epoxy power coated mat finish of SIEMENS GREY structral RAL 7032 shade colour, built in industrial type locking arrangement on front and back and pre wired with PVC insulated multi stranded copper conductor for controls and monitors, PVC sleeved aluminium strip for connecting MCCBs, Panel mounted on suitable size & thickness of angle iron frame(proper mounting shall be done, duly painted and embeded in necessary required quatnity of PCC 1:3:6 type C1, 60cm below ground level and 30cm above ground level including disconnecting all electrical & mechanical connections and taking down old unserviceable and consisting the following provisions:-
(a) Onload change over 4 pole,front handle operated 630Amps,415 volts with along with handle L&T Cat No. CO46300OOOO -01No (b) MCCB 630Amps Four Pole AC 415 Volts,50Hz,50kA , with Thermal & Magnetic release,Cat No CM94104OOT1OG Make: L&T - 01 No(incoming) (c) MCCB 400Amps 3Pole AC 415 Volts ,50Hz,35/36kA, with Thermal & Magnetic release, Cat No .CM984101OOROOG Make: L&T - 01 No(Outgoing) (d) MCCB Three Pole 250 Amps 50Hz 415 Volts, with thermal Magnetic realse with rupturing capacity 35/36 KA-02Nos(outgoings+Spare) Make : L&T Cat No CM98401OOQOOG (e) MCCB 3 pole 63-100 Amps,25kA -01Nos(Outgoing) Make L&T Cat No.CM91612OOKOOG
Design, fabrication, supply and errecting connecting and testing totally enclosed LT Cubical panel board of suitable size(proper space shall be provided for working in each compartment), 3 Phase 4 wire system Outdoor type ,double door front and back openeing type sloped canopy(Hood) on top extended 100mm all-around, separate compartment for each control gear, cable alley, provision of knock out type plates for various sizes of cable up to 400 Sqmm 3.5 Core in and out(panel board shall have sufficent space to accommodate spare cables also if required) , incoming and outgoing feeders duly marked on revited plates etc, CPRI approved factory made fabricated out of 3.15mm thik CRCA sheet duly treated through 7 tank pre treatment process and painted with epoxy power coated mat finish of SIEMENS GREY structral RAL 7032 shade colour, built in industrial type locking arrangement on front and back and pre wired with PVC insulated multi stranded copper conductor for controls and monitors, PVC sleeved aluminium strip for connecting MCCBs, Panel mounted on suitable size & thickness of angle iron frame(proper mounting shall be done) duly painted and embeded in necessary required quatnity of PCC 1:3:6 type C1, 60cm below ground level and 30cm above ground level including disconnecting all electrical & mechanical connections and taking down old unserviceable and consisting the following provisions:-
(a)MCCB 630Amps Four Pole AC 415 Volts,50Hz,50kA , with Thermal & Magnetic release,Cat No CM94104OOT1OG Make: L&T - 01 No(incoming) (b) MCCB 400Amps 3Pole AC 415 Volts ,50Hz,35/36kA, with Thermal & Magnetic release, Cat No .CM984101OOROOG Make: L&T - 01 No(Outgoing) (c) MCCB Three Pole 250 Amps 50Hz 415 Volts, with thermal Magnetic realse with rupturing capacity 35/36 KA-02Nos(outgoings+Spare) Make : L&T Cat No CM98401OOQOOG (d)MCCB 3 pole 63-100 Amps,25kA -01Nos(Outgoing) Make L&T Cat No.CM91612OOKOOG
Design, fabrication, supply and errecting connecting and testing totally enclosed LT Cubical panel board of suitable size(proper space shall be provided for working in each compartment), 3 Phase 4 wire system Outdoor type ,double door front and back openeing type sloped canopy(Hood) on top extended 100mm all-around, separate compartment for each control gear, cable alley, provision of knock out type plates for various sizes of cable up to 400 Sqmm 3.5 Core in and out( panel board shall have sufficent space to accommodate spare cables also if required) , incoming and outgoing feeders duly marked on revited plates etc, CPRI approved factory made fabricated out of 3.15mm thik CRCA sheet duly treated through 7 tank pre treatment process and painted with epoxy power coated mat finish of SIEMENTS GREY structral RAL 7032 shade colour, built in industrial type locking arrangement on front and back and pre wired with PVC insulated multi stranded copper conductor for controls and monitors, PVC sleeved aluminium strip for connecting MCCBs,Panel mounted on suitable size & thickness of angle iron frame(proper mounting shall be done) duly painted and embeded in necessary required quatnity of PCC 1:3:6 type C1, 60cm below ground level and 30cm above ground level including disconnecting all electrical & mechanical connections and taking down old unserviceable and consisting the following provisions:-
(a) MCCB 400Amps 4 Pole AC 415 Volts ,50Hz,50kA, with Thermal & Magnetic release, Cat No CM94103OOR1OG Make: L&T - 01 No(incoming) (b) MCCB 3 pole 100 Amps,25kA -08Nos(Outgoing -07+01 -Spare) Make L&T Cat No.CM91612OOKOOG. (c) MCB 3 -pole 32-63 Amps,10kA -05Nos(Outgoing
Design, fabrication, supply and errecting connecting and testing totally enclosed LT Cubical panel board of suitable size(proper space shall be provided for working in each compartment), 3 Phase 4 wire system Outdoor type ,double door front and back openeing type sloped canopy(Hood) on top extended 100mm all-around, separate compartment for each control gear, cable alley, provision of knock out type plates for various sizes of cable up to 400 Sqmm 3.5 Core in and out( panel board shall have sufficent space to accommodate spare cables also if required) , incoming and outgoing feeders duly marked on revited plates etc, CPRI approved factory made fabricated out of 3.15mm thik CRCA sheet duly treated through 7 tank pre treatment process and painted with epoxy power coated mat finish of SIEMENTS GREY structral RAL 7032 shade colour, built in industrial type locking arrangement on front and back and pre wired with PVC insulated multi stranded copper conductor for controls and monitors, PVC sleeved aluminium strip for connecting MCCBs,Panel mounted on suitable size & thickness of angle iron frame(proper mounting shall be done) duly painted and embeded in necessary required quatnity of PCC 1:3:6 type C1, 60cm below ground level and 30.cm above ground level including disconnecting all electrical & mechanical connections and taking down old unserviceable and consisting the following provisions:-
(a) MCCB 400Amps 4 Pole AC 415 Volts ,50Hz,50kA, Adjustable Thermal & Magnetic release, Cat No CM94103OOR1OG Make: L&T - 01 No(incoming) (b)MCCB 3 pole 100 Amps,25kA -06Nos(Outgoing -05+01 -Spare) Make L&T Cat No.CM91612OOKOOG. (c) MCB 3 -pole 32-63 Amps,10kA -02Nos(Outgoing
Design, fabrication, supply and errecting connecting and testing totally enclosed LT Cubical panel board of suitable size(proper space shall be provided for working in each compartment), 3 Phase 4 wire system Outdoor type ,double door front and back openeing type sloped canopy(Hood) on top extended 100mm all-around, separate compartment for each control gear, cable alley, provision of knock out type plates for various sizes of cable up to 400 Sqmm 3.5 Core in and out( panel board shall have sufficent space to accommodate spare cables also if required) , incoming and outgoing feeders duly marked on revited plates etc, CPRI approved factory made fabricated out of 3.15mm thik CRCA sheet duly treated through 7 tank pre treatment process and painted with epoxy power coated mat finish of SIEMENTS GREY structral RAL 7032 shade colour, built in industrial type locking arrangement on front and back and pre wired with PVC insulated multi stranded copper conductor for controls and monitors, PVC sleeved aluminium strip for connecting MCCBs, Panel mounted on suitable size & thickness of angle iron frame(proper mounting shall be done) duly painted and embeded in necessary required quatnity of PCC 1:3:6 type C1, 45cm below ground level and 15cm above ground level including disconnecting all electrical & mechanical connections and taking down old unserviceable and consisting the following provisions:-
(a) MCCB 4 pole 160 Amps,25kA with thermal magnetic release-01Nos(incoming) Make L&T Cat No.CM90642OOMO (b) MCCB 3 pole 100 Amps,25kA -03Nos(Outgoing -02+01 -Spare) Make L&T Cat No.CM91612OOKOOG. (c) MCB 3 -pole 32-63 Amps,10kA -01Nos(Outgoing)
Design, fabrication, supply and errecting connecting and testing totally enclosed LT Cubical panel board of suitable size(proper space shall be provided for working in each compartment), 3 Phase 4 wire system outdoor type ,double door front and back openeing type sloped canopy(Hood) on top extended 100mm all-around, separate compartment for each control gear, cable alley, provision of knock out type plates for various sizes of cable up to 400 Sqmm 3.5 Core in and out(Quantity of konck out type plates shall be double for incoming & out going cable entries, panel board shall have sufficent space to accommodate spare cables also) , incoming and outgoing feeders duly marked on revited plates etc, CPRI approved factory made fabricated out of 3.15mm thik CRCA sheet duly treated through 7 tank pre treatment process and painted with epoxy power coated mat finish of SIEMENTS GREY structral RAL 7032 shade colour, built in industrial type locking arrangement on front and back and pre wired with PVC insulated multi stranded copper conductor for controls and monitors, PVC sleeved aluminium strip for connecting MCCBs, Panel mounted on suitable size & thickness of angle iron frame(proper mounting shall be done) duly painted and embeded in necessary required quatnity of PCC 1:3:6 type C1, 45cm below ground level and 15cm above ground level including disconnecting all electrical & mechanical connections and taking down old unserviceable and consisting the following provisions:-
(a) MCCB 4 pole 200 Amps,35kA with thermal magnetic release -01Nos(incoming) Make L&T Cat No.CM92109OON1OG (b)MCCB 3 pole 100 Amps,25kA -04Nos(Outgoing -03+01 -Spare) Make L&T Cat No.CM91612OOKOOG. (c) MCB 3 -pole 32-63 Amps,10kA -02Nos(Outgoing -02)
Design, fabrication, supply and errecting connecting and testing totally enclosed LT Cubical panel board of suitable size(proper space shall be provided for working in each compartment), 3 Phase 4 wire system outdoor type ,double door front and back openeing type sloped canopy(Hood) on top extended 100mm all-around, separate compartment for each control gear, cable alley, provision of knock out type plates for various sizes of cable up to 400 Sqmm 3.5 Core in and out( panel board shall have sufficent space to accommodate spare cables also) , incoming and outgoing feeders duly marked on revited plates etc, CPRI approved factory made fabricated out of 3.15mm thik CRCA sheet duly treated through 7 tank pre treatment process and painted with epoxy power coated mat finish of SIEMENTS GREY structral RAL 7032 shade colour, built in industrial type locking arrangement on front and back and pre wired with PVC insulated multi stranded copper conductor for controls and monitors, PVC sleeved aluminium strip for connecting MCCBs, Panel mounted on suitable size & thickness of angle iron frame(proper mounting shall be done) duly painted and embeded in necessary required quatnity of PCC 1:3:6 type C1, 45cm below ground level and 15cm above ground level including disconnecting all electrical & mechanical connections and taking down old unserviceable and consisting the following provisions:-
(a) Onload change over 4pole 200Amps,415 volts,50Hz front handle operated alongwith front handle L&T Cat No.CO22000OOOA. (b) MCCB 4 pole 200 Amps,35/36kA with thermal magnetic release -01Nos(incoming) Make L&T Cat No.CM92109OON1OG (c) MCCB 3 pole 100 Amps,25kA -04Nos(Outgoing -03+01 -Spare) Make L&T Cat No.CM91612OOKOOG. (d) MCB 3 -pole 32-63 Amps,10kA -02Nos(Outgoing -02)
Design, fabrication, supply and errecting connecting and testing totally enclosed LT Cubical panel board of suitable size(proper space shall be provided for working in each compartment), 3 Phase 4 wire system outdoor type ,double door front and back openeing type sloped canopy(Hood) on top extended 100mm all-around, separate compartment for each control gear, cable alley, provision of knock out type plates for various sizes of cable up to 400 Sqmm 3.5 Core in and out(panel board shall have sufficent space to accommodate spare cables also if required) , incoming and outgoing feeders duly marked on revited plates etc, CPRI approved factory made fabricated out of 3.15mm thik CRCA sheet duly treated through 7 tank pre treatment process and painted with epoxy power coated mat finish of SIEMENTS GREY structral RAL 7032 shade colour, built in industrial type locking arrangement on front and back and pre wired with PVC insulated multi stranded copper conductor for controls and monitors, PVC sleeved aluminium strip for connecting MCCBs,Panel mounted on suitable size & thickness of angle iron frame(proper mounting shall be done) duly painted and embeded in necessary required quatnity of PCC 1:3:6 type C1, 45cm below ground level and 15cm above ground level including disconnecting all electrical & mechanical connections and taking down old unserviceable and consisting the following provisions:-
((a)MCCB 4poles 250Amps,35/36KA with thermal magnetic release -01(Incoming) Make L&T Cat No.CM92109OOP1OG (b) MCCB 3 pole 125 Amps,25kA with thermal magnetic release-01Nos(incoming) Make L&T Cat No.CM90632OOLO (c)MCCB 3 pole 100 Amps,25kA -03Nos(Outgoing -02+01 -Spare) Make L&T Cat No.CM91612OOKOOG. (d) MCB 3 -pole 32-63 Amps,10kA -02Nos(Outgoing)
Design, fabrication, supply and errecting connecting and testing totally enclosed LT Cubical panel board of suitable size(proper space shall be provided for working in each compartment), 3 Phase 4 wire system Outdoor type ,double door front and back openeing type sloped canopy(Hood) on top extended 100mm all-around, separate compartment for each control gear, cable alley, provision of knock out type plates for various sizes of cable up to 400 Sqmm 3.5 Core in and out(panel board shall have sufficent space to accommodate spare cables also if required) , incoming and outgoing feeders duly marked on revited plates etc, CPRI approved factory made fabricated out of 3.15mm thik CRCA sheet duly treated through 7 tank pre treatment process and painted with epoxy power coated mat finish of SIEMENTS GREY structral RAL 7032 shade colour, built in industrial type locking arrangement on front and back and pre wired with PVC insulated multi stranded copper conductor for controls and monitors, PVC sleeved aluminium strip for connecting MCCBs, Panel mounted on suitable size & thickness of angle iron frame(proper mounting shall be done) duly painted and embeded in necessary required quatnity of PCC 1:3:6 type C1, 60cm below ground level and 30cm above ground level including disconnecting all electrical & mechanical connections and taking down old unserviceable and consisting the following provisions:-
(a) Onload change over 4 pole,front handle operated 630Amps,415 volts with handle L&T cat No.CO46300OOOO -01 No (b) MCCB 630Amps Four Pole AC 415 Volts,50Hz,50kA , Adjustable Thermal & Magnetic release,Cat No CM94104OOT1OG Make: L&T - 01 No(incoming) (c) MCCB 400Amps 3Pole AC 415 Volts ,50Hz,35/36kA, Adjustable Thermal & Magnetic release, Cat No .CM98401OOROOG Make: L&T - 01 No(Outgoing) (d) MCCB Three Pole 250 Amps 50Hz 415 Volts,Adjustable thermal Magnetic realse with rupturing capacity 25 KA-04Nos(outgoings 03+Spare 01) Make : L&T Cat No CM90638OOPO (e) MCCB 3 pole 63-100 Amps,25kA -01Nos(Outgoing) Make L&T Cat No.CM91612OOKOOG
Design, fabrication, supply and errecting connecting and testing totally enclosed LT Cubical panel board of suitable size(proper space shall be provided for working in each compartment), 3 Phase 4 wire system Outdoor type ,double door front and back openeing type sloped canopy(Hood) on top extended 100mm all-around, separate compartment for each control gear, cable alley, provision of knock out type plates for various sizes of cable up to 400 Sqmm 3.5 Core in and out(panel board shall have sufficent space to accommodate spare cables also if required) , incoming and outgoing feeders duly marked on revited plates etc, CPRI approved factory made fabricated out of 3.15mm thik CRCA sheet duly treated through 7 tank pre treatment process and painted with epoxy power coated mat finish of SIEMENTS GREY structral RAL 7032 shade colour, built in industrial type locking arrangement on front and back and pre wired with PVC insulated multi stranded copper conductor for controls and monitors, PVC sleeved aluminium strip for connecting MCCBs, Panel mounted on suitable size & thickness of angle iron frame(proper mounting shall be done) duly painted and embeded in necessary required quatnity of PCC 1:3:6 type C1, 60cm below ground level and 30cm above ground level including disconnecting all electrical & mechanical connections and taking down old unserviceable and consisting the following provisions:-
(a) Onload change over 4 pole,front handle operated 400Amps,415 volts along with handle L&T Cat No. CO44000OOOO. (b) MCCB 400Amps 4 Pole AC 415 Volts ,50Hz,50kA, Adjustable Thermal & Magnetic release, Cat No CM94103OOR1OG Make: L&T - 01 No(incoming) (c) MCCB 3 pole 250 Amps,35kA with thermal magnetic release -02Nos (Outgoing -01+01 -Spare) Make L&T Cat No.CM92009OOP1OG. (d) MCCB 3 pole 200 Amps,25kA -01Nos(Outgoing -01) Make L&T Cat No.CM90638OONO. (e) MCB 3 -pole 32-63 Amps,10kA -02Nos(Outgoing)
Design, fabrication, supply and errecting connecting and testing totally enclosed LT Cubical panel board of suitable size(proper space shall be provided for working in each compartment), 3 Phase 4 wire system Outdoor type ,double door front and back openeing type sloped canopy(Hood) on top extended 100mm all-around, separate compartment for each control gear, cable alley, provision of knock out type plates for various sizes of cable up to 400 Sqmm 3.5 Core in and out( panel board shall have sufficent space to accommodate spare cables also if required) , incoming and outgoing feeders duly marked on revited plates etc, CPRI approved factory made fabricated out of 3.15mm thik CRCA sheet duly treated through 7 tank pre treatment process and painted with epoxy power coated mat finish of SIEMENTS GREY structral RAL 7032 shade colour, built in industrial type locking arrangement on front and back and pre wired with PVC insulated multi stranded copper conductor for controls and monitors, PVC sleeved aluminium strip for connecting MCCBs, Panel mounted on suitable size & thickness of angle iron frame(proper mounting shall be done) duly painted and embeded in necessary required quatnity of PCC 1:3:6 type C1, 60cm below ground level and 30cm above ground level including disconnecting all electrical & mechanical connections and taking down old unserviceable and consisting the following provisions:-
(a) MCCB 630Amps Four Pole AC 415 Volts,50Hz,50kA , Adjustable Thermal & Magnetic release,Cat No CM94104OOT1OG Make: L&T - 01 No(incoming) (b) MCCB 400Amps 3Pole AC 415 Volts ,50Hz,35/36kA, Adjustable Thermal & Magnetic release, Cat No .CM94104006OOS1OG Make: L&T - 02 No(Outgoing) (c) MCCB Three Pole 250 Amps 50Hz 415 Volts,Adjustable thermal Magnetic realse with rupturing capacity 25 KA-03Nos(outgoings 02+Spare 01) Make : L&T Cat No CM90638OOPO (d) MCCB 3 pole 63-100 Amps,16kA -01Nos(Outgoing) Make L&T Cat No.CM91612OOKOOG
M&L earthing complete with galvanized steel earth plate electrode 60cm x 60cm x 6mm thick buried directly in ground earth pit not less than 2.25 mtr deep below normal ground level) with top edge of plate not less than 1.5m below ground level, connecting to the Galvanized iron earth strip 32 x 6mm dia, by means of nuts, bolts, check nuts and washer etc of galvanized iron and earth lead protected by provision of GI pipe medium grade 40mm bore from earth electrode to test point incl provn of concrete pit in PCC (1:2:4) type B-1 using 20mm graded stone aggregates with 40mm thick cover of RCC (1:2:4) reinforced with XPM sheet (weight not less than 4Kg/Sqm) and frame of angle iron 25 x 25 x 6mm with lugs 2 Nos and with 8mm dia MS bar handle made to shape, GI pipe medium grade 20mm bore pipe for watering perforated at bottom 1.75 mtr long placed on top edge of earth plate, common salt and charcoal filling test point with fixing arrangement, funnel, wire mesh and earth work in hard/dense soil, returning in and removal of surplus soil to a distance not exceeding 50mtr, complete all as specified in electrical plate No 3 of SSR Part I and connection to earth test point including testing on completion all as directed. Note :- Item of earthing includes cost of galvanized iron earth strip of 32 x 6mm size and protection pipe of 40mm bore GI medium grade upto 7.5m long.
M&L Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/ pipe or fixed to poles or any other indicated situation for loop earthing etc. as requied 32x6mm galvanised iron strip including taking old un serviceable one.
Supply,test,install & commsissioning of Bus bar chambers(including 4 bus bars i.e R,Y,B and neutral),3-Ph with netral,1100volts,50Hz including suitable sheet metal enclosure fabricated out of 2mm CRCA sheet along with necessary screws,nuts,bolts and other Misc accessroies and making connections(input &out put) with cable terminal ends complete for the following current carrying capacities,Panel mounted on suitable size & thickness of angle iron frame(proper mounting shall be done) duly powder coated and embeded in necessary required quatnity of PCC 1:3:6 type C1, 30cm below ground level and 15cm above ground level including taking down old unserviceable and consisting the following provisions:- Make: Havells/L&T/Standard
4-Way, 200 Amps
4-Way,250Amps
4-Way,400Amps
8-Way,400Amps
Taking down LED street light fitting/ LED flood light fitting of any watts and type from any height of pole/walls/any location and detecting the fault in the fitting by checking the accessories, wiring and refixing the same after repairs complete all as directed by Engineer-in-Charge. Note : Spares like driver and other accessories etc will be measured and paid separately under relevant items
S&F LED Driver suitable for upto 45 watts LED light fittings complete all as specified and directed. Make :Havells/Philips/Bajaj/Wipro/Luker.
S&F LED Driver suitable for from 60watts to 135 watts LED light fittings complete all as specified and directed. Make :Havells/Philips/Bajaj/Wipro/Luker. Note for item No.05&06:Drivers shall be techincally compitable for existing fittings & frame size shall be matched to existing fittings.
S&F PVC insulated,unarmoured 3 core 2.5Sqmm Aluminum cable including making neccessary cable terminations,lugs,glans complete all as directed by Engr - in-Charge
Disconnecting and taking out unserviceable MCCB and Supply,,install ,test and commissioning of new MCCB 3 pole, 32-63Amps, 16kA, 415volts,50 Hz, suitable for exisitng location(frame size shall match with existing one)for fixing in panel board/sheet metal enclosures/distribution boards with necessary cable connections,suitablel lugs,Spreader links, glands,nuts,bolts and screws complete all as specified and directed.
Disconnecting & taking out unserviceable MCCB and Supply,test,install & commissioning of new MCCB 3 pole, 32-63Amps, 25kA, 415volts,50 Hz, suitable for exisitng location(frame size shall be matched with existing one)for fixing in panel board/sheet metal enclosures/distribution boards with necessary cable connections,suitablel lugs,Spreader links, glands,nuts,bolts and screws complete all as specified and directed.
Disconnecting and taking out unserviceable MCCB and Supply,test,install and commissioning of new MCCB 3 pole, 100Amps, 16/25kA, 415volts,50 Hz, suitable for exisitng location(frame size shall be matched with existing one) for fixing in panel board/sheet metal enclosures/distribution boards with necessary cable connections,suitablel lugs,Spreader links, glands,nuts,bolts and screws complete all as specified and directed.
Disconnecting and taking out unserviceable MCCB and Supply,test,install and commissioning of new MCCB 3 pole, 125Amps, 25kA, 415volts,50 Hz, suitable for exisitng location(frame size shall be matched with existing one)for fixing in panel board/sheet metal enclosures/distribution boards with necessary cable connections,suitablel lugs,Spreader links, glands,nuts,bolts and screws complete all as specified and directed.
Disconnecting and taking out unserviceable MCCB and Supply,test,install and commissioning of new MCCB 3 pole, 160Amps, 35/36kA, 415volts,50 Hz, suitable for exisitng location(frame size shall be matched with existing one) for fixing in panel board/sheet metal enclosures/distribution boards with necessary cable connections,suitablel lugs,Spreader links, glands,nuts,bolts and screws complete all as specified and directed.
Disconnecting and taking out unserviceable MCCB and Supply,test,install and commissioning of new MCCB 3 pole, 200Amps, 25kA, 415volts,50 Hz, with adjustable settings, suitable for exisitng location(frame size shall be matched with existing one) for fixing in panel board/sheet metal enclosures/distribution boards with necessary cable connections,suitablel lugs,Spreader links, glands,nuts,bolts and screws complete all as specified and directed.
Disconnecting and taking out unserviceable MCCB and Supply,test,install and commissioning of new MCCB 3 pole, 200Amps, 35/36kA, 415volts,50 Hz, with adjustable settings, suitable for exisitng location(frame size shall be matched with existing one) for fixing in panel board/sheet metal enclosures/distribution boards with necessary cable connections,suitablel lugs,Spreader links, glands,nuts,bolts and screws complete all as specified and directed.
Disconnecting and taking out unserviceable MCCB and Supply,test,install and commissioning of new MCCB 3 pole, 250Amps, 25kA, 415volts,50 Hz, with adjustable settings, suitable for exisitng location(frame size shall be matched with existing one), for fixing in panel board/sheet metal enclosures/distribution boards with necessary cable connections,suitablel lugs,Spreader links, glands,nuts,bolts and screws complete all as specified and directed.
Disconnecting and taking out unserviceable MCCB and Supply,test,install and commissioning of new MCCB 3 pole, 250Amps, 35/36kA, 415volts,50 Hz, with adjustable settings, suitable for exisitng location(frame size shall be matched with existing one) for fixing in panel board/sheet metal enclosures/distribution boards with necessary cable connections,suitablel lugs,Spreader links, glands,nuts,bolts and screws complete all as specified and directed.
Disconnecting & taking out unserviceable MCCB and Supply,test,install & commissioning of new MCCB 3 pole, 315 Amps to 400Amps, 50kA, 415volts,50 Hz with adjustable settings & thermal,magnetic realse,suitable for exisitng location(frame size shall be matched with existing one) for fixing in panel board/sheet metal enclosures/distribution boards with necessary cable connections,suitablel lugs,Spreader links, glands,nuts,bolts and screws complete all as specified and directed.
Disconnecting & taking out unserviceable MCCB and Supply,test,install & commissioning of new MCCB 3 pole, 630Amps, 50kA, 415volts,50 Hz with adjustable settings & thermal,magnetic realse,suitable for exisitng location(frame size shall be matched with existing one) for fixing in panel board/sheet metal enclosures/distribution boards with necessary cable connections,suitablel lugs,Spreader links, glands,nuts,bolts and screws complete all as specified and directed.
Disconnecting & taking out unserviceable MCCB and Supply,test,install & commissioning of new MCCB 4 pole, 200Amps, 25kA, 415volts,50 Hz, with adjustable settings, suitable for exisitng location(frame size shall be matched with existing one) for fixing in panel board/sheet metal enclosures/distribution boards with necessary cable connections,suitablel lugs,Spreader links, glands,nuts,bolts and screws complete all as specified and directed.
Disconnecting & taking out unserviceable MCCB and Supply,test,install & commissioning of new MCCB 4 pole, 200Amps, 35/36kA, 415volts,50 Hz, with adjustable settings, suitable for exisitng location(frame size shall be matched with existing one) for fixing in panel board/sheet metal enclosures/distribution boards with necessary cable connections,suitablel lugs,Spreader links, glands,nuts,bolts and screws complete all as specified and directed.
Disconnecting & taking out unserviceable MCCB and Supply,test,install & commissioning of new MCCB 4 pole, 250Amps, 25kA, 415volts,50 Hz, with adjustable settings, suitable for exisitng location(frame size shall be matched with existing one), for fixing in panel board/sheet metal enclosures/distribution boards with necessary cable connections,suitablel lugs,Spreader links, glands,nuts,bolts and screws complete all as specified and directed.
Disconnecting and taking out unserviceable MCCB and Supply,test,install and commissioning of new MCCB 4 pole, 250Amps, 35kA, 415volts,50 Hz, with adjustable settings, suitable for exisitng location(frame size shall be matched with existing one), for fixing in panel board/sheet metal enclosures/distribution boards with necessary cable connections,suitablel lugs,Spreader links, glands,nuts,bolts and screws complete all as specified and directed.
Disconnecting and taking out unserviceable MCCB and Supply,test,install and commissioning of new MCCB 4 pole, 315 Amps to 400Amps, 50kA, 415volts,50 Hz with adjustable settings & thermal,magnetic realse,suitable for exisitng location(frame size shall be matched with existing one) for fixing in panel board/sheet metal enclosures/distribution boards with necessary cable connections,suitablel lugs,Spreader links, glands,nuts,bolts and screws complete all as specified and directed.
Disconnecting and taking out unserviceable MCCB and Supply,test,install and commissioning of new MCCB 4 pole, 630Amps, 50kA, 415volts,50 Hz with adjustable settings & thermal,magnetic realse,suitable for exisitng location(frame size shall be matched with existing one)for fixing in panel board/sheet metal enclosures/distribution boards with necessary cable connections,suitablel lugs,Spreader links, glands,nuts,bolts and screws complete all as specified and directed.
Supply andFixing of 3 pole MCB 32-63amps,C-curve,10kA,50Hz,440v in existing location including necessary wiring & misc accessroies for satisfactory completion of job and taking down old unserviceable one complete all as directed by Engineer-in-Charge. Note for item no.19.00 to 36.00: (i)The above item shall be executed immediately as and when required basis.(ii) Make:- Havells/L&T/Standard/HPL.
Supply and Fixing of 200/5 Amps Current transformers -03Nos(in three phases) including necessary wiring and misc accessroies for satisfactory completion of job taking down old unserviceable one complete all as directed by Engineer-in-Charge.
M&L on load change over switch 630 Amps capacity suitable for 3 phase, 4 pole, 415 Volts,font handle operated suitable in open execution type for fixing in existing panels/location including necessary lugs,glands.,nuts,bolts inclduing taking down old unserviceable one complete all as specified and directed
M&L on load change over switch 400 Amps capacity suitable for 3 phase, 4 pole, 415 Volts,font handle operated suitable in open execution type for fixing in existing panels/location including necessary lugs,glands.,nuts,bolts inclduing taking down old unserviceable one complete all as specified and directed
M&L on load change over switch 320 Amps capacity suitable for 3 phase, 4 pole, 415 Volts,font handle operated suitable in open execution type for fixing in existing panels/location including necessary lugs,glands.,nuts,bolts inclduing taking down old unserviceable one complete all as specified and directed
M&L on load change over switch 200 Amps capacity suitable for 3 phase, 4 pole, 415 Volts,font handle operated suitable in open execution type for fixing in existing panels/location including necessary lugs,glands.,nuts,bolts inclduing taking down old unserviceable one complete all as specified and directed
M&L on load change over switch 100 Amps capacity suitable for 3 phase, 4 pole, 415 Volts,font handle operated suitable in sheet metal enclosure type for fixing in existing location including necessary lugs,glands.,nuts,bolts inclduing taking down old unserviceable one complete all as specified and directed
M&L Off load change over switch 200 Amps capacity suitable for 3 phase, 4 pole, 415 Volts,side handle operated with sheet metal enclosure suitable for fixing in existing panels including necessary lugs,glands.,nuts,bolts inclduing taking down old unserviceable one complete all as specified and directed
M&L Off load change over switch 400 Amps capacity suitable for 3 phase, 4 pole, 415 Volts,side handle operated with sheet metal enclosure suitable for fixing in existing panels including necessary lugs,glands.,nuts,bolts inclduing taking down old unserviceable one complete all as specified and directed Note for item no.38 to 44: (i)The above item shall be executed immediately as and when required basis.(ii) Make:- Havells/L&T//HPL/Standard.
Excavation of transformer structure yard upto a depth of 300mm and Removing excavated soils to a distance not exceeding 50m and depositing where directed at a level not exceeding 1.5 above the starting point complete all as directed by Engr -in-charge.
Supply and spread stone dust (powder) of thickness 50mm in 2 pole/6pole structure yard complete all as directed by Engr-in-charge.
Supply and spread graded stone aggregate 40 mm in structure yard of 2/4 poles complete all as directed by Engr-in-charge.
Supply and spread graded stone aggregate 20 mm in structure yard of 2/4 poles complete all as directed by Engr-in-charge.
Supply and connect LT 1100 V outdoor type cable straight through heat shrinkable epoxy joint kit suitable for the following sizes with necessary jointing materials complete all as directed by Engr-in-charge. Make :- M-SEAL/ DENSON/3-M/ RAYCHEM
3.5 core x 25/35 sqmm.
3.5 core x 70/95 sqmm.
3.5 core x 120/150 sqmm.
3.5 core x 185/240 sqmm.
3.5 core x 300/400Sqmm
Isolate,disconnect,dismantle the burnt out lugs from main switches/MCCB/ACB/Breakers and Supply &fix new lugs with crimping tool as per existing one including fixing, insulation, termination tomain switches/MCCB/ACB/Breakers for the following sizes of cables complete all as directed by Engr -In-Charge. Note : cleaning the cable termination ends insulation as required length and fixing new lugs as per size including well crimping to the lugs for both ends of cable complete are included in quoted rates.
25 sqmm to 50 sqmm
70 sqmm to 95 sqmm
120 sqm to 240 sqmm
300 sqmm to 400 sqmm
up to 16 Sqmm
Meggering of HT Overhead conductor between Span to Span/Six pole structure/four pole structure, any type insulator with complete diconnection & reconnection of jumper for checking of fault and rectification for any size any place after disconnection of AB switch complete.
Supply & fixing of 4 pole power contactor 02NO +02NC,63Amps MCX-12,50Hz suitable for existing one and including taking down old unserviceable one complete all as direrected by Engr-in-Charge.
Supply & fixing of 4 pole power contactor 02NO+02NC, 130Amps,MCX-23,50Hz suitable for existing one and including taking down old unserviceable one complete all as direrected by Engr-in-Charge.
Supply & fixing of 4 pole power contactor 02NO+02NC,200Amps,MCX-33,,50Hz suitable for existing one and including taking down old unserviceable one complete all as direrected by Engr-in-Charge.
Supply & fixing of 4 pole power contactor 02NO+02NC,360Amps,MCX-42,50Hz suitable for existing one and including taking down old unserviceable one complete all as direrected by Engr-in-Charge.
Supply & fixing of 4 pole power contactor 02NO+02NC,400Amps,MCX-43,50Hz suitable for existing one and including taking down old unserviceable one complete all as direrected by Engr-in-Charge.
Supply & fixing of 4 pole power contactor,02NO+02NC,100Amps, MCX-22,50Hz suitable for existing one and including taking down old unserviceable one complete all as direrected by Engr-in-Charge. Note for item no.52 to 57:Make: L&T/Schneider/Siemens
Supply & fixing of 3 pole power contactor AC/DC Control ,Ie -1000Amps current rating,415 volts,50Hz suitable for existing one and including necessary fixing elements and wiring and taking down old unserviceable one complete all as direrected by Engr-in-Charge. Make: Cat No. LC1F630 of Schnieder or its techno commercial Equivalent in Siemens/ABB/L&T/GE
Supply & fixing of 3 pole power contactor AC/DC Control ,Ie -350Amps current rating,415 volts,50Hz suitable for existing one and including necessary fixing elements and wiring and taking down old unserviceable one complete all as direrected by Engr-in-Charge. Make: Cat No. LC1F265 of Schnieder or its techno commercial Equivalent in Siemens/ABB/L&T/GE
Supply and fixing of PVC Junction box of size 140mm x 140mm x95mm ,light weight pole mounting hinged type including MCB DP 16Amps -1 No including necessary clamp for MCB mounting and mounting of Box on pole with MS flat frame arrangement and necessary connector for looping in and looping out cable connection and suitable glands complete all as directed by Engr-in-charge. Make :- SINTEX cat No.GSJB1414 or its techno commercial equivalent in Polycon
Supply,test,laying & commissioning of XLPE insulated, armoured (heavy duty) electric cable with aluminium stranded conductor, 1100 volts grade, laid in trenches / duct/ fixed to wall with suitable size clamps / passing through pipe/Tunnel/under ground/surface up to the termination point(as directed by Engr-in-Charge) with necessary end terminations with suitable size cable lugs, cable glands, fixing of lugs with crimping with tool,nuts,boltsetc of the following sizes and including taking out unserviceable burnt out cable from its existing location complete all as specified and directed by Engr-in-Charge :-
3.5 Core x 150Sqmm
3.5 Core X 240 Sqmm
3.5 Core X 300 Sqmm
3.5 Core X 400 Sqmm
3.5core x 95 Sqmm
Excavation in trenches not exceeding 1.5 mtr wide and not exceeding 1.5 mtr depth for foundation, laying of poles in trenches and getting out in hard/ Dense soil complete all as specified and as directed Engineer-in-Charge.
Returning, filling including spreading, levelling, watering and well ramming in layers not exceeding 25 cms thick complete all as directed by Engineer-in-Charge.
Removal of surplus soil to a distance no exceeding 50 mtrs and depositing where directed at a level not exceeding 1.5 mtrs above from the starting point complete all as directed by Engineer-in-charge.
M&L filling approved river sand in trenches for sand cushioning of laying of cables to the full width of excavated trench 8 cm thick before laying the cable and 15 cm above the cable, gently punned down, stretching and testing of cable on transformer yard etc complete all as specified and directed. Note :- Thickness of sand cushion after punning down shall be measured for payment.
M & L Galvanised iron tubing 100 mm dia light grade laind in trenches/floors/walls/under ground for eath lead protection and cables at road crossing etc complete all as specified and directed.
Supply and Lay reinforced precast concrete cable cover LV, Type I,flat, size 250x150x40 mm complete all as specified and directed.
M&L for Disconnecting the the unserviceable LT/Street light UG cable laid in trenches/surface/wall/under ground/tunnel/pipe from LT/Street light pole to Panel board/Kiosk/Busbar chamber/feeder pillar box and meggingring the same and removed the damaged portion,jointing the rest of cable with necessary accessroies complete all as directed by Engr-in-Chrage. Note: if required Earth work shall be measured and paid separately under relevant items.
Dismantling LT/Street light pole of any height by taking out from PCC foundation complete and shifting to other location as directed including fixing the pole in true vertical position including excavation and earth work, PCC 1:4:8 type D2 (using 40mm graded stone aggregate) as base concrete and PCC 1:3:6 type C1 (using 20mm graded stone aggregate) in both foundation and coping of poles all as specified in SSR Part I-2009 and applying two coats of aluminium paint to pole surface complete all as directed by Engineer-in-Charge.
Maruthi international
POWER CONSTRUCTION COMPANY
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .